Zeta Alarm Systems ZT-20EX User manual


User Guide of ZT-20EX & ZT-500EX
3
<User Guide of ZT-20EX & ZT-500EX>
TABLE OF CONTENTS
<User Guide of ZT-20EX & ZT-500EX> .....................................................3
1Unpack & Checking contents ...............................................................4
2Internal Wire Cabling & DIP SW setting ................................................5
3Installation .......................................................................................7
4Operation .........................................................................................8
5Technical Specification ..................................................................... 14
LIST OF FIGURES
Figure 1. Product Contents & Outline Indication............................................................. 4
Figure 2. Removing the back cover.................................................................................. 5
Figure 3. Arranged for wire cabling ................................................................................. 5
Figure 4. Connecting Wires & Securing the cable gland.................................................. 6
Figure 5. Assembling & Combining the covers................................................................ 6
Figure 6. Swivel Mount (TM-AL10)................................................................................ 7
Figure 7. Swivel Mount (TM-ST10)................................................................................. 7
Figure 8. Installed Detectors on wall................................................................................ 7
Figure 9. Typical 4-Wiring for Relay Contact Output.................................................... 11
Figure 10. 4-20mA Output Jumper Placement............................................................... 12
Figure 11. 4-20mA Source and Sink............................................................................... 13
Figure 12. RS-485 Networking....................................................................................... 14
LIST OF TABLES
Table 1. Output Signals/LED Indications versus Detector State ............................. 8
Table 2. DIP Switch Settings......................................................................................... 9
Table 3. Output Interface of Connection PCB........................................................... 10

47-153 / 47-154 , Rev. A, Aug 15, 2019
4
1 Unpack & Checking contents
-Unpack the delivered pack and check the following contents.
Figure 1. Product Contents & Outline Indication
Detector
Ex Cable Gland
(*Optional)
2-meter Cable Wires
(*Optional)
Swivel
Mount
Screws for
Swivel Mount
Label
for wiring colors
Coupler
(*Optional)
Quick Start Guide
/Other Notes
Bracket
Mounting
Knob

User Guide of ZT-20EX & ZT-500EX
5
2 Internal Wire Cabling & DIP SW setting
1). Loose the 3(three) socket-head cap screws of back cover and separate the back cover
from the middle cover, as follows.
At this time, the internal connection harness (connecting the internal circuit boards)
may be inevitably removed.
Figure 2. Removing the back cover
Figure 3. Arranged for wire cabling
2). If you need to change the sensitivity & any other user selectable settings,
change it, refering to Table 2. DIP Switch Setting.
3). Connect(plug) the external cable wires into the relevant positions of terminal block on
the connection PCB ,referring to the wiring configuration, as shown in Table 3.
(Output Interface of Connection PCB).
4). After completion of internal wires connection, make sure to secure tightly the relevant
Ex-proof cable gland into the Back Cover for ultimate water proof.
DIP Switch (in 8 positions)
*Adjustable as required.
Connection Harness
ositions)

47-153 / 47-154 , Rev. A, Aug 15, 2019
6
Figure 4. Connecting Wires & Securing the cable gland
5). Plug the end of removed connection harness first into the relevant connector on PCB of
middle cover and then, into the relevant connector on PCB of back cover.
6). Pull the back cover into middle cover to combine these both covers
*Make sure to SECURELY plug each ends of connection harness to each connectors
inside both covers. If not securely done, both PCBs would be disconnected.
Figure 5. Assembling & Combining the covers
7). Screw up the 3(three) socket-head cap screws of back cover to combine the back
cover with the middle cover.
Make sure that this screwing-up be done SECURELY and, otherwise, the detector may
fail to meet the waterproof.
Secure tightly for
water-proof
(*Optional)
Connection Harness
positions)
Middle Cover
Back Cover
Secure tightly the
3 fasteners for
water-proof

User Guide of ZT-20EX & ZT-500EX
7
3 Installation
The detector can be mounted on the wall with either of two kinds of Swivel
Mounts, (TM-AL10 in aluminum and TM-ST10 in SS316) which are optionally
selectable by customers when ordering the detector.
Figure 6. Swivel Mount (TM-AL10)
Figure 7. Swivel Mount (TM-ST10)
Figure 8. Installed Detectors on wall
1). Place the Swivel Mount in its designated location on the wall and secure it with the
provided four (4) fasteners through four (4) holes of dia. 5.0 or 6.0mm.
2). Put the mounting pole of detector into the mounting hole of Swivel Mount and
secure the detector by screwing the locking screws on Swivel Mount.
3). Release the locking screws on Swivel Mount in such a way that allows rotating the
Detector which is combined the mounting hole of Swivel Mount.
Point the detector towards the protected area and make certain that the view of

47-153 / 47-154 , Rev. A, Aug 15, 2019
8
the area is unobstructed. Secure the detector in that position by tightening the
locking screws on the Swivel mount.
The detector is now correctly located, aligned and ready to be connected to the system.
4 Operation
Once powered up, the detector will begin appr. 20 sec start-up routine.
During this time, all three (3) LED indicators will be blinking.
Once the start-up procedure has finished and no faults are present, the detector will
begin Normal operation (Green LED will remain on).
Table 1. Output Signals/LED Indications versus Detector State
Detector Status
Green
LED
(Power)
Red LED
(Alarm)
Yellow
LED
(Fault)
4-20mA
Output
Power up –20 second start
delay
Blinking
2 mA
Internal Power Fault or system
power out of range / Fault
Off
Off
Blinking
0 mA
Normal Operation
Solid
Off
Off
4 mA
Fire Detection(Warning)
Off
Solid
Off
16 mA
Fire confirmed
All LEDs blinking simultaneously
20 mA

User Guide of ZT-20EX & ZT-500EX
9
Table 2. DIP Switch Settings
Notes:
(1). The detector offers four (4) sensitivity settings. The settings refer to the n-Heptane
fire of 1ft-sq.
(2). When an Alarm (Detection) level condition is encountered, the detector delays the
execution of the Alarm output relay by the specified period of time. The detector will
then, additionally, evaluate the fire condition during the specified Alarm Delay Time.
If the Alarm level is still present, the Alarm outputs will be activated. If this condition
no longer exists, the detector will return to its standby state. The LED will indicate
warning level during the delay time only if the fire condition exists.
(3). The detector has a selectable latched alarm output capability, which operates
according to the selectable function. If selected, upon the detection of a fire, the
detection signal is latched until manually reset (disconnecting the power supply or
DIP Switch Position No.
Mode Selections
1
2
3
4
5
6
7
8
Sensitivity Range (1)
OFF-OFF(00) : Highest
OFF-ON(01) : High
ON-OFF(10) : Medium<default>
ON-ON(11) : Low
Alarm Delay Time (2)
OFF-OFF(00) : 1 sec
OFF-ON(01) : 3 sec
ON-OFF : 5 sec
ON-ON : 7 sec<default>
Alarm Latch Setting (3)
OFF(0) : 20 sec<default>
ON(1) : until reset
Reserved (for design setting)
OFF(0) : <default>
Reserved (for design setting)
ON(1) : <default>
Alarm Relay Setting (4)
OFF(0) : N.O<default>
ON(1) : N.C
1 2 3 4 5 6 7 8
:ON “(1)”
:OFF ”(0)”
ON
(OFF)

47-153 / 47-154 , Rev. A, Aug 15, 2019
10
performing a manual BIT). Latching affects the ALARM RELAY, 4-20mA output, the
ALARM LED.
(4). The detector has a selectable option over alarm relay initialization between normally
open, N.O. (as Default) and normally closed, N.C.
Table 3. Output Interface of Connection PCB

User Guide of ZT-20EX & ZT-500EX
11
Figure 9. Typical 4-Wiring for Relay Contact Output
Notes: 1. ( ) denotes an example of optional colour wirings.
Power Supply
DC24V(+)
Return(-)
Alarm(N.O/N.C)
COM
Alarm(N.O/N.C)
COM
Control Panel
1
2
1
2
J4
J1
1
2
1
2
J4
J1
1
2
1
2
J4
J1
1st Detector
2nd Detector
Last Detector
EQL
(ex:10 ㏀)
EQL Box
(YELLOW)
(BLUE)
(WHITE/YELLOW)
(GREEN/BLUE)
(RED)
(BLACK)
(RED)
(BLACK)
(WHITE
/YELLOW)
(GREEN
/BLUE)

47-153 / 47-154 , Rev. A, Aug 15, 2019
12
Figure 10. 4-20mA Output Jumper Placement

User Guide of ZT-20EX & ZT-500EX
13
Note the INT and ISO Jumper position for each configuration.
Figure 11. 4-20mA Source and Sink
Detector
+VDC
ISO
4-20mA
I
S
O
-VDC
I
N
T
Panel
24VDC(+)
24VDC(-)
4-20mA
○
A
24VDC
+-
Detector Non-Isolated configuration(Source)
Detector
+VDC
ISO
4-20mA
I
S
O
-VDC
I
N
T
Panel
24VDC(+)
24VDC(-)
4-20mA
○
A
24VDC
+-
Detector Non-Isolated configuration(Sink)
Detector
VDC(+)
ISO
4-20mA
I
S
O
VDC(-)
I
N
T
Panel
24VDC(+)
24VDC(-)
4-20mA
○
A
24VDC
+-
Detector Isolated configuration(Source)
24VDC
-+
Detector
VDC(+)
ISO
4-20mA
I
S
O
VDC(-)
I
N
T
Panel
24VDC(+)
24VDC(-)
4-20mA
○
A
24VDC
+ -
Detector Isolated configuration(Sink)
24VDC
-+

47-153 / 47-154 , Rev. A, Aug 15, 2019
14
Figure 12. RS-485 Networking
5 Technical Specification
ZT-20EX (UV/IR)
ZT-500EX (IR3)
GENERAL SPECIFICATION
Spectrum Response
UV/IR (Dual Bands)
Triple IR bands
Detection Range
Fuel Distance
n-Heptane 30m
Gasoline 30m
Diesel 20m
LPG* 20m
Ethanol 20m
IPA 25m
Methane** 20m
*0.5m-high/0.2m-wide
plume fire
**30”plume fire
Fuel Distance
n-Heptane 65m
Gasoline 65m
Diesel 45m
LPG* 30m
Ethanol 40m
IPA 40m
Methane** 35m
*0.5m-high/0.2m-wide
plume fire
**30”plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
1/3/5/7 seconds
Sensitivity Range
4(four) ranges
Field of View
Horizontal 90°, Vertical 90°
Temperature Range
Operation/Storage: -40℃to 75℃
Humidity
Up to 95% non-condensing
ELECTRICAL SPECIFICATION
Operating Voltage
24VDC nominal (18-32VDC)
Power Consumption
Standby: max.65mA , Alarm: max.80mA
Cable Entry
1 x M20 (ISO)
Wiring
AWG 16-26 (Str 1.5mm2 to 0.13mm2)
Electromagnetic Compatibility
EMI/RFI protected to EN61000 series
OUTPUTS
Relays
Alarm(N.O/ N.C selectable), Fault(N.C)
Power Supply
DC24V(+)
Return(-)
RS485
COMPUTER
PORT
Control Panel
1
2
7
8
J4
J1
1
2
7
8
J4
J1
1st Detector
Last Detector

User Guide of ZT-20EX & ZT-500EX
15
SPST volt-free contacts rated 5A at 30VDC or 250VAC
0-20mA (stepped)
Source & Sink, Isolated/Non-isolated configuration
Fault: 0 +1mA
Normal:4mA±10% Warning: 16mA±5%
Alarm: 20mA±5% Resistance Loop : max. 500Ω
RS-485 <optional>
RS-485 Modbus compatible communication link that
can be used in computer controlled installations
MECHANICAL SPECIFICATIONS
Materials
- Heavy duty copper free aluminium with bright grey
- Stainless Steel 316L
Mounting Bracket
<Optional>
- Heavy duty copper free aluminium with bright grey
- Stainless Steel 316L
Dimensions
Detector: 83(D) x 126(L) mm
Weight
Detector (aluminium): 1.0 kg
Detector (ST 316L): 2.7kg
Mounting Bracket (aluminium/ St.): 0.3kg / 0.7kg
APPROVALS
Hazardous Area
ATEX Ex II 2 G, Exd IIC T6, -40℃to +75℃
Performance
- Designed to meet FM3260/EN-54-10
- KFI(for Korea) approved
For additional details or assistance, please contact:
Zeta Alarms Limited
Detection House, 72-78 Morfa Road, Swansea, SA1 2EN, United Kingdom
Phone: +44(0)1792 455175 Fax: +44(0)1792 455176
Website: www.zetaalarmsystems.com Email: info@zetaalarmsystems.com
This manual suits for next models
1
Table of contents
Popular Security Sensor manuals by other brands

Ksenia
Ksenia micro poli installation guide

ADEMCO
ADEMCO 4275EX-SN installation instructions

EXTOL PREMIUM
EXTOL PREMIUM 8831321 Translation of the original user manual

Wenglor
Wenglor Y1TA Series operating instructions

Kistler
Kistler 2629DK instruction manual

Zhuhai Taichuan Cloud Technology
Zhuhai Taichuan Cloud Technology TC-U9AF-SJ/Z installation instructions