Xintex RCM5-XX User manual

1
Part Number 18153, D 10/03/2017
Relay Control Module
RCM5-XX
Owner’s Manual
&
Installation Instructions
Read and comply with all instructions, warnings and limitations before
installing, servicing or removing this device.

2
Part Number 18153, D 10/03/2017
Additional copies of this manual are available at no charge by contacting the manufacturer,
distributor or dealer. Fireboy-Xintex reserves the right to change features without notice.
General Information
3
Specifications
3
System Specifications
3
Compatible Devices
3
Operation of Xintex Relay Control Module(s)
4
Locating a Xintex Relay Control Module
4
Installation
4
Mounting the Relay Control Module
4
Electrical Connections
5
Testing
6
Maintenance
6
Repairing Xintex Relay Control Modules
6
Returning Xintex Relay Control Modules
6
1 Year Limited Warranty
7

3
Part Number 18153, D 10/03/2017
General Information
The RCM5 is a Relay Control Module. It allows you to automatically deactivate devices based on
the status of the connected Xintex detection device. The RCM5 uses a signal provided by the
connected Xintex device to activate the internal relay. This allows you to shutdown generators or
other devices automatically.
Specifications
System Specifications
Operating Voltage: 9-32 VDC
Nominal Current Draw: 15mA @ 12 VDC
Maximum Current Draw: 40mA @ 9 VDC
Maximum Relay Voltage: 30 VDC
Maximum Relay Switching Current: 1 A
Operating/Storage Temperature: -40°F (-40°C) to 158°F (70°C)
Dimensions: 3.1” (76mm) x 2.1” (52mm) x 1.83” (46mm)
Housing Material: Flame Retardant ABS
Compatible Devices
CMD5-MBI-XX Marine CO Alarm, Battery Powered, Interconnect
CMD5-MBI-BX Marine CO Alarm, Battery Powered, Interconnect, Black Housing
CMD5-MDI-XX Marine CO Alarm, 12/24 VDC Powered, Interconnect
CMD5-MDI-BX Marine CO Alarm, 12/24 VDC Powered, Interconnect, Black Housing
CMD5-RBI-XX RV CO Alarm, Battery Powered, Interconnect
CMD5-RBI-BX RV CO Alarm, Battery Powered, Interconnect, Black Housing
CMD5-RDI-XX RV CO Alarm, 12/24 VDC Powered, Interconnect
CMD5-RDI-BX RV CO Alarm, 12/24 VDC Powered, Interconnect, Black Housing
CMD5-HBI-XX Residential CO Alarm, Battery Powered, Interconnect
CMD5-HBI-BX Residential CO Alarm, Battery Powered, Interconnect, Black Housing
WARNING:
12/24 VDC POWERED AND BATTERY POWERED UNITS SHOULD NOT BE INTERCONNECTED
TOGETHER. IF 12/24 VDC POWER IS LOST, THEN THE INTERCONNECTED BATTERY UNITS WILL GO
INTO INTERCONNECT ALARM. THE RCM5 UNIT WILL ALSO BE TRIPPED IF 12/24 VDC POWER IS
STILL PRESENT AT THE RELAY CONTROL MODULE.

4
Part Number 18153, D 10/03/2017
Operation of Xintex Relay Control Module(s)
The RCM5 has a 6 position terminal strip located on the top face of the unit. Power must be
supplied to the unit, as well as the signal from a Xintex detection device. When the RCM5
receives the signal from the connected Xintex device, the relay is tripped. The RCM5 can be used
to interrupt a device’s ground and disable the device.
Locating a Xintex Relay Control Module
Locate the RCM5 in a convenient place near the Xintex detection device for periodic testing and
maintenance. Do not install in the bilge area, engine compartment or other hazardous locations.
Do not install in locations where temperature, moisture, and/or ultraviolet light affect operation.
This is not an ignition protected device.
Installation
Mounting the Relay Control Module
Use appropriate length #8, Pan Head screws to secure Mounting Base. Two styles of
3/4” length provided.
Do not over-tighten.

5
Part Number 18153, D 10/03/2017
Electrical Connections
Use 18 Gauge wire in accordance with ANSI/NFPA 70 to make connections to the device. The
resistance of the interconnected wiring shall be a maximum of 10 ohms.
For CMD5-(x)BI units:
Connect the Yellow wire from the CMD5 to the SIG terminal of the RCM5. Connect both the
Battery NEG and the Brown wire from the CMD5 to the NEG terminal of the RCM5.
For CMD5-(x)DI units:
Connect the Yellow wire from the CMD5 to the SIG terminal of the RCM5. Connect both the
Battery NEG and the Brown wire from the CMD5 to the NEG terminal of the RCM5. The Brown
wire from the CMD5 could also be grounded elsewhere as long as that location is also on the
same battery circuit.

6
Part Number 18153, D 10/03/2017
Testing
Disconnect the NC wire connection on the RCM5. When the wire is disconnected, the connected
device will turn off within 20 seconds.
Maintenance
The system should be tested periodically in the fashion described in the previous section. Use
pressurized air to clean when necessary.
Repairing Xintex Relay Control Modules
Xintex Relay Control Modules are not field serviceable. Components must be returned to the
factory for any repairs.
Returning Xintex Relay Control Modules
No product may be returned for credit or repair without a written “Returned Material
Authorization” (RMA) form. Purchaser must call or email Fireboy-Xintex 616-735-9380 or
returned, after approval it must be received in 100% new/resalable condition. Products stored by
the buyer for more than 26 weeks may not be returned for any reason. Maintaining fresh and
current inventory is the responsibility of the buyer.

7
Part Number 18153, D 10/03/2017
1 Year Limited Warranty
This Warranty is in lieu of all other expressed or implied Warranties
Seller warrants title, materials, and workmanship on equipment, except components
manufactured by others for which the Seller assigns, as permitted, the original manufacturer’s
warranty. Seller’s warranty shall be for a period of (1) one year from the date of sale to the
ORIGINAL CONSUMER PURCHASER, during which non-conforming equipment returned to the
Seller at Buyer’s expense and risk, be repaired or replaced at the Seller’s option. Fireboy-Xintex
LLC will repair or replace products found to be defective in materials or workmanship within the
period set forth above, provided that: (a) the product has not been subjected to abuse,
contamination, neglect, accident, incorrect wiring not our own, improper installation or servicing,
or used in violation of instructions furnished by Fireboy-Xintex LLC and (b) as to any prior defects
in materials or workmanship covered by this warranty, the product has not been repaired or
altered by anyone except Fireboy-Xintex, Inc and (c) the serial number has not been removed,
defaced or otherwise changed, and (d) examination discloses, in the judgment of Fireboy-Xintex
LLC, does not assume the costs of removal and/or installation of the product or any other
incidental costs of removal and/or installation of the product or any other incidental costs which
may arise as a result of any defect in material or workmanship, and (e) upon discovery of defect,
Buyer shall immediately cease use of and notify Fireboy-Xintex LLC.
Any warranty implied by law, including warranties of merchantability or fitness, is in effect only
for the duration of the expressed warranties set forth above, no person is authorized to give any
other warranty, or to assume for Fireboy-Xintex LLC any other liability in connection with the sale
of its products; Fireboy-Xintex LLC shall not be liable for the loss of use, revenue, or profit or for
any injury, or for any other consequential or incidental damages, buyer is not relying on seller’s
judgment regarding his or her particular requirements, and has had an opportunity to inspect the
product to his or her satisfaction.
This warranty gives you specific legal rights, and you may also have other rights, which vary, from
state to state.