Zksoftware C3-100 Instruction Manual

Key hole
Thread hole
Thread hole
3.Get through the thread hole
Get through the thread hole Fixed case
12
4.LED indicators, Wires, Auxiliary Input and Output
Appearance of case
Notes:
C3- 1 0 0 Installation Instructions and Connection Guide
1.Cautions
Please note the following cautions.Mis-operation may lead to personal injury or equipment failure:
1) Do not energize the system before installation is complete; never carry out installation activities when
Vision: 1.0.1 Date:Oct. 2010
2) All peripheral devices must be grounded.
3) It is preferred that all wires run through PVC or galvanized pipes.
5) It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m above ground.
6) It is recommended to use the power supply in case for control panel, and external power supply for each
4) It is strongly recommended that the length of exposed part of any connection cable should not be longer
Professional clamping tools may be used to avoid unintentional contact of exposed wires to than 4 mm.
the system is energized.
short-circuit or communication failure. avoid
Description of normal working state:
Connect the system to the power supply.If the system works properly,the POWER indicator(red) is lit
constantly and the RUN indicator(green) flashes.
Heat
dissipation
hole
2.Components
Power supply
Backup battery Control panel
1)Meaning of LED indicators:
LINK indicator(green): always(green) indicates TCP/IP
ACT indicator(yellow):its flashing indicates data is in transmitting
TX indicator(yellow):its flashing indicates it is sending data through
RX indicator(green):its flashing indicates it is receiving data through
Auxiliary output indicator(green):always(green) indicates it is in use.
Lock indicator(green):always(green) indicates lock is open.
POWER indicator(red): always(red) indicates control panel is power
RUN indicator(green):its flashing indicates the system works normally.
CARD indicator(yellow):its flashing indicates card is punched on reader.
A Use 2-conducotor power cord
2)Recommended use of wires:
3)The auxiliary input may be connnected to infrared body detectors,
4)The auxiliary output may be connected to door bells,alarms,etc.
B Use 6-conductor wire between wiegand reader and control panal
C Use 4-conducotor lock power cord (RVV 4*0.75mm)
D Use 2-conducotor switch power cord(RVV 2*0.5mm)
communication is proper;
on.
alam switches,etc.
Ethernet interface
Dip switch
RS485 interface
Auxiliary output1
Door1
Power of lock
Power of control panel
A
A
C
DD
B
B
{
{
{
{
{
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD card
Advanced Access Control
lock.
through TCP/IP communication.
RS485 communication.
RS485 communication.
(RVVP 6*0.5mm) (To choose the proper cord according to the
interface you connect, such as 6,8,10 cord.)
1# Door Button
1# Door
wiegand reader
1# Door
wiegand reader

BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
1 2 3 4
1 2 3 4
ON
ON
5 6 7 8
5 6 7 8
Diagram of places of DIP switch.
1
2
4
8
16
32
Restore
factory setting.
RS485
terminal
resistance.
figure( 5-1)
Set RS485 address through DIP switch:
1)Internationally accepted RVSP(shielded twisted-pair) wires should be used for communication to effectively avoid interference.
RS485 communication wires should be connected by means
of bus cascade connection.
2.RS485 Communication
1.TCP/IP Communication
The background PC software is able to communicate with the system according to two protocols(RS485 and TCP/IP) for data
exchange and remote management. The communication cable should be away from high-voltage lines as far as possible. Do
not keep the communication cable in parallel with power cords or bind them together.
3)One RS485 BUS may hold 63 units of control panel, but it is not recommended to connect with more than 32 units.
access control panels.
7.Equipment communication
5.RS485 address setting, Restore factory setting, Terminal resistance setting
NO Lock
NC Lock
+
+
+
-
-
Lock power
input
Enlarged diagram
of lock ports
NC
NO
GND
COM
SEN
Diode
Diode
LOCK
LOCK
+
+
-
-
FR10 7
FR10 7
6.Connection of lock
“Wet mode” wiring diagram of lock connecting with external power supply.
-
LED
1
2
3
4
5
Jumper
terminal
Factory
default
wet mode
1 2 3 4 5 6 7 8
ON
Notes:
4)When the bus is longer than 300m, to enhance the stability of communication, it is necessary to keep place 8 of DIP
2)Considering stability of communication, it is recommended the length of RS485 bus is less than 600m
As shown in the figure above, place 8 of the DIP switches of units 1# and 8# is placed at "ON " status.
P C
Switch
DIP switch
1 2 3 4
ON
5 6 7 8
1# control panel 2# control panel 8# control panel
485+
485-
GND
4 85
Converter
485+ 485+ 485+
485- 485- 48 5-
GND GND GND
serial line
P C
3) When the Electrical Lock is connected to the Access Control System, you need to parallel one FR107
in the package) to prevent the self-inductance EMF affecting the system, do not reverse diode (equipped
the polarities.
1# control panel 2# control panel n# control panel
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
BUTTON1READER1READER2
+12V
+12V
GND
GND
WD1
WD1
WD0
WD0
GLED
GLED
BEEP
BEEP
IN
GND
ACT
LINK
1
TX
RX
V+
POWER
PC
NC
COM
NO
COM
NO
NC
LOCK1
GND
SEN
V-
GND
485-
485+
AUXOUT1LOCK
GND
+12V
1 2 3 4
ON
5 6 7 8
1
POWER
CARD
RUN
LAN
SD卡
Advanced Access Control
1) Place 1-6 on DIP switch are for setting the number of control panel when communicating through
RS485, it is adopted for binary coding, and little endian, the address represented by place 1-6 are
shown as figurue(5-1).
2) Before setting the address, please keep the system is power off, Jump place 1-6 to desired status,
and the address number shall not be the same as another one in the network. For example: to set the
device number as 39 (39=1+2+4+32), the corresponding RS485 code is 111001, then Jump place 1,
2,3 and 6 at “ON” status.
3) Place 7 is for restoring factory default settings, Jump it for three times within 10 seconds and restart
the system, then all information in RAM of control panel will be cleared and the system restores factory
default settings.
4) Place 8 is for setting terminal resistance when communicating through RS485. Jump it at “ON” status,
then it is equivalent to have a terminal resistance of 120 ohm between 485+ and 485-.
1) Control panel provides lock control output interfaces. For NO lock ,it is open when power is on, and
closed when power is off, so “COM and NO” interfaces should be used; For NC lock, it is open when
power is off, and closed when power is on, so COM and NC” interfaces should be used.
2) Control panel supports “dry mode” and “wet mode” by setting the jumper, it is “wet mode” when
connecting “V+ V-” Input interfaces to supply power for locks, please shorten 2-3 and 4-5. Equipment
factory default setting is dry mode. For setting “dry mode” and “wet mode”, please refer to <<C3-100/
200/400 access control panel installation instructions>>.
switches of the first and the last control panel at “ON” status.
Other Zksoftware Controllers manuals
Popular Controllers manuals by other brands

GE
GE EntelliPro ES Series Installation and instruction manual

Conrad
Conrad 75 02 01 operating instructions

I2R Tech Lighting Solutions
I2R Tech Lighting Solutions Moving Head Controller 2.0 user manual

Shimaden
Shimaden SR23 series quick reference

SMC Networks
SMC Networks LEFS 16 Installation and maintenance manual

Flowserve
Flowserve Valtek VR User instructions

Evco
Evco EVJ254 manual

Solcon
Solcon RVS-BX Series instruction manual

Atlas Copco
Atlas Copco POWER FOCUS 6000 Configuration manual

RC4 Wireless
RC4 Wireless LumenDim4 quick start guide

Trane
Trane TCONTCCMHCM04A Installation and operation manual

Agilent Technologies
Agilent Technologies W2642A quick start guide