PL-OM-CDL-07-1M-E
INSTALLATION,
OPERATION
&
MAINTENANCE
MANUAL
AIR COOLED CONDENSING UNITS
'CDL' SERIES
(R-22)
Contents Page
General information .................................................................................................................................. 2
Safety issues............................................................................................................................................ 2
Model decoding ....................................................................................................................................... 3
Physical data ......................................................................................................................................... 4-5
Electrical data........................................................................................................................................... 6
Dimensions.......................................................................................................................................... 7-11
Typical schematic wiring diagram...................................................................................................... 12-16
Field wiring connections ......................................................................................................................... 17
Controls & sequence of operation .......................................................................................................... 17
Rigging instructions ................................................................................................................................ 18
Installation clearance.............................................................................................................................. 19
Mounting location ................................................................................................................................... 20
Load distribution ..................................................................................................................................... 21
INSTALLATION INSTRUCTIONS
General................................................................................................................................................... 22
Location of unit ....................................................................................................................................... 22
Refrigerant piping connections ............................................................................................................... 22
Leak testing & refrigerant charging......................................................................................................... 23
Start-up inspection & check list ......................................................................................................... 23-24
Check-out & operational start-up procedure........................................................................................... 24
ELECTRICAL
Power supply.......................................................................................................................................... 25
Unbalanced voltage................................................................................................................................ 25
Motor contactor ...................................................................................................................................... 26
Fan motor............................................................................................................................................... 26
Crankcase heater ................................................................................................................................... 26
Lube oil protection control ................................................................................................................. 26-27
Voltage monitor ...................................................................................................................................... 27
REFRIGERATION
Compressor............................................................................................................................................ 28
High & low pressure protection.......................................................................................................... 29-30
Pump down control................................................................................................................................. 30
Trouble shooting chart....................................................................................................................... 31-33
Parts list ................................................................................................................................................. 34
Recommended spare parts .................................................................................................................... 35
Preventive maintenance schedule.......................................................................................................... 36
Material safety data sheet ...................................................................................................................... 37
Pressure temperature chart............................................................................................................... 38-39
INDEX
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
GENERAL STATEMENT
Cooline CDL series is designed and built for the optimum performance when matched with the right indoor unit (Refer to
indoor unit catalog). However, it is required that you become well acquainted with good practices for the proper installa-
tion, operation, and maintenance procedures in order to ensure a safe trouble free operation, year after year.
Most of the procedures described in this manual require certain skills and experience. Only highly skilled and experi-
enced technicians should perform the installation and other maintenance procedures.
SAFETY ISSUES
There are three levels of safety hazards that are identified throughout this manual as Warning (where the situation will
result in personal injury), Caution (where personal injury might occur), and Attention (where minor personal injury and/or
property damage could happen). Please understand and respect those identifications.
WARNING: These units operate on a high voltage with moving parts (at high speed) which can lead to
serious injuries and/or damage to the unit. Never attempt to service the unit unless the main electrical power
supply has been disconnected.
CAUTION: Extra care should be observed when installing, test running, adjusting, servicing, or maintaining
the unit as the hazard of explosion, fire, electrical shock, and potential personal injury and property damage
are present.
Whenperforming anytask pertainingto the installation andmaintenance of the unit, the skilled technician should observe
all the applicable safety measures (wear of safety helmet, boots, and goggles. Use of proper handling materials for
brazing and use of wet cloth for sequencing. A fire extinguisher should be easily accessible etc). He should also read all
the instructions and information in this manual prior to attempting to perform any installation or servicing of the unit.
All applicable local codes should be observed during installation and servicing.
3
1, 2 & 3
BASIC
4, 5 & 6
NOMINAL COOLING
CAPACITY (TONS)
8
REFRIGERATION
CIRCUIT TYPE
7
ELECTRICAL
SUPPLY (V-Ph-Hz)
9
ELECTRICAL KITS OPTION
CDL
COOLINE
CONDENSING
UNIT
020
025
030
035
040
050
055
065
080
100
110
135
160
195
S:DUAL SCROLL *
H:DUAL SEMI-HERMETIC
RECIPROCATING**
Q:QUADRUPLE SEMI-HERMETIC
RECIPROCATING***
L:DUAL SEMI-HERMETIC
RECIPROCATING WITH
UNLOADER**
(LEAD COMPRESSOR)
M:QUADRUPLE SEMI-HERMETIC
RECIPROCATING WITH
UNLOADER***
(LEAD COMPRESSOR)
A:STANDARD OPTIONS+
K:FAN CYCLING & ADJUST-
ABLE HIGH & LOW
PRESSURE SWITCHES
V:VOLT FREE CONTACTS****
C:COMPRESSOR CIRCUIT
BREAKER
P:PUMPDOWN SOLENOID
VALVE
B: K & V
COMBO
E: K & C
COMBO
G: K & P
COMBO
T: K, V & C
COMBO
M: K, V & P
COMBO
N: V, C & P COMBO
L: K, V, C & P COMBO
MODEL DECODING
L:380/415-3-50
(4 WIRE)
10
CONDENSER COIL
A:ALUMINUM FIN
B:COATED ALUMINUM FIN
C:COPPER FIN
D:ALUMINUM FIN WITH COIL
GUARD
E:COATED ALUMINUM FIN
WITH COIL GUARD
G:COPPER FIN WITH COIL
GUARD
A:STANDARD OPTIONS+
M:REPLACEABLE CORE FILTER DRIER &
SHUT-OFFVALVE
P:PRESSURE GAUGES (SUCTION &
DISCHARGE)
O:PRESSURE GAUGES (SUCTION,
DISCHARGE & OIL)++
H:HOT GAS BYPASS VALVE
R:
CONDENSER PRESSURE RELIEF VALVE
J: M & P
COMBO
K: M & O
COMBO
N: M & H
COMBO
Q: M & R
COMBO
S: M, H & R COMBO
T: M, H & P COMBO
U: M, H & O COMBO
V: A, H & R COMBO
F: A, H & P COMBO
G: A, H & O COMBO
L: A, H, P & R COMBO
B: M, H, O & R COMBO
11
MECHANICAL KITS OPTIONS
NOTES:*– Dual scroll compressors are available up to models CDL055 only.
** – Dual semi-hermetic compressors are available for models CDL065 - CDL100 only.
*** – Quadruple semi-hermetic compressors are available for models CDL110 - CDL195 only.
**** – A combination of volt free contact option: 1. Unit ON indication, 2. Compressor RUN/TRIP, 3. Unit trip indication.
+– Standard options (for models up to CDL065 only) contain sealed type filter drier, fixed low & high pressure switches.
Standard options (for models CDL080 - CDL195 only) contain replaceable filter drier, ball valve, sight glass, muffler and without spring isolator.
++ – Oil pressure gauge is applicable for semi-hermetic compressors only.
4
NOTE:
*Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures.
** Unit is factory supplied with holding charge only.
*** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping.
+Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.
++ Based on free field area at ARI conditions. Tolerance: ±2dBA.
+++ Values indicated are for standard unit with aluminum fin condenser coils.
MODEL NUMBER CDL020 CDL025 CDL030 CDL035 CDL040 CDL050 CDL055
NOMINAL CAPACITY , TONS*18.4 22.3 27.6 35.5 42.1 48.5 54.8
NUMBER OF REFRIGERATION CIRCUIT Dual Dual Dual Dual Dual Dual Dual
COMPRESSOR Type Scroll
Oil per system (liters) 3.25 3.25 4.14 4.67 5.91 6.3/5.91 6.3
Refrigerant** R-22
Charge per system (oz)*** 332 402 497 640 758 987/758 987
CONDENSERFAN Type Propeller
Qty. – Diameter (inch) 2 – 30 2 – 30 4 – 30 4 – 30 4 – 30 4 – 32 4 – 32
Nominal CFM 13000 13000 26000 26000 26000 42776 41376
Motor HP – RPM 1.5 – 950 1.5 – 950 1.5 – 950 1.5 – 950 1.5 – 950 2 – 920 2 – 920
CONDENSER COIL Type Inner grooved tubes and enhanced fins
Tube Dia–Rows–Fins per inch
3/8–3–14 3/8–4–14 3/8–2–14 3/8–3–14 3/8–4–14 3/8–3–14
Total face area (Sq. ft.) 32.9 32.9 59.5 59.5 59.5 75 75
HIGHPRESSURESWITCH
Open (PSIG) 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10
Close (PSIG) 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15
LOWPRESSURESWITCH
Open (PSIG) 25± 5 25± 5 25± 5 25± 5 25± 5 25± 5 25± 5
Close (PSIG) 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5
REFRIGERANT LINES+
Suction line size (OD), inch 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8
Liquid line size (OD), inch 5/8 5/8 5/8 7/8 7/8 7/8 7/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)
++
65.3/61.8/56.5 65.4/61.8/56.6 68.2/64.7/59.5 68.4/64.8/59.6 68.5/65/59.7 68.8/65.3/60 68.9/65.4/60.1
OPERATING WEIGHT, Kg.
+++
716 760 1050 1159 1328 1447 1480
PHYSICAL DATA
3/8–2–14
3/8–3–14
5
NOTE:
*Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures.
** Unit is factory supplied with holding charge only.
*** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping.
+Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.
++ Based on free field area at ARI conditions. Tolerance: ±2dBA.
+++ Values indicated are for standard unit with aluminum fin condenser coils.
MODEL NUMBER CDL065 CDL080 CDL100 CDL110 CDL135 CDL160 CDL195
NOMINAL CAPACITY , TONS*66.7 79.2 97.5 110.9 132.9 158.7 195.1
NUMBER OF REFRIGERATION CIRCUIT Dual Dual Dual Quadruple Quadruple Quadruple Quadruple
COMPRESSOR Type Semi-hermetic reciprocating
Oil per system (liters) 7.4 7.4 7.7 4.0 7.4 7.4 7.7
Refrigerant** R-22
Charge per system (oz)*** 1200 1426 1755 998 1196 1428 1756
CONDENSERFAN Type Propeller
Qty. – Diameter (inch) 4 – 32 6 – 32 6 – 32 6 – 32 8 – 32 10 – 32 12 – 32
Nominal CFM 41240 59400 59856 65736 81280 97620 119712
Motor HP – RPM 2 – 920 2 – 920 2 – 920 2 – 920 2 – 920 2 – 920 2 – 920
CONDENSER COIL Type Inner grooved tubes and enhanced fins
Tube Dia–Rows–Fins per inch
3/8–4–14 3/8–3–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–4–14
Total face area (Sq. ft.) 87.5 100 120 160 168 190 240
HIGHPRESSURESWITCH
Open (PSIG) 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10
Close (PSIG) 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15
LOWPRESSURESWITCH
Open (PSIG) 25± 5 25± 5 25± 5 25± 5 25± 5 25± 5 25± 5
Close (PSIG) 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5
REFRIGERANT LINES+
Suction line size
Dual 2-1/8 2-5/8 2-5/8 N.A. N.A. N.A. N.A.
(OD), inch Quadruple N.A. N.A. N.A. 1-5/8 2-1/8 2-1/8 2-5/8
Liquid line size Dual 7/8 1-1/8 1-1/8 N.A. N.A. N.A. N.A.
(OD), inch Quadruple N.A. N.A. N.A. 7/8 7/8 7/8 1-1/8
SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)
++
68.6/65/59.8 70.5/66.9/61.7 70.6/67/61.8 70.3/66.8/61.5 71.7/68/62.7 72.8/69.2/64 73.3/69.8/64.5
OPERATING WEIGHT, Kg.
+++
1857 2145 2495 3234 3500 3956 4820
PHYSICAL DATA
6
CDL020
CDL025
CDL030
CDL035
CDL040
CDL050
CDL055
CDL065
CDL080
CDL100
CDL110
CDL135
CDL160
CDL195
CRANKCASE HEATER
Volts
CB
(
Qty.
)
OUTPUT
POWER
LRA
(each)
FLA
(each)
Qty.
CB
Poles
LRA
(each)
RLA
(each)
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
MODEL
NUMBER
SUPPLY VOLTAGE COMPRESSOR CONDENSER FAN MOTORS
ELECTRICAL DATA
MOCPMCAMax.Min.
Nominal
(V-Ph-Hz)
342
342
342
342
342
342
342
342
342
342
342
342
342
342
457
457
457
457
457
457
457
457
457
457
457
457
457
457
Qty.
49.4 70 2 19.2 125 3 2 3.12 19 1.5 1 380 61 0.16
50.3 70 2 19.6 118 3 2 3.12 19 1.5 1 380 61 0.16
73.7 100 2 27.2 198 3 4 3.12 19 1.5 2 380 61 0.16
88.1 120 2 33.6 225 3 4 3.12 19 1.5 2 380 120 0.32
108.1 150 2 42.5 250 3 4 3.12 19 1.5 2 380 120 0.32
114.2 150 2 42.5/48.7 250/310 3 4 2.70 13.9 2.0 2 380 120 0.32
120.4 150 2 48.7 310 3 4 2.70 13.9 2.0 2 380 120 0.32
151.4 200 2 60.1 504 3 4 2.70 13.9 2.0 2 240 200 0.83
196.7 250 2 80.2 393 3 6 2.70 13.9 2.0 3 240 200 0.83
236.7 300 2 98.0 500 3 6 2.70 13.9 2.0 3 240 200 0.83
254.9 300 4 54.9 304 3 6 2.70 13.9 2.0 3 240 100 0.42
282.4 325 4 60.1 304 3 8 2.70 13.9 2.0 4 240 200 0.83
373.3 450 4 80.2 393 3 10 2.70 13.9 2.0 5 240 200 0.83
416.5 500 4 98.0 393 3 12 2.70 13.9 2.0 6 240 200 0.83
Total
Watts
Total
Amps
LEGEND:
MCA - Minimum Circuit Ampacity
MOCP - Maximum Over Current Protection
RLA - Rated Load Amps
LRA - Locked Rotor Amps
FLA - Full Load Amps
CB - Circuit Breaker
7
DIMENSIONS
NOTE: All dimensions are in mm.
CDL 020 & CDL 025
CDL 030, CDL 035 & CDL 040
8
DIMENSIONS
NOTE: All dimensions are in mm.
CDL 050 & CDL 055
CDL 065
9
DIMENSIONS
NOTE: All dimensions are in mm.
CDL 080 & CDL 100
CDL 110
MODEL H
CDL 080 1950
CDL 100 2253
DIMENSIONS
10
DIMENSIONS
NOTE: All dimensions are in mm.
CDL 135
CDL 160
11
DIMENSIONS
NOTE: All dimensions are in mm.
CDL 195
12
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS: CDL020 - CDL100
Power supply: 380/415V-3Ph-50Hz
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
T1A
T1B
COMP
1
T2A
T3A
COMP
2
T3B
T2B
DISCONNECT
SWITCH OR CB
(SEE NOTE-4)
TO FUSED
L2
L1
L3
LUG
HVTB
SHEET 2 OF 2 F OR
CONDENSER FAN MOTOR
POWER CONNECTIONS.
PLEASE REFER TO
Y2
STG2 COOLING
LED
POWER INDICATOR
J_PROG
FUSE
TRANS
12v-0-12v
240v
SEC PRI
LIVE
P3_##
DIP SWITCH
ON DIP
LED FAULT INDICATOR
LOCK2
SYSTEM2
LOCK1
SYSTEM1
(LP1)
(LP2)
LP2
23B
22B LPS2
P
(SSPS1)
(SSPS2)
24A
21A
HP1
(HP2)
LP1
(HP1)
HP2
27B
23A
22A
21B
27A
24B
OLR2-1
ON/OFF
(ON/OFF)
ECB
SQMBO4 ( P III ) W2
W1
Y2
OLR1-1
Y2
JP5 26A
JP3 25A
HPS2
LPS1
P
P
(OPS2)
JP6
JP4 25B 26B
P
HPS1
(OPS1)
4B
P2
TO ATB
NEUTRAL
OUTFAN1
OUTFAN2
X2 41B
HEATER2
INFAN
HEATER1
X1 41A
SEE VFC CONNECTION
(AT RIGHT)
TO
FR2
TO
FR1
11B1A
JP1
ATB
JP2
STG1 COOLING
( NOTE 7)
R
COMP1
COMP2
P1
G
Y1
C
4A
3B
3A
R
24Vac
JP
Y1
C
LVTB
CC2
CC1
R
C
Y1
ATB
PLEASE REFER TO FAN MOTOR
CONTROL CONNECTION, (SHEET 2 of 2)
G
W1
W2
Yellow
OFF blinking slow - LPS1 ckt fault
Orange
Set dip switch #3 according to unit's option
(pump down or no pump down)
note:
blinking slow - LPS2 ckt fault
blinking fast - HPS2 ckt fault
blinking fast - HPS1 ckt fault
system 2 fault diagnostic
ECB DIP SWITCH SETTINGS & LED INDICATORS
Green
on-board programming function (always set to on)
(Comp1&2 Auto Lead Lag)
DIP SWITCH #
FACTORY SETTINGS OF DIP SWITCHES
OFF= WITHOUT PUMP DOWN
ON
OFF=
S2
S4
S3
S3S1 S2 Red
S4
LOAD BALANCE
OFF=TEST MODE DISABLES1
system lock-out due to system fault
LED INDICATORS
power on/off indicator
system 1 fault diagnostic
ON= COMPRESSOR 1 LEAD
ON= WITH PUMP DOWN OPTION
ON= TEST MODE ENABLE
TO HVTB
L1
TO NTB
N
NTB
NEUTRAL
PDS1
PDS2
F1
OLR2OLR1
CC1 CC2
DIP SWITCH S 2 SHOULD ALWAYS BE SET TO "ON" POSITION.
COMP1 S HOULD ALWAYS BE LEAD COMPRESSOR.
HGS CONNECTION WITH COMP UNLOADER
AR9-1
HGS CONNECTION W/O COMP UNLOADER
AR9-1
AR9
NO
NC
5A
C
NOTE:
P
LPS5
6D
AR8-1
6E
LPS5
1NO
P
NC
C
Y2 [LVTB]
AR8-1
6E 6D
31B
Y1 [LVTB] 31A AR8
2
HGS
6C
HGS
6C 2
17A
17A C [LVTB]
13
LEGEND
AHU AIR HANDLING UNIT
AFS AIR FLOW SWITCH
AR AUXILIARY RELAY
ATB AUXILIARY TERMINAL BLOCK
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
CC COMPRESSOR CONTACTOR
CCA CC AUXILIARY CONTACT
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP/C
COMPRESSOR
ECB ELECTRONIC CONTROL BOARD
F FUSE
FCS FAN CYCLING SWITCH
FM FAN MOTOR (CONDENSER)
FMC FAN MOTOR CONTACTOR
FMCA FMC AUXILIARY CONTACT
FR FAULT RELAY
HC HEATER CONTACTOR
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
JP JUMPER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUGGROUND
NTB NEUTRAL TERMINAL BLOCK
OLR OVER LOAD RELAY
OPS OIL PRESSURE SWITCH
P PRESSURE
PDS PUMP DOWN SOLENOID
S DIP SWITCH (IN ECB)
SSPS SOLID STATE PROTECTION SYSTEM
TOP FM THERMAL OVERLOAD PROTECTION
TRANS TRANSFORER
UL COMP. UNLOADER SOLENOID
UVM UNDER VOLTAGE MONITOR
FIELD WIRING
TERMINAL BLOCK OR TERMINATION POINT
SPLICE-CLOSED END
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS: CDL020 - CDL100
NOTES
1. ANY WIRE REPLACEMENT SHOULD BE OF 900C
OR ITS EQUIVALENT.
2. USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASE
HEATER FOR MINIMUM OF 12 HOURS PRIOR TO
SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANK-
CASE HEATER MUST BE ON FOR 12 HOURS BE-
FORE OPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS
MAY RESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUIT
BREAKER TO BE PROVIDED BY CONSUMER
WITHRATINGAS RECOMMENDED BYCOOLINE.
5. COMPRESSORSARE PROVIDEDWITHSSPS ORINTER-
NALLINEBREAKTHERMALOVERLOAD PROTECTION.
6. IF PDS IS FACTORY INSTALLED, PLEASE READ
BROKEN LINES AS CONTINUOUS LINES.
7. USE SHIELDED TYPE CABLE, #18 AWG (MIN.)
FOR LVTB FIELD WIRING. GROUND CONNECT
AT BOTH ENDS.
8. COOLING OUTPUTSIGNAL FROM CONTROLLER
SHOULD FOLLOW THE SEQUENCE:
ON SEQUENCE - Y1 FIRST, THEN Y2.
OFF SEQUENCE - Y2 FIRST, THEN Y1.
9.
AT COMP. LOCKOUT CONDITION (FAULT), VOLTAGE
ACROSS TERMINAL X1, X2 OF ECB & ATB #2 IS 230VAC.
ALSO, COMP. LOCKOUT LIGHT (RED) OF ECB IS ON.
_ _ _
Power supply: 380/415V-3Ph-50Hz
(SEE NOTE-4)
SWITCH OR CB
DISCONNECT
TO FUSED L1
L2
L3
LUG
HVTB
T2B
T3B
T1B
T3A
T2A
T1A
COMP
1
COMP
2
OUTFAN1
PRI
OUTFAN2
NEUTRAL
LIVE
SEC
LED
COMP1
COMP2
INFAN
HEATER1
HEATER2
ON/OFF
(ON/OFF)
(LP2)
J_PROG
P3_##
ON DIP
SYSTEM2
LOCK2
SYSTEM1
LOCK1
(HP2)
(LP1)
LP2
LP1
(HP1)
HP2
HP1
W2
W1
G
Y2
Y1
C
R
X2
X1
P2
P1
FUSE
OLR1-1 HPS1
P
21A 25A24A JP3 26A
JP5
27A
DIP SWITCH
26B
27B
21B OLR2-1
25B
JP4
24B JP6
HPS2
P
LPS1
23A
22A
P
22B
23B P
LPS2
TRANS2
230v
12v-0-12v
R
C
Y1
Y2
LVTB
R
Y1
Y2
STG1 COOLING
STG2 COOLING
24Vac
FROM T'STAT CONTROLLER OR DDC
(by others)
CC1
CC2
JP1
ATB
1JP2
1A 1B
ATB
TO ATB
41B
41A
4B
4A
3A
3B
UVM CONNECTION
TO ATB
TO ATB 1A
1
L2L1
L1 L2
1
(REMOVE JP1)
L3
L3
8UVM
UVM-1
ECB1
LED FAULT INDICATOR
POWER INDICATOR
TO
FR2 FR1
TO
SEE VFC CONNECTION
SQMBO4 ( P III )
( NOTE 8)
SWITCHING CONTACTS
JP
( NOTE 9)
C
NEUTRAL
SEC PRI
230v
12v-0-12v
TRANS3
J_PROG
POWER INDICATOR
LED
DIP SWITCH
DIPON
SYSTEM2
FUSE
LIVE
SYSTEM1
P3_##
LED FAULT INDICATOR
LOCK1
LOCK2
ON= WITH PUMP DOWN OPTION
OFF= WITHOUT PUMP DOWN
S3
blinking fast - HPS2 ckt fault
blinking slow - LPS2 ckt fault
system 2 fault diagnostic
blinking fast - HPS1 ckt fault
blinking slow - LPS1 ckt fault
system 1 fault diagnostic
system lock-out due to system fault
power on/off indicator
LED INDICATORS
(pump down or no pump down)
Set dip switch #3 according to unit's option
on-board programming function (always set to on)
FACTORY SETTINGS OF DIP SWITCHES
ON
OFF
note:
DIP SWITCH #
S4
Yellow
Orange
S4S2S1 S3
Green
Red
ECB DIP SWITCH SETTINGS & LED INDICATORS
ON= COMPRESSOR 1 LEAD
ON= TEST MODE ENABLE
(Comp1&2 Auto Lead Lag)
OFF=TEST MODE DISABLES1
S2 OFF= LOAD BALANCE
25D
25C
27C
LP1
LP2
(LP2)
(LP1)
HP2
(HP2)
(HP1)
22C
22D
23D
23C
OLR4-1
27D
21D 24D JP8
SQMBO4 ( P III )
HP1
(ON/OFF)
ON/OFF
ECB2
Y2
W1
W2
Y1
G
OLR3-1
21C 24C JP7
JP
P
LPS4
P
P
LPS3
HPS4
JP10 26D
P
HPS3
26C
JP9
1
SEE VFC CONNECTION
OUTFAN2
OUTFAN1
HEATER2
X2
X1
41D
41C
HEATER1
INFAN
FR3FR4
TO TO
P1
P2
COMP2
4D
3D
4C
COMP1
R
3C
CC4
CC3
TO ATB
TB1
STG3 COOLING
STG4 COOLING Y4
Y3
Y3
Y4
15
17
31A
31B
YR3
YR4
31C
31D
YR3-1
YR4-1
15B
31C
31D
L2
C.HTR1
L1
(REMOVE JP3)
(REMOVE JP4)
COMP. SSPS CONNECTION
(REMOVE JP8)
(REMOVE JP7)
COMP. 2:
1
COMP. 4:
24D M1/11
L1/MP/L
SSPS4
1
COMP. 3:
24C M1/11
L1/MP/L
SSPS3
1
24B
L1/MP/L
M1/11
SSPS2
COMP. 1:
1
24A
L1/MP/L
M1/11
SSPS1
COMP. 3:
COMP. 4:
L2
L1
C.HTR4
C.HTR3
COMP. 2:
L2 C.HTR2
25D
M2/14
L2/R/N 2
25C
M2/14
L2/R/N 2
25B
L2/R/N
M2/14
2
25A
L2/R/N
M2/14
2
(NOTE 5)
L3
L2
L3
SCROLL COMP CRANKCASE HTR CONNECTION
COMP. 1:
COMP
3 4
COMP
T3C
T2C
T1C
T2D
T3D
T1D
NEUTRAL
NTB
TO HVTB
L1 N
TO NTB
PLEASE REFER TO
POWER CONNECTIONS.
CONDENSER FA N MOTOR
SHEET 2 & 3 OF 3 FOR
SEE FM CONNECTION
SEE FM CONNECTION
1
COMP
T1A
T3A
T2A
2
COMP
T2B
T1B
T3B
COMP
3
T3C
T2C
T1C
4
COMP
T2D
T3D
T1D
L1A
L3A
L2A
CB1
L1B
L2B
L3B
CB2
TO HVTB
L1
L1L1
TO HVTB
L1
L1 L1
L3C
L1C
L2C
CB3
L3D
L2D
L1D
CB4
TO HVTB
L1L1 L1
TO HVTB
L1L1L1
COMP WITH CB OPTIONS
CRANKCASE HTR CONNECTION(AS APPLICABLE)
A. SEMI-HERMETIC RECIP. COMP. (BITZER)
C.HTR2
C.HTR1
COMP. 2: 1
COMP. 1: 1
100B
100A
2
2
COMP. 3: 100C C.HTR3
12
COMP. 4: 100D C.HTR4
12
G
2
PDS4
PDS3
OLR4
CC4
PDS1
PDS2
CC1
OLR1 OLR2
CC2
OLR3
CC3
CC4A-1B
CC3A1B
OLR2
CC2
OLR1
CC1
CC1A-1B
CC2A-1B
OLR4
CC4
OLR3
CC3
(SSPS3) (OPS3)
(SSPS4) (OPS4)
(SSPS1) (OPS1)
(SSPS2) (OPS2)
PRESSURE SWITCH SETTINGS
HPS1 TO 4
LPS 9-12
LPS 5-8
FCS1 TO 4
NAME
LPS1 TO 4
360 ± 15450 ± 10
5565
55
190 ± 10
45
290 ± 15
25 ± 5
OPEN (PSIG)
50 ± 5
CLOSE (PSIG)
14
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS: CDL110 - CDL195
Power supply: 380/415V-3Ph-50Hz
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
10537B
11B
FCS2
1
P
1OB
REFER OPTIONAL FCS CONNECTION BELOW.
10A FCS1
P
**
T.O.P
FM3
11A
12C 13C FMC3
FM5
12E
12C
**
1
TO ECB1
OUTFAN 2
FM3
FMC3
T.O.P
13C 2
FMC5
13E
T.O.P
2
12A
TO ECB1
OUTFAN 1
FM1
FMC1
13A
T.O.P
2
36C
37C
35C
FM1
37A
36A
35A
FM3 FM2
36B
35B
FMC1
102
101
100
FMC3
103
104
CB6
L1 L2 L3 L2L1
REFER OPTIONAL FCS CONNECTION BELOW.
FCS4
111D
10D
P
2
10C
**
FCS3
P
11B T.O.P
FM3
12D 13D FMC4
2
FMC1
35C
FMC4
FM6
1
TO ECB2
OUTFAN 2
FM4
T.O.P
12D 13D
13F
T.O.P
12F FMC6
2
TO ECB2
OUTFAN 1
FM2
13B
T.O.P
12B 2
FMC2
2
12A
TO ECB1
OUTFAN 1 FM1
T.O.P
13A
35F
35D
36D
37D
FM4 FM5
37E
36E
35E
FMC4
FMC2
107
106
108
FMC5
FM6
37F
36F
FM1
35A
36A
37A
FMC6
FMC1
101
100
102
2
37C
36C
FM3
6-FAN MOTOR LAYOUT
CDL110
CONTROL
PANEL
CB7 CB8
L3 L1 L2 L3
CB6
L2L1 L3
CONTROL
PANEL
CDL135
8-FAN MOTOR LAYOUT
FMC5
103
35B
35C
37C
36C
FM1
36A
37A
35A
FM3
FMC1
101
102
100
FMC3
37D
35D
36D
FM4FM2
37B
36B
FM5
36E
37E
35E
FMC2
105
104
108
107
106
FMC4
FM8
35F
FM7
35G
36G
37G
FM6
36F
37F
35H
36H
109
FMC7
110
111
FMC6
37H
CB6
L2L1 L3
CB7
L2 L3L1 L2L1 L3
CONTROL
PANEL
CB8 CB9
L2 L3L1
CDL135
8-FAN MOTOR LAYOUT
TO ECB1
OUTFAN 2
TO ECB1
OUTFAN 1
FMC6
T.O.P
12F
FMC5
T.O.P
12E
T.O.P
10C FCS3
P
12G
11C
FM7
FMC7
13G 2
13E 2
FM8
T.O.P
10D FCS4
12H
11D
P
FMC8
13H 2
13F 2
OUTFAN 2
TO ECB2
TO ECB2
OUTFAN 1
13A
12A
T.O.P
10A 11A 12C
P
FM5
FCS1 FM3
FMC3
13C 2
2
T.O.P
FM1
FMC1 13B
12B
FM4
T.O.P
FM6
10B 12D
11B
P
FCS2
13D FMC4
2
2
FM2
T.O.P FMC2
L3L1 L2
CB7
L3L1 L2
CB8
L3L1 L2
CB9
FM2 FM4
36D
35D
37D
37B
36B
35B
FMC2
105
104
103
37E
35E
36E
FM5 FM7
35G
37G
36G
37F
36F
35F
FM6 FM8
35H
37H
36H
111
110
109
106
107
108
FMC3 FMC4
CONDENSER FAN MOTOR POWER, CONTROL CONNECTIONS : STANDARD AND FAN CYCLING OPTION (6FANS)
FM3
T.O.P
12C
12C
FM2
TO ECB2
T.O.P
12B
FM4
T.O.P
12D
13B 12D FMC2
2
OUTFAN 1
FM5
TO ECB1
OUTFAN 2 T.O.P
12E
FM7
T.O.P
12G
13E 12H FMC3
FM6
OUTFAN 2
TO ECB2
2
12F
T.O.P
FM8
T.O.P
12H
13F 12H FMC4
2
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS : WITH FAN CYCLING OPTION (8FANS)
FMC5A-1
FMC1A-1
FMC6A-1
FMC2A-1
FMC1A-1
FMC5A-1
FMC2A-1
FMC6A-1
PANEL
CONTROL
10-FAN MOTOR LAYOUT
CDL160
FMC8
35J
FM1
36A
35A
FM3
37C
37A
36C
35C
35B
FM2
37B
36B
101
100
FMC1
102
CB6
103
105
104
37H
35H
36H
35I
37I
36I
35D
FM4
37D
36D
FM7 FM9 FM8
108
FMC2
CB7
107
106
FMC4FMC3
CB8
111
110
109
CB9
L1 L2 L3 L3L2L1 L3L2L1 L3L2L1
36J
37J
FM10
FM10
FM8
OUTFAN 2
13H
12H
T.O.P T.O.P
12J 12J FMC4
2
13B
13A
13G
12G
OUTFAN 1
TO ECB2
TO ECB2
12B
T.O.P
FM2
TO ECB1
OUTFAN 1
OUTFAN 2
TO ECB1 FM7
T.O.P
12A
FM1
T.O.P
12I FMC3
12I
12D12D
T.O.P
FM4
FMC2
2
2
FM9
T.O.P
FM3
T.O.P
12C 12C FMC1
2
L3L1 L2
CB10
**
FMC8A-1
1FMC7A-1
13E
T.O.P
12E FMC5
21
FMC6
12F 13F 2
FMC2A-1 FM6
FMC1A-1 FM5
CONDENSER FAN MOTOR POWER, CONTROL CONNECTIONS : STANDARD OPTIONS(8FANS)
35E
36E
37E
FM5
FMC6
FM6
FMC6
112
113
114
35G
37G
36G
37F
36F
35F
REFER OPTIONAL FCS CONNECTION BELOW. REFER OPTIONAL FCS CONNECTION BELOW.
FCS3
FCS4
13E
T.O.P
10A
FCS2
FMC7A-1
11OB
12E
P11B
FCS1
FMC1A-1 11A FM5
FMC5
1
2FMC8A-110D
FMC2A-110C FMC6
12F 13F
P11D
P
2
11B FM6
T.O.P
P
(REMOVE JP9)
(REMOVE JP10)
OIL PRESSURE SWITCH CONN.(AS APPLICABLE)
OIL PRESSURE SWITCH CONN.(AS APPLICABLE)
COMP 2
25B
CC2A-1A
COMP 1
25A
1CC1A-1A
(REMOVE JP5)
(REMOVE JP6)
OPS2-1
2
28B OPS2
26B
2
240
OPS1-1
2
28A OPS1
26A
2
240
CC4A-1A
25C
COMP 4
OPS4-1
28D 2
CC3A-1A
25C
COMP 3 1
OPS3-1
28C 2
26D
240
OPS4 2
26D
240
OPS3 2
CONDENSER FAN MOTOR POWER, CONTROL CONNECTIONS : STANDARD AND FAN CYCLING OPTION (10FANS)
15
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS: CDL110 - CDL195
Power supply: 380/415V-3Ph-50Hz
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
61 63
60
COMP2 ON
COMP2 TRIP
INDIVIDUAL COMP. ON/OFF/TRIP
COMP 2
TO ECB1
X2
55
COMP 1
X1
TO ECB1
COMP1 ON
COMP1 TRIP
41B
FR2 2
56
41A
FR1
58
2
UNIT ON
43
1
45
AR1
UNIT TRIP
44A
UNIT TRIP
46
44
2
UNIT ON / OFF
UNIT STATUS (VFC) INDICATION CONNECTION
AR9-1
6D6E AR8-1
C
NC
P
1NO
LPS5
Y2 [LVTB] 31B AR9
HGS CONNECTION W/O COMP UNLOADER
Y1 [LVTB] 31A AR8
HGS 2
6C
17A
C [LVTB]
17A
X2
70
COMP4 ON
COMP4 TRIP
71
TO ECB2
COMP3 TRIP
41D
FR4
COMP3 ON
65 66
COMP 3
TO ECB2
X1 41C
FR3
73
2
68
2
COMP 4
44C44B
73B
72B
71B
73A
71A
72A
CONTROLS
TO ATB
230Vac
HTR1
HTR2
INFAN
(in cond. unit)
(in cond. unit)
TO ECB
30
29
14
HC2 28
AFS
BMC 19
BM CONTROL
STG1 COOLING
STG1 HEATER
STG2 HEATER
STG2 COOLING
( NOTE 8)
(REMOVE JUMPER JP)
Y1
W2
W1
Y2
R
C
G
TB1 (ECB)
Y1
W2
W1
Y2
24Vac R
C
G
LVTB
T3F
T2F
T1F
(Stg. 1 Heating)
T1H
T2H
T3H
(Stg. 2 Heating)
FROM T'STAT CONTROLLER OR DDC
(by others)
W2
W1
Y2
Y1
G
C
R
68
SWITCHING CONTACTS
69
70
OPTIONAL AHU INTER-CONNECTION
(POWER AND CONTROL FOR ELECTRIC HEATER &BLOWER MOTOR)
TO POWER SUPPLY
L1 L3L2
TO POWER SUPPLY
L2
L1 L3
TO POWER SUPPLY
L1C
L2C
L3C
L2L1 L3
YR3
Y4
Y3
STG3 COOLING
STG4 COOLING
YR3
Y3
Y4
LPS5
C
COMPRESSOR UNLOADER CONNECTION (OPTIONAL)
C
LPS6
COMP 2 TO ATB
28B 28B
COMP 1
TO ATB
28A 28A
PNC
6B
NC
P
NC
NO
C
LPS10
P
5B
NO
2
P
NOLPS9
C6A
5A
NO
NC
2
AR9-1
HGS CONNECTION WITH COMP UNLOADER
COMP1 SHOULD ALWAYS BE LEAD COMPRESSOR.
DIP SWITCH S2 SHOULD ALWAYS BE SET TO "ON" POSITION.
NC
P
NOTE:
6E
NO
LPS5
CAR8-1 6D 6C HGS 2
5A
LPS11 NO
C
LPS12
C
NC
NO
UL3 & UL 4 CONNECTION APPLICALBLE FOR COMP WITH 3 STEPS
P
CAPACITY UNLOADING.
NOTE
TO ATB
COMP 4 28D C
28B LPS8
P
NO
NC
6B
P
6C
NC
5B 2
NO
NC
TO ATB
28C
COMP 3
LPS7
P
28C C5C 2
UL3
UL7
UL8
UL4
UL1
UL2
UL6
UL5
FR1-1 FR3-1FR2-1 FR4-1
CC2A-2A
CC4A-2A
AR1-1A
FR3-2A
FR1-2A
FR2-2A
CC1A-2A
FR4-2A
CC3A-2A
OLR-1
HTR2HTR1
CB12
HC2HC1
CB11
BMC
OLR
CB
CONDENSER FAN MOTOR POWER, CONTROL CONNECTIONS : STANDARD AND FAN CYCLING OPTION (12FANS)
35I
112
FM1
36A
35A
37E
FM5
36E
35E
37A
37B
35B
36B
FM2 FM11
36K
35G
35F
36F
37F
FM6
35K
37G
36G
FM7
37H
36H
37K
35H
FM8 FM12
36L
35L
37L
FMC2
101
100
L1
CB7
CB6
FMC1
102
104
103
105
L3L2 L3L2L1
CB9
107
106
FMC5
108
L1 L3L2
CB9
110
109
111
FMC6
L3L1 L2
36J
35J
37I
36I
FM9
37J
FM10
CB10
FMC7
113
114
FMC8
13A 13G
12G
TO ECB1
OUTFAN 1 OUTFAN 2
TO ECB1 FM7
T.O.P
12A
FM1
T.O.P
12K FMC5
12K 2
FM11
T.O.P
FM5
T.O.P
12E 12E FMC1
2
12-FAN MOTOR LAYOUT
CDL195
CONTROL
PANEL
FM9
T.O.P
112I
FMC5A-1 13I FMC7
2
FMC1A-1
1
FMC3
T.O.P
12C 13C 2
FM3
35C
36C
37C
FM3
FMC3
CB8
L3L2L1
FMC4
FM4
37D
36D
35D
FM2
TO ECB2
12B
OUTFAN 1 T.O.P
12F
13B 12D
FM6
FMC2
12F
T.O.P
2FMC2A-1
1
TO ECB2FM4
FMC4
13D
T.O.P
2
OUTFAN 2
12H
T.O.P
FM12
13H
T.O.P
FM8
12L 12L FMC6
212J
FMC6A-1
113J
T.O.P
FM10
FMC8
2
115
116
117
REFER OPTIONAL FCS CONNECTION BELOW.
**
FMC1A-1
1
FM3
FMC3
13C
T.O.P
2
SEE FCS CONN BELOW
SEE FCS CONN BELOW
SEE FCS CONN BELOW
SEE FCS CONN BELOW
10A 11A
FCS1
P
12C
1
FMC2A-1
P
12D
FCS3
10B 11B 13D
T.O.P FMC4
2
FM4
10C
10D
1
1
FMC6A-1
FMC5A-1
12J
FCS4 11D
P
P
FMC8
13J
FM10
T.O.P
12I
FCS2 11C 13I
T.O.P
FM9
FMC7
2
2
16
TYPICAL SCHEMATIC WIRING DIAGRAM
MODELS: CDL110 - CDL195
Power supply: 380/415V-3Ph-50Hz
NOTES
1. ANY WIRE REPLACEMENT SHOULD BE OF 900C
OR ITS EQUIVALENT.
2. USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASE
HEATER FOR MINIMUM OF 12 HOURS PRIOR TO
SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANK-
CASE HEATER MUST BE ON FOR 12 HOURS BE-
FORE OPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS
MAY RESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUIT
BREAKER TO BE PROVIDED BY CONSUMER
WITHRATINGAS RECOMMENDED BYCOOLINE.
5
. COMPRESSOR MOTORS ARE PROVIDED WITH SSPS OR IN-
TERNAL LINE BREAK THERMAL OVERLOAD PROTECTION.
6.
USE DISCONNECT TAB OR SPLICE ONLY WHERE
EVERREQUIREDFOR EXTENSION OFORIGINALWIRE.
7. USESHIELDEDTYPE CABLE, #18 AWG(MIN.) FOR LVTB
FIELD WIRING. GROUND CONNECT AT BOTH ENDS.
8. COOLING OUTPUTSIGNAL FROM CONTROLLER
SHOULD FOLLOW THE SEQUENCE:
ON SEQUENCE - Y1 - Y2 - Y3 - Y4.
OFF SEQUENCE - Y4 - Y3 - Y2 - Y1.
9. AT COMP. LOCKOUT CONDITION (FAULT), VOLTAGE
ACROSS TERMINAL X1, X2 OF ECB & ATB #2 IS
230VAC. ALSO, COMP. LOCKOUT LIGHT (RED) IS ON.
+
LEGEND
AR AUXILIARY RELAY
ATB AUXILIARY TERMINAL BLOCK
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
CC COMPRESSOR CONTACTOR
CCA CC AUXILIARY CONTACT
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP/C
COMPRESSOR
DDC DIRECT DIGITAL CONTROLLER
ECB ELECTRONIC CONTROL BOARD
F FUSE
FCS FAN CYCLING SWITCH
FM FAN MOTOR (CONDENSER)
FMC FAN MOTOR CONTACTOR
FR FAULT RELAY
HGS HOT GAS BYPASS SOLENOID
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
JP JUMPER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUGGROUND
NTB NEUTRAL TERMINAL BLOCK
OLR OVER LOAD RELAY
P PRESSURE
PDS PUMP DOWN SOLENOID
SSPS SOLID STATE PROTECTION SYSTEM
TOP FM THERMAL OVERLOAD PROTECTION
TRANS TRANSFORER
T'STAT THERMOSTAT
VFC VOLT FREE CONTACT
YR COOLING RELAY
FIELD WIRING
TERMINAL BLOCK OR TERMINATION POINT
SPLICE-CLOSED END
JUNCTION OF WIRES, CONNECTED
CROSSING OF WIRES, NO CONNECTION
_ _ _
TYPICAL HIGH AND LOW VOLTAGE FIELD WIRING CONNECTIONS
17
CONTROLS AND SEQUENCE OF OPERATION
The unit is equipped with an electronic control board which can be linked with any commercially available 24V ac thermo-
stat or can be controlled through a DDC panel. With cooling input signals coming from a thermostat or DDC, the motors
in the equipment are started in the following sequential order: condenser fan – compressor motor. The cooling input
signals to the unit’s control board should always start first with the first stage (Y1) followed by the second stage (Y2) and
“OFF” sequence should start with the second stage (Y2) followed by the first stage (Y1).
Balance Loading of Compressors: The user can select the sequence of operation of the compressors; either com-
pressor 1 as always leading (dip switch #2 set at ON) or enabling balance loading of compressor (dip switch #2 set at
OFF). In balance loading function, the compressor with the least run time will be started first to equalize the run time of
the compressors. These functions are selectable through the dip switch on the electronic control board. Please refer to
the settings table shown in the unit’s wiring diagram.
Fault Diagnostics: In case of system fault, LED’s on the board emits a flashing signal indicating the nature or where the
fault is. This is to guide the service technician in identifying the fault. Please refer to the settings table shown in the unit’s
wiring diagram for the details of each respective fault against LED indicators.
Compressor Lock-Out Function: If any of the unit’s safety control devices trips and such condition is maintained for
approximately 3 minutes, the control will lock-out that particular system preventing a re-start. It can be re-set by shutting
off power to the thermostat or if the cooling signal to the board is turned OFF.
Compressor Anti-Recycling Timer: The unit’s electronic control board has a built-in three (3) minutes minimum off
timer for the compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling
through the thermostat due to load demand.
FROM T'STAT CONTROLLER OR DDC
SWITCHING CONTACTS
18
PROPER CLEARANCE TO BE PROVIDED
MUST BE 3" NOMINAL PIPE THROUGH UNIT FOR
MUST BE 3" NOMINAL PIPE THROUGH UNIT FOR
PROPER CLEARANCE TO BE PROVIDED
LIFT
ATTENTION TO RIGGERS
Hook rigging sling thru holes in base rail, as shown below.
Holes in base rail are centered around the unit center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging, to prevent the slings from damaging the unit.
CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.
RIGGING INSTRUCTIONS
MODELS: CDL020 - CDL025
MODELS: CDL030 - CDL040
MODELS: CDL050 - CDL195
19
WALL
INSTALLATION CLEARANCE
FIGURE - 2
CORNER WALL
NOTE: 1. All dimensions are in mm.
2. If unit is installed in special pit, please observe the same tolerance for walls. Pit height should not exceed
the unit height.
FIGURE - 1
STRAIGHT WALL
MODEL NUMBER A B C D E
CDL020 - CDL025 1500 1500 1500 1500 1500
CDL030 - CDL040 1500 1500 2000 1500 1500
CDL050 - CDL195 2000 2000 3000 2000 2000

This manual suits for next models

7

Other Zamil Air Conditioner manuals

Zamil PV036 Instruction manual

Zamil

Zamil PV036 Instruction manual

Zamil PDS Series Instruction manual

Zamil

Zamil PDS Series Instruction manual

Zamil PS036 Instruction manual

Zamil

Zamil PS036 Instruction manual

Zamil MAC-240 Instruction manual

Zamil

Zamil MAC-240 Instruction manual

Zamil CNX150 Instruction manual

Zamil

Zamil CNX150 Instruction manual

Zamil CX SERIES Instruction manual

Zamil

Zamil CX SERIES Instruction manual

Popular Air Conditioner manuals by other brands

Daikin EBHQ006BAV3 Operation manual

Daikin

Daikin EBHQ006BAV3 Operation manual

Soleus Air KC-15U owner's manual

Soleus Air

Soleus Air KC-15U owner's manual

Lloyd LS18HC user manual

Lloyd

Lloyd LS18HC user manual

Panasonic CS-E15NKE3 operating instructions

Panasonic

Panasonic CS-E15NKE3 operating instructions

Gree GWH18TC-K3DNA1B/I Service manual

Gree

Gree GWH18TC-K3DNA1B/I Service manual

Daikin FFQ09Q2VJU Operation manual

Daikin

Daikin FFQ09Q2VJU Operation manual

Haier HWF05XC3 user manual

Haier

Haier HWF05XC3 user manual

CH CH-PDH12AC1 owner's manual

CH

CH CH-PDH12AC1 owner's manual

Mitsubishi Electric MSZ-GE25VA operating instructions

Mitsubishi Electric

Mitsubishi Electric MSZ-GE25VA operating instructions

Fujitsu AUT12 operating manual

Fujitsu

Fujitsu AUT12 operating manual

Samsung AS09HM3N user manual

Samsung

Samsung AS09HM3N user manual

Toshiba RAC-PD0811CRU user manual

Toshiba

Toshiba RAC-PD0811CRU user manual

Daikin Super Multi Plus E-Series CTXG50EV1BW user manual

Daikin

Daikin Super Multi Plus E-Series CTXG50EV1BW user manual

Haier 2HUM14HC03-R2 installation manual

Haier

Haier 2HUM14HC03-R2 installation manual

OMAS Air-Fi AFT7 Installer and User Instruction Manual

OMAS

OMAS Air-Fi AFT7 Installer and User Instruction Manual

Friedrich CCW06B10B operating instructions

Friedrich

Friedrich CCW06B10B operating instructions

LG LP-F8081CL Service manual

LG

LG LP-F8081CL Service manual

York PCG4 Series installation manual

York

York PCG4 Series installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.