YOKOGAWA UM350 User manual

IM 05F01D02-01E (1)
This manual describes installation, wiring, and other tasks required to make the indicator ready for operation.
Contents
1. Safety Precautions
2. Model and Suffix Codes
3. How to Install
4. How to Connect Wires
5. Hardware Specifications
6. Terminal Wiring Diagrams
Introduction
Thank you for purchasing the UM350/UM330 digital indicator with alarms.
The indicator is shipped from the factory with 3 hardcopy user’s manuals (A2 size). The 3 user’s manuals in hardcopy format
describe the operating procedures required for basic use.
It is recommended that you refer to these user’s manuals to understand [1] installation, [2] initial settings, and [3] operating
procedures of the indicator.
■How to Use the Manuals
Purpose Manual Title Description Media
Setup Installation Describes the tasks (installation, wiring, and others) required
to make the indicator ready for operations.
A2-size paper
(Front and back)
Basic operation
Initial Settings
Describes examples of setting PV input types, and alarm
types. Making settings described herein allows you to carry
out basic monitoring.
A2-size paper
(Front)
(Back)
Operating
procedures
and troubleshooting
Operations Describes examples of setting alarm setpoints, as well as
key operation necessary to run the indicator
Brief operation
and setpoint recording Parameters Contains the parameter map used as a guideline for setting
parameters and lists of parameters for recording user settings.
A2-size paper
(Front and back)
1. Safety Precautions
The following symbol is indicated on the indicator to ensure safe use.
CAUTION
This symbol on the indicator indicates that the operator must refer to an explanation in the user’s manual in order to
avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator
should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.
The following symbols are used in the hardcopy user’s manuals.
NOTE
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or features of the indicator.
■Exemption from Responsibility
Make sure that all of the precautions are strictly adhered to.Yokogawa Electric Corporation assumes no liability for any
damage resulting from use of the instrument in contradiction to the precautions.
Also,Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect, caused
by the use or any unpredictable defect of the instrument.
■Regarding Protection, Safety, and ProhibitionAgainst Unauthorized Modification
(1) In order to protect the product and the system controlled by it against damage and ensure its safe use, make certain that
all of the instructions and precautions relating to safety contained in this document are strictly adhered to. Yokogawa
does not guarantee safety if products are not handled according to these instructions.
(2) Modification of the product is strictly prohibited.
2. Model and Suffix Codes
Before using the indicator, check that the model and suffix codes match your order.
Model Suffix Code Description
UM350
UM330
Type
Digital indicator with Alarms (provided with retransmission output and 15
V DC loop power supply as standard)
-0 Standard type with three alarms
-3 Standard type with three alarms (with 24V DC loop power supply)
0 None
1 With communication and additional alarm-4
2 With additional alarm-4
Optional functions
Check that the following items are provided:
• Digital indicator with alarms (of ordered model): .........................................1
• Brackets (mounting hardware): ......................................................................1 pair
• Unit label: .......................................................................................................1
• User’s Manuals: ..............................................................................................3 (A2 size)
• User’s Manual (Reference) (CD-ROMVersion)
(only for indicators with optional communication functions):.......................1
3. How to Install
NOTE
To install the indicator, select a location where:
(1) no one may accidentally touch the terminals,
(2) mechanical vibrations are minimal,
(3) corrosive gas is minimal,
(4) temperature can be maintained at about 23°C and the fluctuation is minimal,
(5) no direct radiant heat is present,
(6) no magnetic disturbances are caused,
(7) no wind blows against the terminal board (reference junction compensation
element),
(8) no water is splashed,
(9) no flammable materials are around,
Never place the indicator directly on flammable items or equipment.
If the indicator has to be installed close to flammable items or equipment, be sure to provide shielding panels all
around the indicator, at least 150mm away from every side; the panels should be made of either 1.43mm-thick
metal-plated steel plates or 1.6mm-thick uncoated steel plates.
NOTE
Never touch the opening at the bottom of the case. It is to be used in the factory at shipping.
●Installation Position
Install the indicator at an angle within 30°from horizontal with
the front panel facing upward. Do not install it facing down-
ward. The position of right and left sides should be horizontal.
■External Dimensions and Panel Cutout Dimensions
(25)
(53)
[(N-1)96+92]117 min.
145 min.
+0.8
0
+0.8
0
92
+0.8
0
92
+0.8
0
92
"N" stands for the number of indicators to be
installed.
However, the measured value applies if N 5.
100
11
UM350
General installation Side-by-side close installation
1 to 10 mm (Panel thickness)
Small bracket
Large bracket
91.8
112
Unit: mm
96
96
48
UM330
96
10011
1 to 10 mm (Panel thickness)
Small bracket
Small bracket
91.8
112
Unit: mm
145 min.
General installation
Front of indicator
(53)
(25) 70 min.
+0.8
0
92
+0.6
0
45
After opening the mounting hole on the
panel, follow the procedures below to in-
stall the indicator:
1. Insert the indicator into the opening
from the front of the panel so that the
terminal board on the rear is at the far
side.
2. Set the brackets in place on the top and
bottom of the indicator as shown in the
figureonthe left, then tighten the screws
of the brackets. Take care not to over-
tighten them.
Note: Right and left mounting for UM330.
4. How to Connect Wires
CAUTION
1) Before carrying out wiring, turn off the power to the indicator and check that the cables to be connected are not
alive with a tester or the like because there is a possibility of electric shock.
2) For the protection and safe use of the indicator, be sure to place a circuit breaker (conforms with IEC60947,
5A, 100V or 220V AC) near the indicator where the breaker can easily be operated. In addition, be sure to
indicate that it is the instrument to cut the power supply of the indicator.
3) Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.
NOTE
1) Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an
insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC2205-00U
from TDK) on the secondary side.
As a countermeasures against noise, do not place the primary and secondary power cables close to each other.
2) For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires
that have low conductor resistance and cause no significant differences in resistance between the three wires.
The cables to be used for wiring, terminal specifications, and recommended parts are as shown below.
3) Alarm output relays have a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off
a load.
4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or
relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as
a spark-removal surge suppression circuit, into the line in parallel with the load.
5) When there is possibility of being struck by external lightening surge, use the arrester to protect the instrument.
■For DC Relay Wiring ■For AC Relay Wiring
R
UM350/UM330
UM’s contact
Diode
(Mount it directly
to the relay coil
terminal (socket).)
External DC power supply
Relay
(Use one with a relay coil rating
less than the UM’s contact rating.)
Relay
R
UM350/UM330
UM’s contact CR filter
(Mount it directly
to the relay coil
terminal (socket).)
External AC power supply
Relay
(Use one with a relay coil
rating less than the UM’s
contact rating.)
●Cable Specifications and Recommended Cables
Purpose Name and Manufacturer
Power supply, grounding, relay contact outputs
600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm
2
Thermocouple Shielded compensating lead wires, JIS C 1610, X- - -
(See Yokogawa Electric's GS 6B1U1-E.)
RTD Shielded wires (three conductors), UL2482 (Hitachi Cable)
Other signals Shielded wires
●Recommended Terminal Lugs
3.7mm
7 mm or less
3.7mm
7 mm or less
or
0.3 to 1.65 mm20.8 N·m or less
Applicable wire size Tightening torque
●Terminal Covers(Optional parts)
Target Model Part Number Sales Unit
UM350 T9115YD 1
UM330 T9115YE 1
Construction, Installation, and Wiring
• Construction: Only the front panel is dust-proof and drip-proof
(protection class IP55)
For side-by-side close installation the indicator loses its
dust-proof and drip-proof protection.
• Material: ABS resin and polycarbonate
• Case color: Black
• Weight: About 1 kg or less
• Dimensions:
UM350 96 (W) 96 (H) 100 (depth from panel face)
mm
UM330 96(W) 48 (H) 100 (depth from panel face)
mm
• Installation: Panel-mounting type. With top and bottom (or right
and left) mounting hardware (1 each)
• Panel cutout dimensions:
UM350 92+0.8
0(W) 92+0.8
0(H) mm
UM330 92+0.6
0(W) 45+0.8
0(H) mm
• Installation position: Up to 30°upward facing
(not designed for facing downward)
• Wiring: M3.5 screw terminals (for signal wiring and power/
ground wiring as well)
Power Supply Specifications
• Power supply: Rated voltage of 100 to 240VAC (10%), 50/60 Hz
• Power consumption: Max. 20 VA (8.0 W max.)
• Internal fuse rating: 250V AC, 1.6A time-lug fuse
• Data backup: Non-volatile memory (can be written to up to
100,000 times)
• Withstanding voltage
- Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
- Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
- Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
- Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay
output terminals
** Secondary terminals indicate analog I/O signal, and
contact input terminals
• Insulation resistance: 20 Mor more at 500 V DC between
power terminals and grounding terminal
• Grounding: Class D grounding (grounding resistance of 100
or less)
Signal Isolations
• PV input terminals: Isolated from other input/output terminals.
Not isolated from internal circuit.
• 15V DC loop power supply terminals: Not isolated from 4-20
mA analog output. Isolated from other input/output
terminals and internal circuit.
• 24V DC loop power supply terminals: Isolated from 4-20 mA
analog output terminals, other input/output terminals and
internal circuit.
• 4-20 mA analog output terminals (for retransmission): Not
isolated from 15 V DC loop power supply. Isolated from
other input/output terminals and internal circuit.
• Contact input terminals: Not isolated from communication
terminals. Isolated from other input/output terminals and
internal circuit.
• Relay contact output terminals: Not isolated between relay
contact output terminals. Isolated from other input/output
terminals and internal circuit.
• RS-485 communication terminals: Not isolated from contact
input terminals. Isolated from other input/output terminals
and internal circuit.
• Power terminals: Isolated from other input/output terminals and
internal circuit.
• Grounding terminals: Isolated from other input/output terminals
and internal circuit.
Environmental Conditions
• Normal operating conditions:
Ambient temperature: 0 to 50C (40C or less for side-by-side
close installation)
0 to 40C if the 24V DC loop power supply of Model
UM330 is used
Temperature change rate: 10C/h or less
Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400A/m or less
Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or
less
Continuous vibration at 14 to 150 Hz: 4.9 m/s2or less
Short-period vibration: 14.7 m/s2, 15 seconds or less
Shock: 147 m/s2or less, 11 ms
Installation height: Height above sea level of 2000 m or less
Warm-up time: 30 minutes or more after power on
• Transportation and storage conditions:
Temperature: -25 to 70C
Temperature change rate: 20C/h or less
Humidity: 5 to 95% RH (no condensation allowed)
• Effects of changes in operating conditions
- Effects from changes in ambient temperature:
- On voltage or thermocouple input, 1 V/C or 0.01%
of F.S./C, whichever is larger
- On RTD input, 0.05C /C (ambient temperature) or less
- On analog output, 0.05% of F.S./C or less
- Effects from power supply fluctuation (within rated voltage
range)
- On analog input, 1 V/10 V or 0.01% of F.S. /10 V,
whichever is larger
- On analog output, 0.05% of F.S./ 10 V or less
5. Hardware Specifications
PV Input Signals
•Number of inputs: 1 (terminals
11
-
12
-
13
)
•Input type: Universal input system. The input type can be
selected with the software.
•Sampling period: 250 ms
•Burnout detection: Functions at TC, RTD, standard signal
(0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred
if it is 0.1 V or less.
•Input bias current: 0.05 A (for TC or RTD b-terminal)
•Measurement current (RTD): About 0.13 mA
•Input resistance: 1 Mor more for thermocouple or mV input
About 1 Mfor DC voltage input
•Allowable signal source resistance: 250 or less for
thermocouple or mV input
Effects of signal source resistance: 0.1 V/or less
2 kor less for DC voltage input
Effects of signal source resistance:About 0.01%/100
•Allowable wiring resistance: for RTD input
Maximum 150 /wire: Conductor resistance between three
wires should be equal
However, 10 /wire for a maximum range of -150.0 to
150.0C.
Wire resistance effect: 0.1C /10
•Allowable input voltage: 10 V DC for thermocouple, mV, or
RTD input
20 V DC for DC voltage input
•Noise rejection ratio: 40 dB (50/60 Hz or more in normal mode
120 dB (50/60 Hz) or more in common mode
•Reference junction compensation error: 1.0C (15 to 35C)
1.5C (0 to 15C, 35 to 50C)
•Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples
and RTD
Loop Power Supply
Power is supplied to a two-wire transmitter.
(15 V DC: terminals
14
-
15
; 24 V DC: terminals
21
-
22
)
A resistor (10 to 250 ) connected between the indicator
and transmitter converts a current signal into a voltage
signal, which is then read via the PV input terminal .
Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided
with a protection circuit against a field short-circuit); 21.6
to 28.0 V DC, max. 30 mA (only for models with 24 V DC
loop power supply)
Retransmission Output
Outputs the PV value.
Either the retransmission output or the 15VDC loop power
supply can be used with terminals
16
-
17
.
•Number of outputs: 1 (terminals
16
-
17
)
•Output signal: 4-20 mA DC
•Load resistance: 600 or less
•Output accuracy: 0.3% of span under standard operating
conditions (23 2C, 55 10% RH, power frequency of
50/60 Hz)
Contact Inputs
•Purpose: Resetting of PV peak and bottom values
•Number of inputs: 1
•Input type: Non-voltage contact or transistor open collector input
•Input contact rating: 12 V DC, 10 mA or more
•On/off determination: For non-voltage contact input, contact
resistance of 1 kor less is determined as “on”and contact
resistance of 20 kor more as “off.”
For transistor open collector input, input voltage of 2V or
less is determined as “on”and leakage current must not
exceed 100 A when “off.”
•Minimum status detection hold time: About 1 second
Contact Outputs
•Purpose: Alarm output, FAIL output, and others
•Number of outputs: 4 (Max).
•Relay contact rating forAlarm 1 to 3: 240 V AC, 1 A, or 30 V
DC, 1 A ; 1a (FAIL output ; 1b)
•Relay contact rating forAlarm 4: 250 V AC, 3 A, or 30V DC, 3
A (resistance load) 3 terminals (NC, NO, Common); 1c
Display Specifications
•PV display:
4-digit, 7-segment red LED display, character height of
20 mm
•Setpoint display: 4-digit, 7-segment, red LEDs, character height
of 9.3 mm
•Status indicating lamps: LEDs
Safety and EMC Standards
•Safety: Complies with IEC/EN61010-1 (CE), approved by
C22.2 No.61010-1, approved by UL508.
Installation category : CAT. II Pollution degree : 2 (IEC/
EN61010-1, C22.2 No.61010-1)
Measurement category : I (CAT. I : IEC/EN61010-1)
Rated measurement input voltage : 10V DC max.(across
terminals), 300V AC max.(across ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safety standard which is assumed
by IEC/EN61010-1 in Measurement category I, and is not
the value which guarantees an apparatus performance.
CAUTION
This equipment has Measurement category I, there-
fore do not use the equipment for measurements
within Measurement categories II, III and IV.
1
2
3
4
Measurement category
CAT.1
CAT.2
CAT.3
CAT.4
Description
For measurements performed
on circuits not directly
connected to MAINS.
For measurements performed
on circuits directly connected
to the low voltage installation.
For measurements performed
in the building installation.
For measurements performed
at the source of the low-voltage
installation.
Remarks
Appliances, portable
equipments, etc.
Distribution board,
circuit breaker, etc.
Overhead wire, cable
systems, etc.
Internal Wiring
Outlet
Entrance
Cable
4
3
1
T2
•EMC standards: Complies with EN61326, EN61000-3-2,
EN61000-3-3 and EN55011 (CE).
Class A Group 1.
The instrument continues to operate at a measuring accuracy of
within 20% of the range during tests.
150mm150mm
150mm
150mm
Front panel
of indicator Must not
exceed 30
30Rear of
indicator
Large bracket
(top mounting hardware)
Terminal board
Small bracket
(bottom mounting hardware)
Panel
Insert a screwdriver into the
brackets to tighten the screws.
Direction to insert the
indicator
Insert the
indicator
into the opening at
the front of the panel.
Recommended
tightening torque
:0.4 N•m
User’s
Manual
IM 05F01D02-01E
Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual
Installation
4th Edition: Jan 31, 2005
■How to Install
CAUTION
Turn off the power to the indicator before installing it on the panel because there is a possibility of electric shock.
Fold the cover in the direction
of the arrow.
Fit the cover hold
over the protrusion
on the mounting bracket.
Figure A
Figure B
1. Before attaching the terminal cover, bend the side with
the groove inward as shown in Fig.A. Be careful not to
bend it backwards. This not only makes it harder to
attach the cover but will also weaken its hold.
2. Fit the holes on the top and bottom (or left and right) of
the terminal cover over the projections on the brackets
(Fig. B) and lock in place. The figure right shows the
attachment of a terminal cover to UM indicator.
Note:Right and left mounting for UM330.

IM 05F01D02-01E (2)
■UM350 Standard Type (Model UM350-䊐䊐)
Power supply
Relay contact output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
* Wiring can only be carried out
for indicators with communication
functions.
Maximum baud rate: 9600 bps
Allowable range: 100 to 240 V AC (10%)
(free voltage)
50/60 Hz shared
Initial Settings User’s Manual
PV input
* Not configured at factory before shipment
See ,
for more information.
*Wiring can only be carried out
for indicators with 24 V DC
loop power supply.
16
17
Retransmission output
4-20 mA DC
16
17
15 V DC loop power supply
14.5-18.0VDC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
Load resistance: 600
Ω or less
*If 15 V DC loop power supply is used,
retransmission output cannot be used.
-
+
-
+
CAUTION
Before carrying out wiring, turn off the power to the
indicator and check that cables to be connected are
not alive with a tester or the like because there is
a possibility of electric shock.
21
22
23
24
25
26
27
11
12
13
16
17
19
20
1
2
3
4
5
6
7
8
9
10
8
9
10
L
N
12
13
11
12
13
12
13
21
22
21.6-28.0VDC
(30 mA DC max.)
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
6
5
4
7
AL1
AL2
AL3
COM
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
1
2
3
Alarm 4 output
NC
NO
COM
A
b
B
UM
+
-
* Wiring can only be carried out for
UM350-ⵧ1 or UM350-ⵧ2.
-
+
-
+
TC input
RTD input
mV/V input
12
13
+
-
Note: Connecting a 250 Ωresistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on
terminal lugs)
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Indicator
250 Ω4-20mA
19
20
DI1
COM
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
.
Common
UM
Contact input
Contact
Contact rating: 12 V DC, 10 mA or more
DI1
COM
+5V
Transistor contact
19
20
RS-485 communication
Alarm output
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Power supply
24 V DC loop
power supply
■UM330 Standard Type (Model UM330-䊐䊐)
24 V DC Power Supply Wiring to Two-wire Sensor
15 V DC Power Supply Wiring to Two-wire Sensor
12
13
+
-
Note: Connecting a 250 Ωresistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on
terminal lugs)
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Indicator
250 Ω4-20mA
12
13
11
12
13
12
13
A
b
B
-
+
-
+
TC input
RTD input
mV/V input
6
5
4
7
AL1
AL2
AL3
COM
UM
16
17
Retransmission output
4-20 mA DC
16
17
15 V DC loop power supply
14.5-18.0VDC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
Load resistance: 600
Ω or less
*If 15 V DC loop power supply is used,
retransmission output cannot be used.
-
+
-
+
11
21
13
23
3
25
5
19
9
1
17
27
7
12
22 24
4
16
26
6
20
10
2 8
8
9
Power supply
10
L
N
Power supply
23
24
RS-485 communication
* Wiring can only be carried out
for indicators with communication
functions.
Maximum baud rate: 9600 bps
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
19
20
DI1
COM
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
.
Common
1
2
Relay contact output
3
Alarm 4 output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
* Wiring can only be carried out for
UM330-ⵧ1 or UM330-ⵧ2.
CAUTION
Before carrying out wiring, turn off the power
to the indicator and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
UM
*Wiring can only be carried out for indicators with 24 V DC
loop power supply.
12
13
16
17
Two-wire transmitter
PV input
0.4 to 2.0 V DC signal
Loop power
supply
14.5 to
18.0 V DC
External
resistor
(Note)
4-20mADC
Note: Connecting a 100 resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
100
12
13
21
22
Two-wire transmitter
PV input
1 to 5 V DC signal
Loop power
supply
21.6 to
28.0 V
DC
External
resistor
(Note)
4-20mADC
Note: Connecting a 250 resistor to the terminals is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
250
Contact input
Contact
Contact rating: 12 V DC, 10 mA or more
DI1
COM
+5V
Transistor contact
19
20
*Wiring can only be carried out
for indicators with 24 V DC
loop power supply.
21
22
21.6-28.0VDC
(30 mA DC max.)
+
-
24 V DC loop
power supply
Alarm output
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Allowable range: 100 to 240 V AC (10%)
(free voltage)
50/60 Hz shared
Initial Settings User’s Manual
PV input
* Not configured at factory before shipment
See ,
for more information.
6. Terminal Wiring Diagrams
Do not use unassigned terminals as relay terminals.
NOTE

IM 05F01D02-02E (1)
This manual describes examples of setting the types of PV input and alarm. Carrying out settings described herein allows
you to perform basic monitoring. Refer to examples of various settings to understand how to set parameters required. Refer
to “1. Parameter Map” in
Parameters User’s Manual
for an easy to understand explanation of setting various param-
eters. If you cannot remember how to carry out an operation during setting, press the
SET/ENT
key for more than 3 seconds.
This brings you to the display (operating display) that appears at power-on.
Contents
1. Names and Functions of Front Panel Parts
2. Setting PV Input Type (Setting First at Power-on)
3. Changing PV Input Type
4. Changing Alarm Type
5. Setting Hysteresis in Alarm Setpoint
1. Names and Functions of Front Panel Parts
Name of Part
Function
1. Process variable (PV)
display
2.
Parameter setpoint display
3. Alarm indicator lamps
3. Alarm indicator
lamps
4. SET/ENT
key
1. Process
variable (PV)
display
2. Parameter
Setpoint display
1. Process
variable (PV)
display
2. Parameter
Setpoint
display
4. SET/ENT key
3.
Alarm indicator
lamps
4. SET/ENT
key
SET/ENT
Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch
between the operating display and the menu for operating parameter setting display alternately.
5.
Used to change numerical values. On setting displays for various parameters, you can change parameters,
setpoint. Pressing the key decreases a numerical value, while pressing the key causes it to
increase. You can hold down a key to gradually increase the speed of change.
• Displays a PV value during operation.
• Displays a parameter symbol when you set a parameter.
• Displays an error code in red if the indicator fails.
Displays the setpoint of a parameter when it is configured.
If any of alarms 1 to 4 occurs, the respective alarm indicator lamp (AL1 to AL4) is lit (in orange).
5. and keys 5. and keys
and
keys
The following explanation of operation for the UM350’s panel, shown in the figure, is the same as that of the UM330’s
panel.
IMPORTANT
The indicator automatically returns to the display at the time of power-on (i.e., Operating display) if no key is
operated for at least one minute.
2. Setting PV Input Type (Setting First at Power-on)
NOTE
• The indicator displays the operating display when the power is turned on. However, if PV input type has not
been set, “IN” appears. In this case, first use the key to
display the input range code to use, then press the
SET/ENT
key
to register it.Then, set the maximum value (RH) and minimum
value (RL) of the PV input range (for voltage input, set the
maximum value (SH) and minimum value (SL) of the PV input
scale).
• The indicator is configured to the initial value of each param-
eter at the factory before shipment.
First check the initial values shown in 2. Lists of Parameters, in
Parameters User’s Manual
and change
parameter values as necessary.
Minimum value of
PV input range (RL)
Instrument
input range
-200°C 1370°C
0°C800°C
Maximum value of
PV input range (RH)
Minimum value of
PV input scale (SL)
1V 5V (input signal)
0.0m
3
/h 50.0m
3
/h
Maximum value of
PV input scale (SH)
2V 4V
RL RH
Parameters to be set for temperature input
1. PV input type (IN): Set according to a sensor
2. Maximum value of PV input range (RH): Set the
maximum value of the range to be displayed.
3. Minimum value of PV input range (RL): Set the
minimum value of the range to be displayed.
Parameters to be set for voltage input
1. PV input type (IN): Set according to an input signal
2. Maximum value of PV input range (RH): Set the maximum value of an input signal.
3. Minimum value of PV input range (RL): Set the minimum value of an input signal.
4. Position of PV input decimal point (SDP): Set the position of the decimal point for PV input display.
5. Maximum value of PV input scale (SH): Set the maximum value of the scale to be displayed.
6. Minimum value of PV input scale (SL): Set the minimum value of the scale to be displayed.
Set the actual
read-out
range. Set the actual
read-out range.
PV input range
PV input range
PV input scale
Instrument
input range
Example of Temperature Input Example of Voltage Input
The following operating procedure describes an example of setting a K-type thermocouple (-199.9°C to 500.0°C) and a
measurement range of 0.0°C to 200.0°C.
2. Press the or key to display the required
setpoint.
The figure below shows an example of setting a
K-type thermocouple (-199.9 to 500.0°C). See the
Instrument Input Range Codes.
1. Display screen at power-on
The parameter “IN”for setting the PV input type
appears.
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
Displays
parameter“IN”.Blinks during
change.
SET/ENT
If the display is as shown on the left,
press the key to show the
range code for the PV input type you
use. Then, register the range code
setting by pressing the key.
NOTE
PV
AL1234
SET/ENT
3.
7.
4.
8.
9.
11.
10.
Press the key once to register the setpoint.
Press the key once to display the parameter
“RL”(minimum value of PV input range).
Press the key for more than 3 seconds. This
returns you to the display shown at power-on (figure
below).
Press the key once to register the setpoint.
Press the key once to display the parameter
“UNIT”(PV input unit). Press the or key to display the required
setpoint. The figure below shows an example of
setting the minimum value of PV input range to
0.0°C.
Press the key once to register the setpoint.
5.
Press the key once to display the parameter
“RH”(maximum value of PV input range).
6.
Press the or key to display the required
setpoint. The figure below shows an example of
setting the maximum value of PV input range to
200.0°C.
The PV display in the figure above shows the error
code for input burnout ( ) if PV input wiring is
not yet complete. The error code disappears when
you wire the PV input terminals correctly.
If the type of input is voltage, also configure the PV
Input Decimal Point Position (SDP), Maximum value
of PV Input Scale (SH), and Minimum value of PV
Input Scale (SL) parameters that are displayed after
this.
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
Displays
PV.
Displays
parameter
“UNIT”.
Displays
parameter
“RH”.
Blinks during
change.
Displays
parameter
“RL”.
Blinks during
change.
■Instrument Input Range Codes
Input Type
Instrument Input
Range Code
Instrument
Input Range Measurement Accuracy
OFF
1-200 to 1370⬚C
-300 to 2500⬚F
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
2-199.9 to 999.9⬚C
0 to 2300⬚F
K
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
J4
-199.9 to 999.9⬚C
-300 to 2300⬚F
5-199.9 to 400.0⬚C
T60.0 to 400.0⬚C
-300 to 750⬚F
-199.9 to 750.0⬚F
⫾0.1% of instrument range ⫾1 digit for temperatures
equal to or higher than 0
⬚
C
⫾0.2% of instrument range ⫾1 digit for temperatures
below 0
⬚
C
⫾0.1% of instrument range ⫾1 digit for temperatures
equal to or higher than 0
⬚
C
⫾0.2% of instrument range ⫾1 digit for temperatures
below 0
⬚
C
B7
⫾0.15% of instrument range ⫾1 digit for temperatures
equal to or higher than 400
⬚
C
⫾5% of instrument range ⫾1 digit for temperatures
below 400
⬚
C
S8
0 to 1700⬚C
R9
0 to 1700⬚C
32 to 3100⬚F
32 to 3100⬚F
⫾0.15% of instrument range ⫾1 digit
N10
-200 to 1300⬚C
⫾0.1% of instrument range ⫾1 digit
⫾0.25% of instrument range ⫾1 digit for temperatures
below 0
⬚
C
E11
-199.9 to 999.9⬚C
L(DIN) 12 -199.9 to 900.0⬚C
-199.9 to 400.0⬚C
13
U(DIN) 14 0.0 to 400.0⬚C
W15
0 to 2300⬚C
⫾0.2% of instrument range ⫾1 digit
Platinel 2 16 0 to 1390⬚C
⫾0.1% of instrument range ⫾1 digit
PR20-40 17 0 to 1900⬚C
⫾0.5% of instrument range ⫾1 digit for temperatures
equal to or higher than 800
⬚
C
No guarantee of accuracy for temperatures below 800
⬚
C
Thermocouple
Unspecified
W97Re3-
W75Re25
18 0 to 2000⬚C
⫾0.2% of instrument range ⫾1 digit
30 -199.9 to 500.0⬚C
⫾0.1% of instrument range ⫾1 digit (Note1) (Note2)
JPt100 31 -150.0 to 150.0⬚C
⫾0.2% of instrument range ⫾1 digit (Note1)
35 -199.9 to 850.0⬚C
36 -199.9 to 500.0⬚C
-300 to 2400⬚F
-300 to 1800⬚F
-300 to 1300⬚F
-300 to 750⬚F
-199.9 to 750.0⬚F
32 to 4200⬚F
32 to 2500⬚F
32 to 3400⬚F
32 to 3600⬚F
-199.9 to 999.9⬚F
-199.9 to 300.0⬚F
-300 to 1560⬚F
-199.9 to 999.9⬚F
⫾0.1% of instrument range ⫾1 digit (Note1) (Note2)
RTD
Pt100
37 -150.0 to 150.0⬚C
-199.9 to 300.0⬚F
⫾0.2% of instrument range ⫾1 digit (Note1)
0.4 to 2 V 40
Standard
signal 1 to 5 V 41
0 to 2 V 50
0 to 10 V 51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55 -10.00 to 20.00 mV
DC voltage
0 to 100 mV
56 0.0 to 100.0 mV
⫾0.1% of instrument range ⫾1 digit (Note)
The read-out range can be scaled between -1999 and
9999.
3
0 to 1800⬚C
32 to 3300⬚F
Select the unit from the UNIT parameter.
* Performance in the standard condition (at 23⫾2⬚C, 55⫾10%RH, and 50/60Hz power frequency.
Note1: The accuracy is ⫾0.3⬚C of instrument range ⫾1 digit for a temperature range from 0⬚C to 100⬚C.
Note2: The accuracy is ⫾0.5⬚C of instrument range ⫾1 digit for a temperature range from -100⬚C to 200⬚C.
* To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250⍀resistor. This resistor is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
PV input terminal
Thermocouple/mV/V input
..............................
RTD input .................................................. - -
131211
-
1312
NOTE
The indicator may automatically initialize the registered operating parameter setpoints if any change is made to the
data item PV Input Type (IN), Maximum Value of PV Input Range (RH), MinimumValue of PV Input Range (RL),
PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH) or MinimumValue of PV Input
Scale (SL). After a change has been made to any of these data items, be sure to verify the registered operating
parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a
required value.
3. Changing PV Input Type
The following operating procedure describes an example of changing
the setting of K-type thermocouple (-199.9 to 500.0⬚C) to RTD Pt100
(-199.9 to 500.0⬚C) and a measurement range of 0.0 to 200.0⬚C.
Press the key once to display the menu
“STUP”.
3.
Press the key once to display the menu “I/O”.
Press the key once to display the parameter
“IN”(PV input type).
Press the key once to register the setpoint.
Press the or key to display the required
setpoint. The figure below shows an example of
changing to RTD Pt100 (-199.9 to 500.0°C).
6.
7.
4.
5.
8.
9.
Press the key once to display the parameter
“UNIT”(PV input unit).
10.
Press the key once to display the parameter
“RH”(maximum value of PV input range).
Press the or key to display the required
setpoint. The figure below shows an example of
setting the maximum value of PV input range to
200.0°C.
Press the key once to register the setpoint.
11.
12.
13.
Press the key once to display the parameter
“RL”(minimum value of PV input range).
Press the or key to display the required
setpoint. The figure below shows an example of
setting the minimum value of PV input range to
0.0°C.
Press the key once to register the setpoint.
Press the key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
14.
15.
16.
17.
Bring the operating display into view (display
appears at power on).
Press the key for more than 3 seconds to
call up the menu “OP.PA”.
1.
2.
Press the key once to display the parameter
“PWD”.
Press the key once to display the menu
“FUNC”.
*If the type of input is voltage, also configure the
PV Input Decimal Point Position (SDP), Maximum
value of PV Input Scale (SH), and Minimum value
of PV Input Scale (SL) parameters that are
displayed after patameter RL.
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
Displays
menu
“
FUNC
”
.
Displays
PV.
Displays
menu “OP.PA”.
Displays menu
“STUP”.
Displays
menu “I/O”.
Displays
parameter “IN”.
Displays
parameter
“RH”.
Displays
parameter
“UNIT”.
Blinks during
change.
Displays
parameter
“RL”.
Blinks during
change.
Displays
PV.
Displays
parameter
“
PWD
”.
Blinks during
change.
4. Changing Alarm Type
The following operating procedure describes an example of changing
alarm-1 (factory-set value: PV high limit alarm) to PV low limit alarm.
When you have changed alarm type, the alarm setpoint will be initial-
ized; set the alarm setpoint again.
1.
Bring the operating display into view (appears at
power-on).
2.
Press the key for more than 3 seconds to
call up the menu “OP.PA”.
3.
Press the key once to display the menu
“STUP”.
7.
Press the or key to display the required
setpoint. The figure below shows an example of
setting PV low limit alarm.
9.
Press the key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
See “1. Setting Alarm Setpoints”in
Operations
User’s Manual
when setting an alarm setpoint.
4.
Press the key once to display the parameter
“PWD”.
8.
Press the key once to register the setpoint.
5.
Press the key once to display the menu
“FUNC”.
6.
Press the key once to display the parameter
“AL1”(alarm-1 type).
You can take the same steps for alarm-2 type (AL2),
alarm-3 type (AL3), and alarm-4 type (AL4) that are
displayed after this.
SET/ENT
SET/ENTSET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
Displays menu
“OP.PA”.
Display menu
“STUP”.
Displays menu
“
FUNC
”
.
Displays
parameter
“PWD”.
Displays
parameter
“AL1”.
Blinks during
change.
Displays
PV.
Displays
PV.
5. Setting Hysteresis in Alarm Setpoint
The following operating procedure describes an example of setting a 5.0°C hysteresis level in the alarm setpoint.
1.
Bring the operating display into view (appears at
power-on).
2.
Press the key for more than 3 seconds to
call up the menu “OP.PA”.
3.
Press the key once to display the menu
“STUP”.
7.
Press the or key to display the required
setpoint.
9.
Press the key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
4.
Press the key once to display the parameter
“PWD”.
8.
Press the key once to register the setpoint.
5.
Press the key once to display the menu
“FUNC”.
6.
Press the key several times to display the
parameter “HY1”(alarm-1 hysteresis).
You can take the same steps for alarm-2 hysteresis
(HY2), alarm-3 hysteresis (HY3), and alarm-4
hysteresis (HY4) that are displayed after this.
SET/ENT
SET/ENTSET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
Displays menu
“OP.PA”.
Display menu
“STUP”.
Displays menu
“
FUNC
”
.
Displays
parameter
“PWD”.
Displays
parameter
“HY1”.
Blinks during
change.
Displays
PV.
Displays
PV.
Alarm output terminals Factory-set defaults
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers )......PV low limit alarm
-
6 7
-
5 7
-
4 7
---
2 31
User’s
Manual Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual
Initial Settings
IM 05F01D02-02E
4th Edition: Jan 31, 2005

IM 05F01D02-02E (2)
This manual describes key entries for operating the indicator. If you cannot remember how to carry out an operation during
setting, press the
SET/ENT
key for more than 3 seconds. This brings you to the display (operating display) that appears at
power-on.
Contents
1. Setting Alarm Setpoints
2. Troubleshooting
NOTE
Do not use the instrument generating strong magnetic field such as radio equipment and the like near the indicator.
This may cause the fluctuation of the PV value.
1. Setting Alarm Setpoints
The following operating procedure describes an example of setting
a value of 160.0 in the alarm-1 setpoint parameter. Before setting
the alarm setpoint, check the alarm type. To change the alarm type,
see “4. Changing Alarm Type” in
Initial Settings User's
Manual
.
Press the key once to display the parameter
“A1”.
Bring the operating display into view (display
appears at power on).
Press the key once to register the setpoint.
You can take the same steps for alarm-2 setpoint
(A2), alarm-3 setpoint (A3), and alarm-4 setpoint
(A4) that are displayed after this.
1.
3.
Press the or key to display the required
setpoint.
4.
5.
Press the key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
Press the key for more than 3 seconds to call
up the menu “OP.PA”.
2.
6.
SET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
Displays PV.
Displays PV.
Displays
parameter
“A1”.
Displays menu
“OP.PA”.
Blinks during
change.
User’s
Manual Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual
Operations
IM 05F01D02-02E
2. Troubleshooting
■Troubleshooting Flow
If the operating display does not appear after turning on the indicator's power, try to solve the problem by following the
procedure below. If the problem seems to be complex, contact the vendor from which you purchased the instrument.
Ask the vendor for repair.
Find the cause.
Totally
inoperable?
Yes
Yes
Yes
No
No
No
Is key
operation
faulty?
Yes
No
Yes
Check wiring on the
power supply
terminals.
Check the key lock
setting.
Is display
faulty?
Yes
No
Turn off power, and
then turn it on
again.
Is I/O
signal faulty?
Yes
No
Check the
instrument’s I/O
specifications.
Check the supply
voltage.
Check the specifications
of I/O counterpart for
wrong polarity.
Check the
communication-related
parameters.
Check the specifications
of communication
counterpart.
Check
communication wiring.
Is
communication
link faulty?
No
Does the code
include a communication
option?
Yes
Normal?
Is
key lock
enabled?
Check the
instrument's suffix
code.
Yes
No Correct?
Correct
errors.
Disable
key lock.
No communication
capability.
Is the instrument
defective?
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
■Errors at Power On
The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.
(E000)
(E002)
(E001)
(E400)
Error indication
(on PV display unit) Description
of error Remedy
Faulty RAM
Faulty ROM
System data error
PV decimal point blinks.
Faulty calibration
value
PV Control
output Alarm
output
Retransmission
output
Communi-
cation
None OFF 0% or less Stopped
0%
0% or less
or OFF 0%
Normal
action
Faulty
Contact us
for repair.
Normal action
(out of
accuracy)
Normal action
(out of
accuracy)
Normal action
(out of
accuracy)
Normal action
(out of
accuracy)
Parameter error
0%
Preset value
OFF 0%
Check and set
the parameters,
as they have
been set to the
limited values.
■Possible Errors during Operation
The following shows possible errors occurring during operations.
Retransmis-
sion output
Commu-
nication
(-OVER)
(OVER) or
Error indication
(on PV display
unit)
Displays “RJC”
and PV
alternately
Faulty
Contact us for repair.
Faulty
Contact us for repair.
Check wires and
sensor.
Description
of error
RJC error
EEPROM
error
A/DC error
PV burnout
error
PV
Measured with RJC=OFF
Normal action
105
%
Dependent on the BSL
parameter Up-scale: 105%
Down-scale: -5%
Control
output
Normal
action
Normal
action
Preset
value
Preset
value
Alarm
output
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Remedy
Normal
action
Normal
action
Normal
action
Normal
action
Check process.
SP decimal pont
blinks (on
setpoint display
unit).
PV value blinks.
Check wires and
communication parameters,
and make resetting.
Recovery at normal receipt
Excessive PV
Out of -5 to
105%
Faulty
communi-
cation line
-5% or 105%
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
All indications off Faulty if power off/on does
not reset start the unit.
Contact us for repair.
All indications off Check for abnormal power.
Runaway (due
to defective
power or
noise)
Power off
None
None
0% or less
or OFF
0
%
OFF
OFF
0% or
less
0
%
Stopped
Stopped
(B.OUT)
(E300)
■If a Power Failure Occurs during Operation
●Momentary power failures shorter than 20 ms
The indicator is not affected at all and continues normal operation.
●Momentary power failures of 20 ms or longer
• The alarm function of the indicator continues to work normally. (Alarms with the stand-by feature temporarily return to
their stand-by state, however.)
• Setting parameters that have already been configured retain their settings.
4th Edition: Jan 31, 2005
Alarm output terminals Factory-set defaults
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers ).......PV low limit alarm
-
6 7
-
5 7
-
4 7
--
123

IM 05F01D02-03E (1)
This manual contains a parameter map as a guideline for setting parameters, and lists of parameters for recording User
Settings.
Contents
1. Basic Key Operation Sequence and Parameter Map
2. Lists of Parameters
1. Basic Key Operation Sequence and Parameter Map
NOTE
Changing the registered value of a setup parameter
may cause the registered value of an operating pa-
rameter to be initialized automatically. Thus, when
you have changed a setup parameter, always check
that the registered value of the operating parameter
is appropriate. If it is initialized to default, reset it to
the required value.
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
YesNo
Alarm-4 setpoint
C
B
Menu
Displayed only for UM350-ⵧ1, UM350-ⵧ2, UM330-ⵧ1, UM330-ⵧ2
Menu
A
If you become unsure of key operation during parameter
setting, hold down the key for more than
3 seconds. This returns you to the display at
power-on (i.e., operating display).
?
SET/ENT
SET/ENT
key
SET/ENT SET/ENT
key
SET/ENT
key
SET/ENT
key
Alarm-3 setpoint
Alarm-1 setpoint
Alarm-2 setpoint
PV peak value
PV bottom value
PV input bias
PV input filter
Nothing is displayed.
Displays the
operating
parameter menu
symbol “OP.PA.”
Displays a setpoint.
Displays a
parameter
symbol.
SET/ENT
Determine PV input type first.
Settings herein are described in “
2. Setting PV Input Type
(Setting First at Power-on)
” in
Initial Settings User’s Manual
.
or key
Password input
(No password is required
when PWD = 0.)
Description of Operating Parameter Setting Display
Description of Operating Parameter Menu Display
Power on
Display?
IN = OFF
Displays PV.
To switch the parameter display, press the key.
Display example Display example
After PV input type (IN), input parameters
such as PV input unit (UNIT), maximum
value of PV input range (RH), and
minimum value of PV input range (RL)
will be displayed.
Press the key to register
the value.
2.1.
Use the or key to set a numerical
value. See
Instrument Input Range Codes
in
Initial Settings User’s Manual
.
Blinks during
change.
Press this key for more
than 3 seconds to
move to the operating
parameter setting
display.
SET/ENT
key
Press this key for
more than 3 seconds
to move to the
operating
display.
SET/ENT
key
Operating Display
Operating Parameter Setting Display
B C
Displayed first after power on.
Menu
Displayed only for indicators
with communication functions
or key
A
SET/ENT
key
SET/ENT
key
SET/ENT
key
SET/ENT
key
Alarm-2 type
Alarm-3 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 hysteresis
Alarm-4 type
Key lock
Alarm-4 delay timer
PV
AL1234
SET/ENT
PV
AL1 2 3 4
SET/ENT
Displays a setpoint.
Displays a parameter.
Nothing is displayed.
Displays a menu, such as
FUNC or I/O.
This parameter is not to be set.
Displayed only for UM350-ⵧ1,
UM350-ⵧ2, UM330-ⵧ1, UM330-ⵧ2.
Displayed only for UM350-ⵧ1,
UM350-ⵧ2, UM330-ⵧ1, UM330-ⵧ2.
Displayed only for UM350-ⵧ1,
UM350-ⵧ2, UM330-ⵧ1, UM330-ⵧ2.
1. Setting display can be switched (moved) using the key.
2. A numerical value is changed by
(1) Using the or key to change a displayed value (decimal point blinking) and
(2) Pressing the key to register it.
3. Pressing the key on an operating display (for more than 3 seconds) brings you to the
operating parameter setting display.
4. Pressing the key on the operating parameter setting display (for more than 3 seconds)
returns you to the operating display.
5. Pressing the key on the setup parameter setting display (for more than 3 seconds)
returns you to the operating display. You cannot return to the operating parameter setting
display from the setup parameter setting display.
Basic Key Operation Sequence
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
Description of Setup Parameter Menu Display
Description of Setup Parameter Setting Display
Alarm/Communication
related Input related
Alarm-1 type
Protocol selection
Baud rate
Stop bit
Data length
Address
Minimum response time
Parity
PV input type
(PV INPUT terminals)
PV input unit
Maximum value of PV input range
PV input decimal point position
(displayed at voltage input)
Selection of
PV input burnout action
Presence/absence of PV input
reference junction compensation
Maximum value of PV input scale
(displayed at voltage input)
Minimum value of PV input scale
(displayed at voltage input)
Minimum value of PV input range
Retransmission output type
Maximum value of
retransmission output scale
Minimum value of
retransmission output scale
DI function selection
SELECT display-1 registration
SELECT display-2 registration
SELECT display-3 registration
SELECT display-4 registration
Password setting
Press this key for
more than 3 seconds
to move to the
operating
display.
SET/ENT
key
Setup Parameter Setting Display
IM 05F01D02-03E
User’s
Manual
4th Edition: Jan 31, 2005
Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual
Parameters

IM 05F01D02-03E (2)
2. Lists of Parameters
■Operating Parameters
Parameter
Symbol Name of Parameter Setting Range and Description Initial Value User setting
Alarm 1-setpoint
Alarm 2-setpoint
Alarm 3-setpoint
Alarm 4-setpoint
PV alarm: -100.0 to 100.0% of PV input range PV high limit
alarm:
100.0% of
PV input range
PV low limit
alarm:
0.0% of
PV input range
PV input filter OFF, 1 to 120 second
Used when the PV input fluctuates. OFF
PV input bias -100.0% to 100.0% of PV input range span
Used to correct the PV input value. 0.0% of PV
input range
span
(A1)
(A2)
(A3)
(A4)
(FL)
(BS)
PV peak value
Displays the maximum value of PV input during operation.
This parameter is not to be set.
PV bottom value
Displays the minimum value of PV input during operation.
This parameter is not to be set.
(PEAK)
(BOTM)
■Setup Parameters
●Alarm/Communication-related Parameters
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
0.0 to 100.0% of PV input range span
Hysteresis can be set in the alarm setpoint.
Setting hysteresis prevents relays from
chattering.
An alarm is output when the delay timer expires
after the alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm-
1 type “AL1”is 1, 2, 9, 10, 11, 12, 19, and 20)
0.00 to 99.59 (min, sec.) (enabled when alarm-
2 type “AL2”is
1, 2, 9, 10, 11, 12, 19, and 20
)
0.00 to 99.59 (min, sec.) (enabled when alarm-
3 type “AL3”is
1, 2, 9, 10, 11, 12, 19, and 20
)
0.00 to 99.59 (min, sec.) (enabled when alarm-
4 type “AL4”is
1, 2, 9, 10, 11, 12, 19, and 20
)
(AL1)
(AL2)
(AL3)
(AL4)
(HY1)
(HY2)
(HY3)
(HY4)
(DY1)
(DY2)
(DY3)
(DY4)
Parameter
Symbol Name of Parameter Setting Range and Description User setting
OFF
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
11: PV high limit (energized, stand-by action)
12: PV low limit (energized, stand-by action)
19: PV high limit (de-energized, stand-by action)
20: PV low limit (de-energized, stand-by action)
21: Fault diagnosis output
Turns on in case of input burnout, A/D
converter failure, or reference junction
compensation (RJC) failure.
22: FAIL output
Turns off in case of program failure, ROM
failure, RAM failure, or power failure. This
output is on during normal operation. If it
turns off, the retransmission output is set to
0%, the alarm output is set to OFF, and the
indicator stops.
See “List of Alarm Types”on the right side of this
manual for details on how these Alarm Type
parameters behave.
Point of on-off action
(Alarm setpoint)
PV value
Output
On
Off Hysteresis
Protocol selection
Baud rate 0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
Parity 0: None
1: Even
2: Odd
Stop bit 1, 2
Data length
Address 1 to 99
However, the maximum number of stations
connectable is 31.
Minimum response
time 0 to 10 (⫻10 ms)
0: PC link communication
1: PC link communication (with checksum)
2: Ladder communication
7: MODBUS (ASCII)
8: MODBUS (RTU)
(P.SL)
(BPS)
(PRI)
(STP)
(DLN)
(ADR)
(RP.T)
1
2
1
2
0.5% of PV
input range span
0.00
Initial Value
0
4
1
1
8
1
0
(TEST)
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
Caution: Do not change the setpoint of the TEST parameter, otherwise the indicator will be disabled.
7, 8
Fixed at 7, when the P.SL parameter is set to
MODBUS (ASCII).
Fixed at 8, when the P.SL parameter is set to
MODBUS (RTU) or Ladder Communication.
Hysteresis setting for PV high limit alarm
Time
Hysteresis
Alarm setpoint
Alarm output
Delay timer
PV
on
off
Delay timer
*Parameters relating to PV should all be set in real numbers.
For example, use temperature values to define alarm setpoints for
temperature input.
*The “User Setting”column in the table below is provided for the customer to record setpoints.
●Input-/Output-related Parameters
-1999 to 9999, however SL < SH
Set the read-out scale of voltage-mode PV input.
OFF
PV input unit °C: degree Celsius
°F: Fahrenheit °C
Max. value of PV input
range
Min. value of PV input
range
Max. value of
instrument
input range
Min. value of
instrument
input range
Set the PV input range, however RL < RH
-Temperature input
Set the range of temperature that is actually indicated.
- Voltage input
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually
indicated should be set using the parameters
Maximum Value of PV Input Scale (SH) and Minimum
Value of PV Input Scale (SL).
PV input decimal point
position (displayed
at voltage input)
Max. value of PV input
scale
(displayed at voltage input)
Min. value of PV input
scale
(displayed at voltage input)
Selection of PV input
burnout action
Presence/absence of
PV input reference
junction compensation
0 to 3
Set the position of the decimal point of voltage-
mode PV input.
0: No decimal place
1: One decimal place
2, 3: Two, three decimal places
1
100.0
0.0
OFF
1: Up scale
2: Down scale
1
OFF, ON ON
(IN)
(UNIT)
(RH)
(RL)
(SDP)
(SH)
(SL)
(BSL)
(RJC)
Parameter
Symbol Name of Parameter Setting Range and Description Initial Value User Setting
PV input type (PV INPUT
terminals)
- - terminals
131211
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56
See Instrument Input Range Codes in
Initial
Settings
User’s Manual .
Retransmission output
type
OFF: Does not work.
1: PV
4: Loop power supply for sensor (15 V)
1
Max. value of
retransmission output
scale
Min. value of
retransmission output
scale
RET=1: RTL + 1 digit to 100.0% of PV
input range
RET=1: 0.0% of PV input range to
RTH - 1 digit
100.0% of
PV input range
0.0% of
PV input range
(RTH)
(RTL)
(RET)
DI function selection 1
(DIS)
SELECT display-1
registration
SELECT display-2
registration
SELECT display-3
registration
SELECT display-4
registration
OFF
OFF, 201 to 1015
For example, registering “231”for C.S1 allows you to
change alarm-1 setpoint in operating display.
Numbers for registering alarm SP parameter for
operating display:
Alarm-1 setpoint: 231 Alarm-2 setpoint: 232
Alarm-3 setpoint: 233 Alarm-4 setpoint: 234
(C.S1)
(C.S2)
(C.S3)
(C.S4)
Password setting 0: Password not set
1 to 9999 0
(PWD)
Key lock
OFF
(LOCK)
OFF: No key lock
1: Change to any parameter prohibited
Prohibits any operating parameter or setup
parameter from being changed. The setpoint
of the LOCK parameter itself can be changed,
however.
2: Change to and display of operating parameters
prohibited
Turns off the display for setting operating
parameters, thus prohibiting any change to
the parameter settings.
(Press the SET/ENT key for more than
3 seconds to show the password check
display.)
OFF: The external contact input is disabled.
1: Resets the values of the PEAK and BOTM
operating parameters to an off-to-on transition
of the DI1 input.
■List of Alarm Types
The table below shows the alarm types and alarm actions.
In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with
stand-by actions.
Alarm action Alarm action Alarm type codeAlarm type code
Alarm type
“Open/close”shows status of relay contact,
and “lit”and “unlit”shows status of lamp
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Alarm type
No alarm OFF
PV high limit
PV low limit
1
11
2
12
De-energized
on PV high limit
De-energized
on PV low limit
9
19
10
20
2221
“Open/close”shows status of relay contact,
and “lit”and “unlit”shows status of lamp
Fault diagnosis output (Note1) FAIL output (Note2)
Alarm setpoint
Closed (lit)
Hysteresis
PV
Open (unlit)
Closed (lit)
Hysteresis
Open (unlit)
Alarm setpoint PV
PV
Open (lit)
Alarm setpoint
Hysteresis
Closed
(unlit)
Alarm setpoint
Hysteresis
PV
Open (lit) Closed
(unlit)
Note1: Fault diagnosis output
Turns on in case of input burnout,A/D converter failure, or reference junction compensation (RJC) failure.
Note2: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns
off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
Treated
as normal
⬚C
Power-on Time
The alarm output does not
turn on in this region even
if the PV value is below the
low limit of the alarm setpoint.
Low limit of
alarm setpoint
Normal Abnormal
The alarm
output turns on.
Stand-by Action
It is effective in the following cases where;
- the power is turned on
- the alarm type is changed
●Behavior of the PV High-limit Alarm Parameter (Alarm Type Code: 1)
Alarm
setpoint
Alarm hysteresis
Alarm
contact output OffOff On
PV value
■Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to
change settings easily. A maximum of four displays can be registered.
Setting method:
Set the parameter numbers (D register numbers) you wish to register for
setup parameters C.S1 to C.S4.
●Numbers for Registration with SELECT Display
Operating Parameter Registration Number
Alarm-1 setpoint (A1)
Alarm-2 setpoint (A2)
Alarm-3 setpoint (A3)
Alarm-4 setpoint (A4)
231
232
233
234
Bias (BS) 243
Filter (FL) 244
Setup Parameter Registration Number
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
919
920
921
922
SET/ENT
key
SET/ENT
key
PV display
Ordinary operating
displays (example)
Alarm-1 setting
display (example)
Useful
operating display
(SELECT display)
PV
AL1 2 3 4
SET/ENT
PV
AL1234
SET/ENT
This manual suits for next models
1
Table of contents
Other YOKOGAWA Touch Panel manuals