Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 12.0
I0000791
PRODUCT SPECIFICATIONS
Supply Voltage:
4-20mA (250 Load): 16-36 VDC / 24VAC ± 10 %, 50/60 Hz
4-20mA (500 Load): 21-36 VDC / 24VAC ± 10 %, 50/60 Hz
0-5 VDC: 12-36 VDC / 24VAC ± 10 %, 50/60 Hz
0-10 VDC: 16-36 VDC / 24VAC ± 10 %, 50/60 Hz
Supply Current mA:
[Power Consumption]
4-20 mA Output: 23 mA minimum [0.83 VA]
VDC Output Signals: 5 mA maximum [0.18 VA]
Output Signals:
4-20 mA: 2-Wire Loop Powered (Output limited to 20.5 mA Max.)
4-20 mA: 3-Wire, VAC Powered (Output limited to 20.5 mA Max.)
0-5 VDC, 1-6 VDC, or 0-10 VDC: 3-Wire, VAC or VDC Powered
(Output limited to 5.25, 6.25, & 10.25 VDC)
Sensor Accuracy:± 0.5 % FSO (Standard); ± 0.25 % FSO (Optional)
Operating Temperature Range: 32 to 185 °F (0 to 85 °C)
Compensated Temperature Range: 32 to 122 °F (0 to 50 °C)
Humidity: 10 to 95 % RH, non-condensing
Thermal Eects2: ± 0.056 % FSO/ºF (± 0.10 % FSO/ºC)
Warm Up Time: 15 Minutes
Response Time (T95): 4 Seconds
Output Update Rate: 0.5 Second intervals
Zero Function: Pushbutton Zero Function (Recommended after 15 minutes warm up)
Proof Pressure [Burst Pressure]:
Ranges < 1” wc (248.84 Pa): Proof: 270” wc (67.2 kPa) [Burst: 415”wc
(103.3kPa)]
Ranges > 1” wc (0.2488 kPa) to < 10” wc (2.488 kPa): Proof: 350”wc (87.12
kPa) [Burst: 550”wc (136.9kPa)]
Ranges > 10” wc (2.488 kPa) to < 40” wc (9953.6 kPa): Proof: 562”wc (140
kPa) [Burst: 1004.7”wc (250 kPa)]
Media Types: Dry air or inert non-conductive gases
Din Rail Mounting: 35 mm (U.S. Patent No. 7,416,421)
Wiring Connections [Wire Size]: 3 Position de-pluggable screw terminal block
[14 AWG (1.628 mm²) to 24 AWG (0.5105 mm²)]
Terminal Block Torque Rating: 4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Tubing Size Accepted: 0.250”(6.35mm) O.D. x 0.170”(4.318mm) I.D. | Push-On Flexible Poly Tubing
Enclosure Material [Flame Rating]: Polycarbonate [UL 94 V-0]
WARRANTY
The ACI MLP2 sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.