ABB ReliaGear ASPMETER A 42 Installation and operation manual

—
ReliaGear™lighting panelboards —
Branch circuit monitoring
Installation and commissioning instructions


004 – 013 ASPMETER solid core
014 – 026 ASPMETER split core
027 – 040 ASPMETER commissioning
—
Table of contents

4BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER solid core
Safety
If ASPMETER products are used in installations with circuits
higher than the product ratings, the circuits must be kept
segregated per UL 508A Sec. 17.5.
NOTE: 277/480 V AC wye-connected (center-grounded) power
systems operate within the 300 V AC line to neutral safety
rating of the ASPMETER series, and the operational voltage
limit (single-phase connection) as the line to neutral voltage
is 277 V AC in such power systems. Corner-grounded delta
480 V AC systems would not qualify, because the actual line
to earth voltage is 480 V AC on each leg, exceeding the
ASPMETER ratings.
NOTE: ASPMETER internal circuitry (cables and CTs) are not
circuits as defined by UL 508A, because they do not extend
beyond the ASPMETER itself without further safety/fire
isolation.
• UL listed under UL 508 as an “open-type device.”
• Maximum ambient air temperature for use is 60 °C.
• Installation category: CAT III
• The ASPMETER series must be installed in an appropriate
electrical and fire enclosure per local regulations.
For use in a pollution degree 2 or better environment only.
A pollution degree 2 environment must control conductive
pollution and the possibility of condensation or high humidity.
Consideration must be given to the enclosure, the correct use
of ventilation, thermal properties of the equipment and the
relationship with the environment.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the device may
be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard
exists.
Documentation must be consulted where this
symbol is used on the product.
DANGER: Hazard of electric shock, explosion or arc
flash. Failure to follow these instructions will result in
death or serious injury.
• Follow safe electrical work practices. See NFPA 70E
in the USA, or applicable local codes.
• This equipment must only be installed and serviced
by qualified electrical personnel.
• Read, understand and follow the instructions before
installing this product.
• Turn off all power-supplying equipment before
working on or inside the equipment.
• Use a properly rated voltage-sensing device to confirm
power is off. DO NOT DEPEND ON THIS PRODUCT FOR
VOLTAGE INDICATION.
• Only install this product on insulated conductors.
NOTICE:
• This product is not intended for life or safety
applications.
• Do not install this product in hazardous or classified
locations.
• The installer is responsible for conformance with
all applicable codes
• Mount this product inside a suitable fire and electrical
enclosure.
FCC Part 15 information note: This equipment has been
tested by the manufacturer and found to comply with the
limits for a class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment
is operated in a commercial environment. This equipment
generates, uses and can radiate radio frequency energy and,
if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential
area is likely to cause harmful interference, in which case the
user will be required to correct the interference at his own
expense. Modifications to this product without the express
authorization of the manufacturer nullify this statement.

5
ASPMETER SOLID CORE
—
ASPMETER solid core
Installer’s specifications Product identification
Quick install
1. Disconnect and lock out power. Use a properly rated
voltage-sensing device to confirm power is off.
2. Mount current sensor strips adjacent to breaker
terminations.
3. Verify that the serial numbers on the CTs match that
on the board.
4. Configure communication and addressing parameters
using DIP switches.
5. Mount the main acquisition board in the electrical
enclosure.
6. Connect current sensor strip cables to the main board,
observing the 2-strip setup and their orientation (A or B)
within the panel.
7. Wire RS-485 communications.
8. Connect CTs to the auxiliary inputs and connect them
onto the main conductors in the enclosure (optional).
9. Wire control power and voltage taps (ASPMETERA and
ASPMETERB only).
10. Download the free configuration tool “NetConfig” from
www.veris.com/modbus_downloads.aspx to commission
the device for operation.
# of CTs
Circuit breakers
AE - TEY
ASPMETER 4 2
Description
Inputs
Input power
Accuracy
Power/energy
Voltage
line-to-neutral
Current
Outputs
Type Modbus RTU
Connection DIP
Address DIP Switch-selectable address
Baud rate DIP
Parity DIP Switch-selectable none, odd, even
Communication
format
Termination
Mechanical
Ribbon
cable support
Environmental
Operating
temperature range
Storage
temperature range
Agency approvals

6BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER solid core
Operations
The ASPMETER series branch current monitor is a device
designed to measure the current, voltage and energy
consumption of up to 46 circuits (42 branch circuits, one
3-phase main and one neutral).
The ASPMETER consists of a data acquisition board and two
21-unit current sensor strips, with four auxiliary inputs. The
strips are mounted on each side of the panelboard along the
termination points of each breaker. The conductor passes
through the appropriate current sensor before terminating
at the breaker. Each strip transmits the current data to the
data acquisition board.
Data is transmitted using an RS-485 Modbus protocol.
Each data acquisition board requires one Modbus address
for the set of two current sensors and four auxiliary inputs.
Data is updated roughly every two seconds. As a circuit
approaches the user-defined threshold, the ASPMETER
activates the alarm indicators.
The ASPMETERA measures both current and power for the
mains and branch circuits. The ASPMETERB measures both
current and power for the mains, and current only in each
circuit. The ASPMETERC measures current only for the mains
and branch circuits.
Dimensions
Circuit board and mounting bracket
Solid-core CT strips
Product diagrams
1. 50-pin ribbon cable connectors (data acquisition board):
18 inch (457 mm) ribbon cables are provided for easy
connection of current sensor strips to this point of the
data acquisition board.
NOTE: Connect CT strips to the correct ribbon cable
connectors for each panel. The top connector is for
strip A, and the bottom connector is for strip B.
2. Auxiliary inputs: These 0.333 V AC inputs are used for
monitoring the main breaker or other high amperage source.
3. Control (mains) power connection:
50/60 Hz connection.
4. Control power fuse: 600 V AC, 500 mA time lag, factory-
replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 7.
6. Voltage taps: 1, 2 or 3 phase plus neutral connections.
For voltage sensing and power calculations (no voltage
taps on the ASPMETERC).
7. Communications address DIP switches: Each Modbus device
must have a unique address. Switches are binary weighted.
a value of 128.
8. Communications settings DIP switch: Configures baud rate,
parity, 2-/4-wire communications.
9. RS-485 2 connection: Used for Modbus serial communications.
The universal plug accommodates 2- or 4-wire connections.
10. RS-485 LEDs:
DIP switches) indicates transmission of information.
11. Power LED: Indicates power to main board
12. Current sensors: Each current sensor is capable of monitoring
conductors rated up to a maximum of 100 amps.
13. 50-pin ribbon cable connectors (current sensor strips):
Connects current signal from the sensor strip to the main
board via the ribbon connectors.
Dimensions
Circuit Board and Mounting Bracket
8.3”
(211mm)
(200mm)
7.9”
3.9”
(100mm)
4.8”
(122mm)
1.75”
(45mm)
5.8”
(146mm)
7.3”
(184mm)
Ø=0.2”
(5mm)
8.9”
(288mm)
Solid-Core CT Strips
0.4” (10mm)
opening
1.0” (26mm)
on center
25.0” (635mm)
1.2”
(31mm)
2.0”
(50mm)
slot: 0.25” x 0.5”
(7 x 13mm)
1.2”
(30mm)
Product Diagrams
7
1
2
3
4
5
6
2
8
9
10
A
B
11 12
13
Dimensions
Circuit Board and Mounting Bracket
8.3”
(211mm)
(200mm)
7.9”
3.9”
(100mm)
4.8”
(122mm)
1.75”
(45mm)
5.8”
(146mm)
7.3”
(184mm)
Ø=0.2”
(5mm)
8.9”
(288mm)
Solid-Core CT Strips
0.4” (10mm)
opening
1.0” (26mm)
on center
25.0” (635mm)
1.2”
(31mm)
2.0”
(50mm)
slot: 0.25” x 0.5”
(7 x 13mm)
1.2”
(30mm)
Product Diagrams
7
1
2
3
4
5
6
2
8
9
10
A
B
11 12
13
Dimensions
Circuit Board and Mounting Bracket
8.3”
(211mm)
(200mm)
7.9”
3.9”
(100mm)
4.8”
(122mm)
1.75”
(45mm)
5.8”
(146mm)
7.3”
(184mm)
Ø=0.2”
(5mm)
8.9”
(288mm)
Solid-Core CT Strips
0.4” (10mm)
opening
1.0” (26mm)
on center
25.0” (635mm)
1.2”
(31mm)
2.0”
(50mm)
slot: 0.25” x 0.5”
(7 x 13mm)
1.2”
(30mm)
Product Diagrams
7
1
2
3
4
5
6
2
8
9
10
A
B
11 12
13

7
ASPMETER SOLID CORE
Commissioning
1. Install according to instructions in mechanical installation.
2. Provide control power to main circuit board.
3. Configure installation mode using Modbus register 6.
4. Configure CT scaling.
5. Configure alarms.
6. Configure demand.
Download the free configuration tool “NetConfig” from
www.veris.com/modbus_downloads.aspx to commission
the ASPMETER for operation.
—
ASPMETER solid core
Data output
Monitoring at mains ASPMETERA ASPMETERB ASPMETERC
Current per phase • • •
Max. current per phase • • •
Current demand per phase • • •
Max. current demand per phase • • •
Current phase angle • •
Energy (kWh) per phase • •
Real power (kW) per phase • •
Apparent power (kVA) • •
Power factor total * • •
Power factor per phase • •
Voltage — L-L and average • •
Voltage — L-N and average • •
Frequency (phase A) • •
Monitoring at branch circuit
Current • • •
Max. current • • •
Current demand • • •
Max. current demand • • •
Current phase angle • •
Real power (kW) •
Real power (kW) demand •
Real power (kW) demand max. •
Energy (kWh) per circuit •
Power factor •
Apparent power (kVA) •
Modbus alarms
Voltage over/under • •
Current over/under • • •
* Based on a 3-phase breaker rotation.
Blink code
Color and pattern Status description
Green, once per second Normal operation
Amber, once per second Volts or amps clipping
Amber, twice per second Invalid firmware image
Amber, three per second Incorrect strips or strip order
Red, solid or blink Device failure

8BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER solid core
Wiring
Power must be disconnected and locked
out before making any wiring connections.
Connect 2-wire or 4-wire Modbus RS-485 daisy chain network
(Figures 1 and 2).
Figure 1.
Figure 2.
2-wire
4-wire
1. Mechanically secure the RS-485 cable where it enters
the electrical panel.
2. Connect all RS-485 devices in a daisy-chain fashion,
and properly terminate the chain (Figure 3).
Figure 3.
2-wire example
3. Shield the RS-485 cable using twisted-pair wire, such as
Belden 1120A. The cable must be voltage-rated for the
installation.
4. When tightening terminals, ensure that the correct torque
is applied: 0.5 to 0.6 N·m (0.37 to 0.44 ft·lb ) for connectors
on main board, 0.22 to 0.26 N·m (0.16 to 0.19 ft·lb) for
connectors on adapter boards (Figure 4).
Figure 4.
WARNING: After wiring the RS-485 cable, remove
all scraps of wire or foil shield from the electrical
panel. Wire scraps coming into contact with high
voltage conductors could be DANGEROUS!
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+

9
ASPMETER SOLID CORE
—
ASPMETER solid core
Configuration
1. Communications configuration: Communications
parameters for the ASPMETER series are field-selectable
for your convenience. Please see the product diagrams
section (page 6) for selector location. The following
parameters are configurable:
• Baud rate: 9600, 19200 or 38400
• Parity: on or off
• Parity: odd or even
• Wiring: two or four
Example: 2-wire 19200 baud, no parity (default only)
2. Address configuration: Each Modbus device on a single
network must have a unique address. Set the switch block
to assign a unique address before the device is connected
to the Modbus RS-485 network. If an address that conflicts
with that of another device is selected, neither device will
be able to communicate.
3. Address the ASPMETER as any whole number between and
DIP switches for addressing. See below.
4. To determine an address, simply add the values of any
switch that is on. For example:
Switch number 4 has an ON value of 8 and switch number
address for the ASPMETER is 40. See the address setup
section (page 10) for a pictorial listing of the first 63
switch positions.
Default DIP switch settings
The ASPMETER includes two DIP switches, as shown below.
Switches are shown in their default positions.
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
1 2 3 4 5 6 7 8
Off Off 9600
On Off 19200
Off On 38400
On On Reserved
Off Off No parity
On Off Odd parity
Off On No parity
On On Even parity
On 4-wire RS-485
Off 2-wire RS-485

10 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER solid core
Address setup
DO NOT
USE ZERO 1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20 21
246
......
22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43
44 45 46 47 48 49 50 51 52
55 56 57 58 59 60 61 62 63
53 54

11
ASPMETER SOLID CORE
—
ASPMETER solid core
Figure 5.
insulation. Use this gauge wire or smaller for 100 A circuits.
E30 CURRENTSENSOR STRIP
E30 CURRENTSENSOR STRIP
20
2020202020202020
20
20202020202020202020
20
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
AB
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
A
B
1
3
5
7
9
11
13
15
17
19
21
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
23
25
27
29
31
33
35
37
39
41
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
A
B
A
B
A
B
A
B
A
B
A
B
A
B
Register 6
Value = 0 (Default)
Register 6
Value = 2
Register 6
Value = 1
Register 6
Value = 3
E30 CURRENTSENSOR STRIP
E30 CURRENTSENSOR STRIP
20
2020202020202020
20
20202020202020202020
20
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
AB
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
A
B
1
3
5
7
9
11
13
15
17
19
21
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
23
25
27
29
31
33
35
37
39
41
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
A
B
A
B
A
B
A
B
A
B
A
B
A
B
Register 6
Value = 0 (Default)
Register 6
Value = 2
Register 6
Value = 1
Register 6
Value = 3
Top feed Bottom feed
Single row — sequential Single row — odd/even
E30 CURRENTSENSOR STRIP
E30 CURRENTSENSOR STRIP
20
2020202020202020
20
20202020202020202020
20
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
AB
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
A
B
1
3
5
7
9
11
13
15
17
19
21
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
23
25
27
29
31
33
35
37
39
41
2
6
10
14
18
22
26
30
34
38
42
4
8
12
16
20
24
28
32
36
40
1
5
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
39
A
B
A
B
A
B
A
B
A
B
A
B
A
B
Register 6
Value = 0 (Default)
Register 6
Value = 2
Register 6
Value = 1
Register 6
Value = 3
Mechanical installation
Observe precautions for handling static-sensitive
devices to avoid damage to the circuitry, which
is not covered under the factory warranty.
Disconnect power to the electrical panel
and lock it out.
1. Install the current sensor strips in the panel (Figure 5).
2. Arrange the sensor strips in one of the four configurations
shown in Figure 6. Adjust orientation of the circuit
numbers in the field during commissioning by writing
to Modbus register 6 or use free configuration software.
Figure 6.

12 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER solid core
3. Verify that the serial numbers printed on the current strip
and on the data acquisition board match. The board and
the strip are sold as a calibrated set.
4. Configure communication and addressing parameters
using DIP switches. See the configuration section for
more information.
5. Install the ASPMETER acquisition board mounting bracket
in the panel using screws and bolts provided (Figure 7).
The grounding connection is located on the mounting
bracket, near the lower right corner. Use this stud to
ground the bracket when it is mounted on a plastic
surface.
Figure 7.
6. Connect current sensor ribbon cables to the 50-pin
connectors on the main board (Figures 8 and 9).
Orient cables so that the red stripe is on the left.
Figure 8.
Figure 9.
7. Wire RS-485 communications (see diagrams in wiring
section (page 8).
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
Recommended CT: AMP1 series available in 100 A max. to 2000 A max.
Contact your local ABB sales rep for recommended CT amperages or
if higher amperages are required.
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
CT Input
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
E30CURRENT SENSOR STRIP
E30CURRENT SENSOR STRIP
Panel 1
A
B
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
I1
I2
I3
IN
±
±
±
±
V1 V2 V3 N
L - L L - N
Align ribbon cable key with connector
keyhole. Orient ribbon cable so that the red
stripe is on the left side of the connector.
Red stripe
8. Connect 0.333 V AC CTs to the main conductors by snapping
CTs around lines, observing local codes regarding bending
Figure 10.
Figure 11.
Observe polarity. For the ASPMETERA and ASPMETERB,
connect lines to the voltage taps (Figure 12). Equip voltage
lines with fuses.
Figure 12.

13
ASPMETER SOLID CORE
—
ASPMETER solid core
Troubleshooting
Problem Solution
Product is not communicating over
Modbus daisy chain
• Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.
• Check parity.
• Check the communications wiring.
• Check that the daisy chain is properly terminated.
• Check for reversed polarity on Modbus communications.
This is usually provided by the master.
The main board has a fast flashing
amber light
(see illustrations in product installation).
• Verify ribbon cable connectors are inserted in the correct orientation.
• If cables are correct, reset main board to re-initialize product.
• Verify serial number on strips matches serial number on main board.
The main board has a slow flashing
amber light
The main board has a flashing green light • Everything is wired properly and the main board has power.
The main board has a flashing or solid
red light
• Light may be red briefly while device powers up.
Power factor reading is not as expected • Verify voltage taps are connected in appropriate phase rotation.
• Verify strip configuration register matches actual strip installation.
Current reading is not as expected,
or reading is on different CT number
than expected
• Verify strip configuration register matches actual strip installation.
• Verify ribbon cable is fully seated and in the correct orientation.
Current is reading zero, even when small
currents are still flowing through circuit
or below this range.
Configuration tool “NetConfig” returns
Modbus error on read/write
• Verify use of the latest release of configuration tool “NetConfig” because older versions may
not support all features in current product firmware. Latest version is available on the website
http://www.veris.com/ modbus_downloads.aspx
For troubleshooting or service-related questions, contact ABB at 800-782-8061 or at epis.component[email protected]om

14 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER split core
Safety
FCC Part 15 information note: This equipment has been tested
by the manufacturer and found to comply with the limits for
a class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated
in a residential environment. This equipment generates, uses
and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may
cause harmful interference to radio communications. This
device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received,
including interference that may cause undesired operation.
Modifications to this product without the express
authorization of the manufacturer nullify this statement.
A qualified person is one who has skills and knowledge related
to the construction and operation of this electrical equipment
and the installation, and has received safety training to
recognize and avoid the hazards involved.
NEC 2011 Article 100: No responsibility is assumed by
manufacturer for any consequences arising out of the
use of this material.
Control system design must consider the potential failure
modes of control paths and, for certain critical control
functions, provide a means to achieve a safe state during
and after a path failure. Examples of critical control functions
are emergency stop and over-travel stop.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol
is used on the product.
DANGER: Hazard of electric shock, explosion
or arc flash. Failure to follow these instructions
will result in death or serious injury.
• Follow safe electrical work practices. See NFPA 70E
in the USA, or applicable local codes.
• This equipment must only be installed and serviced
by qualified electrical personnel.
• Read, understand and follow the instructions before
installing this product.
• Turn off all power-supplying equipment before working
on or inside the equipment.
• Use a properly rated voltage-sensing device to confirm
power is off. DO NOT DEPEND ON THIS PRODUCT FOR
VOLTAGE INDICATION.
• Only install this product on insulated conductors.
NOTICE:
• This product is not intended for life or safety
applications.
• Do not install this product in hazardous or classified
locations.
• The installer is responsible for conformance to all
applicable codes.
• Mount this product inside a suitable fire and
electrical enclosure.
WARNING: Loss of control
Failure to follow these instructions may cause injury,
death or equipment damage.
• Assure that the system will reach a safe state during
and after a control path failure.
• Separate or redundant control paths must be provided
for critical control functions.
• Test the effect of transmission delays or failures
of communication links.
• Each implementation of equipment using communication
links must be individually and thoroughly tested for
proper operation before placing it in service.
For troubleshooting or service-related questions, contact ABB at 800-782-8061 or at epis.component[email protected]om
Save these instructions

15
ASPMETER SPLIT CORE
—
ASPMETER split core
Specifications
Inputs
Input power
Accuracy
Power/energy
Voltage
Current
Operation
Sampling frequency
Update rate
Overload capability
Outputs
Type Modbus RTU
Connection
Address
Baud rate
Parity DIP switch-selectable NONE, ODD, EVEN
Communication format
Termination
Terminal block torque
Mechanical
Ribbon cable support
Operating conditions
Operating temp range
Storage temp range
Altitude of operation
Compliance
Agency approvals
Installation category
Notes:
• If ASPMETER products are used in installations with circuits higher than the product
ratings, the circuits must be kept segregated per UL 508A Sec. 17.5.
• 277/480 V AC wye-connected (center-grounded) power systems operate within the
300 V AC line to neutral safety rating of the ASPMETER series, and the operational
voltage limit (single-phase connection) as the line to neutral voltage is 277 V AC in
such power systems. Corner-grounded delta 480 V AC systems would not qualify,
because the actual line to earth voltage is 480 V AC on each leg, exceeding the
ASPMETER ratings.
• ASPMETER internal circuitry (cables and CTs) are not circuits as defined by UL 508A,
because they do not extend beyond the ASPMETER itself without further safety/fire
isolation.
Product overview
The ASPMETER panelboard monitoring system is designed
to measure the current, voltage and energy consumption
of up to 92 circuits (84 branch circuits, two 3-phase mains,
two neutrals) on a single board. One ASPMETER can monitor
up to two panels.
The ASPMETER consists of a data acquisition board and up to
84 split-core current sensors (50 A, 100 A or 200 A), with eight
auxiliary inputs. Each conductor passes through a current
sensor and terminates at the breaker. Each sensor transmits
the current data to the data acquisition board. Data is
transmitted using an RS-485 Modbus protocol. Each data
acquisition board requires two addresses, one for each set
of 42 current sensors and four auxiliary inputs. Data is
updated roughly every two seconds. As a circuit approaches
the user-defined threshold, the ASPMETER activates the alarm
indicators.
The ASPMETER-A measures both current and power for the
mains and branch circuits. The ASPMETER-B measures both
current and power for the mains, and current only in each
circuit. The ASPMETER-C measures current only for the mains
and branch circuits.
Product identification
# of CTs
ASPMETER
Description

16 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER split core
Dimensions
Circuit board and mounting bracket
7.3"
(184 mm)
8.9"
(226 mm)
5.8"
(146 mm)
4.8"
(122 mm)
3.9"
(100 mm)
7.9"
(200 mm)
8.3"
(211 mm)
1.75"
(45 mm)
Ø = 0.2"
(5 mm)
Current sensors
ASPCT0 50 amp
ASPCT1 100 amp
ASPCT3 200 amp
Adapter board
(117 mm)
4.6"
(70 mm)
2.75"
1.00"
(26 mm)
(26 mm)
1.00"
D
E
C
B
A
D
E
B
A
C
D
E
B
A
C

17
ASPMETER SPLIT CORE
—
ASPMETER split core
Product diagrams
1. 50-pin ribbon cable connectors: Ribbon cables attach
here for easy connection of adapter boards to the data
acquisition board. The two connectors on the left are for
Note: Connect adapter boards A and B to the correct
ribbon cable connectors for each panel. The top connector
is for adapter board A, and the bottom connector is for
adapter board B.
Note: Ribbon cable is not included with all ASPMETER
models. For ribbon cable options, see recommended
accessories on page 25.
2. Auxiliary inputs: These 0.333 V AC inputs are used for
monitoring the main breaker or other high amperage
on the right are for panelboard 2.
3. Control (mains) power connection: Easy 2-wire
4. Control power fuse: 600 V AC, 500 mA time lag,
factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes on page 18.
6. Voltage taps: 1, 2 or 3 phase plus neutral connections. For
voltage sensing and power calculations (no voltage taps on
the ASPMETER-C). Voltage taps are shared by both panels.
7. Communications address DIP switches: Each Modbus
device must have a unique address. Switches are binary
switch has a value of 128.
Note:
configuration section for details.
8. Communications settings DIP switch: Configures baud
rate, parity and 2-/4-wire communications.
9. RS-485 connection: Used for Modbus serial
communications. The universal plug accommodates
2- or 4-wire connections.
10. RS-485 LEDs:
LED (farthest from DIP switches) indicates transmission
of information.
11. Power LED: Indicates power to main board .
12. Branch current sensors: Each split-core current sensor is
capable of monitoring conductors rated up to a maximum
of 50, 100 or 200 amps. Up to 84 sensors can be purchased
with the ASPMETER (see recommended accessories on
page 25). One of each style is pictured here.
13. Ribbon cable connectors
14. CT terminal connectors
7
1
2
3
4
5
6
2
8
9
10
AA
BB
11
13
14
12

18 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER split core
Data output
Monitoring at mains ASPMETER-A ASPMETER-B ASPMETER-C
Current per phase • • •
Max. current per phase • • •
Current demand per phase • • •
Max. current demand
per phase
• • •
Current phase angle • •
Energy (kWh) per phase • •
Real power (kW) per phase • •
Apparent power (kVA) • •
Power factor total * • •
Power factor per phase • •
Voltage L-L and average
• •
Voltage L-N and average
• •
Voltage L-N and per phase • •
Frequency (phase A) • •
Monitoring at branch circuit
Current • • •
Max. current • • •
Current demand • • •
Max. current demand • • •
Current phase angle • •
Real power (kW) •
Real power (kW) demand •
Real power (kW) demand
max. •
Energy (kWh) per circuit •
Power factor •
Apparent power (kVA) •
Modbus alarms
Voltage over/under • •
Current over/under • • •
* Based on a 3-phase breaker rotation.
Blink code for status LED
Color and pattern Status description
Green, once per second Normal operation
Amber, once per second Volts or amps clipping
Amber, twice per second Invalid firmware image
Red, solid or blink Diagnostic event detected
Split-core CT accuracy
Description Split-core CT
50 A 100 A 200 A
Voltage rating
Accuracy
Temperature
Agency
Commissioning
1. Install according to instructions in mechanical
installation.
2. Provide control power to panel.
3. Configure installation mode using Modbus register 6.
4. Configure CT scaling.
5. Configure alarms.
6. Configure demand.
Download the free configuration tool “NetConfig” from
www.veris.com/modbus_downloads.aspx to commission
the E3x for operation.

19
ASPMETER SPLIT CORE
—
ASPMETER split core
Connect 2-wire or 4-wire Modbus RS-485 daisy chain network
(Figures 1 and 2).
Figure 1.
Figure 2.
1. Mechanically secure the RS-485 cable where it enters
the electrical panel.
2. Connect all RS-485 devices in a daisy-chain fashion,
and properly terminate the chain (Figure 3).
Figure 3.
3. Shield the RS-485 cable using twisted-pair wire, such as
Belden 1120A. The cable must be voltage-rated for the
installation.
4. When tightening terminals, ensure that the correct torque
is applied: 0.5 to 0.6 N·m (0.37 to 0.44 ft·lb) for connectors
on main board, 0.22 to 0.26 N·m (0.16 to 0.19 ft·lb) for
connectors on adapter boards (Figure 4).
Figure 4.
WARNING: After wiring the RS-485 cable, remove all
scraps of wire or foil shield from the electrical panel.
Wire scraps coming into contact with high voltage
conductors could be DANGEROUS!
Power must be disconnected and locked out before
making any wiring connections.
Wiring
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wi
re
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wi
re
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+
SHIELD
RX- TX-
RX+ TX+
TX-
TX+
2-wire
Master or Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD SHIELD
4-wire
Master Slave
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
SHLD
TX+
TX+
RX+
TX–
TX-
RX-
SHIELD
2-wire example
–
+
Belden 1120A or
equivalent 120 Ω terminator
on last device of
daisy chain
Not Used
–
+

20 BRANCH CIRCUIT MONITORING INSTALLATION AND COMMISSIONING INSTRUCTIONS
—
ASPMETER split core
Configuration
1. Communications configuration: Communications
parameters for the ASPMETER series are field-selectable
for your convenience. Please see the product diagrams
section (page 17) for selector location. The following
parameters are configurable:
• Baud rate: 9600, 19200 or 38400
• Parity: on or off
• Parity: odd or even
• Wiring: two or four
Example: 2-wire 19200 baud, no parity (default only)
1 2 3 4 5 6 7 8
Off Off 9600
On Off 19200
Off On 38400
On On Reserved
Off Off No parity
On Off Odd parity
Off On No parity
On On Even parity
On 4-wire RS-485
Off 2-wire RS-485
2. Address configuration: Each Modbus device on a single
network must have a unique address. Set the switch block
to assign a unique address before the device is connected
to the Modbus RS-485 network. If an address that conflicts
with that of another is selected, neither device will be able
to communicate.
3. The ASPMETER uses two logical addresses. Panel 1 uses
the base address as set on the DIP switches, and panel 2
equipped with a set of eight DIP switches for addressing.
See below.
4. To determine an address, simply add the values of any
switch that is on. For example:
Switch number 4 has an ON value of 8 and switch number 6
for panel 1 is 40 and the address for panel 2 is 41. See the
address setup section (page 21) for a pictorial listing of
the first 63 switch positions.
Default DIP switch settings
The ASPMETER includes two DIP switches, as shown below.
Switches are shown in their default positions.
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
ON
Reserved2/4
Wire
Odd/
Even
Parity
On
Off/
Parity
B1
1 2 3 4 5 6 7 8
BØ
1
LSB MSB
1 2 4 8 16 32 64 128 DIP Switch
Values
=
ON
1 2 3 4 5 6 7 8
40
LSB MSB
=
ON
1 2 3 4 5 6 7 8
Comms Address Comms Settings
This manual suits for next models
2
Other ABB Measuring Instrument manuals

ABB
ABB SensyMaster FMT230 Installation and operation manual

ABB
ABB KM26 User manual

ABB
ABB Sensyflow FMT500-IG User manual

ABB
ABB FSM4000 Series User manual

ABB
ABB EXGP User manual

ABB
ABB NGC8200 User manual

ABB
ABB SensyMaster FMT430 User manual

ABB
ABB Navigator 550 Sodium wet-section Use and care manual

ABB
ABB C11 User manual

ABB
ABB SM3000 User manual

ABB
ABB AX416 User manual

ABB
ABB PositionMaster EDP300 User manual

ABB
ABB COM600F ANSI User manual

ABB
ABB aquamaster User manual

ABB
ABB Sensyflow FMT400-VTS User manual

ABB
ABB VSN300 User manual

ABB
ABB AO2000-LS25 User manual

ABB
ABB 2410 User manual

ABB
ABB 10D1475 User manual

ABB
ABB VortexMaster FSV430 Installation instructions