
10
EPDT-351
3. Remove the domed cap nut [17] and turn the adjusting screw [14] while watching the pressure gauge
on the outlet side.
•Turn the adjusting screw to the right (clockwise) to increase the reduced pressure.
•Turn the adjusting screw to the left (counterclockwise) to decrease the reduced pressure.
*If the pressure is not set under the condition that the stop valve on the outlet side is
slightly opened, closing the stop valve on the outlet side while operation may lead to shut-off
pressure rise exceeding the set pressure.
4. Fully open the stop valve on the outlet side slowly.
5. After the adjustment is complete, tighten the domed cap nut [17]
6.1 Troubleshooting
Trouble Cause Remedy
Reduced pressure
exceeds the
set pressure.
1. Foreign substances are stuck
between disc [8] and valve seat [3],
or either of the parts is damaged.
1. Disassemble the product
the foreign substances. I
observed on the valve disc
seat, replace it.
2. The O-ring [6] is damaged. 2. Replace the O-ring.
3. The diaphragm [9] is damaged. 3. Replace the diaphragm.
4. By-pass globe valve leaks. 4. Repair or replace the by-pass globe
valve.
Reduced pressure
does not reach the
desired value.
1. Working pressure is improper. 1. Correct the working pressure. (
“1.1 Specifications”.)
2. Nominal size of the product is too
small for the specifications of the
system.
2. Replace the product with
proper nominal size. (See “1.
Nominal size selection”)
3. Pressure adjustment is improper. 3.
Readjust the pressure in accordance
with the given procedure. (See “5
Adjusting procedure”)
4. Strainer [10] built in the product is
clogged.
4. Disassemble and clean it. (See “6
Strainer cleaning procedure”)
5. The strainer installed on the inlet
side of the product is clogged.
5. Clean the strainer.
Outside leakage
1. Bolt [18] or [39] got loose. 1. Tighten the bolts.
2. O-ring [30] is damaged. 2. Replace the O-ring.
3. Strainer cap [11] or plug [31] got
loose.
3. Tighten the strainer cap or plug.
Abnormal sound
1. Nominal size of the product is too
large for the specifications of the
system.
1. Replace the product with one of
proper nominal size.
2. The pressure reduction ratio is too
large or the maximum pressure
difference is exceeded.
2. Reduce pressure in two stages. (
“1.1 Specifications”)
3. Air-induced trouble. 3. Install an air vent.
4. An on-off valve is installed near the
product.
5. The pipe diameter is narrowed within
3m before and after the pressure
reducing valve.
4.
Take as large distance as possible
from the on-off valve.
5. Make sure that pipes at least
before and after the pressure reducing
valve are of the same diameter.
Most of problems with the pressure reducing valve are caused by foreign substances and scale in the
piping. Avoid the ingress of dust and dirt to the product with caution.
A phenomenon similar to valve failure could occur due to the failure of the pressure gauge, leakage or
insufficient tightening of the globe valve in the by-pass line, clogging of the strainer, and other causes.
Check the above possible causes and take a proper remedy and preventive measure.