Yudian AI-519 Technical manual

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: [email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
AI-519 ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER
Operation Instruction
Ver. 8.2
(Applicable for accurate controls of temperature, pressure, flow, level, humidity etc.)
CONTENTS
1. SUMMARY...............................................................................................................................................................1
1.1 MAIN FEATURES 1
1.2 ORDERING CODE DEFINITION 1
1.3 TECHNICAL SPECIFICATION 4
1.4 REAR TERMINAL LAYOUT AND WIRING 6
2. DISPLAYS AND OPERATIONS ..........................................................................................................................10
2.1 FRONT PANEL DESCRIPTION 10
2.2 D7/E7 RAIL MOUNT PANEL DESCRIPTION 10
2.3 PARAMETER SETTING FLOW CHART 11
2.4 OPERATION DESCRIPTION 11
3. PARAMETERS AND SETTINGS........................................................................................................................12
3.1 PARAMETER LOCK (LOC)AND FIELD PARAMETERS 12
3.2 COMPLETE PARAMETER TABLE 13

Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us http://www.yudian.com.hk
Email: [email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796
1. SUMMARY
1.1 Main Features
●Universal thermocouples and selectable RTDs and linear current/voltage signals. Integrating non-linear graduation
tables, digital calibration and auto zero technology to achieve accurate and stable measurement.
●Advanced artificial intelligence (AI) control algorithm with auto tuning function without overshooting.
●Auto/manual bumpless switch and soft-start function.
●New generation X3 and X5 current output modules with accuracy 0.2%F.S., improving the precision of control and
retransmission.
●Advanced modular structure giving plenty of output options to satisfy all kinds of applications. Quick delivery and
easy maintenance.
●User-friendly and customized operating interface for easy learning and simple manipulation. All parameters can be
promoted to quick operator access in Field Parameter Table or kept in password protected Full Parameter Table.
●Worldwide power supply of 100-240VAC or 24VDC and various dimensions. Power frequency 50Hz or 60Hz and unit
of ℃/ ℉are selectable in parameter.
●High quality hardware design, using high performance tantalum capacitor or ceramic capacitor. Compared to
competing models, it consumes less electricity, experiences less temperature shifting, provides higher stability and
reliability, and can work in a wider range of temperature.
●ISO9001 and CE certified, achieving world class level of quality, anti-interference ability and safety.
POINTS TO NOTE
●Always adjust parameters according to input / output type and function. Only correctly wired instruments with
appropriate parameters shall be put into use.
1.2 Ordering Code Definition
AI series instruments adopt advanced modularized hardware design. There are maximum five module slots:
multi-function input/output (MIO), main output (OUTP), alarm (ALM), auxiliary output (AUX) and communication (COMM).
The modules can be purchased in bundle with instrument or separately, and can be installed easily. The input type can be
freely set to thermocouple, RTD, or linear current/voltage.
The ordering code of AI-519 series instrument is made up of 8 parts. For example:
AI-519 A N X3 L5 N S4 —24VDC
①②③④⑤⑥⑦⑧
It implies that the model is AI-519, front panel dimension is 96×96mm, no module installed in MIO (Multi-function I/O) slot,
X3 linear current output module installed in OUTP (main output), L5 (dual relay contact output module) in ALM (alarm), no
module installed in AUX (auxiliary output), RS485 communication interface with photoelectric isolation is installed. The
power supply of the instrument is 24VDC.
Order code in details:
①Model of the instrument
AI-519 economical type instrument with measurement accuracy 0.3%F.S. It adopts artificial intelligent control
technology, with functions of auto/manual bumpless switch.
②Front panel dimension
Afront panel 96×96mm(width×height), cut out 92+0.5×92+0.5mm, depth behind mounting surface 100mm.
A2 On top of A, there is additional light bar with 25 segments and 4 levels of luminosity.

2
Bfront panel 160×80mm(width×height), cut out 152+0.5×76+0.5mm, depth behind mounting surface 100mm.
Cfront panel 80×160mm(width×height), cut out 76+0.5×152+0.5mm, depth behind mounting surface 100mm.
C3 On top of C, there is additional light bar with 50 segments and 2 levels of luminosity.
Dfront panel 72×72mm(width×height), cut out 68+0.5×68+0.5mm, depth behind mounting surface 95mm
D2 front panel 48×48mm(width×height), cut out 45+0.5×45+0.5mm, depth behind mounting surface 95mm, with 10
terminals
D5 width 22.5mm, DIN-Rail mount, external keypad E8 (or communication if address/BAUD rate is correct)
required for display and parameter setting
D6 front panel 48×48mm(width×height), cut out 45+0.5×45+0.5mm, depth behind mounting surface 95mm, with 12
terminals
Efront panel 48×96mm(width×height), cut out 45+0.5×92+0.5mm, depth behind mounting surface 100mm
E2 On top of E, there is additional light bar with 25 segments and 4 levels of luminosity.
E5 48×96mm(width×height), DIN-Rail mount, external keypad E8 (or communication if address/BAUD rate is
correct)) required for display and parameter setting
Ffront panel 96×48mm(width×height), cut out 92+0.5×45+0.5mm, depth behind mounting surface 100mm
③Module type of multiple function I/O (MIO). N means none, no module installed.
I2 Single channel on-off signal input module. When a n external switch is connected, SV=SP1 When the switch is
open; SV=SP2 when the switch is closed.
I4 4~20mA/0~20mA analogue input module, with 24VDC power supply. Directly connecting to 2-wire transmitter.
V24/V12/V10 Isolated 24V/12V/10V DC voltage output module with maximum current of 50mA, supplying power
for external transmitter.
④Module type of main output (OUTP). For control output or SV/PV retransmission.
L1 Large capacity, large size, normal open relay output module (Capacity: 250VAC/2A)
L2 Small capacity, small size, normal open + normal close relay output module (Capacity: 250VAC/1A
recommended for alarm)
L4 Large capacity, small size, normal open + normal close relay output module (Capacity: 250VAC/2A)
K1 “Burnt-proof”single-phase thyristor zero crossing trigger output module, triggering one loop of a TRIAC or a pair
of inverse parallel SCR with current of 5~500A.
K3 “Burnt-proof”three-phase thyristor zero crossing trigger output module, triggering 3-phase circuit. Each loop
can trigger TRIAC or a pair of inverse parallel SCR with current of 5~500A.
K5 “Burnt-proof”single-phase thyristor phase-shift trigger output module, suitable for 200~240VAC power grid.
K6 “Burnt-proof”single-phase thyristor phase-shift trigger output module, suitable for non-standard power
environment below 380VAC.
X3 Photo-electric isolated linear current output module, 0~20mA or 4~20mA, occupying internal 12VDC power.
X5 Photo-electric isolated linear current output module, 0~20mA or 4-20mA. Equipped with isolated power supply
without occupying internal 12VDC power.
W1 TRIAC no contact normal open discrete output module (Capacity: 100~240VAC/0.2A, burnt-proof)
W2 TRIAC no contact normal closed discrete output module (Capacity: 100~240VAC/0.2A, burnt -proof)
GSolid-state relay, SSR voltage output module (DC12VDC/30mA)
⑤Module type of alarm (ALM). For AL1 and AL2 alarm outputs.
L0 Large capacity, large size, normal open relay output module (Capacity: 250VAC/2A, recommended for alarm)
L0/L2/L4 Single relay output alarm, support AL1 one channel alarm
L3 Dual normal open relay output module, support AL1 and AL2 alarm
⑥Module type of auxiliary output (AUX). For AU1 and AU2 alarms and control auxiliary output.
L0/L1/L2/L4 Single relay output alarm
L3 Dual normal open relay output module, supportAL1 andAL2 alarm

3
GSolid-state relay, SSR voltage output module (DC12VDC/30mA)
W1 TRIAC no contact normal open discrete output module (Capacity: 100~240VAC/0.2A, burnt-proof)
W2 TRIAC no contact normal closed discrete output module (Capacity: 100~240VAC/0.2A, burnt -proof)
R RS232 communication interface module, occupying internal 12VDC power.
⑦shows the module type of communication (COMM).
SRS485 photo-electric isolated communication interface module, occupying internal 12VDC power.
S1 RS485 photo-electric isolated communication interface module, occupying internal 24VDC power.
S4 RS485 photo-electric isolated communication interface module, with isolated DC/DC power convertor, without
drawing power from instrument internally.
SL RS485 photo-electric isolated communication interface module + single channel normal open relay output module,
occupying internal 12VDC power.(Only available for D6 panel size)
⑧Power supply of the instrument. If left blank, the power of the instrument is 100-240VAC. 24VDC means the
power supply of 20~32VDC or AC power (24V AC power has to be specified upon order).
POINTS TO NOTE
1. K3 module occupies two slots, OUTP and MIO. MIO cannot be used if K3 is installed. If setpoint switching feature is
required, put I2 module in COMM slot. Then set parameter bAud to 1. Two setpoints switching function can be used
in COMM instead of MIO.
2. The voltage output modules like V24, \/10 or V12 are often used for supplying power for external transducer
or feedback resistance of transmitter. These modules can be installed in any slot except that of D6 dimension
instrument. To standardize the wiring, it is recommended to be installed in the first idle slot in the order of
MIO, AUX, and COMM.
Installation and replacement of modules: Before the instrument delivery, module installation is done on request,
with corresponding parameter set correctly. Users can replace or install modules by themselves when
needed. When replacing a module, you should pull the controller out of the housing at first, insert a
small flat-tip screwdriver into the opening between the original module and the slot on motherboard to
remove the old module, and then install a new module. Changing module type needs to modify the
corresponding parameters.
Electric isolation of the modules: There are a group of 24V and a group 12V power supply built in the instrument
and isolated to the main circuit. The 24V power commonly supplies voltage output module, such as
V24/V12/V10 (24V/12V/10V voltage output module), I2 (on-off signal input module) and I4 (linear current
input module). The 12V power is commonly supplies output or communication module. Generally, the
relay contact output and TRIAC no contact discrete output are self-insulated from the other circuit, no
matter whether other modules are installed or not. SSR voltage output does not need to be insulated
from input circuit, because SSR itself has isolation function. Therefore, only the electric isolation
between the communication interface and the current output should be considered. Those modules, for
example, S (RS485 communication interface), R (RS232 communication interface) and X3 (linear current
output), all need the 12V power supply. If more than one of the above modules are installed, in order to
be electric isolated, only one of them can be module without electric isolation, the other modules should
be S4 or X4, which has its own isolated power supply. For example, if an X module is installed in OUTP
(main output) slot, and an S or X module is installed in COMM (communication interface) slot, then OUTP
and COMM cannot be electric isolated, so S or X should be replaced with S4 or X4.
No contact switch module: W1 and W2 are new types of no contact switch modules which apply the advanced
technology of “burn proof” and zero crossing conduction. It can replace the relay contact switc h.
Compared to the relay contact output module, W1 and W2 have longer life and lower interference. They

4
can largely decrease the interference spark of the equipment, and greatly improve the stability and
reliability of the system. Since the driver element is TRIAC, it is suitable for controlling 100-240VAC (not
for DC power) with current up to 80A. For the current larger than 80A, an intermediate relay is needed.
Protection elements are series wound to the output terminals, so it can control continuous current up to
0.2A with maximum allowed instantaneous current 2A.
Relay Module: The relay modules are widely used in industrial control. However, they are the only modules with
life time limit and volume limit and have much electromagnetic interference. There are four types of
relay modules: L1, L2, L3 and L4. For control output, L1 or L4 large capacity module is recommended.
L4 is equipped with high performance relay with small volume and large capacity but it costs higher. L2
module is small in size. Both of its normal open and normal close terminals have varistor spark absorption
but the capacity is small. It is suitable for alarm output. L1 and L are large in size and large capacity.
For those panel size with 48mm width (including D6, E, F and etc). large size modules cannot be installed
in both PCB board. L3 provides dual output to support two loops of alarm, for example, AL1+AL2. If
mechanical switch is not preferred or L3 is not allowed due to size limitation mentioned above, G5 (dual
SSR DC voltage output) with external SSR can be chosen.
Calibration: The instrument applies the technology of automatic zero and digital calibration, and is free of
maintenance. If the error exceeds certain range, generally, cleaning and drying the inside of the
instrument can fix it. If not, send the instrument back to the factory to examine and repair.
Warranty and maintenance: Free repair and maintenance will be given in specified period of time since the
delivery. In order to get full and correct repair, please state clear the phenomena and causes of the
malfunction of the instrument.
1.3 Technical Specification
Input type: (universal input)
Thermocouple: K, S, R, E, J, T, B, N, WRe3-WRe25, WRe5-WRe26 etc
Resistance temperature detector: Cu50, Pt100
Linear voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~20mV, 0~500mV etc
Linear current (I4 module in MIO): 0~20mA, 4~20mA, two-wire transmitter etc.
Extended input: By keeping all native input specification, another extra specification can be ordered (gradient table
may be required).
Measurement range
K(-50~+1300℃), S(-50~+1700℃), R(-50~+1700℃), T(-200~+350℃), E(0~800℃), J(0~1000℃),B(200~
1800℃), N(0~1300℃)
Cu50(-50~+150℃), Pt100(-200~+800℃)
Linear Input: -9990~+32000 units defined by user.
Measurement accuracy : 0.3 (0.3%FS ± 0.1℃)
Resolution : 0.1℃for K, E, J, N, Cu50, Pt100; 1℃for S, R
Temperature shift : ≤0.015%FS /℃(typical value is 70ppm/℃)
Sampling cycle : A/D converter sampling 8 times per second
Response time : ≤1s ( when digital filter parameter FILt=1)
Alarm function: Four different alarm type, high limit, low limit, deviation high limit and deviation low limit, optional
with alarm blocking at the beginning of power on.
Control mode:
On-off control mode (Hysteresis adjustable)
Standard PID with auto tuning

5
AI PID with auto tuning, adoptingAI artificial intelligence algorithm.
Control Period : 0.5~120.0 seconds selectable at interval of 0.5 seconds
Output mode (modularized)
Relay contact output (NO+NC, L1 or L4 module): 250VAC/2A or 30VDC/1A
TRIAC no contact discrete output (NO or NC): 100~240VAC/0.2A (continuous), 2A (20mS instantaneous, repeat
period≥5s)
SSR voltage output: 12VDC/30mA (used to drive SSR).
Thyristor zero crossing trigger output: trigger TRIAC of 5~500A, a pair of inverse paralleled SCRs or SCR power
module.
Linear current output: 0~20mA or 4~20mA (Output voltage ≥11V, maximum load resistance 500ohm, output
precision 0.2%FS)
Electromagnetic compatibility (EMC) : ±4KV/5KHz according to IEC61000-4-4; 4KV according to IEC61000-4-5.
Isolation withstanding voltage : between power, relay contact or signal terminal ≥2300VDC; between isolated
electroweak terminals ≥600VDC
Power Supply : 100~240VAC, -15%, +10% / 50-60Hz; 120~240VDC; or 24VDC/AC, -15%, +10%.
Power consumption: ≤6W
Operating Ambient : temperature -10~60℃; humidity ≤90%RH
Front panel dimension: 96×96mm, 160×80mm, 80×160mm, 48×96mm, 96×48mm, 48×48mm, 72×72mm
Panel cutout dimension: 92×92mm, 152×76mm, 76×152mm, 45×92mm, 92×45mm, 45×45mm, 68×68mm
Depth behind mounting surface: ≤100mm

6
1.4 Rear Terminal Layout and Wiring
Wiring diagram at back side
1: For linear voltage input, if the range is
below 500mV, connect to terminals 19 and
18. 0~5V or 1~5V signal can be input
from terminals 17 and 18.
2: 4~20mA signal can be converted to 1~
5V signal by a 250 ohm resistor and input
from terminals 17 and 18. If I4 module is
installed in MIO slot, 4~20mA signal can
be input from terminals 14+ and 15- and
2-wire transmitter can be input from
terminals 16+ and 14-.
3: The compensation wires for different
kinds of thermocouple are different, and
should be directly connect to the terminals.
When the internal auto compensation
mode is used, connecting the common wire between the compensation wire and the terminals will cause measurement
error.
4: Main output from terminals 13+ 11- as current output, single channel SSR voltage output.
Wiring diagram of D size instruments (72×72mm)
1: Linear voltage signal of range below 500mV input from
terminals 13 and 12. 0~5V and 1~5V input from terminals 11
and 12.
2: 4~20mA linear current signal can be converted to 1~5V
voltage signal by connecting a 250 ohm resistor and input from
terminals 11 and 12.
3: S, S1 or S4 module can be installed in COMM slot for
communication. If relay, TRIAC no contact switch, or SSR
driver voltage output module is installed in COMM, it can be
used as AL1 alarm output. If I2 module is installed in COMM
and parameter “bAud” set to 1, then on-off signal in MIO is simulated. Setpoints SV1 and SV2 can be switched by
connecting an external mechanical switch at terminals 3 and 4.
Note: This graph is for upright
instruments with dimension A, C
or E.
For instruments with dimension
B and F, just clockwise rotate
the graph 90 degree and the
terminal numbers keep the
same.
AU1
M2/MIO
AUX
ALM
COMM
AL2
1
2
3
4
5
6
7
8
9
10
11
12
15
16
17
18
19
20
13
14
AL1
AU2
COM
COM
N/O
N/C
N/O
N/O
+
+
A
B
+
100-240VAC~
+
+
OUTP
COM
COM
N/O
N/C
N/O
N/O
COM
COM
N/O
N/O
N/O
N/C
+
+
OP2
OP1
+
0-5V
1-5V
G1
G2
G1
G2
G1
G2
Thyristor trigger output(K1/K3)
Thyristor trigger output(K3)
Thyristor trigger output(K3)
+
COM
N/C
V+
N/O
+
+
+
RXD
GND
TXD
AU1
AUX
COMM/AL1
1
2
3
4
5
6
7
8
9
11
12
13
14
10
AU2
COM
COM
N/O
N/C
N/O
N/O
+
+
A
B
+
100-240VAC~
+
+
OUTP
COM
COM
N/O
N/C
N/O
N/O
OP2
OP1
+
0-5V
1-5V
G1
G2
Thyristor trigger output(K1)
COM
N/O
+
TXD
RXD
GND

7
Wiring diagram of D2 size instruments (48×48mm)
1: D2 size instruments don not support native 0~
5V or 1~5V linear voltage input. The workaround
is done by voltage divider into 0~500mV or 100~
500mV. External precise resistor 25ohm can be
parallel shunt to convert 4~20mA to 100~500mV
then input from terminals 9 and 8.
2: For COMM/AUX slot,
installing S or S4 communication module provides
communication, installing L2 module provides AU1
alarm output,
installing L2 module provides AU1 alarm output,
installing L3 dual relay module (with parameter bAud=0) provides AU1 and AU2 alarm output,
installing L3 (with parameter bAud=2) provides AU1 and AL1 alarm output,
installing I2 module (with parameter bAud=1) provides MIO on-off input simulation SP1/SP2. The external switch should
be connected to terminal 3 and 5.
Wiring diagram of D6 size instruments (48×48mm)
1: Linear voltage of 500mV below input from
terminal 10, 11. 0~5V or 1~5V linear voltage
input from terminal 9 and 10.
2: External precise resistor 250ohm can be
parallel shunt to convert 4~20mA to 1~5V
then input from terminals 9 and 10.
3: For COMM/AUX slot, installing S or S4
communication module provides
communication,
installing L2 module provides AU1 alarm
output,
installing L3 dual relay module (with parameter
bAud=0) provides AU1 and AU2 alarm output,
installing SL module provides RS485 communication andAU1 alarm output.
1
2
3
4
5
6
7
9
10
8
COM
N/O
+
100-240VAC~
AU1
COMM/AUX
AU2
A
B
COM
COM
N/O
N/C
N/O
N/O
+
G1
G2
Thyristor trigger output(K1)
OUTP
TXD
RXD
GND
Thyristor trigger output (K1)

8
Wiring diagram of D5 size instruments
1: D5 size instrument are fixed with one channel alarm and communication.
2: Main output can be selected among G, X5, L2, K1, K5, K6 or W1.
Wiring diagram of D7 size instruments (22.5 x 100mm)
1: Input
0~5V/1~5V input from 12+, 11-
500mV below input from 10+, 11-
4~20mA with 250ohm shunt resistor converted to 1~5V,
input from 12+, 11-
2: Fixed with one channel alarm and communication
3: Main output can be selected among G, X3, L2, K1, K5, K6
or W1. Alarm is mandatorily defined as AU1
4: Instrument power and communication wires are
connected to the back side connectors along the rail.

9
Wiring diagram of E7 size instruments (22.5 x 100mm)
1: Input
0~5V/1~5V input from 12+, 11-
500mV below input from 10+, 11-
4~20mA with 250ohm shunt resistor converted to 1~5V, input from 12+, 11-
2: Fixed with one channel alarm and communication
3: Main output can be selected among G, X3, L2, K1, K5, K6 or W1. Alarm is
mandatorily defined as AU1
Thyristor trigger output wiring diagram (applicable for K1, K3, K5 or K6 module)
Load
Thyristor trigger output
100~240VAC
IN4001
1N4001
Load
Thyristor trigger output
SCR X2
5~500A
BX
BX
Capacitor Resistor
Absorber Circuit
Varistor
G1
G2
G1
G2
ZNR
ZNR
V
V
100~240VAC
TRIAC
5~500A
Capacitor Resistor
Absorber Circuit
Varistor
SCR Power Module
1: According to the voltage and current of load, choose suitable varistor to prevent the thyristor. Capacitor resistor
absorber is needed for inductance load or phase-shift trigger output.
2: SCR power module is recommended. A power module includes two SCRs, is similar to the above dashed square.
3: K5 phase-shift trigger module is only suitable for 200~240VAC / 50Hz power. K6 phase-shift trigger module is only for
380VAC below non-standard environment.

10
2. DISPLAYS AND OPERATIONS
2.1 Front Panel Description
①Upper display window, displays PV, parameter code, etc.
②Lower display window, displays SV, parameter value, or
alarm code.
③Setup key, for accessing parameter table and conforming
parameter modification.
④Data shift key, and also for auto tuning, auto/manual switch.
⑤Data decrease key, and also run/pause switch
⑥Data increase key, and also stop key
⑦LED indicator. PRG indicator is non-applicable for AI-519.
The lighting of MAN means in manual output status. MIO, OP1, OP2, AL1, AL2, AU1 and AU2 indicate I/O operation
of the corresponding module. For example, That the COMM indicator is lighting means that the instrument is
communicating with upper device.
Basic display status : When power on, the upper display window of the instrument shows the process value (PV), and
the lower window shows the setpoint (SV). This status is called basic display status. When the input signal is out of the
measurable range (for example, the thermocouple or RTD circuit is break, or input specification sets wrong), the upper
display window will alternately display “orAL” and the high limit or the low limit of PV, and the instrument will automatically
stop output. If the lower display window alternately display “HIAL”, “LoAL”, “HdAL” or “LdAL”, it means high limit alarm,
low limit alarm, deviation high alarm, and deviation low alarm happening. The alarm display can also be turned off by
setting parameter AdIS to oFF. If “EErr” is displayed, it means internal self-test error, and the instrument should be sent
back for repair.
2.2 D7/E7 Rail mount Panel Description
①Upper display window, displays PV, parameter code, etc.
②Lower display window, displays SV, parameter value, or alarm code.
③Setup key, for accessing parameter table and conforming parameter modification.
④Data decrease key, and also run/pause switch
⑤Five LED indicator. O1, O2, O3 and O4 represents OP1, OP2, AU1 and AU2 respectively.
C indicator flashes during it is communicating with upper device.
⑥Data shift key, and also setpoint control operation
Data increase key, and also stop key
MAN
PRG
COM
MIO
AL1
AL2
OP1
OP2
A/M
RUN/HOLD
AU2
STOP
AU1
①
②
③
④
⑤
⑥
⑥
⑦
⑥
PV
SV
AI
①
②
③
④
⑤
⑥
⑦

11
2.3 Parameter Setting Flow Chart
2.4 Operation Description
Parameter Setting
In basic display status, press and hold for about 2 seconds can access Field Parameter Table. Pressing
can go to the next parameter; pressing
、or
can modify a parameter. Press to decrease the data.
Press
to increase the data. The decimal place dot flashes where the data is changing, looking like a mouse
cursor. Press the button and hold, the speed of data change will go faster, and going further faster along with the
shift of cursor. Press
to direct move the cursor. Press and hold
can return to the preceding parameter. The
parameter will be saved. Press
(don't release) and then press key simultaneously can escape from the
parameter table. The parameter will be saved. The instrument will escape auomatically from the parameter table if no key
is pressed within 25 seconds, and the change of the last parameter will not be saved.
In Field Parameter Table, press till the last field parameter Loc appears. Setting Loc=password and then press
can access System Parameter Table.
Setpoint / Output Magnitude Switch
In the basic display status, pressing can switch lower display window between displaying setpoint or output
magnitude. If the instrument is in manual operating mode, even the lower display window is switched to setpoint display, it
will automatically return to output magnitude display after a period of time.
Setpoint (SV) Setting
If the parameter lock “Loc” isn't locked, we can set setpoint (SV) by pressing
, or
. The range of setpoint is
between the parameter SPL and SPH.
Auto / Manual Control Mode Switch (A/M)
When output magnitude is displayed in lower display window, pressing AT key (
) can switch between auto-control
and manual control without bumping. If the instrument is in manual control mode and the lower display window is
Auto Tuning
Parameter AT
High Limit
Alarm HIAL
Process Value
Setpoint
Parameter Lock
Loc
Run
Auto Tuning
Auto Tuning
Parameter AT
Output 60%
(Manual Mode)
High Limit
Alarm HIAL
Output 60%
(Auto Mode)
+
2 Sec
2Sec
Next
Parameter
2Sec
Next
Parameter
Password correct
+
Password
incorrect
2sec
2Sec
AT finished
Power On
Basic Display Status
Field Parameters
Entire Parameter Table
2sec

12
displaying output magnitude, the output magnitude can be modified by pressing or
. By setting M-A parameter,
the instrument can be locked at automatic or manual control mode to avoid entering manual operation by mistake.
Auto Tuning (AT)
When artificial intelligence PID control or standard PID control is chosen (CtrL=APId or nPId), the PID parameters can
be obtained by running auto-tuning. In basic display status, press
for 2 seconds, the “At” parameter will appear.
Press
to change the value of “At” from “oFF” to “on”, then press to active the auto-tuning process. During
auto tuning, “At” will flash at lower display window and the instrument executes on-off control. After 2 cycles of on-off
action, the instrument will obtain the values of PID control parameters. If you want to escape from auto tuning status,
press and hold
for about 2 seconds until the "At" parameter appears again. Change “At” from “on” to “oFF”, press
to confirm, then the auto tuning process will be cancelled. After satisfying PID parameters are obtained, At is
recommended to be “FoFF” which prevents activating auto tuning in basic display status.
Note 1: The advanced artificial intelligence algorithm is able to avoid overshooting problem of standard PID algorithm
and achieve precise control.
Note 2: If the setpoint is different, the parameters obtained from auto-tuning are possibly different. So you’d better set
setpoint to an often-used value or middle value first, and then start auto-tuning. For the ovens with good heat
preservation, the setpoint can be set to the highest applicable temperature. It is forbidden to change SV during auto
tuning. Depending on the system, the auto-tuning time can be from several seconds to several hours.
Note 3: Parameter CHYS (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning.
Generally, the smaller the value of CHYS, the higher is the precision of auto tuning. But the value of CHYS parameter
should be large enough to prevent the instrument from error action around setpoint due to the oscillation of input. CHYS
is recommended to be 2.0.
Note 4: AI series instrument has the function of self-adaptation. It is able to learn the process while working. The
control effect at the first run after auto tuning is probably not perfect, but excellent control result will be obtained after a
period of time because of self-adaptation.
3. PARAMETERS AND SETTINGS
3.1 Parameter Lock (Loc) and Field Parameters
In order to protect important parameters from being modified by mistake but also offer enough flexibility for field control,
parameter lock (Loc) and field parameters are introduced.
The parameters need to be displayed and modified in the work field are called Field Parameters. The set of field
parameters is a subset of the whole parameter set, and can be freely chosen by user.
Loc can authorize different security right as below:
Loc=0~1, allowed to modify field parameters and setpoint, and execute auto tuning;
Loc=2, allowed to modify field parameters, but can’t modify setpoint.
Loc=3~255: can only modify “Loc”
Setting Loc=PASd (Password, a number between 256 and 9999. Default is 808) and then pressing to confirm will
enter the complete parameter table and modify all parameters.
1 to 8 field parameters can be defined by parameters EP1 to EP8. If the number of the field parameters is less than 8,
the first idle EP parameter should be set to “nonE”.
Parameters
EP1
EP2
EP3
EP4
EP5
EP6
EP7
EP8
Loc
Default Value
HIAL
LoAL
HdAL
LdAL
nonE
nonE
nonE
nonE
0
You can redefine field parameters and Loc to change operation style. For example, you can execute auto tuning from field
parameter instead of by pressing
in basic display status, and only take HIAL and HdAL as field parameter.
Parameters
EP1
EP2
EP3
EP4
EP5
EP6
EP7
EP8
Loc
At
Default Value
HIAL
HdAL
At
nonE
nonE
nonE
nonE
nonE
0
FoFF

13
3.2 Complete Parameter Table
The parameters can be divided to 8 groups including alarm, control, input, output, communication, system,
setpoint and field parameter definition. They are listed as below in sequence:
Code
Name
Description
Setting
Range
HIAL
High limit
alarm
Alarm on when PV (Process Value) >HIAL; alarm off when PV<HIAL-AHYS
Alarm output action can be defined by parameter AOP.
-9990~
+30000
units
LoAL
Low limit alarm
Alarm on when PV<LoAL; alarm off when PV>LoAL+AHYS
HdAL
Deviation high
alarm
Alarm on when PV-SV>HdAL; alarm off when PV-SV<HdAL-AHYS
LdAL
Deviation low
alarm
Alarm on when PV-SV<LdAL; alarm off when PV-SV>LdAL+AHYS
HdAL and LdAL can also be used as high limit and low limit alarms when needed.
(Refer to the description of parameterAF)
AHYS
Alarm
hysteresis
Avoid frequent alarm on-off action because of the fluctuation of PV
0~2000
units
AdIS
Alarm display
oFF : don’t display AdIS in the lower display window when alarming;
on : alternately display AdIS in the lower display window when alarming.
oFF
on
AOP
Alarm output
allocation
From right side to left side, the first, second, third and fourth digit of AOP individually
indicate the alarm output terminal of HIAL, LoAL, HdAL, and LdAL. 0 shows no
output. 1,2,3 or 4 indicates alarm outputted to AL1, AL2, AU1 or AU2. For example,
AOP = 3 3 0 1
LoAL HdAL LoAL HIAL
It shows that HIAL is sent to AL1, LoAL has no output, HdAL and LdAL are sent to
AU1.
Note 1: When AUX is used as auxiliary output in bidirectional (heating/refrigerating)
control, allocating alarm to AU1 and AU2 does no effect.
Note 2: Installing L3 dual relay output module in ALM or AUX can implement AL2 or
AU2 alarm.
0~4444
CtrL
Control mode
onoF: on-off control. For situation not requiring high precision;
APId: advanced artificial intelligence PID control. Recommended
nPId: standard PID algorithm with anti–integral-saturation function (no integral when
PV-SV > proportional band);
POP: output PV. The instrument works as a temperature retransmitter.
SOP: output SV. The instrument works as a set current output.
onoF
APId
nPId
POP
SOP
Act
Acting method
rE: Reverse acting. Increase in measured variable causes an decrease in the
output, such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in the output,
such as refrigerating control.
rEbA: Reverse acting with low limit alarm and deviation low alarm blocking at the
beginning of power on.
drbA: Direct acting with high limit alarm and deviation high alarm blocking at the
beginning of power on.
rE
dr
rEbA
drbA
A-M
Auto/Manual
Control Mode
Selection
MAn: Manual control mode. Manually adjust output value of OUTP.
Auto: Auto control mode. The instrument calculate and control the output value.
FMAn: Fixed in manual control mode. Forbid switching to auto-mode by short-cut keys
from panel.
FAut: Fixed in auto control mode. Forbid switching to manual mode by short-cut keys
from panel.
MAn
Auto
FMAn
FAut
At
auto tuning
oFF: Auto tuning function is disable
on: Active auto turning function to calculate the values of parameters P, I, d and CtI.
After auto tuning is accomplished, “At” will be automatically changed to oFF.
FoFF: Auto tuning is disabled, and activating auto tuning from basic display status is
forbidden.
P
Proportional
band
Proportional band in PID and APID control. Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can be obtained by auto tuning. They can also be
manually input if you already know the correct values.
10~9999
units
I
Time of
Integral
No integral effect when I=0
0~9999
seconds
d
Time of
Derivative
No derivative effect when d=0
0~999.9
seconds
CtI
Control period
Small value improves control accuracy.
For SSR, thyristor or linear current output, generally 0.5 to 3 seconds.
For Relay output or in a heating/refrigerating dual output control system, generally 15
to 40 seconds, because small value will cause the frequent on-off action of
mechanical switch or frequent heating/refrigerating switch, and shorten its service life.
0.5~
120.0
seconds

14
CtI is recommended to be 1/4 –1/10 of derivative time. (It should be integer times of
0.5 second.)
When output type is set to relay (OPt or Aut is set to rELY), CtI will be limited to more
than 3 seconds. Auto tuning will automatically set CtI to suitable value considering
both control precision and mechanical switch longevity.
CHYS
Control
Hysteresis
CHYS is used for on-off control to avoid frequent on-off action of relay.
For a reverse acting (heating) system, when PV > SV, output turns off; when
PV<SV-CHYS, output turns on.
For a direct acting (refrigerating) system, when PV<SV, output turns off; when
PV>SV+CHYS, output turns on.
0~2000
units
InP
Input
specification
Code
InP
Input spec.
InP
Input spec.
0
K
20
Cu50
1
S
21
Pt100
2
R
22
Pt100(-80~+300.00℃)
3
T
25
0~75mV voltage input
4
E
26
0~80ohm resistor input
5
J
27
0~400ohm resistor input
6
B
28
0~20mV voltage input
7
N
29
0~100mV voltage input
8
WRe3-Wre25
30
0~60mV voltage input
9
WRe5-Wre26
31
0~500mV voltage input
10
extended input
specification
32
100~500mV voltage input
12
F2 radiation type pyromter
33
1~5V voltageinput
15
4~20mA
(Module I4 in MIO)
34
0~5V voltage input
16
0~20mA
(Module I4 in MIO)
35
0~10V
17
K(0~300.00℃)
36
2~10V
18
J(0~300.00℃)
37
0~20V
Note 1: Setting InP=10 for extended input. If user specified gradient input other than
provided upon ordering, for example, WRe520, JPt100 (BA2), G(Cu53), F2, Square
root of 0~5V or 1~5V, INP=10 will be used up.
Note 2: Input specification and related parameter are already set in factory if the
input is specified upon order.
0~37
dPt
Radix point
position
Four formats (0, 0.0, 0.00, 0.000) are selectable
1: For thermocouples or RTD input, only 0 or 0.0 is selectable, and the internal
resolution is 0.1. When S or R thermocouple is used, dPt is recommended to be 0.
2: When linear input is used and measurement value or corresponding parameter
value may be larger than 9999, please avoid choosing 0 but 0.000 instead. The
display value will become 00.00 when the value is larger than 9999.
0, 0.0,
0.00,
0.000
ScL
Signal scale
low limit
Define scale low limit of input. It is also the low limit of transmitter output (CtrL=POP
or SOP) and light bar display.
-9990~
+30000
units
ScH
Signal scale
high limit
Define scale high limit of input. It is also the high limit of retransmission output
(CtrL=POP or SOP) and light bar display.
Scb
Input Shift
Adjustment
Scb is used to shift input to compensate the error caused by transducer, input signal,
or auto cold junction compensation of thermocouple.
PV_after_compensation=PV_before_compensation + Scb
-1999~
+4000
units
FILt
PV input filter
The value of FILt will determine the ability of filtering noise.
When a large value is set, the measurement input is stabilized but the response
speed is slow. Generally, it can be set to 1 to 3.
If great interference exists, then you can increase parameter “FILt” gradually to make
momentary fluctuation of measured value less than 2 to 5.
When the instrument is being metrological verified, “FILt” s can be set to 0 or 1 to
shorten the response time.
0~40
Fru
Selection of
power
frequency and
temperature
scale
50C: 50Hz, ℃. Input has maximum anti-interference ability to 50Hz frequency;
50F: 50Hz, ℉. Input has maximum anti-interference ability to 50Hz frequency;
60C: 60Hz, ℃. Input has maximum anti-interference ability to 60Hz frequency;
60F: 60Hz, ℉. Input has maximum anti-interference ability to 60Hz frequency;
50C, 50F,
60C, 60F
OPt
main output
type
SSr: to output SSr driver voltage or thyristor zero crossing trigger signal. G, K1 or K3
module should be installed. The output power can be adjusted by the on-off time
proportion. The period (CtI) is generally 0.5~4 seconds.
rELy: for relay contact output or for execution system with mechanical contact switch.
To protect the mechanical switch, the output period (CtI) is limited to 3~120 seconds,
SSr
rELy
0-20
4-20
PHA

15
and generally is 1/5 to 1/10 of derivative time.
0-20: 0~20mA linear current output. X3 or X5 module should be installed in OUTP
slot.
4-20: 4~20mA linear current output. X3 or X5 module should be installed in OUTP
slot.
PHA: single-phase phase-shift output. K5 module should be installed in OUTP slot.
PHA is only for 50Hz power supply, and don’t support bidirectional control system.
OPL
Output low
limit
0~100%: OPL is the minimum output of OUTP in single directional control system.
-1 ~-120%: the instrument works as a bidirectional system having
heating/refrigerating dual output. When Act=rE or rEbA, OUTP (main output) works
as heating, and AUX (Auxiliary output) works as refrigerating. When Act=dr or drbA,
OUTP works as refrigerating, and AUX works as heating.
In a bidirectional system, the heating and refrigerating ability are generally different.
OPL = -(power when AUX output is maximum /power when OUTP output is maximum)
x 100%.
For example, for a heating/refrigerating air condition, its maximum power of
refrigerating is 4000W, and maximum power of heating is 5000W, and AUX works as
refrigerating, then
OPL=- (4000/5000)x100% = -80%
The range of AUX output can’t be freely defined by user. If the internal calculation
requires maximum output of AUX (AUX output=OPL), then in 4~20mA output, the
AUX output is 20mA. User can’t limit the maximum AUX output to 10mA.
-120~
+100%
OPH
Output upper
limit
OPL limits the maximum of OUTP (main output) when PV<OEF. OPH should be
greater than OPL.
0~110%
OPrt
Soft start time
At the beginning of power on, if PV<OEF, it takes OPrt for the output value of OUTP to
rise to OPH; if PV>OEF, then the time for output value of OUTP to rise to 100% is not
more than 5 seconds. This function is only needed by special requirement.
Soft start function doesn’t affect the maximum output at auto tuning or manual control.
If it is needed to lower the impulse current of induction load, CtI=0.5 second, and
OPrt=5 second.
0~3600
second
OEF
Work range of
OPH
When PV<OEF, the upper limit of OUTP is OPL; when PV>OEF, the upper limit of
OUTP is 100%.
For example, to avoid that the temperature raises too quickly, under 150℃, a heater
can work only under 30% of power, then we can set OEF=150.0 (℃), OPH=30 (%)
-9990~
+30000
units
Addr
communication
address
In the same communication line, different instrument should be set to different
address.
0~80
bAud
baud rate
the range of baud rate is 1200~19200bit/s. For D2 dimension instrument, when
COMM/AUX slot is used as AUX, bAud should be set to 0.
0~19200
AF
advanced
function
AF is used to select advanced function. The value of AF is calculated as below:
AF=Ax1 + Bx2 + Cx4 + Dx8
A=0, HdAL and LdAL work as deviation high and low limit alarms; A=1, HdAL and
LdAL work as high and low limit alarms, and the instrument can have two groups of
high and low limit alarms.
B=0, alarm and control hysteresis work as unilateral hysteresis; B=1, as bilateral
hysteresis.
For instruments with light bar, when C=0, the light bar indicates the output value;
when C=1, the light bar indicates the process value.
D=0, Loc=808 can access the whole parameter table; D=1, Loc=PASd can access the
parameter table.
Note: AF=0 is recommended except for advanced user.
0~15
PASd
password
When PASd=0~255 or AF.D=0, setting Loc=808 can enter the whole parameter table.
When PASd=256~9999 and AF.D=1, only setting Loc=PASd can access the whole
parameter table.
Please setting PASd cautiously, if the password is lost, you can’t access the
parameter table again.
0~9999
SPL
Low limit of SV
Minimum value that SV is allowed to be.
-9990~
+30000
unit
SPH
Upper limit of
SV
Maximum value that SV is allowed to be.
SP1
Setpoint 1
Generally, SV=SP1
SPL~
SPH
SP2
Setpoint 2
when I2 is installed in MIO slot, SP1 and SP2 can be switched by an external switch.
If the switch is off, SV=SP1; if the switch is on, SV=SP2.
EP1~
EP8
Field
parameter
definition
Define 0~8 of the parameters as field parameters.
nonE and
all
parameter
codes

16
Additional Notes
Decimal Places
When the measuring value and all parameter value shows 0.1℃or 0.1℉during measuring temperature (depends on
parameter setting Fru), the range of parameter will become –999.0℃~+3000.0℃or –999.0℉~+3000.0℉, even the
default range is-9990~+30000. The decimal place after 999.9 will be truncated. For linear signal definition, the decimal
place are only for display. The value showing does not affect internal resolution and scale.
Alarm blocking at the beginning of power on
Some unnecessary alarms often occur at the beginning of power on. In a heating system, at the beginning of powers on,
its temperature is much lower than the setpoint. If low limit and deviation low limit are set and the alarm condition are
satisfied, the instrument should alarm, but there is no problem in the system. Contrarily, in an refrigerating system, the
unnecessary high limit or deviation high limit alarm may occur at the beginning of power on. Therefore, AI instruments
offer the function of alarm blocking at the beginning of power on. When Act is set to rEbA or drbA, the corresponding low
or high alarms are blocked until the alarm condition first clears. If the alarm condition is satisfied again, the alarm will
work.
Temperature Transmitter
Besides AI PID, stand PID control and on-off control, if the output is defined as current output, the instrument can also
retransmit PV (process value) into linear current. The precision of current output is 0.2%FS, as 0.5%FS transmitter
counted whole system.
Parameter setting suggestion
CtrL=POP
InP=0
SCL=0.0
SCH=400.0
Opt=4-20
The input reads from a K thermocouple, ranging 0~400℃, output current as 4~20mA.
Table of contents
Other Yudian Controllers manuals
Popular Controllers manuals by other brands

TJERNLUND
TJERNLUND MAC4E CONTROL (COMPATIBLE WITH UC1 CONTROL) 8504112 REV A... Operating and mounting instructions

CircuitWerkes
CircuitWerkes Sicon-8 Quick start up guide

Crompton
Crompton 3000 Series Installation and maintenance instruction

Epson
Epson S1S60000 Application notes

Muxall
Muxall Pro BBQ Controller V3 user manual

SOMFY
SOMFY INIS UNO installation guide