Xintex P-1BS-R Original instructions

1
Part Number 18143, E, 01/28/2020
Propane Fume Detection System
With Solenoid Valve Control
Single Channel Systems
P-1BS-R (Black, Round, Solenoid Control, 12V Solenoid)
P-1BS-24-R (Black, Round, Solenoid Control, 24V Solenoid)
P-1CS-R (Chrome, Round, Solenoid Control, 12V Solenoid)
P-1CS-24-R (Chrome, Round, Solenoid Control, 24V Solenoid)
Dual Channel System
P-2BS-R (Black, Square, Solenoid Control, 12V Solenoid)
P-2BS-24-R (Black, Square, Solenoid Control, 24V Solenoid)
Owner’s Manual
&
Installation Instructions
Read and comply with all instructions, warnings and limitations before
installing, servicing or removing this device.

2
Part Number 18143, E, 01/28/2020
Additional copies of this manual are available on the Fireboy-Xintex website. Fireboy-Xintex
reserves the right to change features without notice.
General Information
3
Specifications
3
Operation of Xintex Propane Fume Detector(s)
4
Installation
6
Installing the Display Unit (P1BR-S01-D/P1CR-S01-D & P2BS-S01D)
6
Installing the Solenoid Valve for LPG Applications
6
Routing Sensor Cable(s) (FS-X01 CABLE XX’)
6
Installing Propane Fume Sensor(s) (FS-T01)
7
Electrical Connections (P1BR-S01-D/P1CR-S01-D & P2BS-S01D)
7
Testing the System Operation
7
Testing the Propane Fume Sensors
8
Maintenance
8
In the Event of an Alarm
8
Repairing Xintex Propane Detection Components
8
Returning Xintex Propane Detection Components
8
1 Year Limited Warranty
9

3
Part Number 18143, E, 01/28/2020
General Information
WARNING
PROPANE FUME DETECTORS ARE MEANT TO SERVE AS A SUPPLEMENTAL WARNING SYSTEM. IT IS
NOT MEANT TO REPLACE STANDARD SAFETY PRACTICES WHICH SHOULD BE CARRIED OUT
AROUND EXPLOSIVE GASES.
The P-1BS-R, P-1CS-R, and P-2BS-R Propane Fume Detectors are an effective means to monitor
propane fumes in a compartment or leaking fuel systems. In addition, these units have the ability
to control the flow of CNG/LPG to your appliances. The system uses a sensor, located in a place of
interest, and a central display unit that notifies you of the state of the system.
Specification
System Specifications (P-1BS-R/P-1CS-R)
Operating Voltage: 9-18V DC
Nominal Current Draw: 55mA @ 12V DC
Maximum Current Draw: 725mA @ 9V DC
Operating Temperature: -40°F (-40°C) to 185°F (85°C)
Alarm Horn: ≈ 68 dB
System Specifications (P-1BS-24-R/P-1CS-24-R)
Operating Voltage: 18-30V DC
Nominal Current Draw: 25mA @ 24V DC
Maximum Current Draw: 41mA @ 18V DC
Operating Temperature: -40°F (-40°C) to 185°F (85°C)
Alarm Horn: ≈ 68 dB
System Specifications (P-2BS-R)
Operating Voltage: 9-18V DC
Nominal Current Draw: 95mA @ 12V DC
Maximum Current Draw: 780mA @ 9V DC
Operating Temperature: -40°F (-40°C) to 185°F (85°C)
Alarm Horn: ≈ 68 dB
System Specifications (P-2BS-24-R)
Operating Voltage: 18-30V DC
Nominal Current Draw: 45mA @ 24V DC
Maximum Current Draw: 51mA @ 18V DC
Operating Temperature: -40°F (-40°C) to 185°F (85°C)
Alarm Horn: ≈ 68 dB

4
Part Number 18143, E, 01/28/2020
Operation of Xintex Propane Fume Detector(s)
There are 3 LEDs located on the Display Unit for each channel on the system, as well as an LED for
the Solenoid Valve status. The Green LED, located at the top, indicates that the system is
operational. The Yellow LED, located in the center, indicates that there is a Fault in the system.
This is to notify the user to check the connections and wire runs of the sensors. There may be a
break in the wiring or a disconnected sensor on that channel. The Red LED, located at the bottom,
indicates a fume buildup of 20% of the LEL (Lower Explosive Limit) which is considered an alarm.
The alarm horn will sound when the Red LED is illuminated. The alarm horn will actuate, Solenoid
Valve will close, and the Solenoid Valve status LED will deactivate when the Red LED is
illuminated. Whenever the Solenoid Valve status LED is illuminated, the Solenoid Valve is open.
The alarm status will continue as long as the fume level remains at an elevated level. The alarm
horn may be silenced by pressing the “Check/Reset” button. The alarm will reactivate after 30
seconds as long as the Detector remains in alarm status. The problem should never be considered
corrected as long as the Red LED is illuminated.
P2BS-S01-D
P1BR-S01-D
P1CR-S01-D

5
Part Number 18143, E, 01/28/2020
P1BR-S01-D
P1CR-S01-D
FS-X01 CABLE XX’
FS-T01
RED –Power (+) 1.0 Amp Fuse from Circuit Breaker
BLACK –Ground (-)
Positive (+) voltage
From
Solenoid Circuit
Breaker (2A)
(May be obtained
@ Display Unit. 2A
fuse recommended)
Solenoid
Valve
YELLOW –Switching Ground
2A Fuse Included
FS-X01 CABLE XX’
FS-T01
FS-X01 CABLE XX’
FS-T01
P2BS-S01-D
RED –Power (+) 1.0 Amp Fuse from Circuit Breaker
BLACK –Ground (-)
Solenoid
Valve
YELLOW –Switching Ground
2A Fuse Included
Positive (+) voltage
From
Solenoid Circuit
Breaker (2A)
(May be obtained
@ Display Unit. 2A
fuse recommended)

6
Part Number 18143, E, 01/28/2020
Installation
Installing the Display Unit (P1BR-S01-D/P1CR-S01-D & P2BS-S01D)
The Display Unit should be located at the instrument panel, so that the visible and audible
indicators may be easily observed.
Drill a 2-1/16” hole to accommodate the P1BR-S01-D/P1CR-S01-D Display Unit.
Drill a 2-1/8” hole to accommodate the P2BS-S01-D Display Unit.
Insert Display Unit into hole and secure with the provided threaded mounting nut. A Trim Ring is
available if needed.
NOTE
DO NOT MAKE ELECTRICAL CONNECTIONS AT THIS TIME. THEY WILL BE ADDRESSED IN A LATER
SECTION.
Installing the Solenoid Valve for LPG Applications
The Solenoid Valve should be mounted on the tank side of the LPG regulator, as close to the tank
as practical. The tank itself should be mounted outside the cabin or crew quarters to avoid the
possibility of gas accumulation due to a leak.
NOTE
TIGHTEN TO 12-13 FT/LBS. DO NOT OVER-TIGHTEN.
NOTE
ALL PIPING MUST BE CHECKED FOR LEAKS. USE SOAPY WATER SOLUTION ON ALL JOINTS. NEVER
USE A FLAME TO CHECK FOR LEAKS.
Routing Sensor Cable(s) (FS-X01 CABLE XX’)
A 20 FT Sensor Cable is provided for each Propane Fume Sensor. The Sensor Cables should be
routed starting at the Display Unit, then to the pre-determined location of the Propane Fume
Sensor. Connect to the Display Unit using the attached quick-disconnect connectors. Take care
not to pinch, break, or cut the Sensor Cable or put too much stress on the connectors while
routing the cable. Secure the Sensor Cable with the appropriate hardware for the application.
NOTE
DO NOT CUT EXTENSION CABLE FOR ANY PURPOSE. DOING SO VOIDS THE PRODUCTS
WARRANTY. LONGER CABLES ARE AVAILABLE FROM 20 FT TO 100 FT.

7
Part Number 18143, E, 01/28/2020
Installation Continued
Installing Propane Fume Sensor(s) (FS-T01)
The Propane Fume Sensor should be located by the propane powered appliance, near the floor.
Avoid areas where damage may take place due to cleaning, mopping, kicking, or other physical
damage. Harsh chemicals should not be used to clean sensors.
Use the appropriate #8 mounting hardware to mount the Propane Fume Sensor in the desired
location. The rubber gasket should be installed between the sensor and the mounting surface.
Connect to the Extension Cable using the attached quick-disconnect connectors.
Electrical Connections (P1BR-S01-D/P1CR-S01-D & P2BS-S01-D)
The Display Unit operates on 9-30V DC. A Red and a Black 16 GA wire are provided for connecting
to the power source. Connect the Red wire to Power (+) with an inline 1.0 Amp fuse. Connect the
Black wire to Ground (-).
A 2A fused Yellow 16 GA wire is provided for connecting the Display Unit to the Solenoid Valve.
Connect the Yellow wire to the Solenoid Valve. Connect the positive (+) voltage to the Solenoid
Valve.
NOTE
UNITS MANUFACTURED PRIOR TO JANUARY 01, 2018 DO NOT INCLUDE THE 2A FUSE. A
DEDICATED 2A FUSE OR BREAKER SHOULD BE USED TO POWER THE SOLENOID VALVE.
NOTE
IMPROPER CONNECTIONS WILL DAMAGE THE DISPLAY UNIT AND WILL VOID WARRANTY.
Testing the System Operation
The Propane Fume Detectors can be tested by pressing the “Check/Reset”button on the face of
the Display Unit. The Display Unit will cycle through the LEDs and the alarm horn will activate
while the LEDs cycle.
Unplug the Propane Fume Sensor from each channel of the Detection System one at a time. The
Yellow “Fault” LED should illuminate. If the Yellow LED does not illuminate, remove Display Unit
and return direct to manufacturer following the instructions at the back of this manual.
To test the Solenoid Control function, check that the flame of your appliance extinguishes when
the Solenoid Control function is turned OFF.

8
Part Number 18143, E, 01/28/2020
Testing the Propane Fume Sensors
WARNING
DO NOT USE A PROPANE SOAKED RAG OR A PARTIALLY FULL CONTAINER OF PROPANE TO TEST A
SENSOR. THE RAW PROPANE COULD IGNITE, RESULTING IN SERIOUS INJURY.
Test the Sensors by holding an unlit Butane lighter to the sensor. Within a few seconds, the Red
“Danger” LED should illuminate and the alarm horn will sound. Remove the lighter from the
Sensor and mute the alarm horn. After approximately one minute, the Red LED will shut off.
Maintenance
The system should be tested periodically in the fashion described in the previous sections. Due to
the harsh environmental conditions in marine applications, it is recommended to replace the
Propane Fume Sensors every 3-4 years.
In the Event of an Alarm
Immediately have all passengers and crew exit the passenger compartment and vessel if possible.
Ventilate the space being monitored.
Carefully check all fuel lines and other potential sources of propane fume leaks. If leaks are
identified, shut off fuel supply and make any necessary repairs.
Repairing Xintex Propane Fume Detection Components
Xintex Propane Fume Detection Components are not field serviceable. Components must be
returned to the factory for any repairs.
Returning Xintex Propane Detection Components
No product may be returned for credit or repair without a written “Returned Material
Authorization” (RMA) form. Purchaser must call or email Fireboy-Xintex 616-735-9380 or
returned, after approval it must be received in 100% new/resalable condition. Products stored by
the buyer for more than 26 weeks may not be returned for any reason. Maintaining fresh and
current inventory is the responsibility of the buyer.

9
Part Number 18143, E, 01/28/2020
1 Year Limited Warranty
This Warranty is in lieu of all other expressed or implied Warranties
Seller warrants title, materials, and workmanship on equipment, except components
manufactured by others for which the Seller assigns, as permitted, the original manufacturer’s
warranty. Seller’s warranty shall be for a period of (1) one year from the date of sale to the
ORIGINAL CONSUMER PURCHASER, during which non-conforming equipment returned to the
Seller at Buyer’s expense and risk, be repaired or replaced at the Seller’s option. Fireboy-Xintex
LLC will repair or replace products found to be defective in materials or workmanship within the
period set forth above, provided that: (a) the product has not been subjected to abuse,
contamination, neglect, accident, incorrect wiring not our own, improper installation or servicing,
or used in violation of instructions furnished by Fireboy-Xintex LLC and (b) as to any prior defects
in materials or workmanship covered by this warranty, the product has not been repaired or
altered by anyone except Fireboy-Xintex LLC and (c) the serial number has not been removed,
defaced or otherwise changed, and (d) examination discloses, in the judgment of Fireboy-Xintex
LLC, does not assume the costs of removal and/or installation of the product or any other
incidental costs of removal and/or installation of the product or any other incidental costs which
may arise as a result of any defect in material or workmanship, and (e) upon discovery of defect,
Buyer shall immediately cease use of and notify Fireboy-Xintex LLC.
Any warranty implied by law, including warranties of merchantability or fitness, is in effect only
for the duration of the expressed warranties set forth above, no person is authorized to give any
other warranty, or to assume for Fireboy-Xintex LLC any other liability in connection with the sale
of its products; Fireboy-Xintex LLC shall not be liable for the loss of use, revenue, or profit or for
any injury, or for any other consequential or incidental damages, buyer is not relying on seller’s
judgment regarding his or her particular requirements, and has had an opportunity to inspect the
product to his or her satisfaction.
This warranty gives you specific legal rights, and you may also have other rights, which vary, from
state to state.
www.fireboy-xintex.com
Fireboy-Xintex LLC
O-379 Lake Michigan Dr. NW
Grand Rapids, MI 49534
Phone (616) 735 9380
Fireboy-Xintex UK Operations Limited
10 Holton Road, Holton Heath Trading Park
Poole Dorset BH16 6LT UK
Phone 44 (0) 845 9462