manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Auber
  6. •
  7. Temperature Controllers
  8. •
  9. Auber TD100 User manual

Auber TD100 User manual

TD100 TEMPERATURE CONTROLLER
INSTRUCTION MANUAL Version 1.1
AUBER INSTRUMENTS WWW.AUBERINS.COM
2013.05 P1/3
Instruction Manual
1. Overview
This temperature controller contains one temperature probe and two
independent outputs. One output is for cooling device such as
refrigerator and the other one is for heating device. It can be used for
applications such as beer fermentation or convert a refrigerator to
kegerator. By using both cooling and heating devices, the refrigerator
can be controlled at specific temperature regardless in hot summer or
cold winter.
This controller is a plug and play controller. No wiring is needed for
the heater or cooler. Both the heating and cooling control modes are
simple on/off control, similar to a mechanical thermostat but with
much higher precision due to adjustable hysteresis band, precise
sensor and digital read out. Anti-short function is provided for cooling
to protect the compressor from being turned on with high pressure
Freon.
Different operation temperature ranges of the two outputs can be set
separately. Once the cooling range is set, the controller program will
automatically limit the heating range to prevent both heating and
cooling from being turned on at the same time.
A digital silicon band gap sensor is used. The advantage is being
much more reliable in moisture environment than thermistor sensor. It
can be immersed over extended period of time. It also has a more
uniform accuracy over an entire specified temperature range.
2. Specification
SET
Temperature ControlRange -50~125 °C, -58~257 °F
Temperature Resolution
0.1 °C (between -9.9 ~ 99 °C)
1 °C (between -50 ~ 10 °C, 100~125°C)
0.1 °F (between -9.9~99.9 °F )
1 °F (between -58 ~ 10 °F,100 ~257 °F)
Temperature Accuracy 0.5 °C or 0.9 °F
Temperature Control Mode On/OffControl. Heating and Cooling
Temperature Control Output 10A, 120V or 240V AC *
Audio Alarm High and Low Limit
Sensor Type Silicon Band Gap Sensor
Sensor Size 0.25" OD (6.35 mm) x 1" (25mm) long
Sensor Measuring Range -20~125 °C
AmbientTemperature -20~ 50 °C
Dimension 91x140x46mm
InputPower 85 ~242VAC, 50Hz/60Hz
Sensor Cable Length 3 ft(1m)
Power Cable Length 3 ft(1m)
Warranty 1 Year
4. Setup Flow Chart
When the controller is powered on, it will display the measured
temperature. The controller will keep running according to the saved
setting. If the temperature sensor is shorted, the controller will display
“Err”. Please see Figure 2 for the flow chart to set the parameters.
Up Key
Dn Key, Mute Alarm
Set Key
Measured
Temperature
Cooling Device
Socket
Heating Device
Socket
Heating device
On Indicator
Cooling Device
On Indicator
3. Front Panel
Figure 1. Front Panel
68.9
5 sec
SET
CSP
HSP
SET
AH
SET
AL
SET
CDF
SET
HDF
AS
SFA
OFS
C-F
SET
SET
SET
SET SET 68.9
SET
Figure 2 Set
Up Flow Chart
Alarm High Limit
Alarm Low Limit
Cooling Differential
Heating Differential
Cooling Antishort
Sensor Failure
Operation
Temperature Offset
Temperature Unit
Measured
Temperature Cooling
Set Point
Heating
Set Point
AUBER INSTRUMENTS WWW.AUBERINS.COM
2013.05 P2/3
5. Parameter Settings
To change the target temperature, press SET key momentarily. The
controller will show CSP (Cooling set point), press SET again will
show HSP (heating set point). When the controller shows CSP or
HSP, use Up or Down key to change the value. Then press SET key
to confirm the change.
To change the system parameters, press SET key for 5 seconds, the
controller will enter the parameter set up mode. The first parameter
AH will show on the display. Use Up or Down key to modify the
parameter value. Then press SET key to confirm the change. The
display will show the parameter again. Press the SET key to show
the next parameter. The instrument will automatically exit if no key is
pressed for 10 seconds. Please see the Table 1 for the parameters.
Description Setting range Initial Note
CSPCSP Cooling SetPoint -58~248 ºF
-50~125 ºC 67.0
HSPHSP HeatingSetPoint -58~CSP ºF
-50~CSP ºC 62.0
AH AH Alarm High Limit -58~248 ºF
-50~125 ºC 95.0
AL AL Alarm Low Limit -58~AH ºF
-50~AH ºC 32
CdF CDF Cooling Differential 0~50.0 ºF 3.0
HdF HDF Heating Differntial 0~50.0 ºF 1.0
AS AS Cooling Antishort 0~12 min 0 3
SFA SFA Sensor Failure Operation 0-0, 0-1, 1-0 0-0 4
oFS OFS Temperature Offset 0~10.0 0 5
C-F C-F Temperature Unit C: Celsius
F:Fahrenheit F
1
Code
1
2
Table 1. Parameters Description
Note 2. When the measured temperature is higher than AL, the high
limit alarm will be on; when the measured temperature is lower than
AL, the low limit alarm will be on.
When alarm is on, the display will be flashing between the measured
value and alarm type. To mute the alarm when it is on, press the
Down key momentarily. If the measured value gets out of the alarm
zone then gets back to the alarm zone again, the alarm will be on
again. To disable the alarm, set AH=AL.
The maximum value of the AL can be set is the current value of AH.
But AH can be set to the value between -58~248 ºF or
-50~125 ºC. When AH is set to a value lower than current AL, the AL
will be adjusted to the AH value automatically.
For example, when AH=95.0 ºF, AL=32 ºF, AL can be set to any
value between -58 and 95.0. For AH, it can be set to any value
between -58 and 248. If you set it to 25.0, the AL will be set to 25.0
automatically.
Note 3. The Cooling Antishort is the delay the time to turn the
cooling load on. when the controller is used for cooling and load is a
compressor, it should not turn on the compressor when it is at high
pressure (just after turned off). Otherwise, It may shorten the life of
compressor. The Anti-Short cycle delay function can be used to
prevent the rapid cycling of the compressor. It establishes the
minimum time that the NO contacts remains open (after reaching
cutout) before closing again. The delay overrides any Load Demand
and does not allow the NO contacts to close until the set time-delay
value has elapsed. It gives time to release the refrigerant pressure
through evaporator. It is typically set to 4- 6 (minutes).
Note 4. The SFA defines how the output would be if the sensor fails.
It can be set to 0-0, 0-1 or 1-0. Please refer to table 2 for details.
Table 2. Output of the controller when sensor fails:
For example, when the unit controls a refrigerator for food, you may
want to set the TSF to ON if the sensor fails to keep the food cold.
When it controls a heater, you may want to set the output to OFF for
safety purpose .
Note 5. The offset is used to set an input offset to compensate the
error produced by the sensor or input signal itself.
For example, for temperature, if the unit displays 37 ºF when the
actual temperature is 32 ºF, setting parameter toF= - 5 will make the
controller display 32 ºF.
SFA Controller outputwhen sensor fails
0-0 cooler off, heater off
1-0 cooler on, heater off
0-1 cooler off, heater on
Note 1. For cooling (or heating), the output will be off when the
temperature is blow (or over) the set point; will be on again when the
temperature rises up (or drops down) to CSP+CdF (or HSP-HdF).
The maximum value of the HSP can be set is the current value of
CSP. But CSP can be set to the value between -58~248 ºF or
-50~125 ºC. When the CSP is set to a value lower than current HSP,
the HSP will be adjusted to the CSP value automatically.
For example, when CSP=67.0 ºF, HSP=62 ºF, HSP can be set to any
value between -58 and 67.0. For CSP, it can be set to any value
between -58 and 248. Ifyou set it to 55.0, the HSP will be set to 55.0
automatically.
Small differential gives tight control; large differential reduces the
frequency of cycle on and off. It will extend the life of relay and
compressor.
6. How to install the sensor to the unit.
The connector of sensor contains a slot for correct pin connection. It
also has a spring lock to prevent disconnections from accidental
pulling on the cable. To install the to the unit, please align the slot of
AUBER INSTRUMENTS WWW.AUBERINS.COM
2013.05 P3/3
Auber Instruments Inc.
5755 North Point Parkway, Suite 99
Alpharetta, GA 30022
www.auberins.com
e-mail: info@auberins.com Tel: 770-569-8420
Figure 4. Remove the Sensor
Figure 3. Install the Sensor
the female connector on the sensor to the red mark of the male
connector on the unit, then hold the tail and push the female
connector forward. To remove the connector, please pull the spring
loaded collar of the female connector. Please see the Figure 3 and
Figure 4 below for details.

Other Auber Temperature Controllers manuals

Auber WSD-1203CPH Administrator Guide

Auber

Auber WSD-1203CPH Administrator Guide

Auber WS-1200CPH Administrator Guide

Auber

Auber WS-1200CPH Administrator Guide

Auber WS-1500EBPM Technical manual

Auber

Auber WS-1500EBPM Technical manual

Auber WS-1500ES Administrator Guide

Auber

Auber WS-1500ES Administrator Guide

Auber SYL-2342 User manual

Auber

Auber SYL-2342 User manual

Auber TD220 User manual

Auber

Auber TD220 User manual

Auber SYL-1615 User manual

Auber

Auber SYL-1615 User manual

Auber WS-1500APH Administrator Guide

Auber

Auber WS-1500APH Administrator Guide

Auber TH102 User manual

Auber

Auber TH102 User manual

Popular Temperature Controllers manuals by other brands

Vaillant VRC 470 operating instructions

Vaillant

Vaillant VRC 470 operating instructions

Itho Daalderop HRU 400 Installation & use

Itho Daalderop

Itho Daalderop HRU 400 Installation & use

Husky Altanium Delta3 user guide

Husky

Husky Altanium Delta3 user guide

Elsist SENSIT TG68 DS 18B20 instruction manual

Elsist

Elsist SENSIT TG68 DS 18B20 instruction manual

Polyaire Zonemaster Technical manual

Polyaire

Polyaire Zonemaster Technical manual

Hugo Müller TS 3.10 KNX Series instruction manual

Hugo Müller

Hugo Müller TS 3.10 KNX Series instruction manual

KWE Versatronik COMO OT Quick start-up

KWE

KWE Versatronik COMO OT Quick start-up

alre FETR 101.700 quick start guide

alre

alre FETR 101.700 quick start guide

Campbell IR100 user manual

Campbell

Campbell IR100 user manual

YOKOGAWA TC10 Engineering manual

YOKOGAWA

YOKOGAWA TC10 Engineering manual

oventrop PT1000 Installation and operating instructions

oventrop

oventrop PT1000 Installation and operating instructions

Elk ELK-M1ZTS quick start guide

Elk

Elk ELK-M1ZTS quick start guide

MULTISPAN UTC-421P manual

MULTISPAN

MULTISPAN UTC-421P manual

Siemens REA23 operating instructions

Siemens

Siemens REA23 operating instructions

Alpes Lasers TC-3 user manual

Alpes Lasers

Alpes Lasers TC-3 user manual

MULTISPAN UTC-221G quick start guide

MULTISPAN

MULTISPAN UTC-221G quick start guide

Omron E5ZE datasheet

Omron

Omron E5ZE datasheet

Carrier AQUASMART installation manual

Carrier

Carrier AQUASMART installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.