Wavecom GX64 Installation and operating instructions

Gx64 APPLICATION NOTE
Power Management
Reference:
W
I_DEV_Gx64_APN_007
Version: 001
Date: 2007/01/31

Trademarks
®, WAVECOM®, WISMO®, Open AT®, Wireless CPU®, Wireless Microprocessor®and certain
other trademarks and logos appearing on this document, are filed or registered trademarks
of Wavecom S.A. in France or in other countries. All other company and/or product names
mentioned may be filed or registered trademarks of their respective owners.
Copyright
This manual is copyrighted by WAVECOM with all rights reserved. No part of this manual may
be reproduced in any form without the prior written permission of WAVECOM.
No patent liability is assumed with respect to the use of the information contained herein.
No Warranty
WAVECOM publishes this manual without making any warranty as to the content contained
herein. Further Wavecom Inc reserves the right to make modifications, additions and
deletions to this manual due to typographical errors, inaccurate information, or
improvements to programs and/or equipment at any time and without notice. Such changes
will, nevertheless be incorporated into new editions of this manual.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 2/30

Table of Contents
1Introduction ............................................................................................ 5
1.1 ABBREVIATIONS ............................................................................................................ 5
1.2 NOTATION.................................................................................................................... 6
1.3 ACKNOWLEDGEMENTS .................................................................................................. 6
2Block Diagrams ....................................................................................... 7
2.1 SYSTEM POWER MANAGEMENT BLOCK DIAGRAM ........................................................... 7
2.2 POWER MANAGEMENT BLOCK DIAGRAM........................................................................ 8
2.2.1 GS64.................................................................................................................. 8
2.2.2 GR64001 ........................................................................................................... 9
2.2.3 GR64002 ......................................................................................................... 10
3Implementation Recommendations ....................................................... 11
3.1 APPLYING POWER ON VCC........................................................................................... 11
3.2 POWER STATE CONTROL OF THE WIRELESS CPU........................................................... 12
3.2.1 ON/OFF ........................................................................................................... 13
3.2.2 INTERNAL CHGDET........................................................................................... 14
3.2.3 EXTERNAL PON_H............................................................................................. 14
3.2.4 ALARM............................................................................................................. 15
3.2.5 AT+CFUN ........................................................................................................ 16
3.2.6 AT*E2RESET ..................................................................................................... 16
3.3 HOW TO LOWER POWER CONSUMPTION ...................................................................... 16
3.4 CHARGING.................................................................................................................. 17
3.5 HOW TO USE VREF ...................................................................................................... 17
3.5.1 VREF AS OUTPUT IN GS64 AND GR64001 ......................................................... 17
3.5.2 VREF AS INPUT IN GR64002.............................................................................. 18
3.6 MONITOR “POWER ON” STATE ..................................................................................... 19
3.6.1 GS64 AND GR64001 HW-DETECTION ............................................................... 19
3.6.2 GR64002 HW-DETECTION................................................................................ 20
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 3/30

3.7 VRTC AND ALARM ...................................................................................................... 22
3.7.1 USING ALARM AS PERIODIC POWER ON ............................................................. 22
4Reference Designs ................................................................................ 24
4.1 DISCLAIMER................................................................................................................ 24
4.2 DC/DC POWER SUPPLY ................................................................................................ 24
4.2.1 BILL OF MATERIAL ............................................................................................ 24
4.3 AC/DC POWER SUPPLY ................................................................................................ 25
4.3.1 SPECIFICATIONS ............................................................................................... 25
4.3.2 DESIGN SUMMARY............................................................................................ 25
4.3.3 BILL OF MATERIAL ............................................................................................ 27
Appendix A................................................................................................. 28
Appendix B ................................................................................................. 29
Table of Figures
Figure 1: System Block Diagram ........................................................................................... 7
Figure 2: GS64 Power Management Block Diagram ............................................................... 9
Figure 3: GR64001 Power Management Block Diagram......................................................... 9
Figure 4: GR64002 Power Management Block Diagram....................................................... 10
Figure 5: GR/GS64 HW On/Off Sequence Logic................................................................... 12
Figure 6: Power Management State Diagram....................................................................... 13
Figure 7: Interface circuit implementation for GS64............................................................ 18
Figure 8: Typical VREF level translation implementation in a GR64002 ............................... 19
Figure 9: GR64002 Power State detection........................................................................... 20
Figure 10: ALARM application example .............................................................................. 22
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 4/30

1Introduction
This document describes how to apply power, control power states (On/Off), and give
other hints on how to optimise the Wireless CPU implementation.
1.1 Abbreviations
Abbreviation Description
CSD Circuit Switched Data
CPS Charging Power Supply. Indicates the voltage and current limited
supply connected to CHG_IN when battery charging is used.
DRX
Discontinuous Receive. This indicates how often the Wireless CPU
has to wake up and look for a page. The mode can be between 2
and 9 and is determined by the base station.
FAE Field Application Engineer
PSC Power Supply and Indicator
PSI Power State Change signal
RTC Real-Time-Clock residing in the Wireless CPU.
TP Temperature Protection. Built-in temperature protection of the
Power Management ASIC.
UVLD Under Voltage Level Detect. Voltage level detection of VCC.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 5/30

1.2 Notation
The following symbols and admonition notation are used to draw the reader’s
attention to notable or crucially-important information.
Note
Draws the readers attention to pertinent, useful or interesting
information
Tip
Provides advice, suggestions, guidance or recommendations which
augment the formal text
NOTE
TIP
Caution
Cautionary information must be heeded, it draws the readers attention
to the need for understanding, care or watchfulness in relation to the
information provided
CAUTION
Warning
Notes marked warning must be heeded, they alert readers to
precautionary measures, risks, hazards or safety information which
directly effects equipment function, warranty or personnel safety
!
WARNING
Danger
This information must be heeded, it identifies information and
cautionary behaviour that otherwise ignored could result in
catastrophic equipment failure, bodily injury or death
DANGE
R
1.3 Acknowledgements
Parts of this document, including text passages, tables, and illustrations, are
reproduced from copyright information by kind permission of Agere Systems Inc.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 6/30

2Block Diagrams
2.1 System Power Management Block Diagram
The GR/GS64 Wireless CPUs have a number of signals in the system connector that
affect the power state. The signals in Figure 1 show the signals for all types and
variants of the GR/GS64 family of Wireless CPUs.
Table 1 below lists what features are available for the different types and variants.
Figure 1: System Block Diagram
VREF is implemented differently in the two different GR64 variants. VREF is either an
input or an output and are obviously mutually exclusive. Figure 1 only shows VREF as
an output, which is the way it is implemented in the GR64001 and GS64.
The signal can be divided into two types:
•Power Supplies and indicators (PSI)
•Power state change signals (PSC)
The CHG_IN signal is both a PSI and a PSC.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 7/30

Table 1: Type / Variant Configuration
GR64001 GR64002 GS64
Feature Type
Pin(s) Pin(s) Pin(s)
VCC PSI √1,3,5,7,9 √1,3,5,7,9 √2,4,6,8,10,12
CHG_IN PSI/PSC √11 √11 √13
VUSB PSI √49 √34
VREF as input √
VREF as output PSI √34 34 √65
VRTC PSI √25 √25 √31
ALARM PSC √50 √32
PON_H PSC √21
ON/OFF PSC √14 √14 √33
2.2 Power Management Block Diagram
This section describes the individual implementations in the three different designs;
GS64, GR64001, and GR64002.
Detailed information on the PSC-implementation can be found in 3.2 below
2.2.1 GS64
The GS64 implementation uses all PSC-options listed in Table 1. If a signal is not
used it should be left floating.
The “PM ON/OFF Sequence Logic” block diagram can be found in Figure 5.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 8/30

Figure 2: GS64 Power Management Block Diagram
2.2.2 GR64001
This variant of GR64 only implements two PSC-options, ON/OFF and CHG_IN.
Figure 3: GR64001 Power Management Block Diagram
The “PM ON/OFF Sequence Logic” block diagram can be found in Figure 5.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 9/30

2.2.3 GR64002
This variant of GR64 implements all four PSC-options, ON/OFF, PON_H, ALARM and
CHG_IN.
Figure 4: GR64002 Power Management Block Diagram
The “PM ON/OFF Sequence Logic” block diagram can be found in Figure 5.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 10/30

3Implementation Recommendations
This section describes how to implement features related to the Power Management
of the Wireless CPUs.
3.1 Applying power on VCC
Main power is applied to VCC using GND as reference. The source can be any of the
following listed types:
•Li-Ion battery (3.7V nominal)
•AC/DC power supply (3.6V nominal)
•DC/DC power supply (3.6V nominal)
Reference designs for AC/DC and DC/DC supplies can be found in Appendix A and B
at the end of this document.
Limits
Parameter Condition Min. Avg. Max. Unit
VCC Supply voltage level 3.2 3.6 4.5 V
Voice/CSD call (1up, 1down)
at max power (32dBm), 4.7ms duration 21001mA
IPEAK
GSM850, GPRS, Class 10 (2up, 3down)
at max power (32dBm), 9.4ms duration 21002mA
Voice/CSD call (1 up, 1 down)
at max power (32dBm), 4.7ms duration 350 mA
GSM850, GPRS, Class 10 (2 up, 3 down)
at max power (32dBm), 9.4ms duration 560 mA
Standby (locked on channel) 15 25 35 mA
IRMS
Sleep mode 1.4 3.5 mA
1,2 This is the average maximum current during the transmit pulse. The absolute maximum current can
be up to 2500mA, but is only available for a couple of microseconds.
Gx64 APPLICATION NOTE
This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 11/30

3.2 Power state control of the Wireless CPU
There are a maximum of six signals that affects the HW power state of the GR/GS64
family of Wireless CPUs; four HW and two SW:
•ON/OFF (HW, all Wireless CPUs)
•CHG_IN (HW, all Wireless CPUs)
•PON_H (HW, GS64 only)
•ALARM (HW, GS64 and GR64002 as external, all as internal)
•AT+CFUN (SW, all Wireless CPUs)
•AT*E2RESET (SW, all Wireless CPUs)
Under normal operating conditions, the die temperature should not
exceed 125°C. In the event of an external fault or as a result of device
misuse, the die temperature could exceed this value by a large margin.
Should the die temperature exceed 155°C while the unit is powered up,
the thermal protection circuit will shut-down all functions and remain
disabled until the temperature drops below 130°C, at which point the
device can be restarted. This feature is listed as TP (Thermal
Protection) througout this document.
CAUTION
To power up the hardware VCC must be within 3.2V to 4.5V, and the Power
Management ASIC die temperature must be below 130°C.
Figure 5: GR/GS64 HW On/Off Sequence Logic
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 12/30

The two SW power state control signals are not included in Figure 5. This figure only
shows the HW-signals.
Figure 6: Power Management State Diagram
Figure 6 shows the impact five of the six control signals, listed above, have on the
Power Management status of the Wireless CPU. The AT*E2RESET is described
individually in 3.2.6 below.
If a PSC-signal is held active (PON_H high, ON/OFF low, etc.) while the Wireless CPU is
active, it is not possible for another PSC-signal to generate a power down request.
Any such request will be denied. If a valid power down request is generated while a
CPS is available, the Wireless CPU will be set to “Charge Only”-mode.
3.2.1 ON/OFF
This system connector signal provides a power up feature similar to a normal cell
phone on/off button, i.e. a low pulse will toggle between On-state and Off-state.
This signal is weekly pulled up to VCC in the Power Management ASIC by a constant
current source.
Table 2: ON/OFF signal characteristics
Input Characteristics
Parameter Description Min. Avg. Max. Unit
IIL -60 -25 -12 μA
IIH Input current 0 1 μA
VIL Low level detection limit 0.2*VCC V
VIH High level detection limit 0.8*VCC V
tLow Required time for detection 450 ms
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 13/30

The signal should be held low for at least tLow time for the Wireless CPU to be able to
detect and respond with a power hold signal (PWR_KEEP). The signal can be held low
for an unspecified amount of time but it is not recommended since it prevents the
Wireless CPU from respond to any other power state signal request.
3.2.2 Internal CHGDET
A charge request is initiated on INT_CHGDET when the voltage on CHG_IN is <6.3V,
>3.7V, and is 150mV higher than the voltage level of VCC. This signal is active as
long as a valid CPS is available on CHG_IN.
If the Wireless CPU is in “Power Down”-state when a CPS becomes available, it will
automatically place itself in “Charge Only”-mode. If the Wireless CPU is in “Active”-
mode it will remain there. For more information on charging see the “
GR/GS64 Series
Application Note - Charging Interface
”-document.
3.2.3 External PON_H
This system connector signal is an active high power on signal similar to ON/OFF, but
with the exception that it should be kept active high to keep the Wireless CPU in
“Active”-mode. This signal is weakly pulled down to GND in the Power Management
ASIC by a constant current source.
To power on the Wireless CPU this signal should be tied to VCC. It should remain at
VCC until the Wireless CPU should be powered down. To power down the Wireless
CPU PON_H should be set low or high impedance. This will start the power down
process and place the Wireless CPU in either “Power Down” or “Charge Only”-mode
depending on the internal INT_CHGDET-status.
Table 3: PON_H signal characteristics
Input Characteristics
Parameter Description Min. Avg. Max. Unit
IIL 8 20 60 μA
IIH
Input current -1 0 μA
VIL Low level detection limit 0.2*VCC V
VIH High level detection limit 0.8*VCC V
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 14/30

3.2.4 ALARM
The ALARM-signal can be both an internal and external signal for all Wireless CPUs
except GR64001 where it is only an internal signal. Internal means that the RTC is
capable of waking up the main processor as long as VCC is available. External means
that the signal is provided in the system connector. The external availability enables
the application to use an alarm to fully power on not only the Wireless CPU but also
itself, see 3.7.1 below.
The ALARM feature uses the “Time Commands” found in the AT-manual. These
commands consist of:
•AT+CCLK (Set Clock and Date)
•AT+CTZU (Automatic Time Zone Update)
•AT*EDST (Daylight Saving Time)
•AT+CALA (Set Alarm)
•AT+CALD (Alarm Delete)
The clock must be set to the correct time for the alarm to work properly in absolute
mode.
The easiest way to setup the clock correctly is to enable the Automatic
Time Zone Update by sending AT+CTZU=1 followed by AT&W. The
clock will get the time reported by the network. This eliminates the
need to manually setup the clock using the AT+CCLK-command.
AT*EDST does not have to be used if AT+CTZU=1 is sent since the
correct time will periodically be sent to the Wireless CPU from the base
station.
TIP
The automatic time zone feature is network dependent. It is not
necessarily available in all markets, or might not be enabled in certain
base stations. The safest way to get proper time setup correctly is to
have the application update the time using the AT+CCLK-command at
a regular interval.
CAUTION
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 15/30

3.2.5 AT+CFUN
This AT-command is used to change the power state of the Wireless CPU.
See the AT-command manual for more details.
3.2.6 AT*E2RESET
This AT-command will de-register from network and do the normal shut-down
sequence, but instead of powering down jump to the reset vector.
See the AT-command manual for more details.
3.3 How to lower power consumption
The Wireless CPUs are capable of being set to low current consumption mode where
the average current consumption can be as low as 1.4mA. This mode is referred to as
“sleep mode”. The actual current consumed depends on the base station DRX-mode
setting, which cannot be controlled by the Wireless CPU.
The features that determine the “sleep mode”-setting are the communication
channels UART and USB. The reason for this is that they cannot operate unless the
main 13MHz clock is available. To get the power consumption down the Wireless CPU
must disable the 13MHz clock and instead run of the 32kHz RTC. This means that a
handshake method has to be used for the UART (see
GR/GS64 Series Application Note
- UART Sleep Protocol
), and USB has to support “suspend-resume”.
The USB feature is not supported in all SW-versions. Contact your local FAE if USB-
support is needed. USB will have its own Application Note. Ensure that the USB-
interface is disabled if is not used (AT*USB=0).
Power State Condition Current Unit
Power down VRTC open (no backup battery) <10 μA
Power down VRTC active (backup battery available) <1.6 mA
Sleep mode DRX 2 <3.5 mA
UART active, USB inactive (AT*USB=0) ~25 mA
Standby
UART active, USB active (AT*USB=1) ~35 mA
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 16/30

The numbers given above are approximations. The real current levels might differ,
but should most often be less than what is listed.
3.4 Charging
A CPS should be connected to CHG_IN only if a single Li-Ion battery is used as main
power supply. In any other configuration CHG_IN must be left open (not connected).
For more information about charging see the “
GR/GS64 Series Application Note -
Charging Interface
”-document.
3.5 How to use VREF
VREF operates in two different ways depending on what Wireless CPU is used. In GS64
and GR64001VREF is an output signal and in GR64002 it is an input signal.
3.5.1 VREF as output in GS64 and GR64001
VREF is providing the application with its logic level supply. The application can use
this signal in two ways:
1. Reference voltage for application interface logic (required)
2. Wireless CPU Power On Indication (optional)
As indicated, the application logic interface must be referenced to VREF. The
application cannot supply an active high level in to the Wireless CPU on any signal
unless VREF is active high. The logic interface must also be the same level as VREF.
For GS64 this level is 1.8V, and for GR64001 it is 2.8V.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 17/30

Figure 7: Interface circuit implementation for GS64
The level translator type used in Figure 7 can be either ST2378E from ST
Microelectronics, MAX3001E from Maxim, or any other applicable type. Figure 7
shows a GS64 implementation, but the same figure can be used for a GR64001
solution if the 1.8V regulator is replaced with a 2.8V regulator.
VREF can furthermore be used by the application as an indicator whether the Wireless
CPU is powered on or not. An active high >1.65V indicates power on, while a low
<0.4V indicates power off.
If PON_H or ON/OFF are held active (high and low respectively) while VCC is slowly
increased from <2.7V to 3.3V, VREF will go active when VCC is at 3.050V, while the
SW starts executing when VCC is at 3.135V. This hysteresis is built-in to ensure that
the VREF is within specified levels when SW starts executing.
3.5.2 VREF as input in GR64002
In this variant of GR64 using VREF as an input offers the integrator a flexible interface
solution. The application should apply its logic interface voltage directly onto VREF as
long as it is between 1.8V and 5.0V. The application does not have to implement its
own level translation. It is all done inside the Wireless CPU.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 18/30

Figure 8: Typical VREF level translation implementation in a GR64002
One drawback of this solution is that VREF cannot be used by the application to
determine whether the Wireless CPU is powered on or not. See 3.6.2 below for more
information.
3.6 Monitor “Power On” State
The power state of the Wireless CPU can be verified in two ways; either HW or SW.
The HW-determination depends on what product and variant is used, but the SW-
determination is the same for all products (AT+CFUN). See AT-command
specification for more information on the AT+CFUN-command.
3.6.1 GS64 and GR64001 HW-detection
These products can determine the HW status of the Wireless CPU by monitoring the
VREF signal. A high level VREFHIGH-0.3V indicates unit powered on. A low level <0.4V
indicates unit powered off.
GR64001 GS64 Unit
VREFHIGH 2.8 1.8 V
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 19/30

3.6.2 GR64002 HW-detection
In GR64002, where VREF is an input to the Wireless CPU the HW-detection of the
power state must use SIMDET instead of VREF.
The SIMDET-signal is pulled up inside the Wireless CPU to its internal supply voltage
(1.8V). It does not go through the built-in level translators as the other logic signals.
This can be used to determine the state of the Wireless CPU. It also means that the
SIMDET-signal cannot be used to determine whether a physical SIM is inserted
properly into the external SIM-holder.
Figure 9: GR64002 Power State detection
As can be seen in Figure 9, the SIMDET-signal can be used to determine the power
state of the GR64002. Instead of routing the signal to the physical detection pin of
the SIM-holder, it is routed to a detection circuitry that translates the level from 1.8V
to whatever logic level the Application is using. The “Reference Voltage, R1 and R2
must be selected so that the transition levels correspond to the levels indicated in
Table 4 below.
The pull up resistor that is built in to the Wireless CPU RPU is typically 200k. The
application must ensure that it does not a load that affects the signal. It is
recommended to keep the load (RL) ≥2 Mohm.
Gx64 APPLICATION NOTE This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement.
Ce document est la propriété exclusive de WAVECOM. Il ne peut être communiqué ou divulgué à des tiers sans son autorisation préalable
Power Management
Page: 20/30
Other manuals for GX64
3
Table of contents
Other Wavecom Computer Hardware manuals