Selec TC544C User manual

Auxiliary output
Relay contact (SPST) 5A resistive @ 250V AC / 30V DC
SSR drive (Voltage pulse) 12V DC, 30 mA
Relay contact (SPST) 5A resistive @ 250V AC / 30V DC
Control output (Relay or SSR user selectable)
Output specifications
Features :
! 4+4 digits, 7 segment LED dual display
! TC / RTD input
! PID / ON - OFF control
! Two set points
!o o
C / F selectable
! Auxiliary output : Relay / SSR
! Field selectable control output (Relay or SSR)
! Auto tune / Self tune
TC544C Temperature Controller
Display 4+4 digits, 7 Segment LED dual display
Height of upper display : 15.3mm
Height of lower display : 8mm
Display specifications
LED indication 1. Output 1 ON T : Auto tune
2. Output 2 ON S : Dwell timer
o
Indication accuracy For J, K & T inputs : 0.25% of F.S. ±1
o
For R & S inputs : 0.5% of F.S. ±2
(20 min of warm up time for TC inputs)
o
For RTD inputs : 0.1% of F.S. ±1
(F.S. = Full scale)
Input filter (FTC) 0.2 to 10.0sec
Input specifications
o
Resolution 0.1 / 1 for TC / RTD inputs
o
(fixed 1 for R & S type TC input)
Inputs Thermocouple (J, K, T, R, S) / RTD (PT100)
Sampling time 250 ms
o o
Temperature unit C / F selectable
o
Hysteresis 0.1 to 99.9
o
Proportional band (P) 1.0 to 400.0
Cycle time-cool 0.1 to 99.9 sec
Dead band Programmable from set point low limit
to set point high limit.
Settings for alarm output
Modes Deviation, Absolute
Cycle time 0.1 to 99.9 sec
Heat-cool
Control action PID
o
Hysteresis width 0.1 to 99.9
o
Manual reset value -19.9 to 19.9
o
Proportional band-cool 0.0 to 400.0
Functional specifications
Derivative time (D) 0 to 9999 sec
Control action 1) PID Control with auto tuning
2) ON-OFF control
Integral time (I) 0 to 9999 sec
Weight 116 gms
Mechanical specifications
Mounting Panel
Supply voltage 90 to 270V AC / DC (50 / 60Hz)
Auxiliary supply specifications
Power consumption 6 VA max @ 230V AC
o o
Temperature Operating : 0 C to 50 C
o o
Storage : -20 C to 75 C
Environmental specifications
Humidity (non - condensing) 95% RH
Dimension (All are in mm)
Front bezel Side view Panel Cutout
Terminal Connection

Voltage dips and
interruptions
Dips : 0% residual voltage /
1 cycle (Criteria B), 40% residual voltage /
10 cycles 50Hz / 12 cycles 60Hz
(Criteria C)70% residual voltage /
25 cycles50Hz / 30 cycles 60Hz
(Criteria C)
Interruptions : 0% residual voltage /
250 cycles 50Hz / 300 cycles 60Hz
(Criteria C)
IEC 61000-4-11
Level III
Conducted emission
Radiated emission
Electrical fast transient
CISPR-11
CISPR-11
IEC 61000-4-4
Compliance
Applicable EMI / EMC standards
Product standard : IEC 61326-1
Category Standards compliance
ESD immunity Level III
Surge immunity +/- 2 kV common mode,
+/- 1 kV differential mode
Radiated susceptibility
Level III, 80 to 1000MHz
Level II, 1.4GHz to 2GHz
Level I, 2GHz to 2.7GHz
Conducted susceptibility Level II
IEC 61000-4-2
IEC 61000-4-5
IEC 61000-4-3
IEC 61000-4-6
TC544C Temperature Controller
Supply voltage
Output 2Output 1 Certification
Product code
RELAY
TC544C RELAY SSR 90 to 270V AC / DC
Ordering Information
Accessories (Optional)
Standard SELEC accessories that can be used with this product.
Mounting accessories (Supplied with units)
Input sensor ranges
Download
Device
Independent Downloader module (IDM)

Control Output
(Relay or SSR
user selectable)
OUTPUT SPECIFICATIONS
Relay Contact :
5A resistive@250V AC / 30V DC
SSR Drive Output (Voltage Pulse):
12V DC, 30 mA
Auxiliary Output Relay Contact :
5A resistive@250V AC / 30V DC
Supply Voltage
Temperature
POWER SUPPLY SPECIFICATIONS
85 to 270V AC / DC
(AC : 50 / 60 Hz )
Operating : 0 to 50°C
Storage : -20 to 75°C
Power Consumption 6 VA max@270V AC
Humidity
Weight
95% RH (non-condensing)
116 g
ELECTRICAL PRECAUTIONS DURING USE
Electrical noise generated by switching of inductive
loads can create momentary disruption, erratic display,
latch up, data loss or permanent damage to the
instrument.
To reduce noise :
a) Use of snubber circuits across loads as shown above,
is recommended.
b) Use separate shielded wires for inputs.
N
L
C NO
TC
LOAD
R C
TC
Snubber
MOV
TC
TC
N
L
Snubber
C NO
R C
Contactor
LOAD
C
MOV
For bigger loads, use interposing relay / contactor
For load current less than 0.5A
selec TC544C
Operating Instructions
OP723-V03
LOAD CONNECTIONS
1. The service life of the output relays depends on the
switching capacity and switching conditions. Consider
the actual application conditions and use the product
within the rated load and electrical service life.
2. Although the relay output is rated at 5/10 amps it is
always necessary to use an interposing relay or
contactor that will switch the load. This avoids damage to
the controller in the event of a fault short developing on
the power output circuit.
3. Always use a separate fused supply for the “power load
circuit”and do not take this from the live and neutral
terminals supplying power to the controller.
All safety related codifications, symbols and instructions
that appear in this operating manual or on the equipment must
be strictly followed to ensure the safety of the operating
personnel as well as the instrument.
If the equipment is not handled in a manner specified by
the manufacturer it might impair the protection provided by the
equipment.
Read complete instructions prior to installation and
operation of the unit.
WARNING : Risk of electric shock.
WIRING GUIDELINES
1. To prevent the risk of electric shock power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To eliminate electromagnetic interference use short wire
with adequate ratings; twists of the same in equal size shall
be made. For the input and output signal lines, be sure to
use shielded wires and keep them away from each other.
3. Cable used for connection to power source, must have a
2
cross section of 1mm or greater. These wires shall have
insulation capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring. For the RTD
type, use a wiring material with a small lead resistance (5Ω
max per line) and no resistance differentials among three
wires.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
Isopropyl alcohol or any other cleaning agent.
SAFETY PRECAUTIONS
WARNING :
TERMINAL CONNECTIONS
1. When powering up for the first time, disconnect the
output connections.
2. Fuse Protection : The unit is normally supplied without a
power switch and fuses. Make wiring so that the fuse is
placed between the mains power supply switch and the
controller. (2 pole breaker fuse - rating : 275V AC,1A for
electrical circuitry is highly recommended)
3. Since this is a built-in-type equipment (finds place in main
control panel), its output terminals get connected to host
equipment. Such equipment shall also comply with basic
EMI/EMC and other safety requirements like BSEN61326-1
and BSEN 61010 respectively.
4. Thermal dissipation of equipment is met through
ventilation holes provided on chassis of equipment. Such
ventilation holes shall not be obstructed else it can lead to a
safety hazard.
5. The output terminals shall be strictly loaded to the
manufacturer specified values / range.
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals do
not remain accessible to the end user after installation and
Internal wiring.
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminals to facilitate power 'ON'
or ‘OFF’ function. However this switch or breaker must be
installed in a convenient position normally accessible to the
operator.
4. Use and store the temperature controller within the
specified ambient temperature and humidity ranges as
mentioned in this manual.
CAUTION
INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating sources, caustic vapors, oils,
steam or other unwanted process by-products.
4. Use the specified size of crimp terminals (M3.5 screws) to
wire the terminal block. Tighten the screws on the terminal
block using the tightening torque within the range of 1.2
N.m.
5. Do not connect anything to unused terminals.
MECHANICAL INSTALLATION
EMC GUIDELINES
1. Use proper input power cables with shortest
connections and twisted type.
2. Layout of connecting cables shall be away from any
internal EMI source.
Doc. Name : OP INST TC544C OP723-V03(Page 1 of 4)
48 x 48
52
52
76
45
5.4
46
46
SPECIFICATIONS
PARAMETERS
FUNCTIONAL SPECIFICATIONS
Control Method
Proportional Band(P)
1) PID control with Auto or
Self Tuning
2) ON-OFF control
1.0 to 400.0°C, 1.0 to 752.0°F
Integral Time(I)
Derivative Time(D)
Hysteresis Width
Dwell Timer
Manual Reset Value
Control Method
Proportional
Band-Cool
Cycle Time-Cool
Dead Band
HEAT COOL PID SPECIFICATIONS
0 to 9999 sec
0 to 9999 sec
0.1 to 99.9 sec
0 to 9999 min
-19.9 to 19.9°C / °F
PID
1.0 to 400.0°C
1.0 to 752.0°F
0.1 to 99.9 sec
SPLL to SPHL(Programmable)
Display
4 digits (White) + 4 digits (Green)
Display Height:-
White Display:- 15.3 mm
Green Display:- 8 mm
7 segment digital display
LED Indications
Input Signal
Sampling time
Keys
1 : Output 1 ON
2 : Output 2 ON
T : Tune
S : Dwell Timer
Thermocouple (J,K,T,R,S) /
RTD (PT100)
250 msec
3 keys for digital setting
INPUT SPECIFICATIONS
Resolution
Input Filter (FTC)
Temperature Unit
Indication Accuracy
0.1 / 1° for TC/RTD input
(Fixed 1° for R & S type TC input)
0.2 to 10.0 sec
oC / °F selectable
For TC inputs :
0.25% of F. S ±1°C
For R & S inputs :
0.5% of F. S ±2°C
( 30 min of warm up time
for TC input )
For RTD inputs :
0.1% of F. S ±1°C
Cycle Time
0.1 to 99.9°C
+
SSR
SSR
TC /RTD1
+
TC /RTD2
RTD3
NO2
COM1
NO1
COM2
( )
L
+
N
( )

Resolution: 1 Resolution: 0.1
RANGE
INPUT TYPE
UNIT
FUNCTIONS
To view Level 1
To view Level 2
To view Protection Level
KEY PRESS
Press key for 3 sec.
Press key for 3 sec.
Press + keys for 3 sec.
FRONT KEYS DESCRIPTION
ONLINE
To view online
parameters
PROGRAMMING MODE
To change online
parameter values
Press + / to change
parameter value.
Lower display selectable between
SET1/SET2/TIME using key.
To view parameters on
the same level.
To increase or decrease
the value of a particular
parameter.
or key once to view the next or
previous function in operational menu.
+ to increase and + to
decrease the function value.
Note : Parameter value will not alter
when respective level is locked.
NOTE : The unit will auto exit programming mode after 30 sec.
of inactivity.
By pressing the or or + keys for 3 sec.
OR
NOTE : Elapsed time / Remaining time dependent on the
selection of ONL parameter in level1.
1Process-value (PV) /
Parameter name
display
1) Displays a process value (PV).
2) Displays the parameter symbols
at configuration mode/online menu.
3) Displays PV error conditions.
(refer Table 2)
FRONT PANEL DESCRIPTION
4
3
1
2
1T
2
5
S
6
5Tune
6Dwell timer
Auto tune : Blinking (With faster rate)
Self tune : Blinking (With slower rate)
Blinking : Dwell timer is in progress.
Continuous ON : Time over.
3Control output 1
indication
2Parameter setting
display
The LED is glow when the control
output 1 is ON
Displays the parameter settings at
configuration mode/online menu.
4Control output 2
indication
The LED is glow when the control
output 2 is ON
FOR THERMOCOUPLE
J-199 to 750 °C
When an error has occurred, the upper display indicates error
codes as given below.
Error
Sensor break /
Over range condition
Sensor reverse /
Under range condition OFF
OFF
Description Control Output
Status
Table 2 : ERROR DISPLAY
T
R, S
If upper display is selected as / then,
Pressing key will show on Upper display : /
Lower display: <0>
Press + / keys to increment / decrement
/ value.
If upper display is selected as then,
Pressing key will show on Upper display :
Lower display : <50>
Press + / keys to increment / decrement
value.
Range : SPLL to SPHL
Default : 50
Programming online parameters
Setpoint 1
Range : SPLL to SPHL
Setpoint 2 / Dead band Default : 0
If upper display is selected as / then,
Pressing key will show on Upper display :
Lower display : <OFF>
Press + / keys to increment / decrement
time value.
Range : OFF, 1 to 9999 min
Dwell Timer Default : OFF
Use only the correct thermocouple wire or
compensating cable from the probe to instrument
terminals avoiding joints in the cable if possible.
Failure to use the correct wire type will lead to
inaccurate readings.
Ensure that the input sensor connected at the
terminals and the input type set in the temperature
controller configuration are the same.
USER GUIDEUSER GUIDE
1. Display Bias : This function is used to adjust the PV
value in cases where it is necessary for PV value to agree
with another recorder or indicator, or when the sensor
cannot be mounted in correct location.
2. Filter Time Constant : The input filter is used to filter out
quick changes that occur to the process variable in a
dynamic or quick responding application which causes
erratic control.
The digital filter also aids in controlling processes where
the electrical noise affects the input signal.
Larger the value of FTC entered, greater the filter added
and the slower the controller reacts to the process and
vice versa.
3. Auto tune (AT) : The Auto-tuning function automatically
computes and sets the proportional band (P),
integral time (I), Derivative time (D), ARW% and
cycle time (CY.T) as per process characteristics.
Tune LED blinks at faster rate when auto-tuning is in
progress.
At the completion of Auto-tuning, Tune LED stops
blinking.
If the power goes OFF before auto-tuning is completed,
Auto-tuning will be restarted at next power ON.
!
!
!
Temp.
set point
Proportional band
PID - time proportioning with auto reset & rate
Time
AT off
!
!
!
Self-tuning is initiated under the following conditions :
1) When setpoint is altered.
2) When tune mode is altered. (TUNE=ST)
ST will start only if PV < 50% of setpoint.
ST will work only when ACT=RE.
6. Self Tune (ST) : It is used where modification of PID
parameters is required repeatedly due to frequent
change in process condition eg. Setpoint.
Tune LED blinks at slower rate when Self-tuning is in
progress.
At the completion of self-tuning, Tune LED stop
blinking.
!
!
Time
Set point
Temp. Proportional band Reduced overshoot
5. Manual Reset (for PID control & I = 0) : After some
time the process temperature settles at some point
and there is a difference between the set temperature
& the controlled temperature. This difference can be
removed by setting the manual reset value equal &
opposite to the offset.
!
!
If auto-tuning is not completed after 3-4 cycles, the auto-
tuning is suspected to fail. In this case, check the wiring
& parameters such as the control action, input type, etc.
Carry out the auto-tuning again, if there is a change in
setpoint or process parameters.
4. ON/OFF control action (For Reverse Mode) :
The relay is ‘ON’ up to the set temperature and cuts
‘OFF' above the set temperature. As the temperature of
the system drops, the relay is switched ‘ON' at a
temperature slightly lower than the set point.
HYSTERESIS :
The difference between the temperature at which
relay switches ‘ON’ and at which the relay switches
‘OFF’ is the hysteresis or dead band.
set point
Temp.
Offset Manual reset
adjusted
Time Proportional With Manual Reset
Time
set point
overshoot
Hysteresis
ON ONOFF
Output
Temp.
Time
Reverse
set point
Hysteresis
OFF ON OFF
Temp.
Time
Output
Forward
Table 1 : INPUT RANGE
Resolution: 1 Resolution: 0.1
-238 to 1562 -199.9 to 999.9
RANGE
PT100
FOR RTD
INPUT TYPE
°F
-150 to 850 -150.0 to 850.0 °C
UNIT
-199 to 1350
-199 to 400
0 to 1750
-199 to 999
-199 to 400
N/A
-328 to 2462
-328 to 750
32 to 3182
-199 to 999
-199 to 750
N/A
°C
°C
°C
°F
°F
°F
-328 to 1382 -199 to 999 °F
K
-199 to 750
TC544
Doc. Name : OP INST TC544C OP723-V03(Page 2 of 4)
7. Thermocouple Compensation :
COMP = YES
Configure Yes if compensating cable is connected as
thermocouple extension. Yes should also be configured
in the case if the sensor is directly connected to the
terminal without extension.
COMP = NO
Configure No if non-compensating cable is connected
as thermocouple extension.
IDM Level
IndependentDownloader Module
Upload from product to IDM
Download te Parameter
Display Parameter Description
Download from IDM to product
Operation Successful
Operation unsuccessful
Key
Key
+ Key
+ Key /
/
KeyKey
KeyKey
(Blinking)
(Blinking)
Note:
1) IDM Level - IDM should be connected before
powering on the unit to enter in IDM Level.
2) Long Press or key for 3 sec to exit from IDM mode.
Caution: After Downloading, switch of the unit and then remove the IDM
**IDM is applicable only for IDM compatible Product.

Level 1 Level 2
Display DisplayDefault
Value
Default
Value
Range Range
J/K/T/R/S/RTD
1/0.1
1.0 to 400.0°
°C/°F
0 to 9999 sec
Min range of sensor
selected to SPHL
0 to 9999 sec
SPLL to Max range
of sensor selected
AUTO/USR.F
0.2 to10.0 sec 0.1 to 99.9 sec
0.1 to 99.9 sec
RE/FD
RE/FD/TIME
NO/YES
0.1 to 99.9°
0.1 to 99.9°
PID/ONF
RELAY/SSR
-19.9 to +19.9°
1.0 to 400.0°
NO/YES
OFF, 1 to 9999 min
-19.9 to 19.9°
Display
Condition
Display
Condition
Not prompted
for R & S type
For CNTL=ONF
For HC=NO or
HC=YES &
CNTL=ONF
For CNTL=PID
& I=0
Description
Input type
(Refer Table 1)
Tune
(Refer user guide)
Display Resolution
Proportional band
Temperature unit
Integral time
Set point low limit Derivative time
Set point high limit Cycle time mode
Cycle time
Cycle time-cool
Control action for
relay 1
Control action for
relay 2
Factory default
(Reset all)
Hysteresis 1
Hysteresis 2
Control logic
Control Output selection
Dwell mode enable
Manual reset
Proportional
band-cool
Heat-cool mode
selection
POWER ON
OPERATIONAL MENU
Description
Dwell time
Display bias
Filter time constant
NO/YES
When HC=NO.
TIME prompted
when DWEL
=YES
When DWEL
=YES
When CNTL
=PID
REMN/ELPS
1.0 to 100.0%
Online menu for timer
Anti-reset windup %
DEV/ABS
Relay 2 type When
ACT2=RE/FD
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
& HC=YES
When DWEL
=YES
CONFIGURATION INSTRUCTIONS
Press once to view online parameters Press for 3 sec to enter Level 2 Press once to view next parameter in configuration menu
Press for 3 sec to view Level 1 Press once to view previous parameter in configuration menu
+ or + Allows the user to increase or decrease associated parameter value or or +To exit configuration menu press any of these keys for 3 sec
+Press for 3 sec to enter protection Level
Not prompted
for HC=YES
Protection Level
Display Default
Value
Range
UNLK/READ
Display
Condition
Lock setpoint 1
Lock level 1
Lock level 2
Lock dwell time
Description
Prompted when
DWEL=YES
Note
UNLK/READ/LOCK
UNLK/READ/LOCK
UNLK/READ/LOCK
UNLK/READ/LOCK
Lock setpoint 2
Press key for 3sec.
Press + keys for 3sec.
1. Locking parameters (LVL1 or LVL2 or SP or DWEL) will not permit
change in the value of respective level parameters.
Time value (online) can be altered only when DWEL is not locked
in protection level.
2. Continuous operation of + / keys for SP or other parameters
makes update speed faster in 3 stages after 3 sec.
For CNTL=PID
& HC=YES
Note : At power ON lower display shows (momentary) input type selected in Level 1.
Press key for 3sec.
KEY FUNCTIONS
OFF / ST / AT
1T
2S
TC544
Doc. Name : OP INST TC544C OP723-V03(Page 3 of 4)
YES/NO

K
RTD
SENSOR
SELECTION
VERIFICATION
VALUE (°C)
25.0
0.0
475.0
323.5
975.0
800.0
CALIBRATION CERTIFICATE
Model No : TC544C
Claimed Accuracy :
For TC inputs : 0.25% of FS ±1°C
For R & S inputs : 0.5% of F.S ±2°C
(30 min of warm up time for TC input)
For RTD inputs : 0.1% of FS ±1°C
Standard used for Calibration of product is
traceable to NABL
The calibration of this unit has been verified at the
following values :
The thermocouple / RTD curves are linearized in
this microprocessor based product; and hence the
values interpolated across the input range are also
equally accurate ; at every point in the curve.
Unit is accepted as accuracy is within the specified
limit of claimed accuracy and certificate is valid upto
one year from the date of issue.
(Specifications are subject to change, since development is
a continuous process.)
Selec Controls Pvt. Ltd., India
Factory Address :
EL-27/1, Electronic Zone, TTC Industrial Area, MIDC, Mahape,
Navi Mumbai - 400 710, INDIA.
Tel. No. : +91-22-41 418 452/468 | Fax No. : +91-22-28471733
Toll free : 1800 227 353 (BSNL/MTNL Subscribers only)
Website : www.selec.com | Email : sales@selec.com
Doc. Name : OP INST TC544C OP723-V03(Page 4 of 4)
Other Selec Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

IFM
IFM TM45 1 Series operating instructions

Sentera Controls
Sentera Controls DXTP Mounting and operating instructions

turck
turck TS700 2UPN8-H1141 Series Instructions for use

Sartorius
Sartorius YTM05MA operating instructions

Golander
Golander GL102B user guide

DELTA DORE
DELTA DORE PACK TYBOX 5000 Instructions for use