XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL... User manual

XFP
NETWORKABLE
ANALOGUE
ADDRESSABLE
FIRE ALARM
CONTROL PANEL
user manual
and log book
approved document no. DFU2000501 Rev 2

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 2 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CONTENTS
Important safety notes ........................................................................................................3
Introduction ..........................................................................................................................4
Fire alarm systems - an overview ....................................................................................................................4
The XFP fire alarm control panel ....................................................................................................................4
An overview of the panel’s access levels ........................................................................................................4
User responsibilities ..............................................................................................................5
Panel layout, indicators and controls..................................................................................6
General user operation ........................................................................................................8
(Messages that may appear on the panel’s display and what they mean)
Normal conditions ............................................................................................................................................8
Fireconditions ..................................................................................................................................................9
1st-stage fire conditions ................................................................................................................................10
Pre-alarmconditions ......................................................................................................................................11
Fault conditions ..............................................................................................................................................11
Access level 1 (general user) controls and menu options ..............................................12
Displaying fire, fault, disablement and test events ....................................................................................12
Testing the panel’s lamps (its indicators and liquid crystal display) ..........................................................13
Displaying the panel’s alarm counter ............................................................................................................13
Access level 2 (authorised user) controls and menu options..........................................14
Silencing the alarm sounders ........................................................................................................14
Resounding the alarmsounders....................................................................................................14
Resetting the panel ........................................................................................................................14
Displaying fire, fault, disablement and test events ....................................................................................15
Testing the panel’s lamps (its indicators and liquid crystal display) ..........................................................15
Displaying and/or clearing the panel’salarmcounter ................................................................................15
Changing the panel’s time and date ............................................................................................................16
Printing, displaying and/or resetting the panel’s event log ........................................................................16
Disabling or enabling parts of the system ....................................................................................................17
Changing the access level 2 entrycode ........................................................................................................19
System set-up data chart....................................................................................................20
Firealarm log book ............................................................................................................21
Installation certificate ........................................................................................................27
Commissioning certificate..................................................................................................28

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 3 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
IMPORTANT SAFETY NOTES
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s
instructions and used in accordance with this manual.
Hazardous voltages are present inside the panel - DO NOT open it unless you are qualified and
authorised to do so. There is no need to open the panel’s enclosure except to carry out commissioning,
maintenance and remedial work. This work must only be carried out by competent service personnel
who are fully conversant with the contents of the panel’s separate engineering manual and have the
necessary skills for maintaining this equipment.
Ifthe enclosure is damaged in any way, expert advice should be sought regarding its repair.
Regular servicing of the fire alarm system is highly recommended, preferably on a continuous mainte-
nance contract and by a competent organisation. A fully-itemised report of the installation should be
obtained at least annually.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole.
The manufacturer’s policy is one of continuous improvement and we reserve the right to make
changes to product specifications at our discretion and without prior notice. E&OE.

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 4 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
INTRODUCTION
Fire alarm systems - an overview
The primary purpose of a fire alarm system is to provide an early warning of a fire so that people
and animals can be evacuated and action taken to stop the fire as soon as possible - all according to
apredetermined plan.
Alarms may be raised automatically, by smoke or heat detectors, or manually by a person operating
amanual call point.
To ensure an alarm is dealt with in an orderly manner, it is important to know where the alarm is
coming from. To aid this function, fire alarm systems are usually split into zones, each covering a
different area of a building.
When an alarm has been raised, the panel responds by indicating the zone(s) in which the alarm has
occurred and activating all relevant outputs (sounders, bells, strobes, beacons, relays, etc) to provide
awarning of the fire.
The XFP fire alarm control panel
The XFP is an intelligent ‘addressable’ fire alarm panel designed to work with a wide range of
intelligent fire detection devices. As such, it is able to provide much more detailed information
about a fire condition than just the number of the activated zone.
As well as giving prioritised feedback on the status of the system, its easy-to-read 80-character dis-
play will indicate the name and location of every detector that has responded to a fire and also
show the order in which they went into alarm.
It will also display detailed information on any pre-alarmand/or fault conditions that arise and can
be programmed to operate in a number of different ways to help reduce the incidence of false
alarms and to encourage the orderly evacuation of a building in a true fire condition.
Controls areavailable that will allow authorised users to silence or reset a fire condition, to disable
or enable parts of the system to suit prevailing conditions, to change the time the system enters day
(building occupied) and night (building unoccupied) mode and to test the panel’s indicators and
liquid crystal display to ensurethey areworking correctly.
All of these functions - and more - are explained in detail in this user manual.
An overview of the panel’s access levels
Three access levels areavailable at the panel - access level 1 (general user), access level 2 (authorised
user) and access level 3 (engineer).
Access level 1 is the normal user level which is accessible to everyone. At this level you can:-
•Scroll through any fire, pre-alarm and fault conditions that are displayed on the panel’s display
•View any disablements or zones that arebeing tested (if applicable)
•Test the panel’s lamps (its LED indicators and display) to ensure they are working correctly
•Determine the total number of times the panel has been in a fire condition
•Gain entryto access level 2 (authorised user level) and, if you are an engineer, access level 3.
Access level 2 is the authorised user level which is available to authorised, trained personnel only.
Access to this level on push button versions of the panel requires the input of a special four-digit code.
On keyswitch versions, access is gained by turning the panel’s keyswitch to the armed position.
At access level 2, the panel’s silence, reset and investigate buttons become active and users are able to:
•Scroll through any fire, pre-alarm or fault conditions that are displayed on the panel’s display
•View any disablements or zones that are being tested (if applicable)
•Enable or disable zones, sounders, outputs, relays and devices (as appropriate)
•Print, display and/or reset the panel’sevent history
•Set the time and date
•Change the entry code to access level 2 from its factory default.
Access level 3 is the panel’s engineering/programming level. On no account should access level 3 be
accessed by anyone but an authorised system engineer. A fire panel is a piece of life safety equipment
and unauthorised access may affect the way the panel functions, endanger life and void its warranty. If
you are an authorised engineer, details of access level 3 can be found in the panel’s separate
Engineering manual.

USER RESPONSIBILITIES
BS5839-1: 2002 is the British Standard code of practice for the design, installation, commissioning
and maintenance of fire detection and fire alarm systems for buildings. Section 7 of the standard
(User Responsibilities) states that a named responsible person should be appointed to supervise all
matters pertaining to the fire alarm system {clause 47.2a}.
Highlighted below is a summary of the main functions the responsible person is expected to carry
out with regard to BS5839-1: 2002 only. It does not highlight any other responsibilities that may be
required of the user or responsible person that are listed in documentation such as the Employers
Guide to Fire Safety, the Fire Precautions (Workplace) regulations and/or any other legislation rele-
vant to the premises. If in doubt, the fire authority can advise on the fire legislation that applies to
any given building. For countries outside the UK, different user responsibilities may apply.
BS5839-1: 2002 states the responsible person should:
(The bracketed numbers {xx} identify the BS5839-1: 2002 clauses to which the summary refers).
1Ensure the fire alarm panel is checked daily to confirm there are no faults on the system {47.2b}
2Ensure arrangements are in place for the test, maintenance and regular servicing of the system with
regard to Section 6 of the standard {47.2c}. Important: Clause 44 of BS5839-1: 2002 recommends weekly
and monthly tests that should be carried out by the responsible person. See below for details.
3Ensure the system log book is kept up to date by recording fire signals, fault signals, work on the system,
etc, and make sure it is available for inspection at all times {47.2d / 48}
4Ensure all relevant occupants of the premises are instructed in the proper use of the system {47.2e}
5Take steps to limit the number of false alarms on the system {47f}
6Ensurethe effectiveness of the system is not impaired by ensuring thereis a space of at least 500mm in
all directions around and below every fire detector and that all manual call points are unobstructed and
easy to see {47g}
7Liaise with all relevant building engineers, decorators, etc., to ensureany changes to (or maintenance of),
the building’sfabric does not compromise the protection given by the firealarm system, create faults or
false alarms {47h}
8Ensure that any structural or occupancy changes planned for the building are done so with due and early
consideration given to any changes that may be required to the firesystem {47h}
9Ensurethat a selection of spareparts are held as appropriate within the premises {47j}
Routine weekly and monthly testing to be undertaken by the user/responsible person
To meet the requirements of Clause 44 of BS5839-1:2002 we recommend the following tests are carried
out at approximately the same time each week, during normal working hours:-
Note: It is essential any alarm receiving centre is contacted before and after these tests to avoid unwanted
alarms and to confirm the fire signal is correctly received.
•Carryout an Indicator lamp test to check all zone lights show and the beeper sounds.
•Operate a manual call point or smoke/heat detector to test the fire alarm.
•Check that the alarmsounders operate.
•Reset the system by pressing the Silence/Activate Sounders button and Control Panel Reset button.
•Verify that no manual call points or smoke/heat detectors are obstructed in any way.
•Test a different zone each week using a different call point or detector so all are tested in rotation.
Monthly attention: Ensure authorised service personnel verify the system’s standby power supply (or
supplies) arein good working order.
Quarterly and periodic inspection, testing, servicing and maintenance
It is the user’s responsibility to ensure that an ongoing periodic plan is in place that meets Clause 45
(Inspection and Maintenance) of BS5839-1:2002. The work required to meet this Clause must be carried
out by a competent person with specialist knowledge of fire detection and alarm systems. The standard
recognises this will normally be an outside specialist fire alarm servicing organisation.
Please note: the above summaries do not replace Sections 6 and 7 of BS5839-1: 2002 but are intended to help the user gain a greater under-
standing of his or her responsibilities. We strongly recommend the named responsible person familiarises themselves with the full standard,
copies of which are available from your local reference library or can be purchased from the British Standards Institute, Customer Services
Dept., 389 Chiswick High Road, London, W4 4AL. Tel: +44 (0)20 8996 9001. Web: www.bsi-global.com
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 5 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

PANEL LAYOUT, INDICATORS & CONTROLS
Layout of single loop 16 zone fire panel (code entry version)
Layout of one to two loop 32 zone fire panel (code entry version)
10:59:03 24 Jun : Normal
FREDCO WAREHOUSING
10:59:03 24 Jun : Normal
FREDCO WAREHOUSING
LED Indicators
Liquid crystal display Provides detailed information on the status of the fire alarm system, see pages 8-11
General Fire Flashes red when there is a fire condition on any zone and goes steady red
when the alarmis silenced. Subsequent fireconditions will restartthe General
FireLED flashing until it is silenced again
FireZones LEDs One or more of these LEDs will flash red in an alarm condition (to show
(1-16 or 1-32) which zone(s) the fire is in) and will go steady when silenced
Supply Present Normally lit green to show that all of the panel’s power supplies are
functioning correctly
Test Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
for any other test condition
XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 6 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

Accessed Lit yellow when the panel is in access level 2 or 3
General disablement Lit yellow when one or more zone, sounder, output or relay is disabled
Phased evacuation Flashes yellow when there is a phased evacuation in process
General fault Flashes yellow when there is a fault condition on the panel. Will always
be lit in conjunction with at least one other fault LED
Power supply fault Lit yellow when the panel’s power supply or mains has failed or the panel’s
standby battery is in poor condition
System fault Lit yellow when a system error, such as a microprocessor fault, occurs. Remains
lit even if the panel automatically clears the fault
Sounder status Flashes yellow if there is a faulty sounder or a sounder disablement anywhere
onthe system
Delays Lit yellow when one or more output delays have been programmed into the panel.
Flashes yellow when one or more output delay is running.
Button controls
More Information Displays additional information on any fire, pre-alarm or fault conditions
that appear on the panel’s display
Silence Internal Sounder Silences the panel’s internal sounder
Menu Provides access to the panel’s user menus
Scroll up / down Dependent on the status of the panel, these buttons:-
56 •scroll vertically through any fire, pre-alarm or fault conditions that appear
on the panel’sdisplay
•scroll vertically through the panel’s user menus
•manipulate date, time and disablement settings, etc
•serve as code input buttons to access levels 2 or 3
Escape / accept Dependent on the status of the panel, these buttons:-
34 •scroll horizontally through the panel’s user menus
•escape or accept options available in the panel’suser menus
•serve as code input buttons to access levels 2 or 3
Silence / Resound Sounders Silences or resounds the system’s sounders (access levels 2 & 3 only)
Control Panel Reset Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Investigate Starts the panel’s investigate timer function (access levels 2 & 3 only). Only
available if the panel’s investigate timer function has been enabled by an
engineer.
Keyswitch control (if fitted)
Turning the keyswitch to the armed position gives the user instant access
to access level 2 (authorised user level).
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 7 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

GENERAL USER OPERATION
(
(M
ME
ES
SS
SA
AG
GE
ES
ST
TH
HA
AT
TM
MA
AY
YA
AP
PP
PE
EA
AR
RO
ON
NT
TH
HE
EP
PA
AN
NE
EL
L’
’S
SD
DI
IS
SP
PL
LA
AY
YA
AN
ND
DW
WH
HA
AT
TT
TH
HE
EY
YM
ME
EA
AN
N)
)
At access level 1, the panel’s display provides feedback on the system’s current status. Priority is always
given to the most important current event, i.e. fire conditions will override pre-alarms and/or fault
conditions. This section (pages 8-11) outlines the various messages that may be displayed, what they
mean and what action is required.
NORMAL CONDITIONS
In normal mode (when no fires, faults or pre-alarms are occurring), one of the following messages
will be displayed at the panel:-
Normal is displayed when there are no fires, faults or pre-alarms on the system and the panel’s
day/night (building occupied/unoccupied) facility HAS NOT been set up by the system engineer.
Normal: occupied is displayed when there are no fires, faults or pre-alarms on the system and the
panel is in day (building occupied) mode.
Normal: unoccupied is displayed when there are no fires, faults or pre-alarms on the system and
the panel is in night (building unoccupied) mode.
Day/night (building occupied/unoccupied) settings are normally programmed into the panel by a
system engineer. They allow the system to operate differently dependent on the time of day with,
for example, different detector sensitivity settings and lower sounder volumes. If required, autho-
rised users can manually alter the time the panel enters day and night mode using the access level 2
menu options - see pages 14-19.
Outputs delayed is displayed if one or more delays to outputs have been programmed into the
panel. It indicates that certain outputs (which may include sounders, relays and/or output units) will
not trigger in the event of a fire alarm condition for a set period of time, as programmmed by the
system engineer. Pressing the more information button in a fire alarm condition will give more
information about delays.
Disablements active is displayed if one or more disablements have been programmed into the
panel by an authorised user or engineer. If required, you can view these disablements at access level
1 (or, if you are an authorised user, you can cancel them (or set additional disablements) at access
level 2.
Zone tests active is displayed if one or more of the fire alarm system’s zones have been pro-
grammed into test mode by an authorised engineer. When a zone is in test mode, any fire alarm
conditions raised on it WILL NOT be reported to the panel in the normal way. As such, this message
should only appear when an engineer is working on the system. If required, you can view which
zones are in test mode at access levels 1 or 2. Zones can only be taken out of test mode by an
authorised engineer.
Calibrating... is displayed if automatic adjustments are taking place to allow the system’s smoke
and heat detectors to perform at their optimum level. Normally, this message only appears at 04:00
hours although it is possible that an engineer may have programmed this to happen at an alterna-
tive time. Whilst calibrating, the display will list the ID code of the device being calibrated, i.e. “L:1
D:154” and the system will not return to normal until the process is complete.
XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 8 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Time Date System status
Site specific text
12:10:34 10 JUL :Normal
FREDCO WAREHOUSING
Options
:Normal
:Normal: occupied
:Normal: unoccupied
:Outputs delayed
:Disablements active
:Zone tests active
:Calibrating

FIRE CONDITIONS
In the event of a fire condition:-
• the panel’s general fire indicator will flash;
• the panel’s internal sounder (if enabled) will pulse;
• the relevant Fire Zone indicator on the panel will flash;
• the panel’s display will show the number and name of the zone in fire (see example below); and
• the system’s sounders, relays and other output devices will operate as programmed.
Pressing the more information button will display the actual device that has triggered
the fire condition, for example:-
If more than one device is in a fire
condition on the zone, the top left
corner of the display will show, for
example “1 of 3” and can be scrolled
through using the 5and 6buttons.
In the event of a fire condition on multiple zones:-
• the panel’s general fire indicator will flash, its internal sounder (if enabled) will pulse and its
relevant Fire Zone indicators will flash;
• the panel’s display will show the first and last zones that went into fire together with the total
number of zones that are in fire. For example, if a fire condition has occurred in zones 1, 2 and 3
in that order, the display will show a message similar to the one below.
• the system’s sounders, relays and other output devices will operate as programmed.
To view any additional zones that are in fire, press the 5or 6buttons as appropriate. The display
will continue to show the last zone that went into fire but all previous zones will now appear on a
step-by-step basis with details of which order they went into fire, i.e. 1st zone, 2nd zone, etc.
Pressing the more information button at any time will give you details of the actual device(s) that
are in a fire condition on the zone that is on the top line of the display. These can be scrolled
through using the 5and 6buttons.
In the event of a fire condition, the building’s fire management plan should
always be executed.
Authorised users can silence or reset the system as appropriate by entering access level 2 and
pressing the buttons on the panel’s front. Details on how to do this can be found on page 14.
FIRE CONDITIONS WITH OUTPUT DELAYS
If a fire condition occurs on a zone that has been programmed with one or more output delays, the
panel will report the fire condition as described above but the panel’s delays LED will flash yellow
to indicate that one or more of the zone’s assigned outputs has not yet triggered. Details of which
outputs have delays running can be viewed by pressing the more information button.
XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 9 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Total number of
zones in fire
Last zone:
1 Zones
1:North Stairs :FIRE!
Number of zone in fire Name of zone in fire System status
1st Zone: 1: North Stairs
Lastzone: 3: Ground Floor
:FIRE!
3 Zones
1 of 1 Alarms in: Zone 1
North stairs : Detector near exit
Number of activated
devices within the zone Number of zone in fire
Name of zone in fire Device description
i

1ST-STAGE FIRE CONDITIONS
On sites where there is a high incidence of nuisance alarms or where the consequence of a false
alarm could result in the activation of, say, a sprinkler system, the fire officer may have permitted
certain zones to be set up with:-
• a 1st-Stage zone dependency function - to prevent the zone going into full alarm until certain
other events have occurred on the same zone, such as a second device going into alarm; or
• a 1st-Stage investigation delay period - to give the user time to investigate the cause of an
alarm before a full alarm is initiated.
Details of any zones set up with 1st-Stage alarm function will appear on the system set-up data chart
on page 20, provided it has been completed by the system engineer.
In the event of a 1st-Stage fire condition (zone dependency or investigation delay):-
• the panel’s internal sounder (if enabled) will pulse;
• the relevant Fire Zone LED on the panel will flash;
• the panel’s display will show the number and name of the last zone which entered a “1st-Stage”
fire condition (see example below).
If the 1st-Stage alarm is in a zone set up with a zone dependency function:-
Press the more information button to display the actual device that has triggered the
1st-stage fire condition (the display will also confirm that the panel is waiting for a
confirmatory signal before going into full alarm). Pressing the more information again
will show how long is left before the panel auto-resets (returns to normal mode) should a
confirmatory signal not be received.
If the 1st-Stage alarm is in a zone set up with an investigation delay period:-
Press the more information button to display the actual device that has triggered the
1st-stage fire condition (pressing more information again will count down how long you
have to invoke the zone’s investigation delay period before it goes into full alarm)
To start the zone’s investigation delay period:-
Enter access level 2 (see page 14) and press the investigate button. The period the
investigation delay runs for will be as programmed by the system engineer. Pressing more
information after the investigate button has been pressed will display how long is left before
the investigation period expires and the zone goes into full alarm
If upon investigation you discover the fire condition is correct, you can override the delay by activat-
ing any manual call point in that zone.
Should any additional detection device(s) be activated in the zone being investigated during the
recognition or delay periods, the panel will automatically put the zone into full alarm.
Should you discover the fire condition is false, you can silence or reset the 1st-stage fire condition at
access level 2 (see page 14) and take appropriate action to clear the nuisance alarm.
In effect, the 1st-Stage delay on a zone set up for investigation comprises two delays - the initial recognition
period (where the user is expected to acknowledge the delay) followed by the investigation period itself.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 10 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Total number of
zones in 1st stage fire
Last zone:
1 Zones
1:Ground Floor 1st-Stage
Number of zone in
1st stage fire Name of zone in
1st stage fire System status
i
i

PRE-ALARM CONDITIONS
Pre-alarm conditions are designed to warn the user that a smoke or heat detector is registering an
increase in conditions that could lead to a fire. Pre-alarms must be taken seriously as a fire condition
could be imminent.
In the event of a pre-alarm condition:-
• the panel’s internal sounder (if enabled) will pulse;
• the panel’s display will show details of the smoke or heat detector which is in pre-alarm, for example:
Should there be more than one
detector in pre-alarm, the top right
hand corner of the display will read
‘More. ↑
↑↓
↓’ and can be scrolled
through using the panel’s 5or 6
buttons
FAULT CONDITIONS
If a part of the fire alarm system fails due to detector failure, wiring fault, etc:-
• one or more of the panel’s fault indicators will flash;
• the panel’s internal sounder (if enabled) will pulse;
• the panel’s display will show an appropriate fault message (in the case of a faulty manual call
point, for example, the zone on which the faulty call point is located will be displayed):-
Should there be more than one fault
condition, the top right side of the
display will read ‘More. ↑
↑↓
↓’ and you
can scroll through them using the
panel’s 5or 6buttons.
Press the more information button to view additional details about the displayed fault. For
device specific faults, the actual device that has triggered the fault condition will be shown.
For other faults, information pertinent to that fault will be displayed instead (if available).
For device specific faults, pressing the more information again will display the unique ID code and
address location of the faulty device for the benefit of service engineers, etc.
In the event of a fault condition, the designated responsible person on site should:
• Mute the panel’s internal beeper by pressing the silence internal sounder button.
(Note that any new faults will restart the beeper).
• Note down the nature of the fault(s) in the fire system’s log book (pages 21 to 26)
• Take appropriate steps to ensure the fault(s) is/are rectified.
Pre-Alarm on: This Panel
North stairs :Detector near exit
Pre-alarm message Panel number
Name of zone in pre-alarm Device description
Zone 1:
There are faults on this zone
Ground Floor
i
Device status
Last zone in fault Name of zone in fault
Device Missing
Ground Floor :Reception Call Point
i
Device Missing
Loop:1 Dev:5 Call Point 0x00
Fault message
Name of zone in fault Device description
Device location details for system engineer
Device status
More
More
Zone 1:
There are faults on this zone
Ground Floor
i
Device status
Last zone in fault Name of zone in fault
Device Missing
Ground Floor :Reception Call Point
i
Device Missing
Loop:1 Dev:5 Call Point 0x00
Fault message
Name of zone in fault Device description
Device location details for system engineer
Device status
More
More
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 11 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
i

ACCESS LEVEL 1 (General User) CONTROLS & MENU OPTIONS
Access level 1 is the normal user level which is accessible to everyone. At this level you can:-
• Scroll through any fire, pre-alarm and fault conditions (as described on pages 8-11)
• View any disablements or zones that are being tested (if applicable)
• Test the panel’s lamps (its LED indicators and display) to ensure they are working correctly
• Determine the total number of times the panel has been in a fire condition
• Gain entry to access level 2 (authorised user level) and, if you are an engineer, access level 3.
Pressing the panel’s MENU button at access level 1 activates the panel’s general user menu which can
be navigated using the panel’s scroll (56), accept (4)and escape (3)buttons as appropriate. The
menu options available at access level 1 are explained in detail over the next two pages.
Enter Access Level 2
Access level 2 is for authorised users only and access to it requires the input of a special four digit code.
THIS MENU OPTION WILL NOT BE APPEAR ON KEYSWITCH VERSIONS OF THE PANEL WHERE ENTRY
TO ACCESS LEVEL 2 IS GAINED BY TURNING THE PANEL’S KEYSWITCH TO THE ARMED POSITION
.
On push button panels, when the ENTER ACCESS LEVEL 2? prompt appears, press the accept4
button and you will be asked to enter the code:
Enter the code using the 5(1) 4(2) 6(3)3(4) buttons as appropriate. The default code to access
level 2 is 3 3 3 3 (four presses of the 6button). If this does not work, the code may have been changed
by an authorised user/engineer. A record of any changes should appear on the System Setup Data
Chart on page 20 of this user manual. If they do not, contact your maintenance company for advice.
As soon as the code has been entered correctly you will be taken into access level 2. Additional
panel controls (see page 14) and menu options (see pages 15-19) will now be available to you.
Enter Access Level 3
Access level 3 is the panel’s engineering/programming level. ON NO ACCOUNT SHOULD ACCESS
LEVEL 3 BE ACCESSED BY ANYONE BUT AN AUTHORISED SYSTEM ENGINEER. A FIRE PANEL IS A PIECE
OF LIFE SAFETY EQUIPMENT AND UNAUTHORISED ACCESS MAY AFFECT THE WAY THE PANEL
FUNCTIONS, ENDANGER LIFE AND VOID ITS WARRANTY
. If you are an authorised engineer, details of
access level 3 can be found in the panel’s separate Engineering manual.
Display Fire Events
This function is only available if there are active fire conditions on the system. If available, press the
accept4button once and a window similar to the one below will appear:-
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 12 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENTER ACCESS LEVEL 2
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONES IN TEST
LAMPS TEST
DISPLAY ALARM COUNTER
Enter Access Level 2 code:
Last Zone: 1:North Stairs :Fire!
1 Zone
Note that menu options shown in
bold will only appear if relevant to
the panel’s status. For example, the
DISPLAY FIRE EVENTS function will
not show if there are no active fire
conditions on the system.

Pressing the 5and6buttons will scroll the display through all active fire conditions. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape3button.
Display Fault Events
This function is only available if there are active faults on the system. If available, press the
accept4button once and a window similar to the one below will appear:-
Pressing the 5and6buttons will scroll the display through all active faults. More detailed informa-
tion (if applicable) can be viewed by pressing the panel’s more information button. To return to the
main access level 1 menu press the escape3button.
Display Disablements
This function is only available when there are active disablements on the system. If available, press
the accept4button once and a window similar to the one below will appear:-
Pressing the 5and6buttons will scroll the display through all active disablements. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape3button.
Display Zones In Test
This function is only available if there are zones being tested. If available, press the accept4button
once and a window similar to the one below will appear:-
Pressing the 5and6buttons will scroll the display through all zones in test mode. More detailed
information (if applicable) can be viewed by pressing the panel’s more information button. To
return to the main access level 1 menu press the escape3button.
Lamp test
This function tests the panel’s lamps (its LED indicators and display) to ensure they are working correctly.
When selected, press the accept4button and all of the panel’s LED indicators will illuminate steady
for approximately two seconds and its display will progressively block fill. The panel’s internal
sounder (if enabled) will also sound. Upon completion, the panel will return to the main access
level 1 menu. If any of the LEDs fail to illuminate or the display does not function correctly, report
the fault(s) to the designated site engineer and make a note of it in the fire system’s log book.
Display Alarm Counter
This function displays the total number of times the panel has been in a fire alarm condition. When
selected, press the accept4button once and the display will show the total number of times the
panel has been in a fire condition since it was installed AND the total number of times it has been in
alarm since its alarm counter was last cleared, for example:-
To return to the main access level 1 menu press the escape3or accept4button.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 13 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Zone 1: Ground Floor
There are faults on this zone
1st Zone: 1: Shop floor
On: This Panel: Is Disabled
Zone 1: North Stairs
Is On Test
LAMP TEST?
Display Alarm Counter
AL1
Total Alarms = 12
Alarms since 01/01/05 = 7

ACCESS LEVEL 2 (Authorised User) CONTROLS & MENU OPTIONS
Access level 2 is available to authorised, trained personnel only. At this level, the panel’s
SILENCE/RESOUND SOUNDERS, CONTROL PANEL RESET and INVESTIGATE buttons become active and
you are able to:
• Scroll through any fire, pre-alarm or fault conditions that are displayed on the panel’s display
• View any disablements or zones that are being tested (if applicable)
• Enable or disable zones, sounders, outputs, relays and devices (as appropriate)
• Print, display and/or reset the panel’s event history
• Set the time and date
• Change the entry code to access level 2 from its factory default.
Details of how to use the panel’s SILENCE/RESOUND SOUNDERS, CONTROL PANEL RESET and
INVESTIGATE buttons can be found below.
Entering access level 2
ON PUSH BUTTON VERSIONS OF THE PANEL:-
Entry to access level 2 requires the input of a special four digit code. Press the MENU button on the
panel’s front and when the ENTER ACCESS LEVEL 2? prompt appears, press the accept 4button. The
following message will appear on the display:-
Enter the access level 2 code using the 5(1) 4(2) 6(3)3(4) buttons as appropriate. The default code
is 3 3 3 3 (four presses of the6button). If this does not work, the code may have been changed by an
authorised user/engineer. A record of any changes should appear on the System Setup Data Chart on
page 20 of this user manual. If they do not, contact your maintenance company for advice.
ON KEYSWITCH VERSIONS OF THE PANEL:-
Entry to access level 2 is gained by turning the panel’s keyswitch to the armed position.
Silencing the alarm sounders
To silence any active alarm sounders, enter access level 2 (see above) and momentarily press the
SILENCE/RESOUND SOUNDERS button. The alarm sounders will cease to sound and the panel’s
General Fire and relevant Fire Zone LEDs will go steady.
Should a fire condition occur on another zone whilst the alarm sounders are silenced, the panel:-
• Will sound the sounders programmed for activation by the new zone(s) in alarm
• Will flash its General Fire and appropriate Zone LED(s) for any new zone(s) in alarm
• May, if programmed, automatically reactivate the silenced alarm sounders and flash
any related Fire Zone LED(s).
Resounding the alarm sounders
Momentarily pressing the SILENCE/RESOUND SOUNDERS button when the alarm sounders are
silenced will resound them. Pressing the SILENCE/RESOUND SOUNDERS button again will silence the
alarm sounders.
Resetting the panel
After the cause of an alarm has been cleared and the alarm sounders have been silenced (see above),
the panel can be reset by pressing the CONTROL PANEL RESET button.
The panel will give a double beep to indicate the reset process has started and, after a few seconds,
the Fire Zone LEDs and General Fire LED will go out to indicate the process is complete. If there are
still any fire conditions on any zones, the panel will go back into alarm as before.
Note that the panel’s INVESTIGATE button is only active if an engineer has programmed one or
more zones to operate with a 1st-stage investigation delay period (see page 10 for detailed
information on this feature).
Enter Access Level 2 code:
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 14 of 28

XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 15 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
When in access level 2 (see page 14) the following menu options wil be available at the panel’s display
for authorised users. They can be navigated using the panel’s scroll (56), accept (4) and escape
(3) buttons as appropriate.
Enter Access Level 3
Access Level 3 is the panel’s engineering/programming level. ON NO ACCOUNT SHOULD ACCESS
LEVEL 3 BE ACCESSED BY ANYONE BUT AN AUTHORISED SYSTEM ENGINEER. A FIRE PANEL IS A PIECE
OF LIFE SAFETY EQUIPMENT AND UNAUTHORISED ACCESS MAY AFFECT THE WAY THE PANEL FUNC-
TIONS, ENDANGER LIFE AND VOID ITS WARRANTY. If you are an authorised engineer, details of
access level 3 can be found in the panel’s separate Engineering manual.
Lamp test
This function tests the panel’s lamps (its LED indicators and display) to ensure they are working correctly.
When selected, press the accept4button and all of the panel’s LED indicators will illuminate steady
for approximately two seconds and its display will progressively block fill. The panel’s internal sounder
(if enabled) will also sound. Upon completion, the panel will return to the main access level 2 menu.
If any of the LEDs fail to illuminate or the display does not function correctly, report the fault(s) to the
designated site engineer and make a note of it in the fire system’s log book.
Display alarm counter
This function displays the total number of times the panel has been in a fire alarm condition. When
selected, press the accept4button and the display will show the total number of times the panel
has been in a fire condition since it was installed AND the total number of times it has been in alarm
since its alarm counter was last cleared, for example:-
Press the escape 3button to return to the main access level 2 menu or, to clear the alarm counter,
press the accept 4button. A window similar to the one overleaf will appear:-
Press the accept4button once and the alarm counter will reset and start counting any new fire
conditions from today’s date (assuming that the date programmed into the panel is today’s date).
A short confirmation message will confirm the change has been made before the display returns to
the main access level 2 menu.
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONES IN TEST
LAMPS TEST
DISPLAY ALARM COUNTER
SET TIME/DATE
EVENT LOG FUNCTIONS
SET/CLEAR DISABLEMENTS
CHANGE ACCESS LEVEL 2 CODE
DISPLAY ALARM COUNTER
Clear to todays date?
PRINT EVENT HISTORY?
DISPLAY EVENT HISTORY?
RESET EVENT HISTORY?
ENABLE/DISABLE ZONES
ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
ENABLE/DISABLE DEVICES
ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
ENTER ACCESS LEVEL 2
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONES IN TES
T
LAMPS TEST
DISPLAY ALARM COUNTER
Total Alarms = 12
Alarms since 01/01/05 = 7
The menu options shown
in bold will only appear if
relevant to the panel’s
status. For example, the
DISPLAY FIRE EVENTS
function will not show if
there are no active fire
conditions on the system.
If any of these bold menus
appear, refer to their
listings in access level 1
(pages 12-13) for details of
how they work.
Clear to today's date?
Alarm since 01/01/05 = 7

Set time and date
This function allows the panel’s time and date to be adjusted. When selected, press the accept4
button and the following window (or similar) will appear:
Use the 5and6buttons to adjust the hour (the panel has a 24 hour clock so hours 0 to 23 are available).
When the correct hour is displayed, press the accept4button to move to the minutes field.
Use the 5and4buttons to adjust the minutes.
When the correct time is displayed, press the accept4button to alter the date.
A window similar to the one below will appear:-
Use the scroll 56and accept 4buttons to set the day/month/year as appropriate. When correct,
press the accept 4button again and you will be returned to the main access level 2 menu.
Event log functions
This function allows you to print a hard copy of the panel’s event log to an external printer (if connected),
to view it on the panel’s display or to reset it. When the EVENT LOG FUNCTIONS? prompt appears, press
the accept 4button and scroll down to the desired event log function using the 6button.
The PRINT EVENT HISTORY function, when selected, will print the panel’s log to a printer. When
selected, the following window will appear:-
If you try to print the event history when no printer is connected, the following window will appear:
The DISPLAY EVENT HISTORY menu option, when selected, displays the panel’s 500 event log on
the display. For example:-
Initially only the last event will appear in the window but you can scroll through the list using the
5button to see previous saved events. When the log is full, the oldest record is replaced by the
newest record. Events are listed in chronological order. When you have finished viewing the
required events, press the escape 3button to return to the previous menu.
The RESET EVENT HISTORY? menu option, when selected, clears the log from the panel’s memory. To
help ensure it is not erased by mistake, a warning will appear when the accept 4button is pressed:
Press the accept 4button to confirm you want to erase the log. The following window will appear
whilst the log resets after which the panel will return you to the EVENT HISTORY MENU.
Printing Event 56...
Press ESC to stop printing
Printer fault, Check connections, paper
Ensure the printer is on-line
Event 499 at 05/02/05 11:31:19
Access Level 2 entered
Are you sure you want to erase
the Event log?
Resetting the Event History...
Resetting entry 499
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 16 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Set the time:- 00:00
Set the time:- 16:52
Set the date:- xx:xx:xx

Set/clear disablements
Selecting this menu option takes you to the disablements sub-menu which allows you to enable or
disable zones, sounders, outputs, relays, individual devices and/or the panel’s fault relay.
We strongly recommend all disablements are regularly reviewed and immediately enabled when no
longer necessary as they can have a major effect on how the system works.
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, pre-alarms, etc., and is
normally used to temporarily disable a zone of detectors/call points in areas such as loading bays
where they are prone to nuisance triggering from vehicle fumes. When selected, press the
accept4button and a window similar to the one below will appear:-
Select the zone to be disabled/enabled using the 5and6buttons. Press the accept4button and
the zone’s status (Enabled or Disabled) will flash. Next, use the 5and6buttons to toggle between
enabled and disabled and press the accept 4button to select the desired option.
The window will now move to the next available zone allowing further enablements or disable-
ments to be made. Alternatively, to return to the previous menu press the escape 3button.
Please note: if all the input devices on a zone have been individually disabled using the ENABLE/DISABLE
DEVICES function described on page 18, the zone they belong to will also be disabled. If you try to
re-enable a zone which has no enabled devices on it, a prompt appears saying this cannot be done.
Instead you must first enable at least one device on the zone using the ENABLE/DISABLE DEVICES
function before re-enabling the zone itself.
ENABLE/DISABLE SOUNDERS
This function allows you to disable one or more sounder groups from sounding in a fire condition.
When selected, press the accept4button and a window similar to the one below will appear:-
Select the sounder group (1 to 16 or ALL) to be disabled/enabled using the 5and6buttons.
When the desired sounder group has been selected, press the accept4button once and the sounder
group’s status (Enabled or Disabled) will flash. Next, use the 5and6buttons to toggle between
enabled and disabled and press the accept 4button to select the desired option. The window will
now move to the next sounder group allowing further enablements or disablements to be made.
Alternatively, to return to the previous menu press the escape3button.
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from sounding in a fire condition. It is typically
used to disable, for example, auto-diallers and other ancillary equipment from activating during routine
maintenance. When selected, press the accept4button and a window similar to the one below will appear:-
Select the output set (1 to 16 or ALL) to be disabled/enabled using the 5and6buttons.
When the desired output set has been selected, press the accept4button once and the output set’s
status (Enabled or Disabled) will flash. Next, use the 5and6buttons to toggle between enabled
and disabled and press the accept 4button to select the desired option. The window will now move
to the next output set allowing further enablements or disablements to be made. Alternatively, to
return to the previous menu press the escape3button.
XFP USER MANUAL &LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 17 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Zone: 1: Shop Floor
Enabled
Sounder Group: 1
Output Set: 1

ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel’s 3 auxiliary relays from activating as pro-
grammed. When selected, press the accept4button and a window similar to the one below will appear:-
Select the relay (1, 2 or 3) to be disabled/enabled using the 5and 6buttons.
When the desired relay has been selected, press the accept4button and the relay’s status (Enabled
or Disabled) will flash. Next, use the 5and6buttons to toggle between enabled and disabled and
press accept 4button to select the desired option. The window will now move to the next relay
allowing further enablements or disablements to be made. Alternatively, to return to the previous
menu press the escape3button.
ENABLE/DISABLE DEVICES
This function allows loop devices to be disabled from reporting faults, fires, pre-alarms, etc., and is
normally used to temporarily disable detectors/call points that are nuisance tripping. When selected,
press the accept4button and a window similar to the one below will appear:-
Use the 5and6buttons to select the zone where the device you wish to disable/enable is located.
When selected, press the accept4button and a list of all devices that can be disabled or enabled in
that zone will appear, e.g
Use the 5and6buttons to scroll through the available devices. When the desired device appears,
press the accept4button and the device’s status (Enabled or Disabled) will flash. Next, use the
5and6buttons to toggle between enabled and disabled and press the accept4button to select
the desired option. The window will now move to the next device allowing further enablements or
disablements to be made. Alternatively, to return to the previous menu press the escape3button.
Please note: if all the input devices on a zone are individually disabled, the zone they belong to will
also be disabled. If you try to re-enable a zone which has no enabled devices on it using the
ENABLE/DISABLE ZONES function described on page 17, a prompt appears saying this cannot be done.
Instead you must first enable at least one device on the zone before re-enabling the zone itself.
ENABLE/DISABLE FAULT RELAY
This function can be used to suppress the panel’s fault relay from activating in a fault condition.
When selected, press the accept4button and the following window will appear:-
Use the 5and6buttons to toggle between enabled and disabled and press the accept4button to
select the desired option. Alternatively, to return to the previous menu press the escape3button.
ENABLE/DISABLE OUTPUT DELAYS
This function can be used to globally disable or enable any delays to outputs that have been programmed
into the panel. When selected, press the accept4button and the following window will appear:-
Use the 5and6buttons to toggle between enabled and disabled and press the accept4button to
select the desired option. Alternatively, to return to the previous menu press the escape3button.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 18 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Select Zones:- 1: Shop Floor
Shop Floor:- 1: Gent WC
Loop 1, Device 3: Enabled
Fault relay is:- Enabled
Panel Relay:- 1
Delays to Outputs are:-
Enabled

Change the access level 2 code
This function allows you to change the four digit code needed to activate the panel’s access level 2
menu options. When selected, press the accept 6button and the following window will appear:
Using the 5(1) 4(2) 6(3)3(4) buttons, enter the new four digit access level 2 entry code. After the
fourth digit has been entered, the panel will request you confirm the new code by re-entering it.
Enter the code again by pressing the 5(1) 4(2) 6(3)3(4) buttons in same sequence. If the two
codes match, the panel will accept the code and you will be taken back to access level 2. If you type
an incorrect confirmation code you will be prompted to start the new code entry sequence again.
BE SURE TO KEEP A RECORD OF THE NEW CODE ON PAGE 20 OF THIS USER MANUAL.
Although the CHANGE ACCESS LEVEL 2 CODE menu option IS available on keyswitch versions of
the panel, any changes to the code WILL NOT affect the panel’s operation, i.e. access to the panel’s
authorised user menu will still be available via the panel’s keyswitch.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 19 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Enter NEW Access Level 2 Code
Enter NEW Access Level 2 Code: ****
Confirm NEW Access Level 2 Code:

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000501 Rev 2 • Page 20 of 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
SYSTEM SET-UP DATA CHART
Important: this page should be carefully completed by the system engineer prior to handover.
ZONE FUNCTIONS
Tick the appropriate column for each zone. Note that zones 17-32 are only available on 1-32 zone panels.
Zone
No.
Zone
description Set up for
normal operation
Set up with
dependencies
Set up with an
investigate facility
Set up with
output delays
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
ACCESS LEVEL 2 (AUTHORISED USER) CODE
The factory default code for access level 2 (required on push button versions of the panel only) is 3 3 3 3
(four presses of the6key). If this code is changed, make a note of the changes here:-
New access level 2 code ❑ ❑ ❑ ❑ Date changed __________________
ADDITIONAL INFORMATION
We recommend any additional information the user needs to be aware of is detailed below:-
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
Completed by ____________________________________ of ______________________________________ on ____ / ____ / ____
Table of contents
Other XFP Control Panel manuals