Installation and Startup Guide
This document covers the installation of MT8102iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated (Indoor Only).
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel
from being deformed.)
Type
A(mm)
B(mm)
MT8102iE
260
202
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
Power Connections
System Settings
When HMI is powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
MT8102iE series
Installation Instruction
1
2
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.
NOTE:
1. Connect positive DC line to the ‘+’ terminal and
the DC ground to the ‘-’terminal.
2. When using a USB cable to download project
file, please do not connect HMI with PLC and PC
simultaneously to prevent potential difference from
destroying USB ports of HMI and PC.
(A)
(B)
Cutout
3
5
4
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(5) USB Stick Clamp & Tying Strap *1
(6) Fuse 1.25A/250V 5*20mm *1
(1)
(2)
(5) (3)
(6) (4)
https://www.xueplc.com/weinview-hmi-software-manual.html
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your
project file, press F7 shortcut key to open
the download dialog box:
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI.
( Please refer to EasyBuilder Pro User Manual
for software operation details )
Communication Connections
Con.B Con.A
COM1/COM3 [RS232] 9 Pin, Male, D-sub COM2/COM3 [RS485] 9 Pin, Female, D-sub
Jumper Settings
Please prepare a jumper cap for setting the jumpers.
Another way to enter touch screen calibration mode is: Press and hold anywhere on the screen for
more than 2 seconds when HMI starts.
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
PIN#
COM1
[RS232]
COM3
[RS232]
1
2
RxD
3
TxD
4
5
GND
6
7
RTS
TxD
8
CTS
RxD
9
GND
PIN#
COM2
[RS485]2w
COM2
[RS485]4w
COM3
[RS485]
1
Data-
Rx-
2
Data+
Rx+
3
Tx-
4
Tx+
5
GND
6
Data-
7
8
9
Data+
1-2
3-4
5-6
7-8
Mode
Short
Open
Open
Open
Touch Screen Calibration Mode
Open
Short
Open
Open
Hide HMI System Setting Bar
Open
Open
Short
Open
Boot Loader Mode
Open
Open
Open
Short
Not supported
Open
Open
Open
Open
Normal
NOTE: 1. COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at a time.
2. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.
6
7
8
CAUTION
NN
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.
Power
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power.An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
High
Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME8102E0_MT8102iE1_Installation_160318
DANGER
CAUTION
NN
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.

Other weintek Touch Terminal manuals

weintek MT8090XE Series User manual

weintek

weintek MT8090XE Series User manual

weintek MT8121 series User manual

weintek

weintek MT8121 series User manual

Popular Touch Terminal manuals by other brands

Compsee apex II Operating & programming manual

Compsee

Compsee apex II Operating & programming manual

impro technologies IMPROX I16 installation manual

impro technologies

impro technologies IMPROX I16 installation manual

Sharp UP-X500 installation manual

Sharp

Sharp UP-X500 installation manual

POSIFLEX KS - 6215N user manual

POSIFLEX

POSIFLEX KS - 6215N user manual

AddSecure IRIS-4 Technical reference manual

AddSecure

AddSecure IRIS-4 Technical reference manual

TransAct CampusCash Vx680 user guide

TransAct

TransAct CampusCash Vx680 user guide

Autonics SRHL1 Series product manual

Autonics

Autonics SRHL1 Series product manual

Cromemco 3100 Service manual

Cromemco

Cromemco 3100 Service manual

Smartmove WaveOn 738 troubleshooting guide

Smartmove

Smartmove WaveOn 738 troubleshooting guide

AML TRITON SVC-EW7500 quick start guide

AML

AML TRITON SVC-EW7500 quick start guide

bankSA EFTPOS Now Quick reference guide

bankSA

bankSA EFTPOS Now Quick reference guide

Shenzhen Chainway ITS Co. C4050-Q4 user manual

Shenzhen Chainway ITS Co.

Shenzhen Chainway ITS Co. C4050-Q4 user manual

NCR RealPOS 25 user guide

NCR

NCR RealPOS 25 user guide

CAN Albert Integration guide

CAN

CAN Albert Integration guide

Nematron iPC Series user guide

Nematron

Nematron iPC Series user guide

GESTRA URB 1 Original Installation Instructions

GESTRA

GESTRA URB 1 Original Installation Instructions

Datavan HiFive Series Quick installation guide

Datavan

Datavan HiFive Series Quick installation guide

Dover Triton 9600 Series Operation manual

Dover

Dover Triton 9600 Series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.