York P XU Series Manual

035-19650-001 Rev. C (0404)
USER’S INFORMATION,
MAINTENANCE AND
SERVICE MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: P*XU/ G9D-UP
Tw o S t a g e ( U p f l o w )
EFFICIENCY
RATING
CERTIFIED
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
The manufacturer recommends that the user read all sec-
tions of this manual and keep the manual for future refer-
ence.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate-
rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has
been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed, or spaces
around the furnace.
4. Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.
6. Do not use this furnace if any part has been under water. A flood-
damaged furnace is extremely dangerous. Attempts to use the fur-
nace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace all gas
controls, control system parts, electrical parts that have been wet
or the furnace if deemed necessary.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or prop-
erty damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone
(including cell phone) in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire depart-
ment.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
TABLE OF CONTENTS
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . .3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .3
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . .5
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
DIRECT DRIVE BLOWER MOTOR . . . . . . . . . . . . . . . . . . . . . . . . .6
INSTALLATION OF PSC MOTOR: . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .7
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL . . . . . .12
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail: York International
Consumer Relations
5005 York Drive
Norman, OK 73069
CLICK ANYWHERE on THIS PAGE to RETURN to YORK HVAC AGE & MANUALS & ERROR CODES at InspectApedia.com

035-19650-001 Rev. C (0404)
2Unitary Products Group
7. NEVER . . .Store flammable materials of any kind near your fur-
nace. Gasoline, solvents, and other volatile liquids should be
stored only in approved containers outside your home. These
materials vaporize easily and are extremely dangerous.
8. NEVER . . .Store cleaning materials near your furnace. Materials
such as bleaches, detergents, powdered cleansers, etc., can
cause corrosion of the heat exchangers.
9. NEVER . . . Use the area around your furnace as a storage area
for items which could block the normal flow of air. This flow of air is
required for ventilation of the various furnace components.
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the
entire heating portion of the unit is made by a qualified service agency.
1. Examine the heat exchanger, vent/combustion air piping, vent
connectors and chimney to be sure they are clear and free of
obstructions.
2. Examine the vent pipe making sure it is firmly in place, that it
slopes slightly upward and is physically sound without holes and
all of the connections are secure.
3. Examine the return-air duct connections to make sure they are
physically sound, sealed to the furnace casing, and the ducts ter-
minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is
sound without sagging, cracks or gaps. Examine the furnace base
making sure it is physically sound without cracks, gaps or sagging
and has a good seal.
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust-
ment. Refer to the pictorial sketch shown in Figure 2 as a compari-
son to the actual flame.
7. Examine the furnace as outlined above in steps “1 - 6” before
each heating season. Use Figure 3 for visual reference.
FIGURE 1: Component Locations
FIRE OR EXPLOSION HAZARD
This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN
ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the
furnace heat exchanger, which could result in Fire, Per-
sonal Injury, and/or Property Damage.
BURNER GAS VALVE
VENT PIPE
CONDENSATE
DRAIN SYSTEM
INDUCER
ASSEMBLY
PRESSURE
SWITCH
BLOWER INDUCER
MOTOR
BOX
COMBUSTION
AIR COLLAR
INTEGRATED
CONTROL
FIGURE 2: Burner Flame Drawing
COMBUSTION AIR
INTAKE
BURNER
FLAME
MANIFOLD
INNER FLAME
CONES
MAIN
BURNER
FIGURE 3: Furnace Examination Checkpoints
4EXAMINE
FURNACE
CASING
3
4
3
6
EXAMINE
RETURN AIR
DUCT
CONNECTION
EXTERNAL HEAT EXCHANGER INTERNAL
VENT COMBUSTION AIR PIPE. MUST
REMOVE PANEL TO EXAMINE.
EXAMINE
RETURN AIR
DUCT
CONNECTION
(side or bottom)
REMOVE
PANEL
TO EXAMINE
BURNER
FLAMES
EXAMINE
FURNACE
CASING
5EXAMINE ENTIRE
FURNACE CASING
SHOWN IN ALL
DRAWINGS
EXAMINE EXTERNAL
VENT PIPE
1
2
BURNER DOOR
BLOWER DOOR

035-19650-001 Rev. C (0404)
Unitary Products Group 3
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after
season, it sits there in your home, keeping you warm and comfortable.
For this reason, you may never have given much thought to the way
your furnace operates. In order to get the safest and most efficient oper-
ation from your furnace, you should understand how your furnace does
its job.
When you set your thermostat to provide more heat in your home, you
are starting the heating cycle of the furnace. First, the inducer motor
starts to purge the heat exchanger of any remaining gases. Next, the
hot surface ignitor glows and after a warm-up period the gas valve
opens and ignition occurs. A short time later, the blower starts and dis-
tributes the warm air throughout the home. When the temperature set-
ting on your thermostat is reached, the gas valve closes, the main
burners are turned off, and the blower continues to run until the remain-
ing warm air in the system is distributed. When the blower stops, the
heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the
Furnace
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the
burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t
try to repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner door.
5. Move gas control switch to the “OFF” position. Do not force. See
Figure 4.
6. Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow “B” in the safety information above. If you don’t
smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force. See
Figure 4.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may
take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol-
low the instructions, “TO TURN OFF THE APPLIANCE” and call
your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per-
formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position. See Figure 4.
5. Replace burner access panel.
NOTE: The spring-loaded safety cut-off switch, mounted under the
blower deck will automatically cut off the electrical power supply
to the furnace when the blower panel is removed. As a safety
precaution, all electrical power and the gas supply to the furnace
should be turned off before servicing.
FURNACE USER MAINTENANCE
Every time the filters are changed the following items should be visually
inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury, and/or loss of life.
Should overheating occur, or the gas valve fail to shut off,
turn the external manual gas valve in the gas supply line to
the furnace to the “off” position and let the furnace cool off
before shutting off the electrical power supply. Refer to
Figure 5.
FIGURE 4: Gas Valve - White Rodgers
FIGURE 5: Gas Piping
Before proceeding, be sure the area is well ventilated. Turn
the thermostat OFF. If the blower is running, wait until it
stops automatically. Turn OFF the gas and electrical power
supplies to the furnace. Check all metal parts and surfaces
to be sure they have cooled to room temperature before
you begin.
R
E
P
L
A
C
E
R
E
P
L
A
C
E
S
C
R
E
W
S
C
R
E
W
INLET OUTLET
ON / OFF SWITCH
WRENCH
BOSS
PM
C
HI
O
F
F
ON
EXTERNAL MANUAL
SHUTOFF VALVE
TO GAS
SUPPLY
TO GAS
SUPPLY
GROUNDED JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE UNIT.
DRIP
LEG

035-19650-001 Rev. C (0404)
4Unitary Products Group
• Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the fur-
nace and its components must be done by a qualified service pro-
fessional.
If, during the inspection of your furnace, you find any of the following
conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the fur-
nace, and set thermostat to the desired temperature.
Air Filters
Dirty filters greatly restrict the flow of air and may cause damage to the
moving parts of the furnace. If the filters become clogged the heat
exchangers and blower motor could overheat resulting in a potentially
dangerous situation. The filters should be checked every 3 months. On
new construction, check the filters every week for the first four weeks
and every three weeks after that, especially if the indoor fan is running
continuously. When replacing the filter(s) you must use filters that are
the same size as those recommended in Table 1. Use the following pro-
cedure to determine the filter size. Never operate your furnace without a
suitable air filter.
1. Measure the furnace width and use that measurement to deter-
mine the cabinet width.
• A 14-1/2” wide cabinet is a “A” cabinet.
• A 17-1/2” wide cabinet is a “B” cabinet.
• A 21” wide cabinet is a “C” cabinet.
• A 24-1/2” wide cabinet is a “D” cabinet.
2. Locate the cabinet size on Table 1 then determine whether you
have a bottom or side return air duct using the following method.
a. If the return air filter is on the left or right side of the furnace it
is a side return
b. If the air filter is on the bottom of the furnace then you have a
bottom return.
C. If the air filters are on the bottom and the side of the furnace
then you have a bottom and side return. You must replace
both air filters. Table 1 will indicate 2 filters by using brackets
with the number two (2).
D. If the air filters are on both sides of the furnace then you have
a two sided return. You must replace both air filters. Table 1
will indicate 2 filters by using brackets with the number two
(2).
3. After you determine the cabinet size and what return configuration
you have, look up the recommended filter size from Table 1.
Removing Filters
Internally Mounted Air Filters
Most upflow furnaces have their filters located on the side or bottom of
the furnace in a filter wire retainer located inside the blower compart-
ment. To check filters located in the blower compartment:
1. Remove the upper furnace door by lifting up. Pull out bottom of
door and lower from furnace.
2. Remove the blower compartment panel by lifting up.
3. The filters will be located on the bottom or on one of the sides. To
remove bottom-mounted or side mounted filter (s) on all furnaces,
push the looped end of the filter retainer rod in, and then move the
retainer rod away from the filter.
4. Reverse the procedure to reinstall filters.
Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the cas-
ing of the furnace or placed in the return air duct. You can gain access
to the filter by pulling on the door or unscrewing the retaining screw,
then slide the filter(s) out of its channel. Replace throw away filter(s)
with the same size new filter(s). Throw away filter(s) may be replaced
with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as
described in the manufacturer instructions or as described below and
then re-installed.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
2. Snap the door on or place the door in position and tighten the
retaining screws, if provided.
3. Make sure the door is secure to the end of the filter rack.
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow filter to
completely dry before re-installing the filter.
Blower Care
Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower
assembly should be inspected annually. If the motor and wheel are
heavily coated with dust, they can be brushed and cleaned with a vac-
uum cleaner. If the blower cannot be properly cleaned without removing
it from the furnace, then this service must be performed by a qualified
service agency.
FIGURE 6: Upflow Internal Filter Retainer
TABLE 1:
Filter Sizes
Cabinet Size Side (in) Side (cm) Bottom (in) Bottom (cm)
B 16 x 25 40.6 x 63.5 14 x 25 35.5 x 63.5
B 16 x 25 40.6 x 63.5 14 x 25 35.5 x 63.5
C 16 x 25 40.6 x 63.5 16 X 25 40.6 X 63.5
C 16 x 25 40.6 x 63.5 16 x 25 40.6 X 63.5
C (2) 16 x 25 (2) 40.6 x 63.5 20 X 25 50.8 x 63.5
D (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5
Make sure you DO NOT move the clip on weight on the
indoor fan wheel when cleaning the wheel. This weight is
used to balance the wheel. Moving the weight will cause
the fan wheel to vibrate.
IF FILTER
PROVIDED
POSITION WIRE RETAINER
(IF PROVIDED) UNDER FLANGE
CLIPS
RIGHT SIDE
INSTALLATION
SHOWN
FURNACE
FRONT

035-19650-001 Rev. C (0404)
Unitary Products Group 5
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not
require periodic oiling.
Every time the filters are changed the following items should be visually
inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the fur-
nace and its components must be done by a qualified service pro-
fessional.
If, during the inspection of your furnace, you find any of the following
conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the fur-
nace, and set thermostat to the desired temperature.
SECTION II: SERVICE AND MAINTENANCE
MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing the furnace.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.
1. The vent terminal screen (if applicable).
2. The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem-
bly of components containing flue or vent gases is required, a
qualified service agency must perform the service.
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.
1. Call for 1st stage only
• On a call for 1st stage heat, the thermostat closes a circuit
between R and W1.
• The Microprocessor in the Furnace Control runs a ‘Self Check’.
• The Control checks the Primary Limit, Auxiliary Limit, and Roll-
out Switches for closed contacts.
• The Control checks that the Low Fire Pressure Switch (1LP) is
open.
• The Inducer Motor is energized on high speed, closing the con-
tacts of 1LP.
• The Control checks that 1LP is closed.
• The Inducer is switched to low speed.
• The Igniter is energized for 17 seconds.
• The Gas Valve is energized on 1st Stage (Low Fire).
• Flame Rectification is recognized within 7 seconds.
• 30 seconds after flame is proven, the ‘Heat Low’ relay is ener-
gized providing 120 Volts AC to the Blower Motor.
• At the same time, the EAC and Hum Hot relays are energized,
providing 120 Volts AC to the EAC Hot and Hum Hot terminals.
2. Call for 2nd Stage after 1st Stage is operating
• A call for 2nd Stage can be made by a 2-Stage thermostat, or by
the Second-Stage timer that comes installed in the furnace.
NOTE: When using a 2-Stage thermostat, the Timer should be discon-
nected.
• The Inducer Motor is shifted to high speed by the control, closing
the contacts of 2LP (The High Fire Pressure Switch.).
• The Control checks that 2LP is closed.
• The Gas Valve is energized on 2nd Stage (High Fire).
• The Control simultaneously de-energizes the Heat Low relay
and energizes the Heat High relay, providing 120 Volts AC to a
different speed of the Blower Motor.
3. 2nd Stage is satisfied, 1st Stage still calling.
• If a Single Stage Thermostat and the 2nd Stage Timer are used,
the Furnace will stay on High Fire until the thermostat is satis-
fied.
• When the circuit between R and W2 is opened, the Control
switches the Inducer Motor to low speed, causing the contacts of
2LP to open.
• When 2LP opens, 2nd Stage of the Gas Valve is de-energized.
• 30 seconds later, the Control switches the Blower from Heat
High to Heat Low.
4. 1st Stage Satisfied
• The Thermostat opens the circuit between R and W1
• Immediately the Gas Valve is de-energized and Flame Rectifica-
tion is lost.
• The Inducer Motor is de-energized after a 15 second Post Purge
and the Hum Hot terminal is de-energized.
• The ‘Fan Off Delay’ circuit is initiated. The Delay time can be
field set at 60, 90, 120, or 180 seconds. It comes from the fac-
tory set at 60 seconds.
• The Heat Low terminal is de-energized; stopping the Blower and
the EAC terminal is de-energized.
5. 1st and 2nd Stage called simultaneously
• The 1st stage call is processed as described in paragraph 1
above.
• Once Flame Rectification is established, 2nd Stage is entered
immediately as described in paragraph 2 above.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur-
nace.
• When servicing controls, label all wires prior to discon-
necting. Reconnect wires correctly.
• Verify proper operation after servicing.

035-19650-001 Rev. C (0404)
6Unitary Products Group
6. 1st and 2nd Stage satisfied simultaneously
• Both stages of the Gas Valve are de-energized.
• Flame Rectification is lost.
• The Inducer and Hum relays are de-energized after a 15-second
post purge.
• 30 seconds later the Control shifts the Blower from Heat High to
Heat Low.
• After the Blower-Off Delay Circuit is satisfied, the Blower and
EAC are de-energized.
7. Manual Fan Operation
• With the thermostat in the Fan On position, a circuit is completed
between R and G of the Control.
• The Heat Low and EAC relays are energized by the Control.
8. Call for Cooling
• The thermostat closes two circuits R to Y and R to G. Since the
Outdoor Unit is connected to Y and C at the Control, it is ener-
gized.
• The Cool and EAC relays are energized by the Control.
• A Blower-Off Delay Timing Circuit is energized by the call on Y.
9. Cooling call satisfied
• The thermostat opens the R to Y and R to G circuits.
• The Outdoor Unit is de-energized.
• The 60-second, Blower-Off Delay, timing circuit is initiated.
• After 60 seconds, the Cool and EAC relays are de-energized.
Heating Indoor Fan Off Delay
Changing the dipswitches on the Integrated Control can change the
indoor fan “OFF” time delay. The dipswitches are located above the
thermostat terminals. Refer to Figure 8 for the dipswitch settings to
obtain the desired fan OFF delay. The blower off delay must be long
enough to adequately cool the furnace, but not so long that cold air is
blown into the living space.
The blower on delay is fixed at 30 seconds and cannot be adjusted.
The continuous fan speed dipswitch (switch # 3 on the Integrated Con-
trol) does not function on variable speed models. Dipswitch # 3 should
be left in the off position.
Continuous Blower:
There are two modes of continuous blower operation.
•Mode One: The blower is controlled directly through the blower
motor. In the first mode, when the thermostat fan-switch is set to
the ON position a circuit is completed between terminals “R” and
“G” of the thermostat. The continuous fan speed will be 63% of
the high cool speed. If more air is desirable the green wire
labeled (G Cool Speed) may be connected to the “G” terminal of
the ignition control to achieve HIGH COOL speed (DIP switch
number 3 on the ignition control must be in the OFF position).
•Mode Two: The blower is controlled through the ignition control.
This configuration is used with multi-speed direct drive PSC
motors. Do not use this configuration with a variable speed
motor.Refer to Heating Indoor Fan Off Delay for Fan ON / OFF
Delays.
The air cleaner and the blower motor are energized through the ignition
control or directly through the motor.
DIRECT DRIVE BLOWER MOTOR
A failed PSC motor should always be replaced with a PSC motor suit-
able for the furnace model being serviced. Follow the procedure below
to replace the motor.
Removal of the Variable Speed Blower Motor Assembly:
The procedure for removing the variable speed blower assembly:
1. Disconnect the electrical supply to the furnace and remove the
access doors.
2. Remove blower assembly mounting screws and slide the blower
assembly out of the slots in the deck. If the two shipping screws
were not previously removed, also remove and discard these two
screws located on each front corner of the blower assembly.
3. Loosen the blower wheel set screw that secures the blower wheel
to the blower motor shaft.
4. Remove the motor mount bolts.
5. Slide the variable speed motor out of the blower housing.
Reassembly of the Variable Speed Blower Motor Assembly:
1. Slide the new variable speed motor in to the blower housing. Make
sure you line up the flat side on the motor shaft with the setscrew
on the hub in the center of the blower wheel.
2. Install the motor mount bolts in to the fan housing.
3. Center the indoor fan wheel in the fan housing and tighten the
blower wheel set screw on the flat side the blower motor shaft.
4. Reinstall blower assembly mounting screws and slide the blower
assembly back in the slots in the deck. Do not reinstall the two
shipping screws were removed.
5. Install the access doors.
6. Restore power to the furnace and verify operation.
INSTALLATION OF PSC MOTOR:
The motor speed tap wires are connected to the 1/4" quick connect ter-
minal on the Integrated Control using the black jumper wire that is
secured to the wire harness inside the burner compartment and is
marked “PSC Motor”. Follow the instructions below to properly install
the PSC motor.
1. Install the PSC direct drive motor into motor mount.
2. Slide motor in motor mount insuring there is no interference
between moving and stationary parts. Position wire leads down-
ward. Tighten motor mount band screw to 30 in. lbs.
3. Center the blower wheel in the blower housing and align the shaft
flat with the blower wheel set screw. Tighten setscrew to 30 in. lbs.
4. Replace blower assembly and fasten with 5 screws
5. Strap motor capacitor to electric panel. Refer to Table 2 for proper
capacitor selection.
6. Fasten electric panel to blower housing.
7. Remove red wire from circuit input terminal. Plug jumper wire
(attach to motor power harness) on 120-volt line terminal on igni-
tion control and jumper to circuit Input. Connect brown door switch
wire to jumper.
8. Connect white main harness lead to Line neutral.
9. Connect motor leads to cool, heat lo and heat high per electrical
wire diagram table in the Installation manual.
10. Connect brown capacitor leads from motor to capacitor and cover
terminals with boot supplied.
11. The motor ground (green) wire is secured to the right front of the
blower mounting plate with a screw.
12. Restore power to the furnace and verify operation.
FIGURE 7: White Rodgers Intergrated Control
INDOOR FAN OFF
DELAY DIP SWITCHES

035-19650-001 Rev. C (0404)
Unitary Products Group 7
Hot Surface Ignition System
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3. Remove the burner door and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3. Remove the upper access panel and remove the burner box
cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Remove the upper cover plate at the top of the furnace. Remove
the internal baffle.
8. The upper portion of the heat exchanger is now exposed.
9. With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes and then vacuum loose the scale and dirt from
each tube.
10. Clean - vacuum all burners.
11. Replace all components in reverse order. Reconnect all wiring.
12. Restore electrical power and gas supply to the furnace.
13. Check furnace operation.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 - 8 under cleaning the Heat Exchanger.
2. Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan. The turbulators can then be gently removed from
the secondary heat exchanger.
3. Using a stiff wire brush, remove the loose scale or soot from each
tube.
4. Vacuum the secondary heat exchanger.
5. Finish the cleaning procedure by following steps 11 thru 13 under
cleaning the Heat Exchanger.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control
module is ON.
2. The manual shut-off valves in the gas line to the furnace must be
open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.
TABLE 2:
Replacement PSC Motor / Capacitor Information
High Fire Inputs Airflow Cabinet Size Motor
Part Number Motor
Horsepower Capacitor
Part Number Capacitor
Rating
BTU/H (kW) CFM (m³)
60,000 (17.6) 1,200 (33.98) B 024-23271-000 1/2 024-20045-000 7.5 f
80,000 (23.4) 1,600 (45.31) C 024-26002-000 3/4 024-20046-000 10.0 f
100,000 (29.3) 2,000 (56.63) C 024-23288-001 1.0 024-20446-000 15.0 f
120,000 (35.1) 2,000 (56.63) D 024-23238-001 1.0 024-20446-000 15.0 f
HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.

035-19650-001 Rev. C (0404)
8Unitary Products Group
FURNACE DIAGNOSTICS
Control Module Fault Code Explanatios
1 Flash (Continuous Flash; 1 second on, 1 second off)
Reason: Flame sensed without a call for heat.
Effect: Blower and Inducer operate at Low Heat speed.
Causes: Gas Valve stuck open; Gas Valve is slow closing.
Incorrect wiring (Gas Valve is energized when it should
not be).
Defective ground, Flame rod shorted to ground.
2 Flash
Reason: Contacts of 1LP are stuck in the closed position. It must
first see an open circuit, then a closed circuit to ensure
safety.
Effect: Control will not continue the ignition process.
Causes: Incorrect wiring. (A jumper left in place across the
switch.).
A failed switch.
3 Flash (Part One; 1st Stage)
Reason: 1LP did not close at the beginning of the heat cycle.
Effect: Inducer operates on Low Heat speed. The Control will
not continue the ignition process.
Causes: Faulty Inducer
Blocked or restricted vent system.
Vent system that exceeds the specifications.|
Blocked condensate drain
Broken or leaking pressure switch tubing
Faulty 1LP
3 Flash (Part Two; 2nd Stage)
Reason: 2LP did not close within 30 seconds of a call for 2nd
Stage heat.
Effect: After 30 seconds the Control will enter a ‘Soft Lockout’
period, and the Inducer will be de-energized. After 3
minutes the Control will try again. The procedure will be
repeated if 2LP does not close.
Causes: Faulty Inducer.
Restricted vent system.
Vent system that exceeds specifications.
Blocked or restricted condensate drain.
Broken or leaking pressure switch tubing.
Faulty 2LP.
4 Flash
Reason: Open limit circuit. The limit circuit includes the Primary
Limit, Auxiliary Limit, and Rollout Switches.
Effect: Blower and Inducer operate at Low Heat speed. If the
open switch resets, the furnace will resume normal
operation.
Causes: Dirty Filter
Improperly sized duct system.
Incorrect blower speed selection
Incorrect firing rate
Faulty blower motor
Faulty Control
6 Flash
Reason: 1LP has opened five times during one call for heat.
Effect: Control enters ‘Soft Lockout’. It will automatically reset
and try again after 1 hour.
Causes: Restricted vent system
Vent system that exceeds specifications
High wind
7 Flash
Reason: Flame rectification could not be established
- Flame rectification must be maintained for 7 seconds
to be recognized by the control.
Effect: Control tries 3 times then goes into ‘Soft Lockout’.
- There is a 1-minute delay after a failed ignition
attempt
- 7 seconds is added to the igniter warm-up time after
a failed ignition attempt.
Causes: Faulty hot surface igniter
Contaminated flame rod.
Poor ground connection to furnace.
Reversed polarity to furnace
Moisture on flame sensing circuit
Low gas pressure
Faulty gas valve
8 Flash
Reason: Flame rectification has been lost 5 times, during 1 call
for heat, after it was recognized by the control.
- Flame rectification is recognized after 7 seconds of
burner operation.
Effect: Control goes into ‘Soft Lockout’ after the 5th attempt to
maintain combustion.
Causes: Restricted vent system.
Blocked or restricted condensate drain.
Foreign objects in the inducer housing.
LED on constantly
Reason: The control discovered an internal fault during its self-
check procedure.
Effect: All operations cease.
Causes: Voltage spikes.
Supply voltage is too high or low.
- Reset the control by breaking line voltage for 30
seconds.
Control failure.
Never bypass pressure switch to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.
Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
IGNITION CONTROL (P/N 031-01909-000)
Normal flame sense current is approximately
2.4 microamps DC (µa)
Low flame signal control lockout point is
0.15 microamps DC (µa)

035-19650-001 Rev. C (0404)
Unitary Products Group 9
FIGURE 8: Furnace Control Event Schedule
W2 SIGNAL
ON
CLOSED
OPEN
OPEN
CLOSED
ABSENT
PRESENT
HIGH INDUCER
HIGH STAGE PRESSURE
SWITCH AND 2ND STAGE
MAIN VALVE
CIRCULATOR HIGH
HEAT SPEED
2ND STAGE
CALL HIGH HEAT AFTER LOW
HEAT IS ESTABLISHED
HIGH
HEAT
OFF
DELAY
30 SEC.
HIGH LIMIT
W1 SIGNAL
LOW
INDUCER
LOW STAGE
PRESSURE
SWITCH
HSI
1ST STAGE
MAIN VALVE
FLAME
SENSE
LOW CIRCULATOR
HEAT SPEED
1ST STAGE LOW PRESSURE
SWITCH CLOSE
RECOGNITION
HSI
WARM
UP
17 SEC.
IGNITION
ACTIVATION
PERIOD
4 SEC.
TRIAL FOR
IGNITION
7 SEC.
INTER-
PURGE
60 SEC.
HSI
WARM
UP
27 SEC.
IGNITION
DEACTIVATION
PERIOD
3 SEC.
HEAT FAN
DELAY ON
30 SEC.
BURN
TIME
POST
PURGE
15 SEC.
HEAT FAN DELAY OFF
SELECTABLE
60,90,120,180 SEC.
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
NOTE:
1. THIS DIAGRAM SHOWS TWO IGNITION ATTEMPTS
2. TIMING LENGTHS ARE NOT TO SCALE

035-19650-001 Rev. C (0404)
10 Unitary Products Group
SECTION III: REPLACEMENT PARTS LIST
CGRWY
HUM
EAC
XFMR
LINE
CIR
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
1
4
26
10
12
14
7
89
13
3
5
15
17
16
11
CGRWY
HUM
EAC
XFMR
LINE
CIR
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
19
24
25
31 26
32
33
34
50
21
22
23
27
45
28
29
30
35
37 38
54
65
51
52
58
64
61
60
62
44
46
39
18
53
49
ON
OFF
9
6
14 25
29
28
63
30
20
36
55
48
49
41,43
8,

035-19650-001 Rev. C (0404)
Unitary Products Group 11
ITEM DESCRIPTION
MOTOR
1MOTOR,DIRECT DRIVE BLOWER
2MOTOR,VENTOR ASS’Y
MOTOR,VENTOR ASS’Y
ELECTRICAL
3CAPACITOR (7.5MFD/370V)
CAPACITOR (10 MFD/370V)
4 CAPACITOR, VENTOR(4MFD/370V)
5 CONTROL, HIGH LIMIT
6CONTROL,FLAME ROLL OUT
7 CONTROL,FURNACE
8 IGNITOR
9 SENSOR, FLAME
10 SWITCH, AIR PRESSURE [LP]
SWITCH, AIR PRESSURE [LP]
11 TIMER, 2 STAGE DELAY
12 SWITCH, DOOR
13 TRANSFORMER
14 VALVE, GAS
VALVE, GAS
14A FUSE
AIR MOVING
15 CUTOFF,BLOWER
16 HOUSING, BLOWER
17 WHEEL, BLOWER
FABRICATED PARTS
18 BAFFLE, AIR (LH Recoup.Coil)
19 BAFFLE, AIR (RH Recoup.Coil)
20 BURNER, MAIN GAS
21 COIL, SECONDARY HEAT EXCHANGER
22 DECK, BLOWER (Rear)
23 DECK, FRONT
24 HEAT EXCHANGER ASS’Y (Primary)
25 MANIFOLD, GAS
26 PAN, BASE
27 PAN, CONDENSATE
28 PANEL, BURNER BOX (Bottom)
29 PANEL, BURNER BOX (Front)
30 WRAPPER, BURNER BOX
31 CHANNEL, TOE PLATE
32 COVER, HEAT EXCHANGER
33 PANEL, FRONT (Blower)
34 PANEL, FRONT (Burner)
PANEL, FRONT (Burner)
35 PANEL, TOP
36 SUPPORT, BURNER
37 WRAPPER, CABINET (Insulated)
WRAPPER, CABINET (Insulated)
38 PANEL, VESTIBULE (Lower)
39 PLUG, WINDOW, CLEAR - .875”
MISCELLANEOUS
40 CLIP,FILTER RETAINER (2 Req’d)
41 COLLAR, AIR INTAKE (Burner Box)
42 FILTER, AIR (2 Req’d)
FILTER SIZE
43 GASKET, AIR INTAKE
44 GASKET, COMBUSTION BLOWER
45 GASKET, CONDENSATE PAN
46 GASKET, BURNER BOX
47 GASKET, BURN BOX TO VEST PANEL
48 GROMMET, MANIFOLD SEAL
49 PLUG, WINDOW,CLEAR - 1.5”
50 HANDLE, DOOR
51 ISOLATOR, TUBE (3 Req’d)
52 ISOLATOR, WASHER (3 Req’d)
53 ISOLATOR, SLEEVE (3 Req’d)
54 MOUNT, MOTOR
55 ORIFICE, BURNER (Natural #45)
56
57 RETAINER, FILTER
58 TRAP, CONDENSATE
TRAP, CONDENSATE
59 WIRING DIAGRAM
60 TUBE, DRAIN RAIN GUTTER
61 TUBE, DRAIN CONDENSATE PAN
62 TUBE, DRAIN CONDENSATE TRAP
63 BRACKET, IGNITOR
64 TUBE, CONDENSATE DRAIN
65 PIPE EXHAUST VENT
66 HARNESS, WIRING
67 TUBING, SILICONE
ITEM DESCRIPTION
Major components and suggested stocking items are shown with shaded item number.

035-19650-001 Rev. C (0404)
12 Unitary Products Group
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL
MODEL NO. DESCRIPTION USED WITH
DESCRIPTION USED WITH
PROPANE (LP) CONVERSION KIT ALL MODELS
EXTERNAL SIDE FILTER RACK (6 Pack) ALL MODELS
CONCENTRIC INTAKE/VENT 2” 40, 60, 80, 100 INPUT MBH
CONCENTRIC INTAKE/VENT 3” 120-140 MBH
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices) FOR APPLICATION INFORMATION SEE
FORM 650.75-N2.1V
EXTERNAL BOTTOM FILTER RACK 17-1/2” CABINETS
21” CABINETS
24-1/2” CABINETS
CONDENSATE NEUTRALIZER KIT ALL MODELS
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information.
a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069

035-19650-001 Rev. C (0404)
Unitary Products Group 13
SECTION IV: WIRING DIAGRAM
FIGURE 9: Wiring Diagram

035-19650-001 Rev. C (0404)
14 Unitary Products Group
NOTES

035-19650-001 Rev. C (0404)
Unitary Products Group 15

Subject to change without notice. Printed in U.S.A. 035-19650-001 Rev. C (0404)
Copyright © by York International Corp. 2004. All rights reserved. Supersedes: 035-19650-001 Rev. B (0204)
Unitary 5005 Norman
Products York OK
Group Drive 73069
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace
any parts that prove to have such defects according to the terms outlined on this warranty. This warranty covers only the equipment described by the Product
Model Number and Serial Number listed on the Warranty Registration Card.
UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at
its option, repair or furnish a replacement heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat
exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its
option, extend a replacement allowance to be applied toward the purchase of a new furnace or packaged unit marketed by UPG. The exact amount of the
allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of
the original consumer purchase price of the furnace, excluding such items as ductwork, wiring, piping and installation costs. UPG shall have no responsibility
hereunder for installation, shipping, handling or other charges except as specifically provided herein.
For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and allow us to
contact you, should it become necessary. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from
UPG.
This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed according to
UPG recommendations and specifications, and in accordance with all local, state, and national codes; and the product must not be removed from its place of
original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated on the reverse
side of this warranty.
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is
a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment,
and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere.
This warranty applies only to products installed in the United States and Canada.
EXCLUSIONS
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages resulting from accident, abuse, fire, flood, alteration, or acts of God (tampering, altering, defacing or removing the product serial number will
serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
8. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling
or restriction of the water circuit by foreign material or like causes.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (vent dampers, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL-
ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU.
SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA-
TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH-
ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF
THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC-
TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON
CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT
LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
For Owner's Information
FURNACE TYPE HEAT EXCHANGER PARTSResidential Applications Non-Residential
Applications
Original Owner Subsequent Owner
90% P*XU / G9D-UP Lifetime 20 10 5
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________
UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
This manual suits for next models
1
Table of contents
Other York Industrial Equipment manuals