BH Thermal BriskONE User manual

Owner’s Manual
Caution:
Before using this controller,
read this manual and follow
the Operating Instructions.
• Operation
• Installation
• Troubleshooting
BH Thermal
(Manufacturers of BriskHeat Products)
P.O. Box 1633009 ¥
¥¥
¥Columbus, OH 43216 USA
PH#: (614) 294-3376 ¥
¥¥
¥Fax #: (614) 294-3807
Manual Part# 40890-03

2
Table of Contents Introduction ..................................................................................3
Operations .....................................................................................5
Controller KeyFunctions ............................................................7
Programming Instructions .............................................................8
Security .........................................................................................9
Temperature Unit ..........................................................................10
Setpoint Range...............................................................................11
Setpoint..........................................................................................11
Method of Control.........................................................................11
Setting the Alarm...........................................................................12
Sensor Break Alarm Action ..........................................................14
Loop Break Protection...................................................................15
Tuning............................................................................................15
Input Calibration............................................................................16
Ramp/Soak Feature........................................................................17
Setting FuzzyLogic Parameters....................................................19
Installation.....................................................................................20
Troubleshooting.............................................................................23
Parts List........................................................................................24
Programming: Quick Reference Table..........................................25
List of Figures
and Tables Figure 1: Pictorial of Controller (Front) . . . . . . . . . . . . . . . . . . . 4
Figure 2: Pictorial of Controller (Back) . . . . . . . . . . . . . . . . . . . 4
Figure 3: Layout of Internal Components . . . . . . . . . . . . . . . . . . 6
Figure 4: Dual Display Controller . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5: Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 6: Controller within Bracket . . . . . . . . . . . . . . . . . . . . . . 22
Figure 7: Diagram of Pin and Stripped Wire . . . . . . . . . . . . . . . . 22
Figure 8: Diagram of Pin Insertion into Plug . . . . . . . . . . . . . . . 23
Table 1: Security Levels and Passwords . . . . . . . . . . . . . . . . . . . 10
Table 2: List of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 3: List of Menu Items Located in the Secure Menu . . . . . .25
Table 4: List of Menu Items Located in the Secondary Menu . . .26
Table 5: List of Menu Items Located in the Primary Menu . . . . .26

3
Introduction Meet the BriskHeat BriskONE Controller!
General Description:
BriskONE is a compact one zone controller which provides excellent
temperature control in areas with limited space.
Features:
• Compact size: 7” x 5” x 2” [ 177.8mm x 127mm x 50.8mm]
• Quickly adapts from 120V to 240V input power simply by
changing fuse and cord.
• Provides 15A@120V or 10A@240V output power.
• Output power protected with fuse.
• Type J Thermocouple input.
• Dual display allows user to view both the process and setpoint
temperature simultaneously.
• Displays either οC or οF.
Additional Features:
• Fuzzy Logic
• Self Tuning
• Heater Break Protection
• Sensor Break Protection
• Auto/Manual Control Capability
• 16 segment Ramp and Soak with adjustable time base
Specifications and parts are subject to change at any time without notification.

4
Figure 1: Pictorial of Controller (Front)
Figure 2: Pictorial of Controller (Back)

5
Operation To begin operation of the BriskONE controller, follow these
steps:
1. Plug the input power cord into the controller (see Figure 2 for
input power receptacle location). Then connect the other end of
power cord into a properly grounded 120VAC or 240VAC
outlet.
A BriskONE controller purchased for 120VAC operations can
easily be changed for 240VAC operation and vice versa. A
120VAC controller comes equipped with a 120VAC input
power cord and a 15Amp fuse. To change the operations to
240VAC, a 240VAC input power cord and 10Amp fuse is
required (see page 22 for ordering information).
Note: Before operating the controller, see the “Installation”
section for proper location of the controller.
2. Turn the red on/off rocker switch to the “ON” position. Rocker
switch will light up.
3. Program the controller with the values needed to properly
control the heater (see programming instructions - pages 5-16) .
4. Place the thermocouple tip in a location which best reflects the
heater’s temperature. Depending on the object’s shape, during
heating there may be spots which are warmer or colder.
If all areas of the object must reach a minimum temperature, then
place the thermocouple tip on the coldest spot.
If the temperature of any area of the object cannot go above the
temperature setpoint, then place the thermocouple tip on the
hottest spot.
If a temperature differential is allowable, then place the
thermocouple tip on an area where the temperature is between
the hottest and coldest.
5. Plug thermocouple into the controller. Verify that the
temperature displayed on the upper display is the actual
temperature of the heating system. If not, check to ensure the
thermocouple plug was correctly wired and connected to the
controller.
6. Plug the power cord for the heater into the controller (see
“Installation” section for instructions on how to assemble the
plug to the heater cord).

6
Figure 3: Layout of Internal Components

7
Controller Key Functions
Figure 4: Dual Display Controller
1. Setpoint Display: Displays the SV (setpoint value). The SV is
the setpoint entered by the operator.
2. Process Display: Displays the PV (process value). The PV is
the actual temperature of the system being controlled.
3. oF Lamp: Lit when the temperatures displayed are in degrees
Fahrenheit.
4. oC Lamp: Lit when the temperatures displayed are in degrees
Celsius.
5. Percent Lamp: Lit when controller is programmed to display
percentage of output power.
6. Hold Lamp: Lit when Ramp/Soak program functions are
suspended.
7. ENTER: Pressing ENTER stores the value or the item changes.
If not pressed, the previously stored value or item will be
retained. The display will flash once when ENTER is pressed.
8. This decimal point flashes when SELF-TUNE is operating.
9. DOWN ARROW: Decrements a value, changes a menu item,
or selects the item to OFF. The minimum value obtainable is -
1999 regardless of the decimal point placement.

8
10. UP ARROW: Increments a value, changes a menu item, or
selects the item to ON. Maximum value attainable is 9999
regardless of the decimal point placement.
11. INDEX: Pressing the INDEX key advances the display to the
next menu item. Also used in conjunction with other keys.
12. Manual Indicator: Lit when output of control is being
manually adjusted.
13. Alarm Indicator: Lit when a fault condition exists.
14. Setpoint 2 Lamp: Lit when the SV displayed relates to setpoint
2.
15. Setpoint 1 Lamp: Lit when the SV displayed relates to setpoint
1.
Key Combinations:
• UP ARROW & ENTER: Pressing these keys simultaneously
brings up the Secondary Menu starting at the alarm, tune, or
cycle item (depending on the programming). Pressing these
keys for 5 seconds will bring up the Secure Menu.
• INDEX & DOWN ARROW: Pressing these keys
simultaneously will allow backing up one menu item, or if at the
first menu item, they will cause the display to return to the
Primary Menu. If an alarm condition has occurred, then these
keys may be used to reset the alarm. To reset an alarm press and
hold both keys for three seconds.
• INDEX & ENTER: Pressing these keys simultaneously and
holding them for 5 seconds allows recovery from the various
error messages.
Programming The controller’s programming is divided up into three menus:
Instructions
Primary Menu !Secondary Menu !Secure Menu
Within each menu are menu items. Each of the menu item
pertains to a parameter of the controller.

9
To enter and move from menu item to menu item within the
Primary Menu:
• Press the UP ARROW and ENTER keys.
• Press INDEX to advance through the menu items.
• Simultaneously, press INDEX and DOWN ARROW keys to
back up one menu item.
• Press UP ARROW or DOWN ARROW to change the value in
the display.
• Press ENTER to retain the value.
To enter and move from menu item to menu item within the
Secondary Menu:
• Press the UP ARROW and ENTER keys.
• Press INDEX to advance through the menu items.
• Simultaneously, press INDEX and DOWN ARROW keys to
back up one menu item.
• Press UP ARROW or DOWN ARROW to change the value in
the display.
• Press ENTER to retain the value.
To enter and move from menu item to menu item within the Secure
Menu:
• Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.
• Press INDEX to advance through the menu items.
• Simultaneously, press INDEX and DOWN ARROW keys to
back up one menu item.
• Press UP ARROW or DOWN ARROW to change the value in
the display.
• Press ENTER to retain the value.
Security The security code is located in the Secure Menu. The code
locks out programming access to specific menus. To access the
locked out menus the security level must be changed. To
change the security level, the correct password must be entered
into the SECr menu item.
1. Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.

10
2. The menu item SECr should be the first to appear. The value
shown is the current security level.
3. Change the security level, by using the UP ARROW and
DOWN ARROW keys to change the value in the upper display
until the password of the desired security level is shown.
4. Press the ENTER key to retain the value. The display will
blink, and the new security level will be shown in the upper
display.
Refer to the following table for the correct value to enter for the
security level desired.
Note: The passwords cannot be altered.
Table 1: Security Levels and Passwords
Security Level Security Level Password
Menu Status Value To Enter
Primary Locked
Secondary Locked 1 1110
Secure Locked
Primary Unlocked
Secondary Locked 2 1101
Secure Locked
Primary Unlocked
Secondary Unlocked 3 1011
Secure Locked
Primary Unlocked
Secondary Unlocked 4 111
Secure Unlocked
Temperature Unit
1. Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.
2. Press the INDEX key until Unit is shown on the lower display.
3. Change the unit of measurement, by using the UP ARROW and
DOWN ARROW keys to select C (Celsius) or F (Fahrenheit).
4. Press the ENTER key to retain the value.

11
Setpoint Range Menu items SPL and SPH limit the value that may be entered
for the setpoint.
1. Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.
2. Press the INDEX key until SPL is shown on the lower display.
SPL is the lowest allowable value that the set point may be
entered in as.
3. Use the UP ARROW and DOWN ARROW keys to change the
value.
4. Press ENTER to retain the value.
5. Press the INDEX key until SPH is shown on the lower display.
SPH is the highest allowable value that the set point may be
entered in as.
6. Use the UP ARROW and DOWN ARROW keys to change the
value.
7. Press ENTER to retain the value.
Note: SPL and SPH only limit what value may be entered for the
setpoint. These values are not used in the actual control of the
heater.
Setpoint
1. `Press INDEX to the advance to SP1.
2. Use the UP ARROW and DOWN ARROW keys to change the
value until the desired setpoint is displayed.
3. Press ENTER to retain that value.
Note: For entering the set point while in the Ramp/Soak mode,
see Ramp/Soak instructions on page 15.
Method of Control
1. Press the UP ARROW and ENTER keys simultaneously.

12
2. Press the INDEX key until Out1 is shown on the lower display.
• Menu item Out1 designates the control method to be used by the
controller. There are essentially two selections to choose from:
• ONOF allows the controller to simple on/off mode. This setting
forces the controller to turn off at the setpoint, and turn on at the
setpoint plus the differential (SP_d).
• ##tP sets the controller to time proportioning control. The
available 1 second steps range from 1tP to 80tP. A value of 1tP
is recommended for solid state outputs. For mechanical outputs,
the longest possible time should be selected without causing the
process to wander.
3. Use the UP ARROW and DOWN ARROW keysto changethevalue.4. Press ENTER to retain that value.5. IfONOF is selected under the Out1 menu item, press the
INDEX key until SP_d is shown on the lower display.SP_d isthe Set Point On-OFF Differential (hysteresis), which should be
negative for a heatingprocess.
66. . Use the UP ARROW and DOWN ARROW keysto changethe
value.
7. Press ENTER to retain thatvalue.
Setting the Alarm
1. Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.
2. Press the INDEX key until AL is shown on the lower display.
AL is the temperature alarm function. Five different options are
available for this menu item.
• OFF Alarm is disabled.
• Lo Low Alarm only.
• Hi High Alarm only.
• HiLo High and Low alarm share the same alarm output.
• Evnt Alarm is controlled by the Ramp/Soak program
function
3. Use the UP ARROW and DOWN ARROW keysto changethe
value.

13
4. Press ENTER to retain that value.
If OFF is selected for the value for AL, the following menu
items will not appear.
5. Press the INDEX key until ALT appears on the display. ALT is
the menu item that selects the temperature alarm type. There are
two values to choose from.
• AbS Absolute Alarm may be set anywhere between 0-
1600 and is independent from SP1.
• dE Deviation Alarm is dependent on SP1, and alarms
when the process temperature is beyond acceptable
limits enter in ALLo and ALHi.
6. Use theUP ARROW and DOWN ARROW keysto changethe
value.7.After a value is selected, press ENTERto r etain that value.
8. Press the INDEXkeyuntil ALiH is shown on the lower display.
ALiH is the alarm inhibit menu item.
• On The alarm action is suspended until the process
temperature first enters a non-alarm condition.
• OFF Turns the alarm inhibit off.
9. Use the UP ARROW and DOWN ARROW keysto changethe
value.10.After a value is selected, press ENTERto retain thatvalue.11.Press the INDEXkeyuntil ALS tappears on the display.
ALSt is the alarm output state menu item. BriskONE’s design
requires ALSt be set to OPEn.
If ALSt is set to CLOS, then press UP ARROW and DOWN
ARROW keys until the value shown is OPEn. Press ENTERto retain thatvalue12.Press the INDEXkeyuntil ALLP appears on the display.
ALLP is the alarm lamp. BriskONE’s design requires ALLP be
set to OoFF.
If ALLP is set to O on, the press UP ARROW and DOWN
ARROW keys until the value shown is OoFF. Press ENTER
to retain that value.

14
13. Press the INDEXkeyuntil ALLb appears on the display. ALLb
is the alarm loop break menu item.
• On The controller will alarm if no change has been
detect by the sensor under full output conditions for
a period of time.
• OFF The controller will not alarm.
14. Use the UP ARROW and DOWN ARROW keysto changethe
value.
15. Press ENTER to retain that value.
16.The nexttwo menu items are located in the Secondary Menu.
Their appearance depends on the values entered in the menu
items above. To return to the Primary Menu, wait 30 seconds,
or for a faster response, press the UP ARROW and ENTER
keys followed by pressing the DOWN ARROW and INDEX
keys.
17. Press the UP ARROW and ENTER keys simultaneously to
enter the Secondary Menu.
18. Press the INDEXkeyuntil ALLo appears on the display. ALLo
is the low limit alarm and will only appear, if AL has a value of
Lo or HiLo.
19. Use the UP ARROW and DOWN ARROW keysto changethe
value.
20. Press ENTER to retain that value.
21. Press the INDEXkeyuntil ALHi appears on the display. ALHi
is the high limit alarm and will only appear, if AL has a value of
Hi or HiLo.
22. Use the UP ARROW and DOWN ARROW keysto changethe
value.
23. Press ENTER to retain that value.
Sensor Break
Alarm Action
1. Hold the UP ARROW and ENTER simultaneously for five
seconds to enter the secure menu.
2. Press the INDEX key until InPt appears on the display. InPt is
the input fault timer. When the input is out of range, shorted, or
open, the timer will start. OFF or a range from 0.1 to 540.0
minutes can be selected.

15
3. Use the UP ARROW and DOWN ARROW keys to change the
value.
4. After a value is selected, press ENTER to retain that value.
5. Press the INDEX key until InPb appears on the display. InPb
determines the action the controller will perform, when the InPt
timer runs out. If InPt has a value of OFF, InPb will not be
displayed. There are three options for this menu item:
• FAIL Output is disabled.
• AVE The output will hold at the last known average
percentage of output.
• PrE The output will maintain a preprogrammed
percentage of output as specified in PrE1 and PrE2.
If PrE is selected, the following menu item will appear.
• PrE1 Select 0 to 100% for Set Point 1
6. Use the UP ARROW and DOWN ARROW keysto changethe
value.
7.After a value is selected, press ENTER to retain that value.
Loop Break
Protection
1. Press the UP ARROW and ENTER keys to enter the
Secondary Menu.
2. Press the INDEX key until LPbr appears on the display. If,
during the operation, the output is at its minimum or maximum,
and the input has moved less than 5oF (3oC) over the time
specified in LPbr, the LOOP bAd message will appear. If
ALLb is On, then this condition will cause an alarm. LPbr has
a range 1to 9999 seconds, or OFF.
3. Use the UP ARROW and DOWN ARROW keys to change the
value.
4. Press ENTER to retain that value.
Tuning
1. Press the UP ARROW and ENTER keys to enter the
Secondary Menu.

16
2. Press the INDEX key until tun appears on the display. tun is
where the type of tuning choice is selected. There are five
options to choose from.
• SELF allows the controller to evaluate the process and select its
own PID values to maintain good control. This is the
recommended choice since all systems react differently. If
SELF is selected, the following two menu items will appear.
• Lern -- select YES or no.
YES starts the learning process, and finishes by reverting to
no.
no will keep the present variables.
• dFAC is the damping factor that sets the ratio of Rate to
Reset for the SELF mode. For a fast response
process, the value should be lowered. For a slower
process, the value should be increased.
• Pid allows manual adjustment of PID values. This option
should only be selected if the end user has an understanding of
how a PID system works. If Pid is selected, the following menu
items will appear.
• Pb1 is the proportional band. Select 1to 9999.
• rES is the automatic reset time. Select OFF, 0.1 to 99.9
minutes. Select OFF to switch to OFS.
• OFS is the manual offset correction. Select OFF, 0.01
to 99.9%. Select OFF to switch to rES.
• rtE is the rate.
• SLO presets PID values for a slow response process on a default
system.
• nor presets the PID values for a normal response process on a
default system.
• FASt presets PID values for a fast response process on a default
system.
3. Use the UP ARROW and DOWN ARROW keysto changethe
value.
4.After a value is selected, press ENTER to retain that value.
Input Calibration
1. Press the UP ARROW and ENTER keys to enter the
Secondary Menu.

17
2. Press the INDEX key until InPC appears on the display. InPC
allows the input value to be changed to agree with an external
reference or to compensate for sensor error. InPC can have a
value of + 500. (The units depend on which value was entered
in the Unit menu item.)
3. Use the UP ARROW and DOWN ARROW keys to change the
value.
4. After a value is selected, press ENTER to retain that value.
Ramp/Soak
Feature
1. Press the UP ARROW and ENTER keys to enter the
Secondary Menu.
2. Press the INDEX key until Prog appears on the display. Prog is
a Ramp/Soak feature that allows the process to be started.
• On allows the Programmed Ramp/Soak function to be started by
the Run/Hold key on the control front panel. This option can
only be selected after the parameters of the Ramp/Soak
operation are entered.
• OFF turns Ramp/Soak function off and resets program to
beginning.
3. Use the UP ARROW and DOWN ARROW keysto changethe
value.
4. Press ENTER to retain that value.
5. Press the INDEXkeyuntil PSEt appears on the display.PSEt
enables the rest of the menu items that are used in programming
the Ramp/Soak.
• On enables Ramp/Soak programming. PSEt must be in this
position to start programming the Ramp/Soak features.
• OFF skips Ramp/Soak programming.
6. Use the UP ARROW and DOWN ARROW keysto changethe
value.
7.After a value is selected, press ENTER to retain that value.
8. Press the INDEXkeyuntil StAt appears on the display. StAt
controls how the Primary Menu will display the Ramp/Soak
parameters.
• OFF allows the Primary Menu to operate normally.

18
• On alters the Primary Menu to display the following items.
####/ti is time remaining in segment.
####/##ti is the total time in active segment.
####/##SP is the target set point for the segment.
9. Use the UP ARROW and DOWN ARROW keys to change the
value.
10. After a value is selected, press ENTER to retain that value.
11. Press the INDEX key until tbAS appears on the display. tbAS is
the Ramp/Soak time unit measurement.
• 1_S is the time base in 1 second increments.
• 60_S is the time base in 1 minute increments.
12. Use the UP ARROW and DOWN ARROW keysto changethe
value.
13. After a value is selected, press ENTER to retain that value.
The following items are located in the secondary menu after
tbAS, and are the parameters for the 16 segments of the
Ramp/Soak. To save space, only the descriptions for the first
segment will be listed. The number at the beginning of the
display represents the segment of the Ramp/Soak.
14. Press the INDEX key until 1ti appears on the display. 1ti is the
time for the first segment with a range of 0to 9999. The units
will depend on what was entered in tbAS.
15. Use the UP ARROW and DOWN ARROW keys to change the
value.
16. After a value is selected, press ENTER to retain that value.
17. Press the INDEX key until 1SP appears on the display. 1SP is
the first segment’s Set Point.
18. Use the UP ARROW and DOWN ARROW keys to change the
value.
19. After a value is selected, press ENTER to retain that value.
20. Press the INDEX key until 1AL appears on the display. 1AL is
the first segment’s alarm event.
• On activates the alarm during segment 1’s time.
• OFF deactivates the alarm during segment 1’s time.
21. Use the UP ARROW and DOWN ARROW keysto changethe
value.
22. After a value is selected, press ENTER to retain that value.

19
The following items appear at the end of the 16 segment
program in the Secondary Menu.
23. Press the INDEX key until PEnd appears on the display. PEnd
is the program’s end action.
• Hold keeps the temperature at the present set point.
• OoFF turns off the output at the end of the program.
• LooP repeats the program starting at 1ti. If the program is to
repeat, the last segments must return the process to the same
condition when the program started.
• SP1 reverts to the SP1 (Primary Menu) value.
The next two menu items can be found in the Primary Menu.
Their appearance will be dependent on which values were
entered in the menu items above.
• To return to the Primary Menu, wait 30 seconds, or for a faster
response, press the UP ARROW and ENTER keys followed by
pressing the DOWN ARROW and INDEX keys.
24. If StAt is On, three menu items will appear in the Primary
Menu.
• ti is the time remaining for the current segment.
• ##ti is the total time for segment ##.
• ##SP is the target set point for segment ##.
25. IfProg, in Secondary Menu, is OFF, then Prog will not appear
in Primary Menu. Prog is the Ramp/Soak Run/Holds function
• run means the Ramp/Soak is in operation.
• OFF holds the Ramp/Soak program.
26. Use the UP ARROW and DOWN ARROW keysto changethe
value.
27. After a value is selected, press ENTER to retain that value.
Setting Fuzzy
Logic Parameters

20
1. Press the UP ARROW and ENTER keys to enter the
Secondary Menu.
2. Press the INDEX key until Fint appears on the display. Fint
determines the amount of impact fuzzy logic will have on the
output, and can be 0 to 100%. 0% is OFF.
3. Use the UP ARROW and DOWN ARROW keys to change the
value.
4. After a value is selected, press ENTER to retain that value.
The following menu items will not appear if Fint is set to 0%.
5. Press the INDEX key until Fbnd appears on the display. Fbnd
is the bandwidth of the fuzzy logic, and can be set at 0 to 4000.
The units depend on what value the menu item Unit is set for.
Set Fbnd equal to PID proportional band for best results.
6. Use the UP ARROW and DOWN ARROW keys to change the
value.
7. After a value is selected, press ENTER to retain that value.
8. Press the INDEX key until FrtE appears on the display. FrtE is
the fuzzy logic’s rate of change with a range of 0.00 to 99.99
counts/second. For best initial setting, find the count/second
change of process value near setpoint 1 with output on.
Multiply this value by 3 and set FrtE to this value.
9. Use the UP ARROW and DOWN ARROW keys to change the
value.
10. After a value is selected, press ENTER to retain that value.
Installation The following procedure should be used when installing the
BriskONE temperature controller.
1. Choose an appropriate location with the following:
• Proximity to a suitable power supply.
• Appropriate clearances (for example: clearance to allow
easy installation of connectors).
• Ambient temperature does not go beyond the range of -
10 to +55 oC (+14 to 131 oF).
• Humidity conditions do not go beyond 0 to 90% up to 40
oC non-condensing, 10 to 50% at 55 oC non-condensing
2. If the temperature controller is not to be mounted, then:
• The controller’s resting surface must be stable and easy
to access for inspection.
Table of contents