YOKOGAWA UM33A/S006 User manual

User’s
Manual UM33A/S006
Digital Indicator with Alarms
(with RS485 Communication Function
(Modbus Master/Monitor))
User’s Manual
<Detailed Instructions> IM UM33A-01EN-S6
IM UM33A-01EN-S6
1st Edition
Functional
Enhancement

1
1Introduction
1.1 Overview
The following two functions are incorporated into the UM33A/S006.
• Modbus/RTU master function (read only)
• Modbus/RTU communication data monitor function
The Modbus/RTU master function allows the registers of Modbus slave devices on the same circuit
line to be read out. The Modbus/RTU communication data monitor function allows communication
between a Modbus master and slaves to be monitored and the response values of the slaves to be
displayed.
This instruction manual describes the difference between this TOKUCHU model and standard model.
Before reading this document, please read the instruction manual of standard model (document
number: IM 05P03D21-01EN)
2Model and Suffix Code
UM33A-010-□□/□/S006
□: Specified when ordering
Note 1: When the /LP option is specified, the RS-485 communication of the Type 2 code “1” is 2-wire
system.
Note 2: When the /CT option is specified, the product does not conform to the safety standards (UL and
CSA) or CE marking (Products with /CT option are not intended for EEA-market).
Model Optional suffix code Description
UM33A
Digital Indicator with Alarms (Power supply 100-240 V AC)
(provided with retransmission output or 15 V DC loop power
supply, 2 DIs, and 3 DOs)
Type 1 (Basic) -0 Standard type
1(Note 1)
1 additional DO (c-contact) and RS485 communication (Max.38.4
kbps, 2-wire/4-wire)
0NONE
-0 English (degC)
-1 English (deg C& deg F)
0White (Light gray)
1Black (Light charcoal gray)
/LP 24 V DC loop power supply
/DC Power supply 24 V AC/DC
/CT (Note 2) Coating
/CV Terminal cover
/S006
RS485 communication (Max.38.4 kbps, 2-wire/4-wire)
MODBUS RTU Master/Moniter
Display language
TOKUCHU
Suffix code
Type 2 (Functions)
Type 3 (Open networks)
Case color
LPS option
Power supply option
Additional treatment option
Terminal Cover
Communication
Modbus
Modbus slave

2
3UM33A Modbus/RTU Master Function, Communication
Data Monitor Function
3.1 Modbus/RTU Master Function
This TOKUCHU product has a Modbus/RTU master function. The Modbus/RTU master function allows
the registers of slave devices on the same circuit line to be read out and displayed on the UM33A
screen.
From the master side, Modbus Coil, Discrete Inputs, Holding Resister, and Input Resister can be read
out. The supported Modbus/RTU function codes are 01 (Coil), 02 (Discrete Inputs), 03(Holding
Resister), and 04 (Input Resister). The maximum number of read commands and displays is eight.
Modbus master function
Description
Notes
Read
Allowed
Write
Not allowed
Maximum number of commands
8
8 maximum also
for displays
Supported function codes
01 (Coil: 1 to 9999)
02 (Discrete Inputs: 10001 to 19999)
03 (Holding Resister: 40001 to 49999)
04 (Input Resister: 30001 to 39999)
Supported data types
Bit
16 bit integer (signed only)
32 bit integer (signed only)
FLOAT
Maximum number of slave devices
that can be connected on the
same circuit line
31
VOLt
Up to 31 connected slaves with a maximum length of 1200 m
Slave Slave
Master
Slave

3
3.2 Modbus/RTU Communication Data Monitor Function
This TOKUCHU product has a Modbus/RTU communication data monitor function. The Modbus/RTU
communication data monitor function allows the monitoring of register readout communication
between a Modbus/RTU master and slave devices on the same circuit line. This function allows
communication response values transmitted on the same circuit line to be displayed on the UM33A
screen without the UM33A sending communication commands.
Communication to Modbus Coil, Discrete Inputs, Holding Resister, and Input Resister can be
monitored. The supported Modbus/RTU function codes are 01 (Coil), 02 (Discrete Inputs),
03(Holding Resister), and 04 (Input Resister). The maximum number of read commands and displays
is eight.
For the continuous readout commands sent from the Modbus master side to the slave side, the first
setting parameter length of data (16 bits (1 register) for the Bit and 16 bit integer data types and 32
bits (2 registers) for the 32 bit integer and FLOAT data types) can be obtained.
Modbus communication data
monitor function
Description
Notes
Read command support
Allowed
Write command support
Not allowed
Maximum number of commands
8
8 maximum also
for displays
Supported function codes
01 (Coil: 1 to 9999)
02(Discrete Inputs: 10001 to 19999)
03(Holding Resister : 40001 to 49999)
04(Input Resister : 30001 to 39999)
Supported data types
Bit
16 bit integer (signed only)
32 bit integer (signed only)
FLOAT
Maximum number of devices that
can be connected on the same
circuit line
The total number of Modbus slave
devices and Modbus communication
data monitors is 31.
VOLt
Slave Slave
Monitor
Slave
Master
Up to 31 connected slaves and monitor with a maximum length of 1200 m

4
3.3 Communication Conditions
○ Connected devices
Up to 31 devices equipped with Modbus RTU communication function can be connected.
○ Restrictions on connected devices
The communication conditions, namely the baud rate, parity, stop bit, and data length, of connected
devices must be the same as those of this instrument.
3.4 Simple flow for using Modbus RTU Master/Monitor
3.5 Display Error of Communication PV
For the FLOAT data type, the display error of communication PV is ± 1digit.

5
3.6 Data Types Supported by Communication PV and Display
Limits
The following table shows the display limits for each of the data types supported by communication
PV. For the FLOAT type, a fixed decimal place display and an auto range display (see section 3.4) are
available. The following table shows the figures for the fixed decimal place. Numbers outside the
-19999 to 99999 range ignoring the decimal point are displayed as ±OVER.
Table 3.5.1 Data types supported by communication PV and display limits
Decimal
place
parameter
Low limit
of
expression
High limit
of
expression
BIT
display range
16 bit integer
(signed)
display range
32 bit integer
(signed)
display range
FLOAT
display range
(when fixed
decimal point
is selected)
0
-19999
99999
High limit: 1
Low limit: 0
High limit:
32767
Low limit:
-19999
High limit:
99999
Low limit:
-19999
High limit:
99999
Low limit:
-19999
1
-1999.9
9999.9
High limit: 0.1
Low limit: 0.0
High limit:
3276.7
Low limit:
-1999.9
High limit:
9999.9
Low limit:
-1999.9
High limit:
9999.9
Low limit:
-1999.9
2
-199.99
999.99
High limit:
0.01
Low limit:
0.00
High limit:
327.67
Low limit:
-199.99
High limit:
999.99
Low limit:
-199.99
High limit:
999.99
Low limit:
-199.99
3
-19.999
99.999
High limit:
0.001
Low limit:
0.000
High limit:
32.767
Low limit:
-19.999
High limit:
99.999
Low limit:
-19.999
High limit:
99.999
Low limit:
-19.999
4
-1.9999
9.9999
High limit:
0.0001
Low limit:
0.0000
High limit:
3.2767
Low limit:
-1.9999
High limit:
9.9999
Low limit:
-1.9999
High limit:
9.9999
Low limit:
-1.9999

6
3.7 L-H and H-L Register Arrangements When 32 bit LONG or
FLOAT Is Selected
For 32 bit integer and FLOAT types, L-H or H-L order can be selected. Set it according to the devices in use.
Figure 3.6.1 32 bit L-H register arrangement
Figure 3.6.2 32 bit H-L register arrangement
3.8 Display Screen (Communication PV1 to Communication PV8)
The measured value of the specified register (MB.ST menu) is displayed. Communication PV number
is shown on the group display. Only when the acquired data type is 16 bit integer, hexadecimal
expression can be used by changing FRMT (MB.ST menu) to HEX.
When the acquired data type is FLOAT and the auto range function is in use, a unit prefix is displayed.
The unit prefix display can be switched between “T, G, M, k, etc.” and exponential type (E03, E00,
etc.). Table 3 shows the unit prefix display during auto range. If the value is smaller than ±p (pico)
range when auto range is in use, “0” is displayed.
k VOLt
Group display
Prefix display
Unit display
Communication
PV display

7
Table 3.7.1 Unit prefix display
Unit display (when unit is selected)
Unit display (when exponent is selected)
T (tera)
E12
G (giga)
E09
M (mega)
E06
k (kilo)
E03
No display
E00
ML (milli)
E-03
u (micro)
E-06
N (nano)
E-09
P (pico)
E-12
The unit display shows the selected unit (VOLT, A, C, etc.).
The display can be shown or hidden with the communication ONOFF (MB.ST menu) value.
When the communication function ONOFF (MB.ST menu) values are all set to hidden, only the PV
input is displayed.
If the PV input is hidden, at least one of the ONOFF (MB.ST menu) value is ON.
3.9 Display Screen (PV Input)
The PV input is displayed.
The unit (VOLT, A, C, etc.) is displayed.
The display can be shown or hidden with display U.PV (KLOC menu) OFF/ON value.
When the communication function ONOFF (MB.ST menu) (1 to 8) values are all set to OFF, the PV
input cannot be hidden. When any of the communication function ONOFF (MB.ST menu) (1 to 8)
values is ON, the PV input can be hidden.
VOLt
Unit display
Communication
PV display

8
3.10 Auto/Manual Switching of the Operation Screen
When auto switching of the operation screen is used, the PV input value switches automatically
between communication PV1, communication PV2, . . . communication PV8 at the specified display
update interval (3S, 10S, 30S, 1M).
When manual switching of the operation screen is used, the PV input value is switched between
communication PV1, communication PV2, . . . communication PV8 every time the DISP key is
pressed.
You can switch between auto switching and manual switching using the Fn key. Switching is also
possible using parameters.
3.11 Display Screen for Communication Errors
When a communication error occurs, the PV display area of the communication PV1 to
communication PV8 measurement display operation screen blinks.
In addition, if a communication error occurs in any of the communication PVs (PV1 to PV8), the EV
lamp 8 lights.
When a communication error occurs, the previously acquired value is displayed.
Note: On the standard UM33A, the decimal point blinks when a communication error occurs. This
feature is not available on this TOKUCHU product.
k VOL t k VOL t k VOL t
VOL t
k VOL t k VOL t k VOL t
VOL t
k VOL t
●
1.000
k VOLt

9
3.12 Retransmission Output
Retransmission output can be produced using 4-20mA by selecting PV, communication PV1 to
communication PV8.
The high and low limits of the scale are as follows:
○When RTS=PV: RTL + 1 digit to 30000
-19999 to RTH-1digit
The decimal place is the same as that of the PV input.
(This is the same as the standard UM33A.)
○When RTS=C.PV: RTL + 1 digit to 99999
-19999 to RTH-1digit
The decimal place is the same as that of SDP in MB.NT.
The setting range is the same also for FLOAT.
If communication is disconnected, retransmission output produces the
previously saved value.
Note: The communication PV retransmission output continues produce the selected communication
PV even when the operation screen is changed.
Note: Note that if the span exceeds 49999, the resolution of the retransmission output will
decrease.
Note: If the auto range function is enabled when FLOAT is in use, do not use the
retransmission output function.
Note: The retransmission output will be under 4mA until the communication establishes
because the initial value of communication PV is set to -19999 at Power ON.

10
3.13 Alarms and Event Lamps
The number of alarms is different between PVs and communication PVs.
PV: 4 alarms
Communication PV: 2 alarms (can be set only for a single communication PV)
Event lamps EV1 to 4 are for PV alarms. EV5 and 6 are for communication PV alarms. EV8 is for
communication error indications. These indications are fixed. They cannot be changed.
Event lamps do not change their indications even when the operation screen is different.
The indications are fixed as follows:
Note: If the auto range function is enabled when FLOAT is in use, do not use the
communication PV alarms.
Table 3.12.1 Alarm function
Item
PV
Communication PV
Number of alarms
4
2
Type of alarm
Not set (0)
PV high limit (1)
PV low limit (2)
PV velocity (29)
Self-diagnostics (30)
FAIL(31)
Not set (0)
PV high limit (1)
PV low limit (2)
Standby
Allowed
Not allowed
Energize/De-energize
Allowed
Allowed
Latch
Allowed
Not allowed
PV velocity alarm time setpoint
Allowed
Not allowed
Hysteresis
Allowed
Allowed
On-delay timer
Allowed
Not allowed
Off-delay timer
Allowed
Not allowed
The required information can be output to DO by setting I relay number to AL1.S to AL4.S (see
“Setting Contact Output Function” in the standard UM33A IM). Table 3.12.2 shows the additional I
relays.
VOLt
Event lamp
1~4
PV alarm
display
Event lamp
8
Communication
Error display
Event lamp
5~6
Communication
PV alarm
display

11
Figure 3.12.1 Block diagram of the alarm peripheral circuit
Table 3.12.2 I relays for communication PV alarms and communication error
I relay number
Description
Notes
4641
Communication PV1 alarm 1 value
4642
Communication PV1 alarm 2 value
4643
Communication PV2 alarm 1 value
4644
Communication PV2 alarm 2 value
4645
Communication PV3 alarm 1 value
4646
Communication PV3 alarm 2 value
4647
Communication PV4 alarm 1 value
4648
Communication PV4 alarm 2 value
4649
Communication PV5 alarm 1 value
4650
Communication PV5 alarm 2 value
4651
Communication PV6 alarm 1 value
4652
Communication PV6 alarm 2 value
4653
Communication PV7 alarm 1 value
4654
Communication PV7 alarm 2 value
4655
Communication PV8 alarm 1 value
4656
Communication PV8 alarm 2 value
4657
Communication error
Logic OR of communication 1 to 8 errors
(Handled as no error when not in use)

12
3.14 Deleted Functions
The following ten functions have been deleted from this TOKUCHU product.
• PV alarms 5 to 8 are not available. The only available PV alarms are 1 to 4.
• RS485 PC link communication, ladder communication, Modbus (ASCII) slave, Modbus (RTU) slave
communication protocols are not available.
• Quick setting mode is not available.
• The function for changing the event display is not available.
• The decimal point blinking for communication errors is not available. See section 3.10, “Display Screen for
Communication Errors.”
• Guide display is available only in English. Other languages are not supported.
•SELECT Display.
•Function key function of standard model.
• Guide Display ON/OFF function (parameter or Fn Key) is not available.
•PV peak and bottom value display function.
3.15 Troubleshooting
PV area display
Error description
Handling
PV area blinking
Communication error
Check the communication settings
and wiring.
NAN
When the FLOAT data type is
selected, the readout value is not a
number, ±infinity, or denormalized
number.
Check whether the data type of
the connected register is integer.
Check the connected device error.
3.16 LL50A
Parameter Setting Software LL50A cannot be used.

13
4Setting Parameters
The following tables show the setting parameters.
4.1 Parameters
The additional parameters on this TOKUCHU product are shown below.
[Setup Parameters]
Function setting menu (menu: CTL)
Parameter symbol Name of parameter Display level Setting range Initial value
ALNO. Number of alarms PRO 0 to 4 4
ALSL
Communication PV alarm selection STD
C.PV1: Use communication PV1 for the communication alarm
C.PV2: Use communication PV2 for the communication alarm
C.PV3: Use communication PV3 for the communication alarm
C.PV4: Use communication PV4 for the communication alarm
C.PV5: Use communication PV5 for the communication alarm
C.PV6: Use communication PV6 for the communication alarm
C.PV7: Use communication PV7 for the communication alarm
C.PV8: Use communication PV8 for the communication alarm
C.PV1
Input range setting menu (menu: MPV)
Parameter symbol Name of parameter Display level Setting range Initial value
M.UNI
Analog operation screen display unit STD
-: no units
VOLT: voltage
A: current
%: %
C: Celsius
F:Fahrenheit
ppm: concentration
PSCL: pressure,
KPACL: pressure,
MPACL: pressure
pH: hydrogen ion exponent
l: volume
m3/s: flow rate-m3/s
m3/m: flow rate-m3/min,
m3/h: flow rate-m3/hr
l/s: flow rate-l/s
l/min: flow rate-l/min
l/h: flow rate-l/hr
-: no units
Output setting menu (menu: OUT)
Parameter symbol Name of parameter Display level Setting range Initial value
RTS RET retransmission output type EASY
OFF: Not set
PV: PV
LPS: 15 V DC loop power supply
C.PV1: Communication PV1
C.PV2: Communication PV2
C.PV3: Communication PV3
C.PV4: Communication PV4
C.PV5: Communication PV5
C.PV6: Communication PV6
C.PV7: Communication PV7
C.PV8: Communication PV8
PV
RTH
RET retransmission output scale
maximum
STD 100% of PV input range
RTL
RET retransmission output scale
minimum
STD 0% of PV input range
When RTS=PV,
RTL+1 digit to 30000
-19999 to RTH-1 digit
The decimal place when RTS=PV is the same as that for PV
input.
When RTS=C.PV,
RTL+1 digit to 99999
-19999 to RTH-1digit
The decimal place is the same as that of SDP in MB.ST.
The setting range is the same for Float.

14
※WAIT, RTRY, RVV are effective when UM33A is Modbus RTU Master.
※When RVV=OFF(0), once a communication error occurs, it will not automatically
reconnect. To reconnect, turn on the power again or set the setting value of RVV
to other than OFF(0).
RS-485 communication setting menu (menu: R485)
Parameter symbol Name of parameter Display level Setting range Initial value
PSL
Protocol selection EASY MSMST : Modbus Master
MSMNT : Modbus Monitor MSMST
BPS Baud rate EASY
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
19200
DLN
Data length EASY 8:8 bits 8
INT Modbus master interval EASY 100 to 2000 (ms) 500
TMO Modbus master timeout EASY 100 to 1000 (ms) 100
WAIT Modbus master gap between messages EASY
OFF : OFF
10 : 10ms
20 : 20ms
50 : 50ms
100 : 100ms
OFF
RTRY Modbus master retry count EASY
OFF: OFF
1: Once
2: Twice
3: Three times
4: Four times
5: Five times
OFF
RVV Modbus master connection recovery wait EASY OFF(0): Disabled, 1 to 120 s OFF
Setting menu (menu: MB.ST)
Parameter symbol Name of parameter Display level Setting range Initial value
ONOF Master, monitor function on/off EASY
OFF: Function disabled (not shown on the operation screen)
ON: Function enabled (shown on the operation screen)
OFF
ADR Slave address EASY 1~247 1
DATA Read data type EASY
BIT: BIT
SHRT: 16 bit integer (signed)
LNG.LH : 32 bit integer (signed) lower 16 bit -> upper 16 bit
order
LNG.HL : 32 bit integer (signed) upper 16 bit -> lower 16 bit
order
FLT.LH: 32 bit floating point lower 16 bit -> upper 16 bit
order
FLT.HL: 32 bit floating point upper 16 bit -> lower 16 bit
order
SHRT
REG Read device register number EASY 1 to 19999 (Bit),
30001 to 49999(SHRT, LNG, FLT) 40001
SDP Decimal place EASY 0 to 4 1
DP.CG Float type auto range on/off EASY FIX: Fixed decimal point
AUTO: Auto range FIX
PR.UN PV input unit prefix selection STD
0: T, G, M, k and other unit prefix notation
1: Exponential notation
0
P.UNI Operation screen display unit STD
-: no units
VOLT: voltage
A: current
%: %
C: Celsius
F:Fahrenheit
ppm: concentration
PSCL: pressure,
KPACL: pressure,
MPACL: pressure
pH: hydrogen ion exponent
l: volume
m3/s: flow rate-m3/s
m3/m: flow rate-m3/min,
m3/h: flow rate-m3/hr
l/s: flow rate-l/s
l/min: flow rate-l/min
l/h: flow rate-l/hr
-: no units
FRMT
Decimal/hexadecimal display STD DEC: Decimal
HEX: Hexadecimal DEC
* The same setting applies to group 1 to 8.

15
Note1: When the communication function ONOFF (MB.ST menu) values are all set to hidden, only the
PV input is displayed.
If the PV input is hidden, at least one of the ONOFF (MB.ST menu) value is ON.
Note2: The display can be shown or hidden with display U.PV (KLOC menu) OFF/ON value.
When the communication function ONOFF (MB.ST menu) (1 to 8) values are all set to OFF, the PV
input cannot be hidden. When any of the communication function ONOFF (MB.ST menu) (1 to 8)
values is ON, the PV input can be hidden.
Note: The following example describes how the A.STS display works.
Example: When communication PV1 alarm 1 status is ON, this expressed in binary is 0000 0000
0000 0001, which is 0x0001 in hexadecimal notation.
When communication PV1 alarm 1 and 2 statuses are ON, this expressed in binary is 0000 0000
0000 0011, which is 0x0003 in hexadecimal notation.
Setting menu (menu: MB.DP)
Parameter symbol Name of parameter Display level Setting range Initial value
AT.SC
Automatic switch to program operation
display
EASY
OFF: Automatic switch to program operation display
disabled
ON: Automatic switch to program operation display enabled
OFF
D.CYC
Automatic switch to program operation
display refresh time
STD
3 : 3s
10 : 10s
30 : 30 s
60 : 60s
3
Menu lock setting menu (menu: MLOC)
Parameter symbol Name of parameter Display level Setting range Initial value
MB.ST
MB.ST menu lock PRO OFF
MB.DP MB.DP menu lock PRO OFF
M.ALM
M.ALM menu lock PRO OFF
OFF:Display
ON:Nondisplay
System setting menu (menu: SYS)
Parameter symbol Name of parameter Display level Setting range Initial value
LANG Guide display language EASY ENG: English
Depends on the model and
suffix codes
Error/version confirmation menu (menu: VER)
Parameter symbol Name of parameter Display level Display only
A.STS Communication PV alarm status EASY
The on/off state of alarms assigned to each bit is displayed
in hexadecimal notation. However, only assigned
communication PVs will be set to on or off.
Bit 0: Communication PV1 alarm 1 status
Bit 1: Communication PV1 alarm 2 status
Bit 2: Communication PV2 alarm 1 status
Bit 3: Communication PV2 alarm 2 status
Bit 4: Communication PV3 alarm 1 status
Bit 5: Communication PV3 alarm 2 status
Bit 6: Communication PV4 alarm 1 status
Bit 7: Communication PV4 alarm 2 status
Bit 8: Communication PV5 alarm 1 status
Bit 9: Communication PV5 alarm 2 status
Bit 10: Communication PV6 alarm 1 status
Bit 11: Communication PV6 alarm 2 status
Bit 12: Communication PV7 alarm 1 status
Bit 13: Communication PV7 alarm 2 status
Bit 14: Communication PV8 alarm 1 status
Bit 15: Communication PV8 alarm 2 status
P.STS Communication error status EASY
0x0001: Communication error present
0x0000: Communication error absent

16
[Operation Parameters]
Communication PV alarm function setting menu (menu: M.ALM)
Parameter symbol Name of parameter Display level Setting range Initial value
AL1.T to AL2.T Communication PV alarm type 1 and 2 EASY
0: Not set
1: PV high limit
2: PV low limit
PV high limit: 1 (AL1.T)
PV low limit: 2 (AL2.T)
AL1.D to AL2.D
Communication PV alarm energize/de-
energize 1 and 2
EASY 0: Energize
1: De-energize 0
M.HY1 to M.HY2
Communication PV alarm hysteresis 1
and 2
EASY -19999 to 99999 10
MB.A1 to MB.A2
Communication PV alarm setpoint 1 and
2
EASY -19999 to 99999 0
PV1 to PV8 can be set.

17
4.2 Parameter Map
[Setup Parameters]
Parameters added in this TOKUCHU product are indicated in yellow.
Parameters deleted from this TOKUCHU product are indicated in gray.
PASS CTL PV MPV OUT R485 MB.ST
ALNO. IN P.UNI RTS PSL ONOF ONOF ONOF ONOF ONOF ONOF ONOF ONOF
SMP UNIT P.DP RTH BPS ADR ADR ADR ADR ADR ADR ADR ADR
ALSL RH P.RH RTL PRI DATA DATA DATA DATA DATA DATA DATA DATA
END RL P.RL RET.H STP REG REG REG REG REG REG REG REG
SDP M.UNI RET.L DLN SDP SDP SDP SDP SDP SDP SDP SDP
SH END RET.A ADR DP.CG DP.CG DP.CG DP.CG DP.CG DP.CG DP.CG DP.CG
SL END RP.T PR.UN PR.UN PR.UN PR.UN PR.UN PR.UN PR.UN PR.UN
BSL INT P.UNI P.UNI P.UNI P.UNI P.UNI P.UNI P.UNI P.UNI
RJC TMO FRMT FRMT FRMT FRMT FRMT FRMT FRMT FRMT
ERJC WAIT END END END END END END END END
A.BS RTRY
A.FL RVV
A.SR END
A.LC
END
P
S
S
S
S
P
P
P
S
S
S
S
P
P
P
S
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
MB.DP KEY DISP CSEL KLOC MLOC DI.SL DI.D ALM I/O SYS INIT VER LVL END PASS
AT.SC Fn PCMD CS1 U.PV CTL RST DI1.D AL1.S KEY R.TM U.DEF PA.ER LEVL
D.CYC END PCH CS2 COM.W PV LAT DI2.D AL2.S X000 C.GRN F.DEF OP.ER
END PCL CS3 DATA MPV LCD END AL3.S Y000 FREQ END AD1.E
EV1 CS4 END OUT PVRW AL4.S Y100(E1) QSM PV1.E
EV2 CS5 R485(E1) MG1 AL1.D END LANG MCU
EV3 END CC-L(E1) MG2 AL2.D PASS DCU
EV4 MB.ST MG3 AL3.D END ECU1(E1)
EV5 MB.DP MG4 AL4.D PARA
EV6 KEY END END H.VER
EV7 DISP SER1
EV8 CSEL SER2
PV.D KLOC A.STS
SP.D DI.SL P.STS
STS.D DI.D END
SPD ALM
GUID DO(E1)
HOME I/O
ECO SYS
BRI INIT
B.PVW VER
B.PVR LVL
B.SP AL
B.STS ALRM
D.CYC M.ALM
OP.JP PVS
MLSD PYS1
MKTP PYS2
END END
S
S
P
P
S
S
S
S
S
S
P
P
P
P
P
P
S
S
S
S
P
P
P
P
P
P
S
S
P
P
P
P
P
P
P
P
S
S
S
S
P
S
P
P

18
[Operation Parameters]
Parameters added in this TOKUCHU product are indicated in yellow.
Parameters deleted from this TOKUCHU product are indicated in gray.
AL ALRM M.ALM PVS PYS1 PYS2 END AL
A1 AL1 AL1.T AL1.T AL1.T AL1.T AL1.T AL1.T AL1.T AL1.T BS A1(1) A1(2)
A2 AL2 AL2.T AL2.T AL2.T AL2.T AL2.T AL2.T AL2.T AL2.T FL B1(1) B1(2)
A3 AL3 AL1.D AL1.D AL1.D AL1.D AL1.D AL1.D AL1.D AL1.D PEAK A2(1) A2(2)
A4 AL4 AL2.D AL2.D AL2.D AL2.D AL2.D AL2.D AL2.D AL2.D BOTM B2(1) B2(2)
A5 AL5 M.HY1 M.HY1 M.HY1 M.HY1 M.HY1 M.HY1 M.HY1 M.HY1 END A3(1) A3(2)
A6 AL6 M.HY2 M.HY2 M.HY2 M.HY2 M.HY2 M.HY2 M.HY2 M.HY2 B3(1) B3(2)
A7 AL7 MB.A1 MB.A1 MB.A1 MB.A1 MB.A1 MB.A1 MB.A1 MB.A1 A4(1) A4(2)
A8 AL8 MB.A2 MB.A2 MB.A2 MB.A2 MB.A2 MB.A2 MB.A2 MB.A2 B4(1) B4(2)
END VT1 END END END END END END END END A5(1) A5(2)
VT2 B5(1) B5(2)
VT3 A6(1) A6(2)
VT4 B6(1) B6(2)
VT5 A7(1) A7(2)
VT6 B7(1) B7(2)
VT7 A8(1) A8(2)
VT8 B8(1) B8(2)
HY1 A9(1) A9(2)
HY2 B9(1) B9(2)
HY3 A10(1) A10(2)
HY4 B10(1) B10(2)
HY5 A11(1) A11(2)
HY6 B11(1) B11(2)
HY7 PMD PMD
HY8
DYN1
DYN2
DYN3
DYN4
DYN5
DYN6
DYN7
DYN8
DYF1
DYF2
DYF3
DYF4
DYF5
DYF6
DYF7
DYF8
END END END
P
P
P
S
S
S
S
S
S
S
S
P
P
P
P
P
P
P

19
5Wiring the RS485 Communication Interface
To perform Modbus Master/Monitor communication, wire the system as shown below. Attach a terminator to
the device at the end of the circuit.
Modbus Master 4-wire system wiring
2-wire system wiring of Modbus Master 4-wire system terminals
Wiring of Modbus Master 4-wire system terminals and 2-wire system terminals
Table of contents
Other YOKOGAWA Touch Panel manuals