AAON Auto-Zone 2 GPC-XP User guide

WSHP Loop Control
Using The
GPC-XP Controller
Application Guide
www.az2controls.com

Table of Contents
WattMaster Controls, Inc.
8500 NW River Park Drive, Parkville, MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101
E-mail: mail@wattmaster.com
GPC-XP Controller............................................................................................................................................ 3
Overview ......................................................................................................................................................................................3
Features .......................................................................................................................................................................................3
Water Source Heat Pump System Operation .................................................................................................. 4
Water Source Heat Pump Unit .....................................................................................................................................................4
Water Source Heat Pump System ...............................................................................................................................................5
Operation Of The WSHP Loop Controller ........................................................................................................ 6
Overview ......................................................................................................................................................................................6
Typical Sequence .........................................................................................................................................................................6
Pump On/Off -Control...................................................................................................................................................................6
Pump VFD Control .......................................................................................................................................................................6
WSHP Unit Compressor Enable ..................................................................................................................................................7
Heat Rejection..............................................................................................................................................................................7
Heat Addition................................................................................................................................................................................7
Emergency Shutdown ..................................................................................................................................................................7
Controller, Sensors & Related Hardware........................................................................................................ 8
Optional Communication Devices and Software ............................................................................................ 9
Communication, Baud Rate Settings & Wiring Info...................................................................................... 10
System Settings .........................................................................................................................................................................10
Important Wiring Considerations................................................................................................................................................10
Environmental Requirements.....................................................................................................................................................10
Mounting.....................................................................................................................................................................................10
Power Supply .............................................................................................................................................................................10
Communication, Baud Rate Settings & Wiring Info...................................................................................... 11
Input Wiring.................................................................................................................................................... 12
Output Wiring ................................................................................................................................................. 13
Conguring The Controller ............................................................................................................................ 14
General .....................................................................................................................................................................................14
Status Screen ...........................................................................................................................................................................14
Analog Input #1 ..........................................................................................................................................................................15
Analog Input #2 ..........................................................................................................................................................................17
Analog Input #3 ..........................................................................................................................................................................17
Analog Input #4 ..........................................................................................................................................................................17
Analog Input #5 ..........................................................................................................................................................................19
Analog Input #6 ..........................................................................................................................................................................19
Analog Input #7 ..........................................................................................................................................................................19
Analog Input #8 ..........................................................................................................................................................................19
Binary Input #1 ...........................................................................................................................................................................21
Binary Input #2 ...........................................................................................................................................................................21
Binary Input #3 ...........................................................................................................................................................................21
Binary Input #4 ...........................................................................................................................................................................23
Binary Input #5 ...........................................................................................................................................................................23
Binary Input #6 ...........................................................................................................................................................................23
Binary Input #7 ...........................................................................................................................................................................25
Binary Input #8 ...........................................................................................................................................................................25
Relay Output #1 .........................................................................................................................................................................25
Relay Output #2 .........................................................................................................................................................................27
Relay Output #3 .........................................................................................................................................................................27
Relay Output #4 .........................................................................................................................................................................29
Relay Output #5 .........................................................................................................................................................................29
Relay Output #6 .........................................................................................................................................................................31
Relay Output #7 .........................................................................................................................................................................31
Relay Output #8 .........................................................................................................................................................................33
Analog Output #1 .......................................................................................................................................................................33
Analog Output #2 .......................................................................................................................................................................35
Analog Output #3 .......................................................................................................................................................................35
Analog Output #4 .......................................................................................................................................................................36
Visit our web site at www.az2controls.com
Form: AZ2-WSLC-AGD-01B Copyright 2017 WattMaster Controls, Inc.
WattMaster Controls, Inc. assumes no responsibility for errors or omissions.
This document is subject to change without notice.
Table Of Contents
2WSHP Loop Controller GPC-XP Guide

Overview
General
The GPC-XP is a software driven, multi-function controller which can
be congured to a variety of applications from simple on/off time clock
control to more complex sequences involving multiple input and outputs
control based on basic logic functions.
The purpose of this guide is to illustrate the GPC-XP capability for Water
Source Heat Pump Central Plant control applications.
GPC-XP Used As A WSHP Loop Controller
The GPC-XP Controller can be congured to control the central water
loop for individual water source heat pumps installed in a typical water
source heat pump system. See Figure 2 for a general layout of a typical
Water Source Heat Pump system.
The GPC-XP can operate stand-alone or be used with the Auto-Zone
2 (AZ 2) Control System to utilize the transfer of commonly shared
information such as outside air temperature and proof of water ow
over a communication network.
The main purpose of the GPC-XP controller, when used as a Water
Source Heat Pump Loop Controller, is to provide water ow in the sys-
tem when needed. It also maintains the proper loop water temperature
required at any given time by monitoring either the Loop Return Water
Temperature or the Loop Supply Water Temperature. The settings should
typically be congured to supply between approximately 60° F to 90° F
water temperatures to the installed water source heat pumps. Generally
any loop water temperature below 60° F would require heat addition
(hot water boiler) and any loop water temperature above 90° F would
require heat rejection (closed circuit cooling tower).
When a higher water temperature is required, (water is below the de-
sign loop water temperature) the cooling bypass valve is energized and
bypasses the cooling tower and the heat addition (hot water boiler) is
enabled by the controller to heat the water to the required temperature.
The heat addition setpoints are fully adjustable and can be set according
to your systems requirements.
When a lower water temperature is required in the loop, (water is
above the design loop water temperature) the cooling bypass valve is
de-energized and the cooling tower is enabled by the controller to bring
on a cooling tower fan and tower spray pump to cool the water to the
required temperature. The heat rejection setpoints are fully adjustable
and can be set according to your systems requirements.
The AZ 2 Unit Controller can be congured to control individual water
source heat pumps. The AZ 2 Controller will work in conjunction with
the GPC-XP Loop Controller to send and receive data critical to an ef-
cient WSHP system.
For additional information about the Auto-Zone 2 control system, please
visit our web site at www.az2controls.com for complete information
and resources.
GPC-XP Controller
Features
Controller
• Stand-alone or network operation.
• Onboard time clock
• Built in USB port for direct connection to computer
• Status indicators for:
• Power
• Communications
• Binary inputs
• Relay outputs
• Congurable controller provides exibility for variations in
the application.
Software
• Purpose built Prism front end graphical software eliminates
programing. Simple conguration through point & click
selection and drop down menus
• Prism software is free to download from AZ 2 web site
Conguration and Setpoints for:
• Outside air low limit
• Pump control:
• On/Off based on time schedule or demand call
• Variable ow pump control based on differential
pressure
• Proof of ow
• Minimum runtime timers
• Automatic lead/lag changeover to equalize pump
usage
• Automatic pump failure changeover
• Runtime counters
• Boiler control:
• Adjustable setpoints
• Boiler enable
• Automatic loop temperature control
• Bypass valve control
• Proof of run
• Boiler fail alarm
• Emergency shutdown
• Cooling Tower:
• Adjustable setpoints
• Tower Fan – on/off and VFD
• Spray pump
• Spray pump proof of ow
• Sump heater control
• Monitor sump water temp
• Built in USB port for direct connection to computer
Introduction
3
WSHP Loop Controller GPC-XP Guide

Water Source Heat Pump System Operation
Figure 1: Typical Water Source Heat Pump Unit Operation Diagram
Water Source Heat Pump Unit
A water source heat pump is a self-contained water-cooled packaged
heating and cooling unit with a reversible refrigerant cycle. Its compo-
nents are typically enclosed in a common casing, and include a tube-
in-tube heat exchanger, a heating/cooling coil, a compressor, a fan, a
reversing valve and controls.
During the cooling mode, the tube-in-tube heat exchanger functions
as a condenser and the coil as an evaporator. In heating mode, the
tube-in-tube heat exchanger functions as an evaporator and the coil
as a condenser. A reversing valve is installed in the refrigerant circuit
permitting changeover from heating to cooling, and vice versa. The
condenser and evaporator tubes are designed to accept hot and cold
refrigerant liquid or gas.
General Information
4WSHP Loop Controller GPC-XP Guide

Water Source Heat Pump System Operation
Figure 2: Typical Water Source Heat Pump System Diagram
Water Source Heat Pump System
The water source heat pump system is, by denition, a heat recovery
system. It is best applied to buildings that have simultaneous cooling
and heating loads. This is the case during winter months when the
interior zones of a typical building require cooling while the exterior
zones require heating. When a water source heat pump system is used,
the heat rejected by the cooling units is used to warm the zones calling
for heat. A water heater or boiler is generally used for adding heat to the
condensing water during peak heating periods, if necessary. The system
also utilizes a water cooling tower to reject the heat energy from the
condenser water loop during periods of high cooling demand.
Water source heat pump units can be suspended in the ceiling plenum,
oor mounted behind walls or placed directly in the occupied space as
a console unit. There are also rooftop and unit ventilator type water
source heat pumps.
Water source heat pump systems generally cost less to install than central
built-up systems. They offer individual zone control with the added
exibility of being able to accommodate changes in location and sizes as
thermal zones or zone occupancy change. This system is often installed
in ceiling plenums, which frees up valuable oor space.
Another valuable benet of water source heat pumps is that they can
accommodate simultaneous calls from zones requiring heating or
cooling. Depending on the climate, outside air may require preheat or
cooling prior to being introduced to the unit. In the example of ceiling
mounted water source heat pumps, put outside air ducts near each unit
to improve indoor air quality.
Normally, multiple units serve an occupied space. This gives component
redundancy to the system so if one unit were to fail, the other units could
back it up until the unit was repaired. The packaged design of most unit
types allows quick change-out by service personnel so maintenance can
typically be performed off site.
As with any HVAC system, there is a negative side as the water source
heat pump system often requires higher maintenance costs than conven-
tional air side systems. The system also typically has a shorter replace-
ment life than other systems because of continuous fan and compressor
operation during heating and cooling modes. The system can also create
room noise since the compressor and fan are commonly located close
to the zone occupant. Placing units away from the occupied space and
ducting the supply air to the zone can minimize potential noise problems.
General Information
5
WSHP Loop Controller GPC-XP Guide

Overview
The GPC-XP Controller can be congured to control the water loop
to the individual water source heat pumps installed in a typical water
source heat pump system. The GPC-XP can operate stand-alone or be
used with the AZ 2 Control System to utilize the transfer of commonly
shared information , such as outside air temperature and system active
conditions over a communication network.
The main goal of the GPC-XP Loop Controller is to provide water ow
and to maintain the loop water temperature by monitoring either the Loop
Return Water Temperature or the Loop Supply Water Temperature. If
a higher temperature is required, a water heating device is enabled. If
the temperature needs to be lowered, a water cooling device is enabled.
The AZ 2 Controller can be congured to control individual water
source heat pumps. The AZ 2 Controller will work in conjunction with
the GPC-XP Loop Controller to send and receive data critical to an ef-
cient WSHP system.
Typical Sequence
On a typical system as is shown and congured in this manual the GPC-
XP WSHP Loop Controller waits for a Request to Run from an AZ 2
Controller on a Global Binary Channel or a Binary Contact Closure from
another source when the AZ 2 Controllers are not being used. Once the
request is received the GPC-XP energizes the Request to Run Relay and
the System Active relay. The System Pump (usually using a Lead/Lag
pump conguration) is then activated to initiate water ow in the system.
Once the System Pump is activated and Proof of Water Flow has been
determined a Global broadcast or 24 VAC from the System Active relay
is sent to the Heat Pumps to enable their compressors to run as needed.
The GPC-XP monitors the System Return Water Temperature or the
System Supply Water Temperature to determine if the water needs to
be heated or cooled to maintain the desired loop water temperature. The
typical conguration uses the Return Water Temperature to determine
the need for Heating or Cooling of the loop water.
Pump On/Off -Control
When a Request to Run is received, the GPC-XP Loop Controller
activates the System Pump to initiate water ow to the heat pumps
and other devices on the loop. The pumps can either be constant ow
or controlled by a VFD (see “Pump VFD Control”). If controlled by
a VFD, a water pressure transducer must be used for pump control. In
addition if the Request To Run goes away or if the Proof of Water Flow
is lost, the pump will turn off.
Typically the System Pumps are Lead/Lag controlled based on a user
denable number of hours of operation. If one pump exceeds the other
pump’s run time by this amount, the lead is changed until that pump
exceeds the rst pump’s run time by the same amount. This keeps both
pumps with roughly the same number of hours on each pump. The run-
ning pump is shut off at the same time the standby pump is energized,
this prevents any down time or alarms.
The GPC-XP Loop Controller monitors water ow in the loop with either
a Binary contact closure (BIN1) or a 0 to 50 PSI pressure transducer
from one of the analog inputs congured for this. The user can congure
the pressure setpoint that needs to be met to initiate the System Pump.
Pump VFD Control
The GPC-XP Loop Controller has 4 optional modulating output signals
available for control of pumps, boilers and cooling towers utilizing
VFD control. If the system is using a Pressure Transducer instead of a
pressure switch for System Pump control, the GPC-XP can monitor the
loop pressure and use a Reverse Acting PID Loop to maintain a user
dened Loop Pressure Setpoint.
The Loop Pressure is maintained by decreasing the signal output voltage
when the pressure exceeds the user dened setpoint plus the deadband
and increasing the voltage output signal with the pressure is below the
setpoint.
The pump relays are still activated and Lead/Lagged as described in the
previous section. Both output signals are enabled by their correspond-
ing relays.
Operation Of The WSHP Loop Controller
Operation
6WSHP Loop Controller GPC-XP Guide

Operation Of The WSHP Loop Controller
WSHP Unit Compressor Enable
If after the Lead/Lagged pump activates and Proof of Water Flow has
been established, the System Active relay is energized and when AZ
2 Controllers are being used for the WSHP units, a Global enable is
broadcast to the controllers letting them know to enable their compres-
sors. If using another control system for the WSHP units the System
Active relay would be used to send a 24 V relay signal to the units to run.
Heat Rejection
Staged Cooling
The GPC-XP Loop Controller monitors the loop water temperature to
determine if the loop water needs to be cooled. If the loop water tempera-
ture rises above a user dened setpoint the GPC-XP Loop Controller will
energize the cooling tower spray pump. This will remain on if the spray
pump proof of ow proves ow until the setpoint temperature is satised.
This acts as the rst stage of heat rejection. If the loop water temperature
continues to rises above a second set of user dened setpoints the cooling
tower fan will be energized providing a second stage of cooling for the
water owing through the cooling tower.
Modulating Cooling
The GPC-XP Loop Controller has the ability of sending a modulating
signal to the cooling tower fan if equipped with a VFD, to provide an
increase or decrease using a direct acting oating point control of the
output signal for modulating the cooling tower fan VFD.
Heat Addition
Staged Heating
The GPC-XP Loop Controller monitors the loop water temperature to
determine if the loop water needs to be heated. If the loop water tem-
perature falls below a user dened setpoint the GPC-XP Loop Control-
ler will energize the Cool Bypass Valve and enable the heat addition
device. This will remain on if the boiler proof of ow proves ow until
the setpoint temperature is satised.
Modulating Heating
The GPC-XP Loop Controller has the ability of sending a modulating
signal to a modulating mixing valve or a variable heat source. When
the loop water temperature drops below a user dened setpoint, the
Cool Bypass Valve will be energized and the analog output voltage
will increase or decrease using a reverse acting oating point control to
modulate a valve or variable heat source.
Emergency Shutdown
The GPC-XP Loop Controller uses an Emergency Shutdown input on
one of the binary inputs from a restat or smoke detector (by others) to
force shutdown of the entire system should a safety condition be initi-
ated by the safety device. It is congured as a Normally Closed (NC)
contact that is only active when the circuit is opened.
Operation
7
WSHP Loop Controller GPC-XP Guide

Controller, Sensors & Related Hardware
Components
GPC-XP Controller
OE338-23-GPCXP
The OE338-23-GPCXP Controller is used for controlling equipment or processes that cannot be controlled us-
ing a standard HVAC controller. The Prism 2 computer front end software is required to interface with the GPC-
XP controller functions. The GPC-XP Controller provides the exibility to control, schedule and/or monitor equip-
ment such as unit heaters, exhaust fans, motorized louvers, boilers, pumps and other mechanical equipment.
• 8 congurable analog inputs
• All analog inputs accept 10 K ohm thermistor sensors, 4-20 mA, 0-5 VDC or 0-10 VDC signals and
are set by means of jumpers on the controller
• Create custom formulas for analog inputs
• Highest/lowest/average of the analog inputs. Can be used in the internal logic or can be broadcast to
other controllers on the system
• 8 wet 24 VAC binary contacts which can be congured for N.O. or N.C. operation
• 8 congurable N.O. or N.C. relay outputs for On/Off control of equipment
• 4 analog outputs with proportional control signals. All selectable for 0-10 VDC output
• 8 separate 2 event per day time schedules which can be used for operational control or alarm
recognition based on time of day
• Lead/lag start capabilities.
Duct Temperature Sensor - 6” Probe
OE230
Used for return or supply air water sensing applications. 10k Ohm Duct Temperature Sensor, 2 wire. Used with
OE291 immersion well listed below
Immersion Well for OE230 Water Temperature Sensor
OE366
Includes: Stainless steel thermowell to be used with the OE230 Temperature Sensor listed above. The ther-
mowell is designed to thread into a ½″ FPT elbow or tee in the water piping system.
Strap-on Temperature Sensor Kit
OE233
10k Ohm Type 3, Strap-on Temperature Sensor, 2 wire. Used for water temperature sensing on outside of pipe.
Includes sensor, thermal mastic, and plastic mounting strap.
Outdoor Air Temperature Sensor
OE250
Used for temperature sensing applications. 10k Ohm Outside Air Temperature Sensor, 2 wire, mounted in a
weatherproof handy box only.
Outdoor Air Mounted RH Sensor 3% - 0-5 VDC Output
OE265-13
Used for outdoor air humidity sensing applications.
Water Differential Pressure Transducer
OE262
Includes: 0-5 VDC Differential Pressure Transducer and mounting bracket. The water pressure transducer
is used with the WSHP Loop Controller to detect water ow differential pressure in the system water loop.
Required when a VFD pump is used..
Water Differential Pressure Switch
OE261
Includes Differential Pressure Switch only. This SPDT switch is used with the WSHP Loop Controller to detect
ow in the system water loop.
8WSHP Loop Controller GPC-XP Guide

Optional Communication Devices and Software
Components
Note: The GPC-XP has its own USB port for direct connection to a desktop or laptop Windows based PC. For remote
communications via an internet connection or if you need to locate your PC further than the USB cable length allows,
you will need to consider the following devices listed in the table below. To congure and change setpoints on the
GPC-XP controller you will need to connect a Windows based PC or Laptop with WattMaster’s free Prism 2 software.
Information about the Prism 2 software is also listed in the table below
CommLink 5 Communications Interface
OE361-13
The CommLink 5 provides a PC connection to your AZ 2/GPC-XP network. If your GPC-XP Water
Source Controller is being used in conjunction with the Auto-Zone 2 Controls System, be sure to
consult the AZ 2 installation manual for wiring details.
Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power supply.
IP Module Kit - Internet/LAN Connection
OE415-02
Used for Internet or Local Area Network communications with the control system. Field installs by
plugging into the CommLink 5 circuit board and provides an addressable Ethernet connection to
the controls system from any computer connected to your building’s LAN. It can also be congured
to allow access to the control system from the Internet through your LAN if your Ethernet rewall is
congured for this option.
Includes: IP Link module, 10 ft. long Ethernet cable, and installation instructions.
MiniLink 5
OE364-23-AZ2
Used with all AZ 2 Controllers to provide network communications, zone voting, alarming, and ten-
ant logging capabilities.
USB-Link II Kit
OE366
The IP Module provides Internet or Local Area Network connectivity to the CommLink 5. Simply
install the IP Module into your CommLink 5 and congure per the installation guide.
Includes: USB-Link, USB cable, modular connection cable, two mini-DIN to terminal adapters, and
Prism 2 software.
Prism 2 Front-End Computer Software
Free!
Prism 2 provides standard, easy to understand status screens for each type of AZ 2 equipment
installed. Prism software has provisions for custom screens which allow oor plans, equipment
photos, or user-dened summary screens to be implemented to meet their own individual needs.
All controlling setpoints, trend logs, and alarm conditions are accessed in the Prism 2 environment.
Prism 2 can be congured for direct on-site installation, remote modem connection, or TCP/IP
Internet connection to several installations.
Free Download
From AZ 2 Web Site
www.az2controls.com
9
WSHP Loop Controller GPC-XP Guide

Communication, Baud Rate Settings & Wiring Info
Before Applying Power
In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the rst time, it is very
important to correctly address the controller and run through a few
simple checks.
System Settings
Stand Alone Operation
The GPC-XP has an on-board CommLink that is used during Stand-
Alone Operation. When configured for Stand-Alone operation, a
computer running Prism 2 software can be connected directly to the
USB port located at the bottom of the GPC-XP for programming and
monitoring. In order to operate in Stand-Alone Mode, two things need
to be set. First, both CommLink Jumpers found on the upper left-hand
side of the board need to be set to ON. See Figure 4 for details. Second,
the Baud Rate is determined by setting ADDRESS Dipswitch 7 to ON
and Dipswitch 8 to OFF. See Figure 5 for details.
Network Operation
The GPC-XP can be congured for connection to a networked system
that has an external CommLink. In this case, the on-board CommLink
would not be used. For this conguration, two things need to be set.
First, both CommLink Jumpers found on the upper left-hand side of the
board need to be set to OFF. See Figure 4 for details. Second, the Baud
Rate determined by setting ADDRESS Dipswitches 7 and 8 needs to
be set to OFF/OFF if using a CommLink IV and to OFF/ON if using a
CommLink 5. See Figure 5 for details.
Controller Addressing & Baud Rate
The GPC-XP Controller is equipped with address switches. When using
Prism 2 to program and congure the GPC-XP Controller, you would
enter this address to communicate with the controller. When the system
is to be connected to other HVAC unit controllers on a communication
loop, each controller’s address switch must be set with a unique address
between 1 and 59.
Settings
Important Wiring Considerations
Please read carefully and apply the following information when wiring
the GPC-XP Controller:
1. To operate the GPC-XP Controller, you must connect power to
the 24 VAC input terminal block.
2. Check all wiring leads at the terminal block for tightness.
Be sure that wire strands do not stick out and touch adjacent
terminals. Conrm that all sensors required for your system are
mounted in the appropriate location and wired into the correct
terminals. See Figure 6 & 7 for wiring connections drawings.
Environmental Requirements
The GPC-XP Controller needs to be installed in an environment that can
maintain a temperature range between -30°F and 150°F and not exceed
90% RH levels (non-condensing).
Mounting
The GPC-XP Controller is housed in a plastic enclosure. It is designed
to be mounted by using the 3 mounting holes in the enclosure base. It is
important to mount the module in a location that is free from extreme high
or low temperatures, moisture, dust, and dirt. Be careful not to damage
the electronic components when mounting the module.
Power Supply
The GPC-XP Controller requires a 24 VAC power connection with a
minimum rating of 8 VA.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to
observe polarity could result in damage to the
boards.
Figure 3 GPC-XP Controller Dimensions
10 WSHP Loop Controller GPC-XP Guide

Figure 4: GPC-XP Controller On-Board CommLink Switch Setting
GPC-XP Controller
COMFROMGND
CUT TO ISOLATE
WATTMASTER CONTROLS
YS102432 REV 3
LOOP COMM
GND
+24V
+5V
OUTPUTS
ADDRESS
ADD
1
2
4
8
16
32
POWER
EBUS
STATUS2
STATUS1
OUTPUTS
ANALOG
SERIAL#
OUTPUTS
RELAY
SH
R+
T-
BIN8
BIN7
BIN6
BIN5
BIN4
BIN3
BIN2
BIN1
BINARY
INPUTS
INPUTS
ANALOG
0-5v
0-10v
4-20 mA
AOUT1-2
C14
R109
TB8
U19
U17
TB7
TB6
TB4
TB3
TB2
TB1
SW1
R97
R74
R61R59R55R51
R47
R43
R41
R38
R21
R16
R14
D13
D12
D10
D9
D8
D7
D6
C46
C36
C21
RLY1
RLY2
RLY3
RLY4
COMMON
MADE IN USA
RLY1
RLY2
RLY3
RLY4
COMMON
AOUT1
AOUT2
AOUT3
AOUT4
GND
GND
1002
1002
.1uF
.1uF
AOUT3-4
GND
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
.1uF
.01uF
LOOP
BAUD
1
2
AI7
AI8
AI6
AI5
AI4
AI1
AI2
AI3
GND
GND
GND
GND
AI8
AI7
AI6
AI5
AI4
AI3
AI2
AI1
THERM
VDC
300
300
300
300
300
300
300
300
COM
COM
COM
COM
D11
CONNEC
ON BOA
COMMLI
ON-BOARD COMMLINK SETTING
Jumper 2
ON
Jumper 1
OFF
ON
OFF
Use On-Board CommLink
Setting
Use External CommLink
USE ON-BOARD
COMMLINK
Both Jumpers ON
Both Jumpers OFF
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R”TO“R”,“T” TO “T”“SHLD” TO “SHLD”
RELAY2
RELAY6
RELAY1
RELAY5
RLY1=
VDC
OUTPUTS
AI1 =
+ 24 VDC
+ 5 VDC
GND
BI1 = AO1 =
AI2 =BI2 = AO2 =
AI3 =BI3 = AO3 =
AI4 =BI4 = AO4 =
AI5 =BI5 =
AI6 =BI6 =
AI7 =BI7 =
AI8 =BI8 =
RLY2=
RLY5=
RLY3=
RLY6=
RLY4=
RLY7=
RLY8=
RELAY3
RELAY7
RELAY4
RELAY8
COMMON
COMMON
USB
PORT
E-BUS
PORT
NOTES:
1.) ANALOG INPUT JUMPER SETTINGS MUST BE
SET FOR YOUR SPECIFIC INPUT DEVICE
REQUIREMENT.
2.) IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE INPUT, AND/OR
OUTPUTSYOU ARE CONNECTINGTOTHE
CONTROLLER IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE) FOR
FUTURE REFERENCE.
®
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.wattmaster.com
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
THERM
4-20mA
0-10V
0-5V
ANALOG
INPUT
JUMPERS
LEDBLINK CODES
LEDNAMESTATUS1STATUS2
NORMAL OPERATION01
SCHEDULEOVERRIDE 02
OE338-23-GPC-XP
GPC-XP CONTROLLER
WattMaster Label
#LB102095
Rev.: 1C
+24VAC
GND
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution:
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.
USE EXTERNAL
COMMLINK
Figure 5 GPC-XP Controller Address Switch Setting
GPC-XP Controller
16
32
Baud 0
Baud 1
8
4
2
1
Address Switch Shown Is
Set For Address 1
Address Switch Shown Is
Set For Address 13
Controller
Address Switch
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution:
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.
Address 1 @ 9600 Baud
ADD
ADD
ADD
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
COMFROMGND
CUTTOISOLATE
WATTMASTER CONTROLS
YS102432 REV 3
LOOP COMM
GND
+24V
+5V
OUTPUTS
ADDRESS
ADD
1
2
4
8
16
32
POWER
EBUS
STATUS2
STATUS1
OUTPUTS
ANALOG
SERIAL #
OUTPUTS
RELAY
SH
R+
T-
BIN8
BIN7
BIN6
BIN5
BIN4
BIN3
BIN2
BIN1
BINARY
INPUTS
INPUTS
ANALOG
0-5v
0-10v
4-20 mA
AOUT1-2
C14
R109
TB8
U19
U17
TB7
TB6
TB4
TB3
TB2
TB1
SW1
R97
R74
R61R59R55R51
R47
R43
R41
R38
R21
R16
R14
D13
D12
D10
D9
D8
D7
D6
C46
C36
C21
RLY1
RLY2
RLY3
RLY4
COMMON
MADE IN USA
RLY1
RLY2
RLY3
RLY4
COMMON
AOUT1
AOUT2
AOUT3
AOUT4
GND
GND
1002
1002
.1uF
.1uF
AOUT3-4
GND
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
.1uF
.01uF
LOOP
BAUD
1
2
AI7
AI8
AI6
AI5
AI4
AI1
AI2
AI3
GND
GND
GND
GND
AI8
AI7
AI6
AI5
AI4
AI3
AI2
AI1
THERM
VDC
300
300
300
300
300
300
300
300
COM
COM
COM
COM
D11
CONNEC
ON BOA
COMMLI
BAUD RATE SELECTION
Switch 7 Switch 8
9600
Baud
57600
OFF OFF
ON
OFF
16
32
Baud 0
Baud 1
8
4
2
1
Address 5 @ 57,600 Baud
ADD
CommLink IV
Communication Setting
CommLink 5 Set at High Speed*
or GPC-XP is Stand Alone
RELAY CONTACT
RATING IS 1AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R”TO“R”,“T” TO “T”“SHLD”TO“SHLD”
RELAY2
RELAY6
RELAY1
RELAY5
RLY1=
VDC
OUTPUTS
AI1 =
+ 24 VDC
+ 5 VDC
GND
BI1 = AO1 =
AI2 = BI2 = AO2 =
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
AI7 = BI7 =
AI8 = BI8 =
RLY2=
RLY5=
RLY3=
RLY6=
RLY4=
RLY7=
RLY8=
RELAY3
RELAY7
RELAY4
RELAY8
COMMON
COMMON
USB
PORT
E-BUS
PORT
NOTES:
1.) ANALOG INPUT JUMPER SETTINGS MUST BE
SET FOR YOUR SPECIFIC INPUT DEVICE
REQUIREMENT.
2.) IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE INPUT, AND/OR
OUTPUTS YOU ARE CONNECTING TO THE
CONTROLLER IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE) FOR
FUTURE REFERENCE.
®
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.wattmaster.com
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
THERM
4-20mA
0-10V
0-5V
ANALOG
INPUT
JUMPERS
LEDBLINK CODES
LEDNAMESTATUS1STATUS2
NORMAL OPERATION01
SCHEDULEOVERRIDE 02
OE338-23-GPC-XP
GPC-XP CONTROLLER
WattMaster Label
#LB102095
Rev.: 1C
+24VAC
GND
9600 OFF OFF
CommLink 5 Set at Low Speed*
* The CommLink 5 must be set to Low Speed if it is being used on a
system that includes the VCM-X Controller, older generation of Orion
Controllers, or original Auto-Zone Controllers.
** The CommLink 5 can be set to High Speed if is being used on a
system that only includes VCB-X, VCC-X, or Auto-Zone 2 Controllers
along with this GPC-XP Controller.
Communication, Baud Rate Settings & Wiring Info
Settings
11
WSHP Loop Controller GPC-XP Guide

Figure 6: Typical Water Source Heat Pump Loop Controller Input Wiring using GPC-XP
Input Wiring
Wiring
12 WSHP Loop Controller GPC-XP Guide

Figure 7: Typical Water Source Heat Pump Loop Controller Output Wiring using GPC-XP
Output Wiring
Wiring
13
WSHP Loop Controller GPC-XP Guide

Conguring The Controller
Figure 8: GPC-XP Status Screen
Status Screen
Figure 8 shows a typical GPC-XP status screen after being congured
for use as a Central Plant Controller. To create a description for an
input “double click” on any of the existing descriptions to change to an
appropriate description for the Central Plant Controller input or output
you selected. A popup window will appear allowing you to change the
description as needed. See Figure 9.
For Analog Input #1 change the description to “Outdoor Air Tempera-
ture” and hit the “Enter” key as shown above.
If you have a Supply Water Temperature sensor enter it as the Analog
Input #2 with its description. If you have a Return Water Temperature
sensor enter it as Analog Input #3 with its description. If you have a Dif-
ferential Pressure Sensor enter it as theAnalog Input #4 with its descrip-
tion. Enter a description for any other input sensors you have in the rest
of the remaining input description areas. At the very minimum you will
need to create Analog Inputs for OA Temperature and Return or Supply
Water Temperature in order to control the equipment on your Central
Plant system. Other inputs may be required for your specic project.
NOTE: Be sure to hit “Enter” after each description is changed
or the change will not occur.
The conguration and setpoints can also be reached from the ‘Status
Screen” by double clicking the data display box to the right of the de-
scription area. Once congured and the system is communicating this
box will contain the current value of the input you have entered. “Double
click” the data box next to the “Outdoor Air Temperature” description
to open the conguration and setpoint screen for AIN1.
General
Using the GPC-XP as a Water Source Heat Pump Loop Controller
requires that it be congured for your application. The information that
follows will show you how to congure a GPC-XP controller for a typical
Central Plant Loop Controller application. If you want to start with the
typical setpoints we have used in this manual as a starting point you can
enter them by hand or you can download and install a pre-congured
setup screen and setpoints used in these examples if you wish.
To download the typical WSHP Loop controller setup screen go to the
Auto-Zone 2 Controls web site at www.az2controls.com. Click on the
software tab at the top of the web page. Scroll to the bottom of the web
page and nd the listing “GPC-XP Used For WSHP Loop Control-
ler – Setup File” and click on the “click here” text to download the
self extracting le.
Once you have downloaded the le go to its location and “double click”
on the le and then unzip it to the directory listed in the “unzip to win-
dow”. You can now select the “Restore To File” tab located under the
“Setpoints” tab at the top of the GPC-XP Status screen to select the le
“WSHP-Typ-Setpoints.SPT” and it will populate the GPC-XP status
screen with all the typical setpoints and descriptions like the screen
shown in Figure 8. You can now change or delete the setpoints or con-
gurations as desired to match your requirements.
Figure 9: Entering Input & Output Descriptions
Conguration
14 WSHP Loop Controller GPC-XP Guide

Analog Input #1
This is the input conguration screen that would be congured for the
Outdoor Air Temperature sensor (“OSA Temp”) on Analog Input #1
(AIN1).
This is a required sensor in all Central Plant Controller applications.
Also either a Supply Water or Return Water Temperature Sensor is al-
ways required as well as either a Differential Pressure Transducer or a
Differential Pressure Switch. All other inputs may or may not be needed
for your specic application.
Item #1 in Figure 10 indicates the Outdoor Air Temperature sensor is
congured for a thermistor type sensor with a Fahrenheit output. This
could also be congured for a thermistor type sensor with a Celsius
output if you desire by selecting that option instead. In addition you may
have a sensor that uses one of the other options listed. No matter what
type of signal your sensor has, be sure to set the jumper on the GPC-XP
controller board‘s Analog Input being congured for the correct sensor
signal you are using.
In this example Item #2 indicates that the sensor reading will be shown
in degrees Fahrenheit on the status screen. You may also set this to
Celsius if desired.
Figure 10: AIN1 Sensor Screen
1
23
4
5
Item #3 indicates the Sensor Scaling has been congured to “10” which
will show tenths of a degree on the screen. So at a 74.51 degrees actual
temperature signal from the sensor the screen would show 74.5 degrees.
If the scaling factor is set to “1” the screen would show 74 degrees
from the same sensor signal. If it is set to “100” for the same signal
it would show 74.51. Congure this typically as either “1” or “10” as
one hundredth of a degree is beyond the accuracy of most thermistor
sensors anyway.
Item #4 is the “Send Global Analog” setting. In this case if you are us-
ing the Auto-Zone 2 controllers for the WSHP units on your controls
system and you have a single loop communications system you would
broadcast the Outdoor Air Temperature to the other units on the local
loop by selecting “Send to Local Loop” as shown. If you have a multiple
loop communications system you would set this to “Send to ALL Loops”
as shown in the example.
Item #5 is the Analog Broadcast Channel selection box. In this case it
should be set to “2”.
Conguring the Controller
Conguration
15
WSHP Loop Controller GPC-XP Guide

Conguring The Controller
Conguration
Figure 11: AIN2 Sensor Screen
1
23
Figure 12: AIN3 Sensor Screen
1
23
16 WSHP Loop Controller GPC-XP Guide

Conguring the Controller
Conguration
Analog Input #2
This is the input conguration screen used for the Supply Water Tem-
perature sensor (TW Supply Water”) on Analog Input #2 (AIN2). Item
#1 in Figure 11 indicates the Supply Water Temp sensor is congured
for a thermistor type sensor with a Fahrenheit output. All the other
congurations are the same as described for the previous conguration
of the Outdoor Air Temperature sensor except no broadcasting of the
signal is required as was done with the Outdoor Air Temperature Sensor.
Analog Input #3
This is the input conguration screen used for the Return Water Tem-
perature sensor (“TW Return Water”) on Analog Input #3 (AIN3). Item
#1 in Figure 12 indicates the Return Water Temp sensor is congured
for a thermistor type sensor with a Fahrenheit output. All the other
congurations are the same as described for the previous conguration
of the Supply Water Temperature sensor.
Analog Input #4
This is the input conguration screen used for the Differential Pressure
Sensor (“Loop Pressure”) when used. It is located on Analog Input #4
(AIN4). Either a Differential Pressure Sensor or a Differential Pressure
Switch is required for the Loop Controller operation. If a Differential
Pressure Switch is used instead, it is wired to the Binary Input #2 (BIN2)
which is described under the Binary Input #2 information section that
follows.
Item #1 in Figure 13 indicates the Differential Pressure sensor is
congured for a 0-5 VDC type sensor. This is the requirement for the
sensor WattMaster offers. Yours may be different. Congure the sensor
accordingly.
Item #2 indicates that the sensor reading will be shown in PSI.
Item #3 indicates the Sensor Scaling has been congured to “10” which
will show tenths of a PSI on the screen. So at a 30.47 PSI actual pressure
signal from the sensor the screen would show 30.5 PSI.
Item #4 indicates the User Scaling has been congured to “50 PSI”
maximum reading and “0” PSI Minimum Reading. This should be set
to the range of the sensor you are using.
Figure 13: AIN4 Sensor Screen
1
2 3
4
17
WSHP Loop Controller GPC-XP Guide

Conguring The Controller
Conguration
Figure 14: AIN5 Sensor Screen
1
23
Figure 15: AIN6 Sensor Screen
1
23
4
18 WSHP Loop Controller GPC-XP Guide

Conguring the Controller
Conguration
Analog Input #5
In this example this is the input conguration screen for the Boiler Loop
Temperature sensor (“Boiler Loop Temp”) when used on Analog Input
#5 (AIN5). Item #1 in Figure 14 indicates the Boiler Loop Temperature
sensor is congured for a thermistor type sensor with a Fahrenheit output.
All the other congurations are the same as described for the previous
conguration for the Supply Water Temperature sensor.
Figure 16: AIN7 Sensor Screen
Analog Input #7
In this example this is the input conguration screen for the cooling tower
Sump Water Temperature (“Sump Temp”) sensor when used, located
on Analog Input #7 (AIN7). Item #1 in Figure 16 indicates the Sump
Water Temperature sensor is congured for a thermistor type sensor
with a Fahrenheit output.
All the other congurations are the same as described for the previous
conguration of the Supply Water Temperature sensor.
Analog Input #8
Analog Input #8 (AIN8) is not congured in this typical Central Plant
Controller conguration but could be used for any other sensor applica-
tion your project may need.
Analog Input #6
In this example this is the input conguration screen for the Outdoor
Air Humidity sensor (“OAS Humidity”) when used, located on Analog
Input #6 (AIN6). Item #1 in Figure 15 indicates the “OAS Humidity”
sensor is congured for a 0-5 VDC signal sensor.
Item #2 in Figure 15 indicates the sensor reading will be in RH percent
and item #3 indicates it will be scaled to a factor of 10 so that tenths of
a percent will be shown in its display. The Outdoor Air Humidity Sensor
would typically be used for information only and would generally not
be used as a control input for the Central Plant Controller.
Item #4 indicates the User Scaling for the sensor has been congured to
“100.0 RH % ” maximum reading and “0.0 %” Minimum Reading. This
should be set to the range of the sensor you are using.
1
23
19
WSHP Loop Controller GPC-XP Guide

Conguring The Controller
Conguration
Figure 17: BIN1 Input Screen
1
Figure 18: BIN2 Input Screen
1
20 WSHP Loop Controller GPC-XP Guide
Table of contents
Popular Control System manuals by other brands

Crestron
Crestron FT-TSC600 FlipTop Operations & installation guide

ICON
ICON TOTALPASS quick start guide

GiBiDi
GiBiDi BARR 600 Instructions for installation

Comm Box
Comm Box Joey Micro Programming & installation manual

Atlas IED
Atlas IED IP100 quick start guide

HySecurity
HySecurity StrongArmPark DC 10 Programming and operations manual

Spraying Systems
Spraying Systems TeeJet TECHNOLOGIES BoomPilot installation manual

HIK VISION
HIK VISION DS-K260X-G Quick setup guide

dbx
dbx DriveRack PA user manual

GiBiDi
GiBiDi PASS 3 Instructions for installation

Landi Renzo
Landi Renzo A1 V05 Installation and adjustment manual

A/DA
A/DA PLATINUM II owner's manual