The model II of this series provides 5-Pin
5.08mm pitch terminal blocks. The serial
port is isolated and its pin definitions are
as follows:
PIN 1 2 3 4 5.
RS-485 D+ D- GND — —
RS-422 T+ T- GND R+ R-
【Checking LED Indicator】
The device provides LED indicators to monitor the device
working status with a comprehensive simplified
troubleshooting; the function of each LED is described in the
table as below:
LED Indicate Description
PWR
ON PWR is connected and running
normally
OFF PWR is disconnected and running
abnormally
RUN
Blinking System runs normally
OFF The system is not running or running
ON System is running abnormally
LINK
(1-2)
ON Copper port has established an
active network connection.
Blinking Copper port is in a network activity
state.
OFF Copper port has not established an
active network connection.
TX(1-4)
OFF
No data or abnormal data is being
transmitted through serial port.
Blinking Serial port is transmitting data.
RX(1-4)
OFF
Serial port is not receiving data or
receiving data abnormally
Blinking Serial port is receiving data.
Logging in to WEB Interface
This device supports WEB management and configuration.
Computer can access the device via Ethernet interface. The
way of logging in to device’s configuration interface via IE
browser is shown as below:
Step 1 Configure the IP addresses of computer and the
device to the same network segment(The network
segment of Network Port 1 is 1, and the network
segment of network port 2 is 8), and the network
between them can be mutually accessed.
Step 2 Enter device’s IP address in the address bar of the
computer browser.
Network Port 1:
Network Port 2:
Step 3 Enter device’s username and password in the login
window as shown below.
Step 4 Click “OK” button to login to the WEB interface of
the device.
Notes:
The default IP address of the device network port 1 is
“192.168.1.254”, port 2 is “192.168.8.254”.
The default username and password of the device are
“admin”.
If the username or password is lost, user can restore it to
factory settings via device DIP switch or management
software; all modified configurations will be cleared
after restoring to factory settings, so please backup
configuration file in advance.
Please refer to user manual for specific configuration
method of logging in to WEB interface and other
configurations about network management function.
【Specification】
Panel
100M Copper Port 10/100Base-T(X) self-adapting RJ45
port
Serial Port 3IN1 RJ45 interface or RS-485/422
terminal block with isolation
Indicator
Power indicator, Running indicator,
Copper port connection indicator,
Serial port transmission and
receiving data indicator
Power supply
Input power supply 12~48VDC
block
3-pin 5.08mm pitch terminal blocks
Power
consumption
Model I No-load: 2.16W@12VDC
Full-load: 3.00W@12VDC
Model II No-load: 2.94W@12VDC
Full-load: 2.94W@12VDC
Working
environment
Working
temperature
-40~75℃
Working humidity 5%~95% (no condensation)
Protection grade IP30(metal)