WINEL RM+ Instructions for use

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 1/ 24 Approved by: AvdV
Instructions &
Maintenance
Manual.
Incl. spare parts list.
T
Ty
yp
pe
e:
:
R
RM
M
+
+
T
Ty
yp
pe
e:
:
B
Bo
ol
le
er
ro
o

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 2/ 24 Approved by: AvdV
1. Table of content
Chapter
Content Page
1 Page index 2
2 General information 3
3 General product information 4
4 Types of Tank Vent Check Valves 5
5 Safety regulations 6
6 Installation, assembly- and disassembly instructions 7
7 Basic operation caracteristics 9
8 Recommended planned maintanance 10
9 Spare parts 13
10 Contact information 20
11 Other Winel B.V. products 21
12 Velocity and pressure characteristics 22

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 3/ 24 Approved by: AvdV
2. General information
manufactured by:
Winel B.V.
PO Box 70
9400 AB ASSEN
The Netherlands
Head office
Visiting address:
Dr. AF Philipsweg 55
9403 AD ASSEN
The Netherlands
Tel: +31 (0)592 366 060
Fax: +31 (0)592 340 833
e-mail: [email protected]
web: www.winel.nl
For the world wide network of agents, dealers and service support centres
please visit our web-site for morde information.

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 4/ 24 Approved by: AvdV
3. General product information:
3.1 The
WINEL B.V.
Tank Vent Check valves are designed and tested for a long
and trouble-free lifetime. However, to keep the valves in the best possible condition
we recommend maintenance as per enclosed maintenance instructions.
3.2. WINEL B.V. Tank Vent Check valves types RM ® and BOLEREO ® are made
of the finest materials in state-of-art manufacturing facilities.
Please understand that the WINEL B.V. Tank Vent Check valves have been
installed by the shipyard facility and will be used according owners instructions. As a
result Winel B.V. does not necessarily know the detailed application of the WINEL
B.V. Tank Vent Check valves. In respect to that fact WINEL B.V. cannot be held
responsible for any damage to the ship, its crew and/or its contents.
For the above-mentioned reason, installation and operating personnel should
carefully read the instructions on integrated systems before using the WINEL B.V.
Tank Vent Check valves.
3.3. WINEL B.V. Tank Vent Check valves work by means of a PE or SS (stainless
steel) floating ball situated in the ball holder compartment. In case (sea-) water enters
the WINEL B.V. Tank Vent Check valve the ball floats up to the Neoprene seat and
closes the tank.
3.4. WINEL B.V. Tank Vent Check valves can be used on amongst others
Ballast water tanks, Drinking water tanks, Fuel oil tanks, Lubricating Oil tanks,
Grey water tanks, to let air flow in and out the tank while preventing
overcoming (sea-) water to enter the tanks.
WINEL B.V. Tank Vent Check valves should NEVER
be used for any other purpose then indicated in these
instructions. In case of doubt, you are advised to consult
Winel B.V. and/or the surveyor responsible.
3.5. WINEL B.V. Tank Vent Check valves are not designed for overflow
purposes of fluids. While filling a.o. the ballast tanks, the responsible officer on the
vessel should prevent an overflow situation. In case of frequent or continuous
overflows with fluids the Neoprene seats and the floating balls may be damaged

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 5/ 24 Approved by: AvdV
4. Types of Winel B.V. tank vent check valves
Bolero RMO
RM1 RM2
RMD RMOE

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 6/ 24 Approved by: AvdV
5. Safety and Warranty
5.1. Abbreviations and symbols.
This symbol denotes safety precautions, the non-observance of which can
endanger persons and the environment.
This symbol denotes safety precautions, the non-observance of which can
endanger persons by electrical voltage.
This symbol marks an important note for the proper use of the system. The non-
observance of these notes can lead to damage or failures.
User tips and particularly useful information follow this symbol.
5.2. General safety instructions.
•Always READ INSTRUCTIONS BEFORE OPERATING any WINEL B.V.
product. Note: NOT following the instructions can endanger persons and the
environment.
•Be aware that screens installed in the valves might freeze in winter conditions.
Always check the free airflow of the valves, especially before filling or
emptying any tanks.
•Be aware that dust etc might pollute screens installed in the valves. Always
check the free airflow of the valves, especially before filling or emptying any
tanks.
5.3. Use of replacement- and spare parts.
Use only original WINEL B.V. parts or WINEL B.V. recommended parts. The use of
any other kind of parts may result in unsafe operations and severe damage to
equipment, operating personnel and the environment. All damages resulting from
using non-original parts are beyond the responsibility of WINEL B.V.
5.4 WINEL B.V. will only accept warranty claims if the maintenance instructions are
carefully followed and original Winel B.V. parts have been used. In case of neglected
maintenance procedures and mounting non-Winel B.V. parts, WINEL B.V. will not
accept any responsibility. Please note that a proper execution of these maintenance
instructions is the interest of the ship’s – and its crew’s safety and reliability.

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 7/ 24 Approved by: AvdV
6.
Installation, assembly- and disassembly instructions.
6.1 Installation
6.1.1. Type: RM / RMO / RM / RMOE;
•The valves have to be fitted properly on the flanges using fitting bolts in all
boltholes.
•Make sure a proper gasket is fitted between the two flanges.
•The valves have to be fitted in such a way that the in-/outlet is not blocked or
hindered to allow free flow.
•Always install the valves in accordance to the class society regulations.
6.1.2. Type Bolero:
•The valves have to be fitted properly on the flanges using fitting bolts in all
boltholes.
•Make sure a proper gasket is fitted between the two flanges.
•The valves have to be fitted in such a way that the in-/outlet is not blocked or
hindered to allow free flow.
•Always install the valves in accordance to the class society regulations.
•Always install the valve in such a way that the “hood” is facing forward
(See fig. 6.1.2.1).
If the valves need to be painted, make sure any screen is covered or
removed before painting. Paint on the screen can block, but will most certainly
reduce, the capacity of the valve and it’s flame-retarding function. Uncover and clean
the screen before replacing it after painting.
6.2 Dis- and assembly:
6.2.1 Type RM etc.
See fig. nr 6.2.1.2
6.2.2 Type Bolero
See fig. nr 6.2.1.3

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 8/ 24 Approved by: AvdV
Fig. 6.1.2.1
“HOOD” of BOLERO always facing forward.
Fig. 6.1.2.2
Fig. 6.1.2.3

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 9/ 24 Approved by: AvdV
7. Basic Operation Characteristics.
WINEL B.V. Tank Vent Check valves work by means of a PE or SS (stainless steel)
floating ball situated in the ball holder compartment. When seawater enters the
WINEL B.V. Tank Vent Check valve the ball floats up to the Neoprene seat, closing
the tank.
The floating balls and Neoprene gaskets are subject to wear and tear. Check
operation of the parts regularly. The Winel B.V. Tank Vent Check valves are
designed and tested for a long and trouble-free lifetime. However to keep the valves
in the best possible condition under the corrosive conditions at sea keep all metal
part well coated.
7.1. Type RM / RMO:
For velocity and pressure characteristics see from page 22
7.2. Type Bolero:
For velocity and pressure characteristics see from page 22

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 10/ 24 Approved by: AvdV
8. Recommended regular Maintenance:
8.1. ROUTINE MAINTENANCE & INSPECTION TABLE
Item monthly 1 year 2 years 6 years 8-10 years
Screen
Seat
Float ball
Complete valve
= inspection / replace when damaged = clean
= replace
This is a recommended maintenance - and inspection table for general use.
In case of special conditions, the inspection frequency has to be intensified. Screens
may become polluted sooner, therefore we recommend regular sampling of screens.
In case of hindering pollution on the screens, intensify the screen-cleaning table.
This frequency has to be determined by the ship’s management
8.2. Inspection of the float ball and seal
While inspecting the float ball also inspect the neoprene seal inside the top of the
valve. The seal is a neoprene ring glued to the valve. If the floating ball is damaged,
replace it. If the seal has been damaged or if it is loose, replace it.
8.3. Steps to take (also see Chapter 6.2.)
1) Remove one of the cover plates on one of the sides of the valve.
2) Remove the screen if present.
3) Take out the float ball, inspect for surface damages and check if the float ball
is still round.
4) If the float ball has been damaged, replace it.
5) Mount the cleansed screen and cover plates, use new bolts.
6) Make sure the screen is properly mounted.

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 11/ 24 Approved by: AvdV
If the valve has been damaged by rust or corrosion check for holes in the
valve body. When holes are discovered the valve has to be replaced.
8.4. Exchange of the neoprene seat
•Remove the used seal.
•Remove the glue-remainder with a filling-knife or by sandpapering.
•Clean both surfaces by sandpapering carefully.
•Both surfaces need to be dry, dust free and grease free.
•Mix the glue and hardener.
oThe proportion hardener: glue equals to 1:20.
oSafety precautions: wear suitable gauntlets do not inhale vapour.
•Apply the glue with a paintbrush or spatula on both surfaces(the rubber seal and
the surface of the valve). The best adhesion of the glue on both surfaces will be
achieved in 15-30 minutes drying time after adding the hardener.
•It is recommended to apply the glue twice on both surfaces with a short break of
10 minutes.
•Wait until the glue gets sticky (approximately 10 minutes).
•Apply the seal on the valve.
During load line-surveys/classification the valves have to be
examined upon correct functioning. In practice this means
that the valves have to meet the following requirements:
The valves may not have been rusted through
The ball has to be in good condition
The seat has to seal
If present the screen may not have been painted tight
or polluted by other substances
To examine the valves upon these requirements mind the following:
•The cover plate of type RM must be removed
•
The ball holder of type Bolero must be removed

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 12/ 24 Approved by: AvdV
For reasons of safety, complete replacement of the valve is recommended after
8-10 years.
Note:
Repair costs can go beyond
purchasing costs of a new valve.
Please contact WINEL B.V. sales department or your
local representative for up-dated price information.

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 13/ 24 Approved by: AvdV
9. SPARE PARTS
Float ball
See PE Float Balls and
Stainless Steel Float Balls
Seal
See Neoprene seals 10
mm
Glue, two-components,
base and hardener
See Glue
Repair kit
The repair kits consist of float balls,
seals and taptipe bolt sets
See Repair kits
Cover plate steel galvanised
(example type RM)
See Cover Plates Steel Galvanised
Screen kit for type Bolero
The screen kits consist of screens
and taptipe bolt sets
See Screen kits
Screen kit for remaining types
The screen kits consist of screens
and taptipe bolt sets
See Screen kits

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 14/ 24 Approved by: AvdV
9.1. PE Float Balls
Size Suitable for tank vent check valve type … Article code
50 mm 9553.1010.050
70 mm Bolero DN 40 / DN 50 9553.1010.070
75 mm 9553.1010.075
85 mm RM / RMO/E DN 40 / DN 50; Bolero DN 65 9553.1010.085
100 mm Bolero DN 80 9553.1010.100
115 mm 9553.1010.115
120 mm RM / RMO/E DN 65 / DN 80 9553.1010.120
130 mm Bolero DN 100 9553.1010.130
145 mm RM / RMO/E DN 100 9553.1010.145
150 mm 9553.1010.150
155 mm Bolero DN 125 9553.1010.155
175 mm 9553.1010.175
185 mm RM DN 125 / DN 200; RMO/E DN 125; Bolero DN 150 9553.1010.185
240 mm RM DN 150 / 175 / 250 RMO/E DN 150 / 175 Bolero DN 200
9553.1010.240
300 mm RM DN 300 RMO/E DN 200 Bolero DN 250 / DN 300 9553.1010.300
325 mm RM DN 350 / DN 400 RMO/E DN 250 Bolero DN 350 9553.1010.325
340 mm 9553.1010.340
360 mm RM DN 450 RMO/E DN 300 9553.1010.360
400 mm 9553.1010.400
Prices on request

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 15/ 24 Approved by: AvdV
9.2. Stainless Steel Float Balls
Size Suitable for tank vent check valve type … Article code
50 mm 9553.1050.050
70 mm Bolero DN 40 / DN 50 9553.1050.070
75 mm 9553.1050.075
85 mm RM / RMO/E DN 40 / DN 50; Bolero DN 65 9553.1050.085
100 mm Bolero DN 80 9553.1050.100
115 mm 9553.1050.115
120 mm RM / RMO/E DN 65 / DN 80 9553.1050.120
130 mm Bolero DN 100 9553.1050.130
145 mm RM / RMO/E DN 100 9553.1050.145
150 mm 9553.1050.150
155 mm Bolero DN 125 9553.1050.155
175 mm 9553.1050.175
185 mm RM DN 125 / DN 200; RMO/E DN 125; Bolero DN 150 9553.1050.185
240 mm RM DN 150 / 175 / 250; RMO/E DN 150 / 175; Bolero DN 200
9553.1050.240
300 mm RM DN 300; RMO/E DN 200; Bolero DN 250 / DN 300 9553.1050.300
325 mm RM DN 350 / DN 400; RMO/E DN 250; Bolero DN 350 9553.1050.325
340 mm 9553.1050.340
360 mm RM DN 450; RMO/E DN 300 9553.1050.360
Prices on request

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 16/ 24 Approved by: AvdV
9.3. Neoprene seals 10 mm
Suitable for tank vent check valve type … Article code
Bolero DN 40 9553.1511.040
Bolero DN 50 9553.1511.050
Bolero DN 65 9553.1511.065
Bolero DN 80 9553.1511.080
Bolero DN 100 9553.1511.100
Bolero DN 125 9553.1511.125
Bolero DN 150 9553.1511.150
Bolero DN 200 9553.1511.200
Bolero DN 250 9553.1511.250
Bolero DN 300 9553.1511.300
Bolero DN 350 9553.1511.350
RM / RMD DN 40 / DN 50 9553.1515.040
RM / RMD DN 65 / DN 80 9553.1515.065
RM / RMD DN 100 9553.1515.100
RM / RMD DN 125 9553.1515.125
RM / RMD DN 150 / DN 175 9553.1515.150
RM / RMD DN 200 9553.1515.200
RM / RMD DN 250 9553.1515.250
RM / RMD DN 300 9553.1515.300
RM / RMD DN 350 9553.1515.350
RM / RMD DN 400 9553.1515.400
RM / RMD DN 450 9553.1515.450
RMO/E DN 40 / DN 50 9553.1519.040
RMO/E DN 65 / DN 80 9553.1519.065
RMO/E DN 100 9553.1519.100
RMO/E DN 125 9553.1519.125
RMO/E DN 150 / DN 175 9553.1519.150
RMO/E DN 200 9553.1519.200
RMO/E DN 250 9553.1519.250
RMO/E DN 300 9553.1519.300
Prices on request
9.4. Glue, two-components, base and hardener, for tank vent check
valves
(neoprene seal 10 mm)
Size Article code
1 litre can 9553.25

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 17/ 24 Approved by: AvdV
9.5. Cover Plates Steel Galvanised
Suitable for tank vent check valve type … Article code
RM DN 40 / DN 50 9553.2010.040
RM DN 65 / DN 80 9553.2010.065
RM DN 100 9553.2010.100
RM DN 125 9553.2010.125
RM DN 150 / DN 175 9553.2010.150
RM DN 200 9553.2010.200
RM DN 250 9553.2010.250
RM DN 300 9553.2010.300
RM DN 350 9553.2010.350
RM DN 400 9553.2010.400
RM DN 450 9553.2010.450
RM DN 500 9553.2010.500
RMD DN 40 / DN 50 9553.2050.040
RMD DN 65 / DN 80 9553.2050.065
RMD DN 100 9553.2050.100
RMD DN 125 9553.2050.125
RMD DN 150 / DN 175 9553.2050.150
RMD DN 200 9553.2050.200
RMD DN 250 9553.2050.250
RMD DN 300 9553.2050.300
RMD DN 350 9553.2050.350
RMD DN 400 9553.2050.400
RMD DN 450 9553.2050.450
RMO DN 40 / DN 50 9553.2090.040
RMO DN 65 / DN 80 9553.2090.065
RMO DN 100 9553.2090.100
RMO DN 125 9553.2090.125
RMO DN 150 / DN 175 9553.2090.150
RMO DN 200 9553.2090.200
RMO DN 250 9553.2090.250
RMO DN 300 9553.2090.300
Prices on request

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 18/ 24 Approved by: AvdV
9.6. Repair kits
Contents: float balls, seals and taptide bolts
Suitable for tank vent check valve type … Article code
BOLERO DN 40 9553.3010.040
BOLERO DN 50 9553.3010.050
BOLERO DN 65 9553.3010.065
BOLERO DN 80 9553.3010.080
BOLERO DN 100 9553.3010.100
BOLERO DN 125 9553.3010.125
BOLERO DN 150 9553.3010.150
BOLERO DN 200 9553.3010.200
BOLERO DN 250 9553.3010.250
BOLERO DN 300 9553.3010.300
BOLERO DN 350 9553.3010.350
RM/RMD DN 40 / DN 50 9553.3050.040
RM/RMD DN 65 / DN 80 9553.3050.065
RM/RMD DN 100 9553.3050.100
RM/RMD DN 125 9553.3050.125
RM/RMD DN 150 / DN 175 9553.3050.150
RM/RMD DN 200 9553.3050.200
RM/RMD DN 250 9553.3050.250
RM/RMD DN 300 9553.3050.300
RM/RMD DN 350 9553.3050.350
RM/RMD DN 400 9553.3050.400
RM/RMD DN 450 9553.3050.450
RMO DN 40 / DN 50 9553.3090.040
RMO DN 65 / DN 80 9553.3090.065
RMO DN 100 9553.3090.100
RMO DN 125 9553.3090.125
RMO DN 150 / DN 175 9553.3090.150
RMO DN 200 9553.3090.200
RMO DN 250 9553.3090.250
RMO DN 300 9553.3090.300
•Additional: glue, two-components, base and hardener; to use for 40-60
pcs. valves
•If applicable: screen kit
Prices on request

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 19/ 24 Approved by: AvdV
9.7. Screen kits
Contents: screens and taptide bolts
Suitable for tank vent check valve type … Article code
BOLERO DN 40 9553.3510.040
BOLERO DN 50 9553.3510.050
BOLERO DN 65 9553.3510.065
BOLERO DN 80 9553.3510.080
BOLERO DN 100 9553.3510.100
BOLERO DN 125 9553.3510.125
BOLERO DN 150 9553.3510.150
BOLERO DN 200 9553.3510.200
BOLERO DN 250 9553.3510.250
BOLERO DN 300 9553.3510.300
BOLERO DN 350 9553.3510.350
RM/RMD DN 40 / DN 50 9553.3550.040
RM/RMD DN 65 / DN 80 9553.3550.065
RM/RMD DN 100 9553.3550.100
RM/RMD DN 125 9553.3550.125
RM/RMD DN 150 / DN 175 9553.3550.150
RM/RMD DN 200 9553.3550.200
RM/RMD DN 250 9553.3550.250
RM/RMD DN 300 9553.3550.300
RM/RMD DN 350 9553.3550.350
RM/RMD DN 400 9553.3550.400
RM/RMD DN 450 9553.3550.450
RMO DN 40 / DN 50 9553.3590.040
RMO DN 65 / DN 80 9553.3590.065
RMO DN 100 9553.3590.100
RMO DN 125 9553.3590.125
RMO DN 150 / DN 175 9553.3590.150
RMO DN 200 9553.3590.200
RMO DN 250 9553.3590.250
RMO DN 300 9553.3590.300
Prices on request

Instructions & Maintenance
Manual
Tank Vent Check Valves.
WINEL B.V.
P.O. Box 70, 9400 AB Assen,
Dr AF Philipsweg 55, 9403 AD Assen,
The Netherlands
Tel. 31 (0)592 366060, Fax 31 (0)592 340833
E-mail:[email protected]
http://www.winel.nl
Rev: D Written: GdH / MT
Checked by: YX
Date: 25-03-2009 Page: 20/ 24 Approved by: AvdV
10. HOW TO CONTACT WINEL B.V. (AFTER-) SALES DEPARTMENT
10.1. Ordering spare parts:
For a quick transaction of your spare parts order please use the example
shown below:
EXAMPLE
Quantity : …
Article code : … (see spare parts lists)
Description : … (see spare parts lists)
10.2.Ordering service:
Please use the example shown below:
EXAMPLE
Name of vessel : M/V …
Yard / hull number : …
WINEL B.V. original order number: …
Reason for ordering service* : inspection 5 pcs. tank vent check valves
E.T.A. : 15-01-2003 6.00 hrs.
E.T.D. : 17-01-2003 18.00 hrs.
Harbour : …(place)..., harbour no. ..., …
Tel. or fax no. agent / ship : …
*(description of malfunction)
You can contact us by:
Phone : 31-(0)592-366060
Fax : 31-(0)592-340833
Visit our web site : http://www.winel.nl
This manual suits for next models
6
Table of contents