XFP XFP501E/X Installation and operation manual

XFP
NETWORKABLE
ANALOGUE
ADDRESSABLE
FIRE ALARM
CONTROL PANEL
Single Loop 16 Zone Version
Part Nos. XFP501E/X, XFP501E/H
engineering
manual
Approved Document No. DFU1200510 Rev 3

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CONTENTS
Important notes....................................................................................................................................3
Key features..........................................................................................................................................4
Installation and wiring ........................................................................................................................5
The fire panel enclosure ..................................................................................................................................5
Removing the lid and base PCBs......................................................................................................................5
Mounting the base onto a wall ......................................................................................................................6
Planning the cable layout in the panel ..........................................................................................................6
Mains wiring......................................................................................................................................................6
Connecting Mains to the Power Supply PCB ..................................................................................................7
Analogue addressable loop wiring..................................................................................................................8
Connecting the analogue loop to the Main Control PCB..............................................................................9
Conventional sounder circuit wiring ............................................................................................................10
Auxiliary input wiring ....................................................................................................................................10
Relay output wiring........................................................................................................................................10
Remote PC connection ..................................................................................................................................11
Aux. 24V output..............................................................................................................................................11
Installing the standby battery supply............................................................................................................11
Network/repeater wiring (optional)..............................................................................................................12
Controls and indicators......................................................................................................................14
Commissioning and programming ..................................................................................................16
Recommended commissioning procedure ....................................................................................................16
System operation / terms of reference..........................................................................................................16
Access levels menu tree ..................................................................................................................................17
How to enter access level three ....................................................................................................................18
Fitting the panel’s NVM ‘memory unlock’ link ............................................................................................18
A detailed description of the functions available at access level ........................................................19-33
Maintenance ......................................................................................................................................34
Standby battery calculation guide....................................................................................................35
Technical specification ......................................................................................................................36
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 2 of 36
Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD. www.c-tec.com
Niederlassung Deutschland: C-TEC Germany Limited, Virchowstr. 32, D-33332 Gϋtersloh. www.c-tec-germany.de
Errors & Omissions Excepted. The manufacturer of this product operates a policy of continuous improvement and reserves the right to alter product
specifications at its discretion and without prior notice. All of the instructions covered in this manual have been carefully checked prior to publication.
However, no responsibility can be accepted by the manufacturer for any inaccuracies or for any misinterpretation of an instruction or guidance note.
176b
0832 13
XFP 16 Zone (Hochiki)
0832-CPR-F1585
XFP 16 Zone (Apollo)
0832-CPR-F1586

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Read these instructions thoroughly before installation and operation
General Warning Sign Danger Electrical Hazard
Symbols
IMPORTANT NOTES
This equipment must only be installed and maintained by a suitably skilled
and technically competent person.
This equipment is a piece of Class 1 permanently connected equipment and
MUST BE EARTHED
ALWAYS isolate the panel’s Mains and battery backup supplies before making
connections to its PCBs. Failure to observe this WILL destroy the panel’s
electronic components and the warranty will be void.
Items supplied with this panel
• Engineering manual (this manual). This manual must not be left accessible to the user.
• User Manual / Log Book
• Torx key, for unfastening / securing the panel lid
• Electrical accessory pack, containing:
2 x 6K8 0.25W conventional sounder circuit resistors
1 x 20mm 1ATH 230V ceramic fuse (spare primary fuse)
1 x set of battery connection leads (red wire, black wire, jumper link and 2 x nylon cable ties)
System design
Fire alarm system design is beyond the scope of this document. A basic understanding of general
fire alarm system components and their use is assumed.
Contact the Fire Officer concerned with the property at an early stage in case he has any special
requirements. We strongly recommend that a suitably qualified and competent person is
consulted in connection with the design of the fire alarm system and that the system is
commissioned and serviced in accordance with the laid down specification and national
standards. If in doubt please consult your supplier.
We recommend you read BS 5839: Part 1 "Fire Detection and Alarm Systems for Buildings (Code
of Practice for System Design, Installation, Commissioning and Maintenance)" available at your
local reference library or from the BSI. Other national standards of installation should be
referenced where applicable.
Cable types and limitations
All system wiring should be installed to meet current national standards - in the United Kingdom
these are BS 5839 Part 1 and BS 7671 (Wiring Regulations).
Fire resistant screened cable should be used throughout the installation. This not only shields the
data moving up and down the cables from outside interference but is essential to ensure
compliance with EMC regulations. Cables such as FP 200, Firetuff™, Firecel™ and MICC may be
acceptable provided they are properly terminated at the fire panel and meet national standards /
the system specification as applicable. Consult Clause 26 of BS 5839 Part 1 for more detailed
information on cables, wiring and other interconnections.
Equipment guarantee
This equipment is not guaranteed unless the complete installation is installed and commissioned
in accordance with the laid down national standards (in the UK BS 5839: Part 1) by an approved
and competent person or organisation.
Anti-static handling guidelines
Always observe appropriate electro-static handling precautions prior to handling the
panel’s PCBs or any other static-sensitive components.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 3 of 36

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
KEY FEATURES
This single loop 16 zone analogue addressable fire alarm panel is designed for use with fire and
security systems and offers the following features:
•Full compliance with EN54 parts 2 and 4, including EN54-2 Clauses 7.8 - Output to fire alarm
devices, 8.3 - Fault Signals from points and 9.5 - Disablement of addressable points.
•Full compatibility with Hochiki’s ESP (Part No. XFP501E/H) and Apollo’s XP95 (Part No. XFP501E/X),
Discovery and Xplorer protocols (dependent on the model purchased)
•Two independently programmable conventional sounder circuits
•Two programmable inputs
•A fault output relay and three programmable relay outputs with volt free changeover contacts
•A selection of zone dependency functions (EN54-2 Clause 7.12, type A, B or C) as detailed below:
Type A - If there is an alarm from a detector, the panel will look for a confirmatory alarm from
the same or another detector in the same zone before a full alarm is established. If there is no
confirmatory alarm, the first alarm will automatically reset.
Type B - As type A except the confirmatory signal must be from another detector in the same zone.
Type C - As type A except the confirmatory signal may also be from another zone, and the first
alarm will not automatically reset.
•A day/night (building occupied/unoccupied) function (engineer programmable day/night changes
include detector sensitivity (high/low) and zone dependency settings
•An investigation delay period function (programmable for length of time, which zone(s) it applies
to and whether or not it operates in day/night mode) which works as follows:
When there is an alarm in a zone programmed to operate in ‘investigate’ mode, the full alarm
condition will occur after a delay. It is possible to manually impose a further delay, to allow the
source of the alarm to be investigated. If the second delay expires, or there is another alarm in
the same zone, then a full alarm condition is established. During either delay period, the panel
may be reset in the case of a false alarm
•Individual sensitivity settings for each device
•EN54-2 Clause 7.11 Delays to outputs, and a phased evacuation facility
•An EN54-2 Clause 7.13 alarm counter to record the number of times the panel has been in an
alarm state
•A powerful short circuit protected loop driver, capable of supporting a total of 126 addressable devices
•An integral 1.5A EN54-4 switch mode PSU rated @ 185-260V a.c. 50/60Hz
•Earth fault monitoring
•Keypad access code to access levels 2 & 3. Keyswitch entry to access level 2.
•40 characters of custom text per device
•500 event monitoring
•Comprehensive EN54-2 Clause 10 test with maintenance and commissioning functions
•An intuitive Windows based upload-download PC program (Part No. XFP507) that MUST be used
to configure the system.
Networking (Optional)
If required, the panel can be configured to sit on a non-redundant network of up to eight interconnected
XFP main panels (any variant), OR it can have up to eight XFP repeaters connected to one non-
networked XFP main panel. If you wish to utilise either of these options, the panel will require a
separately available Network Communication Card (Part No. XFP761).
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 4 of 36
Note: The XFP network and XFP repeaters have
not been assessed to EN54-2.

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 5 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
INSTALLATION AND WIRING
The fire panel enclosure
The panel is supplied with a plastic detachable lid, a plastic back box, a Main Control PCB and a
Power Supply PCB. Space is available inside the panel for the rated capacity of VRLA backup
batteries and an optional Network Communication Card.
The panel MUST be installed indoors, positioned to avoid accidental damage, and NOT subject to
conditions likely to affect its performance, e.g. dust, conductive or corrosive gases or liquids, nor
subject to temperatures, input voltages and electrical loads outside the stated operating range.
It should be sited at a height where it is easily accessible and in a prominent position within the
building. Ideally, its front panel indicators should be at eye level. Typical locations for the panel are
in the entrance foyer/hallway at ground floor level (the first and most obvious point of contact for
emergency services), or a permanently manned security office.
It is recommended that you remove the panel’s lid and base PCBs prior to first fix installation to
protect the electronics from damage.
Removing the lid and base PCBs
Fig. 1 : Location of the panel’s base PCBs and removal details
1 Take the panel out of its box and undo the two lid screws using the Torx key provided. Remove
the lid to expose the Main Control PCB (the Power Supply PCB is located underneath).
2 Carefully remove the five retaining screws on the Main Control PCB and slide the PCB up and
over the mounting pillars, taking care not to damage any of the components.
3 Disconnect the telecoms-style connecting cable at PL1 on the Power Supply PCB, making sure
that the cable remains connected to the reverse of the Main Control PCB to prevent it being
misplaced.
4 Pull the Power Supply’s earth distribution strap off the spade connector at the base earth
distribution post.
5 Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and
over the mounting pillars, again taking care not to damage any of the components.
6 Store the PCBs in a clean, dry place which is free from vibration, dust and excessive heat.
Retaining the PCBs in a suitable cardboard box will also guard them against mechanical damage.
MAIN CONTROL PCB
POWER SUPPLY PCB
Leave this endof the connector cable connected
to SK2 on the reverse of the Main Control PCB
push tab
andgently
lift cable
PL1
PPL1PL1

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Mounting the base onto a wall
The panel can be surface, or semi-flush mounted, onto a vertical wall, ≤2 m mounting height, using the
five mounting holes provided (see Fig. 2 below). To access the mounting holes, first remove the panel’s
lid and base PCBs, as detailed on page 5. The mounting holes are suitable for use with No.8-10 or 4-
5mm countersunk screws. Always assess the condition and construction of the wall and use suitable
screw fixings for the in-service weight of the product. Any dust or swarf created during the fixing
process must be kept out of the base. Note that the central mounting hole can be used to temporarily
hang the back box so it can be levelled and its remaining fixing points marked for drilling.
Fig. 2 : Location of mounting holes and drill points / side view of panel for flush mounting
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 6 of 36
Planning the cable layout in the panel
All cables should be brought into the panel via the drill outs provided.
Note that the analogue loop and conventional sounder circuit cabling is
classed as low voltage and MUST be segregated away from Mains voltages.
Careful planning is needed to ensure this (see Fig. 2 above for guidance).
We recommend tails of at least 20-30cm are left inside the panel to ensure
straightforward connection of the field wiring to the panel’s terminals.
Drill centre points are provided in the panel base to aid drilling tools. Cut
out suitable holes in the panel using a hole saw directed by a pilot bit in
the centre of the hole saw (see right). Always ensure that if a hole is cut
out it is filled with a good quality strain relief cable gland. Any unused
holes must be securely blanked off.
Mains wiring
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs. (BS 7671), or
relevant national standards. The requirement for the Mains supply to the panel is fixed wiring (no less
than 1mm2and no greater than 2.5mm2), either using 3-core cable, or a suitable three conductor system
fed from an isolating switched fused spur at 3 A, or a 6 A Type B circuit breaker to IEC/EN 60898-1.
The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post.
Do not drill any additional holes
for cable entry in thisshadedarea.
Thisiswhere the PCBsand
backup batterieswill be located.
339mm
170mm
Fixingcentres
Fixingcentres
75mm
WALL
These four drill centre
points are reserved
for incoming Mains
cable only
Hint! As an alternative to a switched
fused spur, a double-pole isolating
switch (S), with 3mm air gaps on the
contacts & switching L & N only, may
be used in the Mains feed from the Main
Distribution Board (A) to the Panel (C),
providing it meets the appropriate wiring
regulations (see drawing right).
A
S
C
≥1.0 mm2<2.5 mm2

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Connecting Mains to the Power Supply PCB
The panel’s PSU combines the functions of a power supply unit, battery charging unit, battery
monitoring unit and earth fault monitoring unit. It should be positioned in the panel’s enclosure as
shown in Fig. 3 below. DO NOT operate the panel without the Power Supply PCB correctly mounted in
the enclosure with its three PCB retaining screws securely tightened.
CAUTION: DO NOT CONNECT MAINS TO THE POWER SUPPLY PCB UNTIL THE INSTALLATION IS
COMPLETE AND ALL RELEVANT PCBS ARE CORRECTLY ATTACHED WITHIN THE PANEL.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 7 of 36
Fig. 3 : Power Supply PCB layout and Mains connection (Full Protective Cover & Cable Cover shown fitted)
C
C
C
C
C
C
C
C
C
C
C
C
C
C
ON
O
ON
ON
O
ON
ON
ON
ON
N1
N1
N1
N1
N1
N1
N1
N1
N
N
N
N
N
N
N
N
N
L
L
L
L
L
L
CONN2
BLK
-
RED+
VR1
F2
F1.6A
PL2
PL1
F
F
F1
F
F
1A
1A
2
2
50V
50V
0V
50V
50V
50V
V
H
H
H
RC
RC
C
RC
C
C
RC
F1
F
F
F
V
V
V
HRC
F
F1 1A
2
0
50
250
0
0V
V
0V
V
V
V
V
HRC
V
0
V
V
0
HR
R
V
V
0V
1
A 250
R
1A
R
THIS WAY UP
CONN1
NL
Mains Input (CONN1)
L = Live (BROWN)
N = Neutral (BLUE)
= Earth (GREEN/YELLOW)
The incoming Mains earth wire MUST be
connected to the terminal marked
and NOT to the base earth distribution
post.
Exposed live parts under cable
cover. Isolate first, then remove
the small cable cover by
loosening its single retaining screw which
is retained in the cover. Only operate the
PSU with this cover securely fitted.
Connector Cable Socket (PL1)
Connect other end of lead to
the rear of Main Control PCB.
WHEN THE RED ‘HAZARDOUS
VOLTAGES PRESENT’ LED IS LIT
HAZARDOUS VOLTAGES ARE
PRESENT. ALLOW TO DISCHARGE FOR AT
LEAST 5 MINUTES BEFORE REMOVAL &
HANDLING.
Incoming Mains Cable
This cable MUST be segregated from
other cables. Good quality cable
glands MUST always be fitted.
Battery Connector
(CONN2)
(Leads supplied in the
panel’s accessory
pack.) See page 11 for
connection details.
PSU Earth Distribution Strap
This strap MUST be
connected to the spade
on the base earth
distribution post before
operation.
Battery Fuse (F2)
Primary Fuse (F1)
Exposed Live
parts under fuse
cover. Isolate
before removal.
CABLE
COVER
REMOVED

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 8 of 36
Analogue addressable loop wiring
Fig. 4 below shows a typical analogue addressable loop complete with loop isolators, detectors, loop-
powered sounders, modules and monitors. The descriptions and availability of the devices shown may
not be applicable to all manufacturers’ protocols – check with your supplier for further details. Also this
example arrangement of devices may not be permitted by design and installation regulations in certain
countries. The loop should be connected to the relevant 5mm connector block on the panel’s Main
Control PCB and its screens terminated at the panel’s base earth distribution post as shown on page 9.
Fig. 4 : A typical analogue addressable loop
Design issues - reducing faults and their consequences
To ensure a reliable system, it should be designed and maintained to local design and installation
regulations. The XFP has loop isolators included in the panel, and loop isolators should be included in
the loop wiring. A single short circuit fault will now only disable devices in the section of wiring
between isolators. Local design and installation regulations will dictate how many devices or zones may
be lost in the case of this type of fault. In the case of a single open circuit no devices will lost, since
communication is from both ends of the loop, but a loop integrity fault will be shown.
Note that a critical design issue with any analogue fire system is the combined effect of loop resistance,
loop capacitance and the current demand of items connected to the loop.
Factors that influence this include loop length, cable diameter, cable type, the number of isolators used
and the number and type of devices between isolators. There are no hard and fast rules regarding these
factors as every situation is unique. However, if the following conservative advice is followed, the loop
WILL almost certainly work.
• Absolute maximum loop length = 1km, with either 1mm2or 1.5mm2cables.
• No more than 20 addressable devices between loop isolators of which no more than 6 are loop sounders.
• If loop sounders are used, use 1.5mm2cable and do not fit more that 32 loop sounders per loop in total.
•If more than 10 loop sounders are used per loop then the maximum loop length per loop should be no
greater than 750m.
The above SHOULD NOT be considered the maximum operating conditions for the panel as many other
permutations are possible. Any limitations are a consequence of device manufacturers’ protocol, coupled
with the cable’s characteristics. The panel’s loop driver is easily capable of driving lightly loaded loops up to
4 km long without a problem. However, devices connected at the end of 4 km may not be able to read the
data if corrupted by the cable. Always refer to the instructions supplied with each device prior to installation.

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 9 of 36
Connecting the analogue loop to the Main Control PCB
The analogue loop should be connected to the Main Control PCB as illustrated in Fig. 5 below.
Remember to isolate the panel’s Mains and battery backup supplies before making any connections.
The loop’s earth screens should be adequately insulated and connected between the nut and washers on
the base earth distribution post using eyed crimp connectors. Do not disturb the lower nut - this must
be secure to ensure earth continuity.
The base earth distribution post is provided for terminating earth screens or drains and is NOT the
main earthing point. The installer must review the external earth bonding (if required) with
respect to the national wiring rules. If the installation requires protective earth bonding, then this
must be applied externally and in conjunction with the type of earthing system employed on site.
Note that the Main Control PCB connects to the Power Supply PCB via an 8-way telecoms-style connector
cable, the socket for which is located on the PCB’s reverse. This cable must be connected before the Main
Control PCB is secured in the panel. Ensure all six PCB retaining screws are properly tightened before oper-
ation as they play an important part in the electrical safety and EMC immunity of the panel.
Fig. 5 : Typical analogue addressable loop connection
GENERAL
FIRE ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8
ZONE 9 ZONE 10 ZONE 11 ZONE12 ZONE 13 ZONE 14 ZONE 15 ZONE 16
D45
SUPPLY
PRESENT TEST ACCESSED
GENERAL
DISABLEMENT
PHASED
EVACUATION
GENERAL
FAULT
PSU
FAULT
SYSTEM
FAULT
SOUNDER
STATUS
DELAYS
RUNNING
Auxilliary
+24V I/P1 I/P2 0v
Relay 1
NC C NO
Relay 2
NC C NO
Relay 3
NC C NO
Fault
NC C NO
Sounder Circuits
+ 1 - + 2 -
Earth Fault Detect Addressable Loop
+ A - + B -
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
INSTALLATION INSTRUCTIONS
WARNING
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS. FOR OPERATIONAL DETAILS PLEASE
CONSULT THE MAINTENANCE MANUAL
Mute
Beeper
A Short B Short
Analogue loop
Earth distribution
strap from power
supply PCB
PSU PCB connector
cable (connects to rear
of Main Control PCB
and PL1 on PSU PCB
This LED will
be lit amber
if there is a
short circuit
on the loop’s
B+ B- leg
This LED will
be lit amber
if there is a
short circuit
on the loop’s
A+ A- leg
nut 3 x plain
washer
crimped
connection
Do not untighten lower nut
spring
washer
screens
Base Earth Distribution Post
PSU Earth
Distribution
Strap

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 10 of 36
Conventional sounder circuit wiring
Two conventional sounder circuits are provided. These can accommodate up to 40 conventional
polarised sounders (at 20mA) or 32 bells (at 25mA) per system. If a full complement of sounders or
bells are to be used, split them equally across both circuits. A 6k8 end of line resistor (provided) must
be connected at the end of each sounder circuit to allow the wiring to be monitored. If the sounder
circuit is unused, you must still connect the 6k8 resistor at the panel. Remember to isolate the
panel’s Mains and battery backup supplies before making any connections.
Each sounder circuit should be connected to the terminal marked Sounder Circuits on the Main Control PCB
as shown in Fig. 6 below and its earth screens terminated at the panel’s base earth distribution post.
Fig. 6 : Typical conventional sounder circuit connection and detail
Auxiliary input wiring
Two programmable auxiliary input connections are
provided. These can be programmed using the panel’s
PC programming software tools to operate as required.
The wiring for each input should be connected to the
terminal block marked Auxiliary on the Main Control
PCB as shown in Fig. 7 right. Remember to isolate the
panel’s Mains and battery backup supplies before
making any connections.
If applicable (i.e. in electrically noisy environments),
input wiring screens should be terminated at the
panel’s base earth distribution post in the same way as
the analogue loop earth screens, as detailed on page 9.
Relay output wiring
Four volt-free relay output connections are provided - a failsafe fault output, which switches for any
fault condition, and three programmable auxiliary relay outputs. All four relays are capable of switching
1A @ 30Vdc. They should NOT be used for switching Mains voltages.
The three auxiliary outputs (Relays 1, 2 and 3) can be programmed using the panel’s PC programming
software tools to operate as required but their default operations are:
Relay 2
C NO
Relay 3
NC C NO
Fault
NC C NO
Sounder Circuits
+ 1 - + 2 -
Earth Fault Detect Addressable Loop
+ A - + B -
Conventional
sounder circuit
For more precise earth screen termination
details refer to the typical analogue loop
wiring diagram on page 9.
Earth distribution strap
from power supply PCB
END OF LINE
RESISTOR
(6k8 Ohm)
POLARISED
SOUNDER
POLARISED
SOUNDER
++ +
–
+
POLARISED
SOUNDER
+
✗
DO NOT SPUR
(wiring not
monitored)
PANEL
SOUNDER
CIRCUIT
TERMINALS
Fig. 7 : Typical auxiliary input wiring / connection
Auxilliary
+24V I/P1 I/P2 0v
Relay 1
NC C NO
Input 1
Input 2
Conventional sounder circuit detail

ZONE 9 ZONE 10 ZONE 11 ZONE12
D45
SUPPLY
PRESENT TEST ACCESSED
GENERAL
DISABLEMENT
GENERAL
FAULT
PSU
FAULT
SYSTEM
FAULT
SOUNDER
STATUS
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES- PLEASE REFER TO
INSTALLATIONINSTRUCTIONS
WARN IN G
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIESACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
Mute
Beeper
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 11 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Relay 1
NC C NO
Relay 2
NC C NO
Relay 3
NC C NO
Fault
NC C NO
43434343
NVM ‘memory unlock’ link,
must be fitted when
uploading or downloading
information from/to the PC
Plug the lead’s ‘D’-type connector
into the appropriate serial socket
(com1, com2, etc) on the PC
Fig. 8 : Relay output detail
Fig. 9 : Connecting a PC to the panel’s RS232 connector
+
–
+–
+
I
+
+
I
–
+–
Location of small
sized batteries
typically 1.2 Ah
Location of medium
sized batteries
typically 2.1 Ah
++
–
–
+
Take care to arrange
batteries so terminals
do not touch
Location of large
sized batteries
typically 3.0 Ah
Connection of leads
to Power Supply PCB
Run the battery leads
(supplied) through slits
in the plastic ribs
R E D
BLACK
Nylon
tie wraps
Link wire
Remote PC connection
A four-way RS232 molex connector
is provided on the Main Control PCB
for the connection of a Windows
based PC for programming
purposes.
The ONLY way to program this fire
panel is using a PC loaded with the
panel’s sophisticated programming
tools (Part No. XFP507). The lead
supplied with the software tools
should be connected to the panel
and the PC as shown in Fig. 9 (right).
Aux. 24V output
One fused 24V d.c. output, rated at 100mA, is provided and can be used for supplying power to ancillary
fire alarm equipment.
Installing the standby battery supply
There is a risk of explosion if incorrect battery types or sizes are used. Always replace both
batteries and always dispose of used batteries in accordance with the battery manufacturers
instructions and local regulations. Batteries are heavy and can produce dangerously high currents
if shorted. Take care when handling and routing battery leads to avoid damage.
Two new, good quality and fully charged 12V valve regulated lead acid batteries are required as the
emergency stand-by power supply for the panel. The batteries should be connected in series and located
in the panel’s enclosure as shown in Fig. 10 below. The battery leads, link wire and nylon cable ties are
provided in the panel’s accessory pack. Run the battery leads through the slits in the panel’s lower
plastic ribs and secure the batteries into position using the nylon cable ties as shown.
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by
activating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not
fitted, are discharged or in poor condition, a PSU fault will show at the panel.
The capacity of the batteries used will depend upon the required stand-by time. To calculate the
batteries required for any given stand-by period, refer to the battery calculation guide on page 35.
Fig. 10 : Battery location and connection details
Relay 1 : Switches when any zone goes into fire, switches back when the panel is silenced;
Relay 2 : Switches when any zone goes into fire, switches back when the panel is reset;
Relay 3 : Has no default operation.
The wiring for each output should be connected to the
relevant connector block on the Main Control PCB
(remember to isolate the panel’s Mains and battery
backup supplies before making any connections).
Fig. 8 (right) explains how the outputs work.

Fig. 11: Installing the network communication card
Important: Before installing the network communication card, isolate the Mains supply and
disconnect the panel’s battery back-up supply. With reference to the diagram below:
• Secure the card inside the panel using the two
retaining screws provided.
• Connect the two-way polarised power supply loom
(supplied with the card) between PL1 on the card
and PL2 on the Power Supply PCB.
• Connect the 8-way telecoms-style connector cable
(also supplied with the card) between PL2 on the
card and the socket on the reverse of the Main
Control PCB (socket SK2 which is located alongside
the PCB’s microprocessor).
Note: The DIP switch (SW1) on the network
communication card has no function when used
with the XFP. However, all networked XFP main
panels require a unique ID number (1-8) so they
can be recognised by other panels on the
network. This is assigned using the NETWORK
FUNCTIONS menu option at access level 3.
XFP repeaters DO NOT require an ID number.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 12 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
To SK2 on
the reverse
of the Main
Control PCB
PL2
PL1
PL2
PL1
POWER
SUPPLY
PCB
NETWORK
DRIVER
CARD
To SK1 on
the reverse
of the Main
Control PCB
A B C A B
Network/repeater wiring (optional)
The XFP’s network protocol allows the connection of up to eight XFP main panels (any variant) over a
2-wire RS485 non-redundant network. Alternatively, the network can be used to connect up to eight XFP
repeaters to one non-networked XFP main panel.
It is NOT possible to mix XFP main panels and XFP repeaters on the same network.
Key features of the non-redundant network protocol when used for interconnecting XFP main panels:
• Allows the interconnection of up to eight XFP main panels (any mix of single loop 16 zone XFPs and
1 and 2 loop 32 zone XFPs)
•Up to 1 km of cable may be fitted to an XFP main panel network.
• Each networked XFP main panel can be programmed to:
Accept Fires from other main panels.
Accept Faults from other main panels.
Accept Control actions such as Silence Alarm Sounders and Control Panel Reset from other main panels.
Accept Disablement commands for zones, sounders and output sets from other main panels.
(Each of these four functions may be individually selected via the panel’s PC Programming Software Tools.)
•All panels monitor all other panels for network wiring faults.
•Fires on remote panels are displayed on local panels including the point description of the alarm’s origin.
•Faults on remote panels are displayed on local panels.
•Cause and effect can be programmed into local panels dependent on which remote panel is in alarm.
•The network supports the programming of site information into remote panels from a PC connected
at a local panel.
•Time and date is common to all panels throughout the network.
Key features of the non-redundant network protocol when used for connecting XFP repeaters
• Allows the connection of up to eight XFP repeaters (any mix of single loop 16 zone repeaters and
1 or 2 loop 32 zone repeaters) to any non-networked main panel.
•Up to 500m of cable may be fitted to an XFP repeater network.
• Each XFP repeater offers all the functions and controls of an XFP main panel
Any XFP main panel connected to the non-redundant network requires the installation of a Network
Communication Card (Part No. XFP761), as shown in Fig. 11 below. (Repeaters come with a Network
Communication Card already fitted). Typical network wiring details are shown in Fig. 12.
To SK2 on
the main
control
PCB
To SK1 on
the main
control PCB
See Fig. 12 for typical
network wiring details
Note: The XFP network and XFP repeaters have
not been assessed to EN54-2.

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 13 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Fig. 12: Typical network wiring
Connect A to A, B to B and terminate incoming and outgoing earth screens to terminal C.
Note that earth screens should also be terminated at the base earth distribution post of
ONE main panel ONLY, as illustrated below.
TO NEXT
NETWORKED
PANEL IF
REQUIRED
TO NEXT
NETWORKED
PANEL IF
REQUIRED
NETWORK
COMMUNICATION
CARD
NETWORK
COMMUNICATION
CARD
NETWORK
COMMUNICATION
CARD
POWER SUPPLY
PCB
The network wiring should be installed to meet BS 5839: Part 1 and BS 7671 (Wiring Regulations)
and/or other national standards of installation where pertinent - see cable types & limitations, page 3.
A typical XFP main panel non-redundant network
A typical XFP repeater non-redundant network
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
MAXIMUM DISTANCE = 1km
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
XFP MAIN
PANEL 1
XFP MAIN
PANEL 2
XFP MAIN
PANEL 3
XFP MAIN
PANEL 4
XFP MAIN
PANEL 5
XFP MAIN
PANEL 6
XFP MAIN
PANEL 7
XFP MAIN
PANEL 8
SPUR WIRING
NOT ALLOWED
XFP MAIN
PANEL
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
MAXIMUM DISTANCE = 500m
XFP
REPEATER 2
XFP
REPEATER 4
XFP
REPEATER 3
XFP
REPEATER 1
XFP
REPEATER 5
XFP
REPEATER 6
XFP
REPEATER 7
XFP
REPEATER 8
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 14 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CONTROLS AND INDICATORS
Front panel layout
General fault
Fire Alarm Control Panel Instructions
To view more events use the scroll buttons
To silence the internal sounder:press
To silence/resound the alarm sounders:
Turn key to and press
press and . Enter code and press
l
OR
To reset the panel:
Ensure all alarm conditions are silenced and
investigations are complete and press
To exit access mode:
ORRemove key press and hold
flashing light - call engineer
Fire
12345678
910
11 12 13 14 15 16
control panel
reset silence/resound
sounders
silence internal
sounder
accessed
phased
evacuation
general
disablement
test
sounder
status
power
supply
fault
general
fault
system
fault
delays
running
supply
present
more
information
escape accept
10:59:03 24 Jun : Normal
FOXCO WAREHOUSING
LED Indicators
Liquid Crystal Display Provides detailed information on the status of the system (the type of messages
displayed and what they mean is covered in greater detail in the panel’s
separate user manual).
(General) Fire Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart the (General)
Fire indicator flashing until it is silenced again.
Fire Zones (1-16) One or more of these indicators will flash red in an alarm condition and will go
steady when silenced.
Supply Present Normally lit green to show that all of the panel’s power supplies are
functioning correctly.
Test Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
for any other test condition
Accessed Lit yellow when the panel is in access levels 2 or 3.
General Disablement Lit yellow when one or more zone, sounder, output or relay is disabled.
Phased Evacuation Flashes yellow when there is a phased evacuation in process.
General Fault Flashes yellow when there is a fault condition on the panel. Will always be lit
in conjunction with at least one other fault LED.
Power Supply Fault Lit yellow when the panel’s power supply or Mains has failed or the panel’s
standby battery is in poor condition.
System Fault Lit amber when a system error, such as a microprocessor fault, occurs. Remains
lit even if the panel automatically clears the fault.
Sounder Status Flashes yellow when a fault is detected on either of the panel’s two
conventional sounder circuits or if there is a sounder disablement anywhere on
the system.
Delays Running Lit yellow when one or more output delay has been programmed into the
panel. Flashes yellow when one or more output delay is running.

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 15 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Button controls
More Information Displays additional information on any fire, pre-alarm or fault conditions that
appear on the panel’s display. Will also display additional context dependent
information where appropriate.
(Scroll Up) 51 Dependent on the status of the panel, these two buttons:
(Scroll Down) 63 • scroll vertically through any fire, pre-alarm or fault conditions that appear on
the panel’s display
• scroll vertically through the panel’s user menus
• manipulate date, time and disablement settings, etc.
• serve as code input buttons to access levels 2 or 3.
Accept 42 Dependent on the status of the panel, these two buttons:
Escape 34 • scroll horizontally through the panel’s user menus
• escape or accept options available in the panel’s user menus
• serve as code input buttons to access levels 2 or 3.
Menu Provides access to the panel’s menus
Silence Internal Sounder Silences the panel’s internal sounder
Control Panel Reset Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Silence / Resound Sounders Silences or resounds the system’s sounders (access levels 2 & 3 only)
Investigate Starts the panel’s investigate timer function (access levels 2 & 3 only)
Keyswitch control
Turning the keyswitch to the armed position (I) gives the user instant access to
access level 2 (authorised user level).

COMMISSIONING AND PROGRAMMING
Overview
Commissioning is the setting to work of the equipment. The efficiency with which this is done
depends upon:
• The accuracy of information received regarding the wiring and devices fitted.
• The freedom of the installation from faults and errors.
• The completeness of the information received from the client/specifier as regards the zoning,
naming and functioning of the system.
The final quality of the installation ALWAYS depends upon the quality of these three factors.
Recommended commissioning procedure
Re-fit the panel’s PCBs and all connection leads by reversing the removal procedure detailed on page
5. Ensure all PCB retaining screws are firmly fastened down and that the PSU earth distribution strap
is connected to the base earth distribution post. If an optional network communication card is
required, this should be fitted as shown on page 12.
Check the continuity of the loop, the resistance of the conventional sounder circuits (if applicable)
and all other field wiring as appropriate to ensure they are free from faults. DO NOT use a high
voltage insulation tester with any electronic devices connected.
If okay, connect all field wiring to the main control PCB as detailed on pages 8 to 11.
Connect the Mains supply to the L, N and Earth terminals on the power supply PCB and the standby
battery supply to its BAT1 terminals.
Upon powering up, the panel’s LCD will display a number of start up messages detailing the protocol
of the panel, etc.
Investigate any faults reported on the panel’s display and take the necessary steps to correct them.
When all faults have been corrected, carry out a loop learn as detailed on page 21. Rectify any
problems resulting from loop learn (e.g. double addresses, missing devices, incomplete loops etc.
Note that a wide range of test and fault-finding functions are available in access level 3.
When all faults have been cleared, proceed to program the panel as appropriate.
When you are satisfied the panel has been programmed and is working correctly, secure the
panel lid and instruct the client/customer in the operation of the system.
Complete and handover all necessary manuals and other documentation prior to leaving site.
System operation / terms of reference
Input devices such as detectors, manual call points and the input channels of I/O units are
programmed to be members of a Zone.
Output devices such as loop powered sounders, sounder control units and the panel’s
conventional sounder circuits are programmed to be members of a Group.
The output channels of I/O units and the panel’s relays are programmed to be members of a Set.
Zones are programmed via the panel’s software to activate Groups and/or Sets as appropriate.
The method of activation of Groups can be continuous or pulsed, with or without a delay, as
required.
Note that the panel’s two auxiliary inputs can be programmed to function in a multitude of ways
using the special cause and effects options available in the XFP programming software.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 16 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 17 of 36
ACCESS LEVELS MENU TREE
Three access levels are available at the panel - access level 1 (general user), access level 2 (authorised
user) and access level 3 (engineer). The diagram below shows the menu options available at each level,
all of which can be navigated using the panel’s scroll (56), Accept (4) and Escape (3) buttons.
Note: The menu options shown in bold will only be available if relevant to the panel’s status.
This manual focusses on the functions available at access level 3 only (access levels 1 and 2 are
covered in the panel’s separate user manual). Details of how to gain entry to access level 3 and an
explanation of the various functions available can be found on the following pages.
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONESIN TEST
LAMPSTEST
DISPLAY ALARM COUNTER
SET TIME/DATE
EVENT LOGFUNCTIONS
SET/CLEAR DISABLEMENTS
CHANGE ACCESS LEVEL 2 CODE
DISPLAY ALARM COUNTER
Clear to todays date?
PRINT EVENT HISTORY?
DISPLAY EVENT HISTORY?
RESET EVENT HISTORY?
ENABLE/DISABLE ZONES
ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
ENABLE/DISABLE DEVICES
ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
ENTER ACCESS LEVEL 2
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONESIN TEST
ENTER ACCESS LEVEL 3
LAMPSTEST
DISPLAY ALARM COUNTER
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
SETUP PASSWORDS
CONNECT TO PC
NETWORK FUNCTIONS
COMMISSIONINGFUNCTIONS
ENGINEER FUNCTIONS
CHANGE ACCESS LEVEL 2 CODE
CHANGE ACCESS LEVEL 3 CODE
SET COMMSFUNCTION
SET PANEL NUMBER
SET PANEL FITTED
LOOP LEARN
FIND NEW DEVICES
SHOW FITTED DEVICES
ASSIGN ZONE/GROUP
CALIBRATE DEVICES
COMMISSION THE LOOP(S)
SHOW CALIBRATION PROBLEMS
SHOW DUPLICATE ADDRESSES
SET DAY/NIGHT TIMES
ENABLE/DISABLE DST ADJUSTMENT
CONFIGURE SOUNDER DISABLEMENTS
MAKE A CLEAN START
SET/CLEAR DISABLEMENTS
MONITOR A POINT
TEST DEVICE OUTPUTS
TEST OUTPUTSSETS
TEST SOUNDER GROUPS
TEST PANEL RELAYS
WALK TEST
BLINK DETECTORSLEDS
INTENSIVE DEVICE MONITOR
LOOP TEST
DISPLAY DATABASE
VERSION NUMBERS
SHOW PSU STATS
ENABLE/DISABLE EARTH FAULT
SHOW LOOP CURRENT
SHOW DISCOVERY EEPROM
SHOW NETWORKED EVENTS
ENABLE/DISABLE ZONES
ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
ENABLE/DISABLE DEVICES
ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
AL1
AL2AL3
Menu button
on front of panel
CODE ENTRY
CODE ENTRY
K/SENTRY
PRINT OPTION
NOT AVAILABLE!

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 18 of 36
How to enter access level three
Access level 3 can be entered in one of two ways:
(1) By pressing the Menu button on the panel’s front, scrolling down to ENTER ACCESS LEVEL 3 and
pressing the Accept4button. When you have done this, the following prompt will appear:
Enter the four-digit access level 3 code using the 5(1) 4(2) 6(3)3(4) buttons as appropriate.
The default code is 4 4 4 4 (four presses of the3button). If this does not work, the code may
have been changed. As soon as the code has been entered correctly, you will be taken into
access level 3 (see pages 19 to 33).
(2) By entering access level 2 as detailed in the panel’s separate user manual, scrolling down to
ENTER ACCESS LEVEL 3 and repeating the process described above.
In access level 3, the panel’s Silence/Resound Sounders, Control Panel Reset and Investigate buttons
become active and you can:
• Scroll through any fire, pre-alarm or fault conditions which are displayed on the panel’s LCD
• View any disablements or zones that are in test (if applicable)
• Change the entry codes to access levels 2 and 3 from their factory default settings
• Connect the panel to a compatible PC for system programming
• Set the panel up to belong to a non-redundant network of eight XFP main panels, or allow it to
have up to eight XFP repeaters connected to it
• Gain access to a wide range of commissioning functions including auto loop learn, device
calibration and group/zone assignment
• Gain access to a wide range of engineering test and fault finding functions
• Ascertain software revision numbers, loop current and PSU statistics
• Enable/disable earth faults
•Set the time the panel enters and exits day (building occupied) and night (building unoccupied) mode
• Access all of the panel’s access level 2 menu options as described in the panel’s separate user manual.
This section of the engineering manual explains in detail the various functions available via the
access level 3 menu options. (Note that information on how fire, pre-alarm and fault conditions are
reported, and how the panel’s control buttons operate, can be found in the separate user
manual/log book.)
Fitting the panel’s NVM ‘memory unlock’ link
To allow site-specific changes to be made to the panel’s
non-volatile memory, the NVM ‘memory unlock’ link must
be fitted to the Main Control PCB, as shown right. It is
recommended that you fit this link as a matter of course
whenever you are in access level 3.
Remember to re-lock the memory (remove the link) when
programming is complete to guard against data corruption.
If you do not re-lock the memory, a reminder message will
appear when you leave access level 3.
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
GENERAL
FIRE ZONE 1 ZONE 2 ZONE
ZONE 9 ZONE 10 ZONE
D45
SUPPLY
PRESENT TEST ACCESSED
Mute
Beeper
Memory
Unlock
Enter Access Level 3 code:
NVM memory
unlock link
A detailed description of the functions available at access level 3 can be found overleaf.

Display Fire Events
This function is only available if there are active fire conditions on the system. If available, press the
Accept4button and a window similar to the one below will appear:
Pressing the 5and6buttons will scroll the display through all active fire conditions. More detailed
information (if applicable) can be viewed by pressing the panel’s More Information button. To return
to the main access level 3 menu press the Escape3button.
Display Fault Events
This function is only available if there are active faults on the system. If available, press the Accept4
button and a window similar to the one below will appear:
Pressing the 5and6buttons will scroll the display through all active faults. More detailed
information (if applicable) can be viewed by pressing the panel’s More Information button. To return
to the main access level 3 menu press the Escape3button.
Display Disablements
This function is only available when there are active disablements on the system. If available, press
the Accept4button and a window similar to the one overleaf will appear:
Pressing the 5and6buttons will scroll the display through all active disablements. More detailed
information (if applicable) can be viewed by pressing the panel’s More Information button. To return
to the main access level 3 menu press the Escape3button.
Display Zones In Test
This function is only available if one or more zones are being tested. If available, press the
Accept4button and a window similar to the one below will appear:
Pressing the 5and6buttons will scroll the display through all zones currently in test. More detailed
information (if applicable) can be viewed by pressing the panel’s More Information button. To return
to the main access level 3 menu press the Escape3button.
Setup Passwords
This function allows you to change the four digit access codes required to activate the panel’s access level
2 or 3 menu options. When selected, press the Accept4button and the following window will appear:
Use the 5and 6buttons to scroll to the desired option (the option in block capitals is the selected
option) and press the Accept4button. The following message will appear if the CHANGE ACCESS
LEVEL 2 CODE?prompt is accepted.
Using the 5(1) 4(2) 6(3)3(4) buttons, enter the new four digit access level 2 code. After the fourth
digit has been entered, the panel will request you confirm the new code by re-entering it:
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 19 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Last Zone: 1:North Stairs :Fire!
1 Zone
Zone 1: GroundFloor
There are faults on this zone
1st Zone: 1: Shop floor
On: This Panel: Is Disabled
Zone 1: North Stairs
Is On Test
CHANGE ACCESS LEVEL 2 CODE?
Change Access Level 3 code
Enter NEW Access Level 2 code:

Enter the code again by pressing the 5(1) 4(2) 6(3)3(4) buttons in same sequence. If the two codes match,
the new code will be accepted and you will be taken back into Access Level 3. If you type an incorrect
confirmation code you will be prompted to start the code entry sequence again. The same process can be
used to change access level 3 code. BE SURE TO KEEP A RECORD OF ANY CHANGED CODES FOR FUTURE USE.
Connect to PC
This function allows you to activate the panel’s PC connection for system programming purposes. ALL of the
panel’s cause and effect programming, device and zone naming, zone dependency functions, etc., must be
carried out using our separately PC programming software tools (XFP507). When the CONNECT TO PC?
prompt appears, press the Accept4button. If all connections are correct, the following message will appear:
If there is a problem with the panel to PC connection, this will be flagged at the PC when you try to
upload or download any site specific data.
Network functions (optional)
Selecting this menu option takes you to the network functions submenu where you can configure the
panel to be part of a non-redundant network of up to eight XFP main panels, OR allow it to have up to
eight XFP repeaters connected to it. This option is only available if you have a network communication
card fitted at the panel (see pages 12 & 13 for a detailed overview of main panel networking and
repeater panel connection). The network functions submenu has three options - SET COMMS FUNC-
TION, SET PANEL NUMBER and SET PANEL FITTED. Other options, such as what events and what level
of control is allowed between networked panels is implemented using the panel’s PC programming
software tools.
SET COMMS FUNCTION
This function allows you to set the panel’s RS485 comms to operate in Network or Repeater mode.
When selected, press the Accept4button and a message similar to the one below will appear:
Use the 5and 6buttons to scroll between Repeater and Network and press the Accept4button as
appropriate. The panel’s flash database will update and you will be returned to the Network Functions submenu.
SET PANEL NUMBER
If networking XFP main panels, this function allows you to give the panel a unique ID number (1-8) so it can
be recognised by other panels on the network. Note that Repeaters do not need to be assigned an ID number.
When selected, press the Accept4button and a message similar to the one below will appear:
Use the 5and 6buttons to scroll to the desired number and press the Accept4button to select it.
The panel’s flash database will update and you will be returned to the Network Functions submenu.
SET PANEL FITTED
This function allows you to turn off the fault monitoring of other networked XFP main panels. Typically used if
maintenance work is to be carried out at a networked panel to temporarily prevent integrity faults being
flagged. When selected, press the Accept4button and a message similar to the one below will appear:
Use the 5and 6buttons to scroll to the desired networked panel and press the Accept4button to accept
it. The panel’s flash database will update and you will be returned to the Network Functions submenu.
Remember to reverse the function when maintenance work is complete.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 20 of 36
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
SET PANEL NUMBER:1
NETWORK PANEL:1
Enter NEW Access Level 2 code:****
Confirm New Access Level 2 code:
PCconnected...
Press ESC to disconnect from PC
COMMSISSET FOR: REPEATER
Note: The XFP network and XFP repeaters have
not been assessed to EN54-2.
This manual suits for next models
1
Table of contents
Other XFP Control Panel manuals