weintek cMT-G01 series Datasheet

Installation and Startup Guide
This document covers the installation of cMT-G01 Series, for the detailed specifications and operation,
please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
Electrical
Environment
The cMT-G01 Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise.
This does not guarantee noise immunity insevere cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the units are installed correctly and that the operating limits
are followed.Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Rail mounting: DIN rail 35mm
Panel mounting: Use two M4 or #8 panhead screws, mounting hole size is 4.6mm
Power Connections
System Settings
There are two ways to connect cMT-G01.
Connect through Ethernet 1: Connect cMT-G01 with a router using a RJ-45 cable, launch EasyBuilder Pro
on your computer, open Download window as shown in part 6 in this document to find this cMT-G01.
Connect through Ethernet 2: Connect cMT-G01 with a computer using a RJ-45 cable, assign IP address
192.168.100.2 to the computer, open a browser on the computer, and then enter IP address 192.168.100.1.
After connecting cMT-G01 successfully, use the default password “111111” to log in and configure
cMT-G01.
cMT-G01 series
Installation Instruction
NOTE:
Place the unit on a stable surface during
installation. Dropping it or letting it fall may
cause damage.
3
5
4
NOTE:
Connect positive DC line to the „+‟ terminal and
the DC ground to the „-‟ terminal.
1
2
(1) Installation Instruction, A4 double sided *1
(2) Power Connector *1
(3) cMT-G01 *1
(1)
(3)
(2)

Click the System Settings button and configure
cMT-G01.
The interface can be used to download or upload
project files.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your
project file, press F7 shortcut key to open
the download dialog box:
Select Ethernet > IP tab > Enter your cMT-G01
IP > Click Download to download this project
file to cMT-G01.
( Please refer to EasyBuilder Pro User Manual
for software operation details )
Communication Connection
9 Pin, Male, D-sub
COM1 [RS232]
COM2 [RS485]
COM3 [RS485]
Restore Factory Default
Press and hold on the Default button on the unit for more than 15 seconds to restore factory default.
The IP setting will be restored to default:
Ethernet 1: DHCP
Ethernet 2: 192.168.100.1
Please note that the projects and data stored in the unit are all cleared after pressing this button.
CAUTION
NN
Limited Warranty
This product is limited warranted against defects in design and manufacture. The proven
defective product will either be repaired or replaced, at Weintek‟s discretion. This warranty
shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.
PIN#
COM1
RS-232
COM2 RS-485
COM3
RS-485 2W
2W
4W
1
Data+
2
RxD
3
TxD
4
Data-
5
GND
6
Data+
Rx+
7
Data-
Rx-
8
Tx+
9
Tx-
6
7
8
CAUTION
NN
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.
NOTE: COM2 and COM3 RS-485 support MPI 187.5K, please use one at a time.
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GMECMG100_cMT-G01_Installation_161214
DANGER
Power
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply.The peak starting current can be as high as 500mA.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power.Aresettable fuse will
protect against overcurrent faults in DC circuit and the resetting will take place after a period of
time. Check wiring for proper connections and try to power up again.
High
Voltage
A resettable fuse will prevent damage for overcurrent condition however it isn‟t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using a HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.