ACO DMMS User manual

ACO - DMMS - DIGISYS
Moisture Measuring System
Operating Instructions
ACO-DMMS- Moisture Measuring System (2008)


ACO AUTOMATION COMPONENTS
Table of Contents
1. FOREWORD .............................................................................................................. 3
2. NOTES ON SAFETY.................................................................................................. 4
3. TECHNICAL DATA.................................................................................................... 6
3.1 DMMS sensor .....................................................................................................................................6
3.2 Bus connection socket......................................................................................................................7
3.3 Interchange and evaluation unit.......................................................................................................8
3.4 Power pack (DIN rail mounting)........................................................................................................9
3.5 Profibus DP measured value transmission...................................................................................10
3.6 PC-Software......................................................................................................................................10
4. SYSTEM SUMMARY ...............................................................................................11
5. MOISTURE SENSOR................................................................................................12
6. DIGISYS BUS CONNECTION SOCKET...................................................................14
7. DIGISYS INTERCHANGE AND EVALUATION UNIT...............................................15
7.1 Measuring operation........................................................................................................................15
7.2 Configuration and programming interface....................................................................................15
7.3 LED-signalisation...........................................................................................................................156
7.4 Profibus...........................................................................................................................................157
7.5 Connection / wiring..........................................................................................................................18
8. PC-SOFTWARE DMMS/DIGISYS ............................................................................20
8.1 Installation ........................................................................................................................................20
8.2 General notes on operation ............................................................................................................21
8.3 Extras / Settings...............................................................................................................................22
8.4 info.....................................................................................................................................................22
8.5 Moisture / Temperture-Image..........................................................................................................23
8.6 Service ..............................................................................................................................................23
8.7 Configuration....................................................................................................................................23
8.8 Test image ........................................................................................................................................25
8.9 Take Sample .....................................................................................................................................26
8.10 Curves ...............................................................................................................................................27
8.11 System ..............................................................................................................................................29
8.12 Example - install a measuring channel..........................................................................................30
8.13 Error reports .....................................................................................................................................32
8.14 Software versions ............................................................................................................................32
9. SPARE-PARTS LIST ................................................................................................33
1


ACO AUTOMATION COMPONENTS
1. Foreword
These operating instructions relay important information regarding safety, operation, maintenance and
repair.
Every person involved with utilisation, assembly, start-up, operation and maintenance, must have read and
understood these operating instructions and must retain them within their immediate proximity at all times.
In order that a safe, fault-free and cost-effective operation can be guaranteed, it is absolutely imperative that
the notes on safety, operation and maintenance are strictly adhered to.
The operating instructions are to be supplemented with any existing national guidelines concerning accident-
prevention and environmental protection.
The valid, relative regulations for accident-prevention in the country of utilisation, as well as on the applica-
tion site and the recognised, specialist-technical laws for safe and professional operation are to be noted.
The operating instructions must be available at the application site of the measuring system at all times.
Acknowledgements
We would like to thank the company, WAGO Kontakttechnik GmbH, Minden, for the documentation material
which was so kindly submitted by them.
Registered trademarks
MS-WINDOWS (95/98/ME, NT4, 2000, XP), MS-EXCEL are registered trademarks of the Microsoft Corpora-
tion.
PROFIBUS s a registered trademark of the PROFIBUS User Organisation PNO.
Copyright and company address
© Copyright 2005
ACO AUTOMATION COMPONENTS
Johannes Mergl e.k.
Industriestrasse 2
79793 Wutöschingen-Horheim /Germany
Tel.: +49 7746 91316
Fax.:+49 7746 91317
ACO AUTOMATION COMPONENTS have taken all necessary care to ensure utmost correctness during compilation of these operating
instructions. The data specified serves the product description only and should not be interpreted as guaranteed properties in a legal
sense. We refuse to accept liability for errors, omissions or the data included herein as regards utilisation.
All rights, particularly those rights regarding reproduction and distribution, as well as translations, are reserved. Under no circumstances
should any part of this work be reproduced or stored within an electrical system, modified or distributed in any way or form (printing,
photocopying, microfilm or reprinted) without expressed written permission from ACO/LMT.
As errors may never be completely ruled out, despite every endeavour on our behalf, we are always appreciative of any comments
submitted.
3

ACO AUTOMATION COMPONENTS
2. Notes on safety
Warning information and symbols
Tasks and operating phases which represent an increased danger to persons or the system are indicated
with special symbols.
In these operating instructions, the symbols carry the following meanings:
DANGER indicates a particularly dangerous situation.
Possible causes:
DANGER
•Serious injuries or death.
•Serious consequential damage to the plant.
WARNING indicates a very dangerous situation.
Possible causes:
•Very serious injuries, possibly fatal.
•Serious consequential damage to the plant.
WARNING
CAUTION indicates a possibly dangerous situation.
Possible causes:
•Serious injuries. CAUTION
•Damage to the plant.
INFO
Important note or important information.
Operation and maintenance of the plant becomes considerably easier if this information is observed
Use as directed
•The measuring system has been designed around state-of-the-art technology and all recognised regula-
tions regarding technical safety. Nevertheless, even if these standards are observed, there is a possibil-
ity that the life of the user or a third party could be put at risk, or that the plant or other equipment could
sustain damage.
•Only use the measuring system as directed i.e conscientious of safety and dangers which may occur,
and only if it can be guaranteed that the system is in a technically sound condition! In particular, faults
which may impeded safety must be remedied immediately.
•The measuring system is to be used exclusively for measuring the water content in the bulk material and
liquids or in the dry matter in water. It is not permissible to measure the water content in flammable or
explosive liquids. Any other use, as well as exaggerated use, is not considered use as directed. The
manufacturer or supplier can not be held responsible for any damage which occurs as a result of this.
The user is solely responsible. Use as directed also includes observation of the operating instructions
and adherence to the maintenance and inspection guidelines.
4

ACO AUTOMATION COMPONENTS
General operational safety
•Ensure that the operating instructions are on-hand in the switch cabinet, within which the Interchange
and evaluation unit is installed, at all times!
•Observe and apply any supplements to the operating instructions, general valid, legal and other obliga-
tory regulations regarding accident-prevention (e.g. providing or wearing of personal protective equip-
ment, road traffic regulations) and environmental protection (e.g. handling of dangerous substances)!
•Supplement the operating instructions with all necessary information including duty of supervision and
reporting obligations for the observance of operational particulars (e.g. work organisation, working pro-
cedures, hiring of personnel).
•Refrain from all working procedures which appear dubious as regards safety!
•Ensure that personnel are familiar with the location of fire extinguishers and how to use them! Observe
all fire alarms and firefighting possibilities!
•Ensure safe and environmentally-friendly disposal of all fuels and lubricants, as well as replacement
parts!
Personnel and supervision
•Personnel which are actively involved with the measuring system must have read the operating instruc-
tions before beginning work, in particular the chapter concerning the notes on safety. During operation is
too late. This applies in particular to personnel working opportunely on the sensor (e.g. when carrying
out maintenance).
•Carry out regular checks as to whether the personnel are working conscientiously as regards safety, and
are observing the operating instructions!
•Ensure that only contracted personnel are actively involved with the measuring system
•Employ trained or instructed personnel only. Explain responsibilities regarding operation, maintenance
and repair clearly to all personnel! Observe the legal minimum age!
•Before commencing work, inform all operating personnel of repair tasks which may be required! Nomi-
nate supervisors! Only allow repair tasks to be carried out by specialist personnel.
•Tasks to the electrical equipment of the measuring system may only be carried out by electrical special-
ists or by trained personnel under the instruction and supervision of an electrical specialist in accordance
with electro-technical regulations.
•Always wear personal protective equipment when necessary or when otherwise required by the safety
guidelines!
Operation and maintenance
•Prescribed times or intervals specified in the operating instructions or for repeated inspections must be
adhered to!
•For all tasks which concern operation or adjustment of the measuring system, as well as the safety-
relevant devices, observe the activation and deactivation procedures, as well as control displays in ac-
cordance with the operating instructions and notes for repair tasks!
•All screw connections loosened for maintenance and repair tasks must be retightened!
•Spare-parts must meet the technical requirements determined by the manufacturer. This can always be
guaranteed by using original spare-parts.
Assembly and repair
•Before commencing work, inform all operating personnel of repair tasks which may be required! Nomi-
nate supervisors! Only allow repair tasks to be carried out by specialist personnel.
•If not expressly otherwise specified, only carry out tasks to the measuring system when the voltage sup-
ply for the system has been disconnected. Always disengage the power supply prior to carrying out work
on the measuring system.
5

ACO AUTOMATION COMPONENTS Technical data
3. Technical data
3.1 DMMS sensor
Technical data sheet:
Physical principal Determination of capacity in the high-frequency stray field
frequency
Measuring location Outside of the silo, within the silo, via deflection plate, on a
belt with guide shoe slides, pipes, conveyor screws
Measuring frequency 0.016 ..0.022 GHz
Measuring range 0 %M - 100 %M (adjustable measuring window)
Capacity dissolution 10 fF
Actualisation cycle 32.64 ms
Sampling rate mean value calculator 16 × 106- 25 × 106
Maximum attainable measuring precision ± 0.05 %F 1.)
Measured value transmission digital: RS-485{XE "RS-485"}, multiprocessor protocol
Max. number of sensors at the bus 16
Maximum bus length 1.2 km
Microprocessor AT89C51ED2
Power supply 8..30V, 0.4 VA
Measuring range, temperature measurement -10°C - 90°C
Measuring precision, temperature measurement ± 0.5°C
Operational ambient temperature 5°C - 72°C
Operating temperature, electronic -20°C - 80°C
Storage temperature -25°C - 80°C
Protection device IP68
Connection line, type LiYD11Y 6 x 0.14mm2
Connection line, length 6m
Wear protection ZrO2 Al2O3
Material housing / flange V4A 1.4571
Dimension: ∅/ height 78 / 57 mm
Weight without cable 500 g
Weight of tensioning flange 300 g
1.) Representative of the batch or of the time window with the continuous process ,in connection with the respective
evaluation unit DIGISYS, material-dependent, with ideal flow properties and with sound calibration
Dimensions illustration Master gauge
Ø
76
70
60 mm var
6

ACO AUTOMATION COMPONENTS
3.2 Bus connection socket
Technical data sheet:
Housing material Aluminium
Weight 200 g
Colour Grey
Height [mm] 57.5 mm
Height [inches] 2.26 in
Width [mm] 125 mm
Width [inches] 4.92 in
Depth [mm] 80 mm
Depth [inches] 3.15 in
Operating temperature -25 °C ... +85 °C
Storage temperature -25 °C ... +85 °C
Relative moisture (without condensation) 95 %
Identification of conformity CE
Vibration resistance in accordance with IEC 60068-2-6
Shock resistance in accordance with IEC 60068-2-27
Protection device IP 66
EMC interference immunity in accordance with EN 50082-2 (96)
EMC interference emission in accordance with EN 50081-2 (94)
Cable glands 4 x Pg 11 or M16 stainless steel
Shield clamps 4 x CAGE-CLAMP 2.5 mm²
Bus clamps 18 x CAGE-CLAMP 0.5 mm²
Cross-section from [mm²] 0.08 mm²
Cross-section up to [mm²] 0.5 mm²
Cross-section from [AWG] 28 AWG
Cross-section up to [AWG] 20 AWG
Stripping length [mm] 5 -6 mm
Stripping length [inches] 0.236 in
Dimension illustration:
113.00
125.00
52.00
57.50
80.00
ø8.00
ø4.00
7

ACO AUTOMATION COMPONENTS Technical data
3.3 Interchange and evaluation unit
These technical data sheets can be obtained directly from WAGO Kontakttechnik GmbH, Minden, or by
way of the internet site: http://www.wago.com
WAGO 750-833 WAGO 750-550
Field bus controller 2-channel
PROFIBUS DP/V1 analogue output terminal
with ACO/LMT Firmware 0..10 V
WAGO 750-513
WAGO 750-402
Relay output terminal 250V
AC, 30V DC,
4-channel digital
input terminal 3ms 2A AC/DC
WAGO 750-504 WAGO 750-653/000-020
4-channel digital Serial interface RS485
output terminal
WAGO 750-554
2-channel WAGO 750-600
analogue output terminal End terminal
4..20mA
HAMA 00049262
USB / RS-232 - adapter
http://www.hama.de
Dimension illustration:
12.0
ADDRESS
35.0
100.0
48.2
35.0
X10
X1
DIA
USR
BUS
RUN
I/O
BF
PROFIBUS
25.0
25.0
12.0 10.0
8

ACO AUTOMATION COMPONENTS
3.4 Power pack (DIN rail mounting)
Technical data sheet:
Type PH15-2406
Manufacturer: MGV Stromversorgungen (Internet: www.mgv.de)
Weight 0.130kg
Dimensions (B x H x D) 25 x 76 x 74 mm
Operating temperature 0...70°C, with free convection
Overtemperature protection yes
Input
Mains voltage range Ue AC 94 – 264 V, 50/60 Hz
Efficiency 77 – 87%
current limitation = 20 A peak in cold conditions
Derating 2.5% / K from +50°C
Mains buffering > 40 ms (with Ue = 187 VAC)
Interbal fuse 2.5 A flink
Output
Nominal voltage tolerance +2% / -1%, at 5V + 3%
Residual ripple < 50 mVss
Interference voltage < 150 mVss
Temperature coefficient 0.025% / K
Switch on / switch off performance No overshooting of Ua (soft-start)
Rise-delay time 0.8 s
Run-up time 30 ms
Overvoltage protection < 130% from Ua nominal
Current limitation 105 – 200% / 250% I nominal,
Continious short circuit proof yes
Operation indicator Green LED
Protection IEC 60950 / EN 60950 / VDE 0805 safety classification I
UL508 listed, UL 60950, CSA 22.2 - 60950
Dimension illustration:
25.0mm
75.0mm
N
L
PE
-
+
9

ACO AUTOMATION COMPONENTS Technical data
3.5 PROFIBUS DP measured value transmission
Technical data sheet:
Hardware WAGO 750-833/000-002 field bus controller
Transmission medium Cu-cable EN50170
Bus segment length 100..1200m
Baud rate 9600.. 12M bit/s
Bus connector 9-pin Sub-D male
Protocol DP / DPVI
GSD - file WAGOB756.GSD download: www.wago.com
Measuring channels 1..16
1.) input data / measuring channel(s) (n*2+2) byte
2.) Output data / measuring channel(s) (n*6+4) byte
1.) This regards output variables where the PROFIBUS-Master is concerned.
2.) This regards input variables where the PROFIBUS-Master is concerned.
3.6 PC-software
Technical data sheet:
Channels visualisation moisture 16 of 16
Number of channels for simultaneous visualisation moisture 16 of 16
Manual/automatic changeover 16 of 16
Graphic measured value representation 1 of 16
Parameterisation 1 of 16
Calibration 1 of 16
Material curve changeover yes
Service and diagnosis yes
Software system requirement
Microsoft Windows ® WIN 95/98/ME,
NT4.0, 2000, XP
Operating systems
Documentation Acrobat Reader
Hardware system requirement:
CPU Pentium min133MHz
RAM – memory 32MB
Harddisk free 10MB
Installation drive CD-ROM
Interface RS232B or USB / RS-232 adapter
if necessary, LAN connection Ethernet 10/100 Mbit/s
10

ACO AUTOMATION COMPONENTS
4. System summary
The DIGISYS with intelligent bus sensors is an independently operating moisture-measuring system, without
the necessity of installing indication and operating units. It is thus ideally suited for controls featuring a visu-
alisation system. The Interchange and evaluation unit can be installed compactly in a switch cabinet. A multi-
tude of interfaces can be realised for the overriding systems. An easy-to-use PC-software allows a quick and
precise calibration of the measuring channel.
1.. 16
Moisture sensors
on the bus
Sensor bus
Bus length
max. 1200m
Bus connection socket-
for 1..2 sensors
DIGISYS Interchange and
evaluation unit
modular upgradable
Power pack
24V DC
PROFIBUS-DP
Measured value transmission-
Material curve chan
g
e-ove
r
DIGISYS/DMMS PC software
Measured value display, cali-
bration,set-up, material curves,
recording
Analogue measured value out-
put 0-10V, 4-20mA digital in-
puts for Start/Stop control
RS-232
and material curve change-over, digital
outputs for limit signalisation
USB
11

ACO AUTOMATION COMPONENTS DMMS moisture sensor
5. DMMS moisture sensor
The DMMS sensor is a so-called "intelligent sensor", thus, the installed µ-processor allows complete solving
of the problem in one component, as well as an expanded functionality.
•Direct digital measuring procedure
•Calibration data memory
•Linearisation
•Inspection of thresholds
•Start / Stop control
•Mean value calculation
•Temperature measurement
•Temperature compensation
•Material-specific adjustment
•Digital interface / networking
•Error report
A precise calibration at the factory allows complete reproducibility over a wide temperature range. The costly
material-specific adjustment therefore is also possible for wider measuring channels and no readjustment is
necessary, in the case the sensor is replaced.
The sensor receives a measuring task from the DIGISYS Interchange and evaluation unit and makes avail-
able the ready-processed measuring result available at the precise required time. The data transfer is re-
duced to a minimum and the resources of controls which have a higher priority are less burdened.
Sensor assembly
The sensor can be installed in a container, guide shoe carriage, batching table or in a material chute using
the mounting flange. The sensor can be installed flush on wall thicknesses of 1 to 25 mm by shifting in the
flange.
•Open up a mounting hole in the wall partition - see master gauge
•Loosen the straining screw (E)
•Fix the mounting flange (C) with 3 countersunk screws (a) on the rear side of the wall partition, leav-
ing the nuts (d) loose
•Adjust the sensor in the flange until it is flush with the wall partition.
•Tighten the straining screw (E) first, and then the fastening (B)
•Clamp the sensor cable to the bus connection socket and tighten the cable gland
Master gauge:
Assembly:
a: Countersunk
screw M5 with
Allen head
E
D
C
B
Ac
d
a
b
ø10.0
120°
R55
ø5.2
R39.1
b: Washer:
c: Snap ring
d: Nut M5
A: Wall partition
C: Mounting flange
D: Sensor
E: Straining screw
B: Fastening
12

ACO AUTOMATION COMPONENTS
CAUTION Damage to the system.
•Do not open the cable clamp on the sensor.
•Do not strike the ceramic wear shield directly with a hammer.
•Install the sensor flush to prevent material encrustations or premature wear.
•Hot water from evaporation in the silo damages the sensor or leads to measuring discrepancies.
•The temperature inside the sensor housing may not exceed 80°C.
•The sensor may not be installed in immediate proximity to vibratory discharge aids (vibrators).
•When replacing sensors, do not cut away the connecting cable of the old sensor.
•When filling the silo for the first time, ensure that the sensor is protected against falling rocks.
•A mounting flange installed at a tilt in the sensor can fall out if it becomes overloaded.
•The 3 fastening screws (a) and the straining screw (E) must be made of stainless steel.
Maintenance
•Correct functioning of the measuring channel (s) must undergo a daily inspection.
•The wear shield made of ceramic must be examined for damage and wear
•Remove any material which adheres to the ceramic wear shield.
•An even flow of material with sufficient over-layer (>50mm) must be present.
•The moisture measuring value must be verified via a laboratory test. A sufficient quantity of material,
representative of the mix, is extracted and at the same time the moisture measuring value or the digit
value is recorded. If the deviations prove too great, the calibration curves can be adjusted. (see PC soft-
ware or indication and parameterisation module)
Replacing the sensor
Electric shock!
Connection of the plant and all tasks to the electrical equip-
ment may only be carried out by an electrical specialist.
DANGER Moving machine parts!
The sensor can be fitted in the immediate proximity of mov-
ing machine parts. Switch off the machine!
1. Cut the voltage supply to the measuring system.
2. Open the bus connection socket, loosen the cable clamp and unclamp the sensor cable.
3. First loosen the fastening (B) and then loosen the straining screw (E) until the mounting flange releases
the sensor.
4. Install a new sensor in the mounting flange, adjust. and tighten the straining screw (E).
5. Tighten the fastening (B).
6. Clamp the sensor cable, tighten the cable clamp and connect the bus connection socket.
7. Clean and dry the surface of the sensor.
8. Start up the measuring system once again
9. Read off the digit value for the air and carry out an offset. A recalibration of the measuring channel is
then not necessary. (see PC software or APM)
13

ACO AUTOMATION COMPONENTS Bus connection socket
14
6. Bus connection socket
The ACO bus connection socket facilitates installation of the sensor bus:
•Protection type IP66
•Connection of 1 or 2 moisture sensors
•Connection of 1 or 2 bus lines
•Bus termination
•Allocation of sensor address
•Fine protection against lightning
•CAGE CLAMP connection technology
•4 cable clamps
Assembly of the bus connection socket
1. Fasten the socket using suitable screws
through the holes B.
2. Connect 1 or 2 sensors, the white and grey
wires serve to determine the sensor address.
3. Connect the cable from the sensor bus, at the
last socket attach clamps A and B as bus con-
nection instead of 120 Ohm resistance.
4. All shieldings on shield clamp
5. Tighten the cable glands.
6. Connection socket - mount the cover
Sensor
+-
ABKanal Nr.
gr
ws
gn
ge
rs
bn
B
Sensorbus
+-
AB
BUS
C1
V1
Sensor
R7
+-
AB
BUS
R8
R1
R2
R3
R4
Schirm
+-
ABKanal Nr.
gr
ws
gn
ge
rs
bn
R5
R6
Sensorbus
B
V2
Sensor Sensor cable connection
address + -
A
B Channel no.
1 bn rs ge gn ws gr
2 bn rs ge gn ws gr
3 bn rs ge gn ws gr
4 bn rs ge gn ws gr
5 bn rs ge gn ws gr
6 bn rs ge gn ws o----o gr
7 bn rs ge gn ws gr
Do not set any double
sensor addresses!
Sensor cable length is a
maximum 6m!
8 bn rs ge gn ws gr
Wire colours
{
XE 9 bn rs ge gn ws gr
bn brown 10 bn rs ge gn ws o-------o gr
rs pink 11 bn rs ge gn ws o----o gr
BUS
120
-
AB
+
ge yellow 12
bn rs ge gn ws o----o gr
gn green 13 bn rs ge gn ws gr
For the last connection socket, set a resistance
with 120 ohms between clam
p
s A and B . ws white 14
bn rs ge gn ws o----o gr
gr grey 15 bn rs ge gn ws gr
Circuit diagram:
o----o Bridge 16 bn rs ge gn ws gr
Schirm / shield
Sensorbus
+-AAB+-B
rs
gn
ge
ws
bn
gr
Sensor
R22k
R11k
R48k
R34k
V110N391K
C110n
gr
AB+-
rs
gn
ge
ws
bn
Sensor
R51k
R62k
R74k
R88k
A+- B
Sensorbus
V210N391K

ACO AUTOMATION COMPONENTS
7. DIGISYS interchange and evaluation unit
The ACO_DIGISYS interchange and evaluation unit is comprised of a WAGO - I/O - SYSTEM 750. A de-
tailed description of all components can be obtained from the company, WAGO Kontakttechnik GmbH, Min-
den, or alternatively, from the internet site from WAGO Kontakttechnik GmbH: http://www.wago.com.
The field bus controller 750-833000-002 includes a ACO-specific Firmware, comprising the complete ACO-
DIGISYS - approach:
•Communication with overriding system (PROFIBUS)
•Issue of measured values via diverse interfaces
•Start-Stop control mean value calculator
•Distribute measuring orders
•Storage of measuring channel configuration, curves, thresh-
olds etc.
•Summarisation of measured values from several sensors
•Material curve changeover
•Error report
7.1 Measuring operation
Moisture measuring is initiated automatically following activation of the DIGISYS.
No operation is necessary in this operating mode.
This operation is not discontinued, even within the service functions, thus the measurement continues to run
in the background.
7.2 Configuration and programming interface
The configuration and programming interface is located behind the cover flap. It is
used for communication with the PC-software, the indication and parameterisation
module and for transmission of the Firmware. The communication cable is con-
nected to the 4-pin port (1).
The switch for the operation mode (2) is also located behind the cover flap. The
switch (2) is a push-slide switch featuring three positions and a key function.
Functions of the operation mode switch
Operation mode switch (2) Function
From the middle to the upper
position Activate program processing (RUN)
From the upper to the middle
position Stop program processing (STOP)
Lower position Bootstrap for booting the Firmware, not necessary for the user.
Hardware-Reset
Press down (using a screwdriver,
for example) All outputs and flags are reset; Variables are set to 0 or to FALSE or to an initial
value. The Hardware - Reset can be initiated with STOP, as well as with RUN in
each position of the operation mode switch!
A change in operation mode occurs internally at the end of a PFC-cycle.
15

ACO AUTOMATION COMPONENTS DIGISYS interchange and evaluation unit
7.3 PROFIBUS DP
Moisture and temperature values, status and error reports from all 16 channels can be read from the control-
ler via the PROFIBUS DP, and all control signals such as Start, Fine and Manual can be set.
Detailed description 750-121 and a supplement for 750-333/-833 PROFIBUScan be ob-
tained from the WAGO Kontakttechnik GmbH company in Minden, or on their internet
site:http://www.wago.com
.
All documentation regarding the PROFIBUS is available on the PROFIBUS user organisation internet page:
www.PROFIBUS.com.
16

ACO AUTOMATION COMPONENTS
7.4 LED-signalisation
Explanation
LED Colour
A B C D green Operating voltage available
RUN green The field bus was efficiently initialised.
BF (flashing) red Communication via the PROFIBUS is not functioning.
DIA red An external diagnosis is being performed.
BUS Flashing code Projection error
Data cycle unavailable on the nodeFaulty operation of the
PROFIBUS nodeNormal operation of the PROFIBUS
node.Flash-access of the equipment-Firmware
Offflashing
redgreenorange
I/O
red Initiate system start
off Boot
flashing
green/orange
Sensors on the sensor bus are being searched for or occur-
rence, interchange and evaluation unit
green System running
USR
orange System running with indication and parameterisation module
red flashing
code
DIGISYS -error, see error - flashing code
Error - flashing code error signalisation
First wait until the LED begins to flicker red, then sequence flashes 4 times. e.g. error code = 2 5 1 4 :
flickering code 2 code 5 code 1 code4
The most important codes and their meaning:
Code Description Remedy
2 3 # $
2 4 # $
Measuring channel: # S-Adr.: $ - overrun mean value
calculator Start signal too long, adapt CMW-pause
Measuring channel: # S-Adr.: $ - TO measuring value
processing
2 5 # $ Eliminate sensor error (sequence error)
3 1 $ 1 Sensor S-Adr.: $ - used, however, not found Check cabling and addressing
3 2 $ 1 Sensor S-Adr.: $ - not used, however, found Check addressing, register sensor $
3 3 # $ Sensor channel: # S-Adr.: $ - data transfer error
3 4 # $ Sensor channel: # S-Adr.: $ - no answer
3 5 # $ Sensor channel: # S-Adr.: $ - incorrect answer Cabling, check power supply
3 6 # $ Sensor channel: # S-Adr.: $ - error report
3 11 $ 1 Sensor S-Adr.: $ - found twice Cabling, check addressing
7 6 1 1 WAGO RS-485 module unavailable
7 7 1 1 WAGO digital input module unavailable
7 8 1 1 WAGO digital output module unavailable
7 9 1 1 WAGO relay module unavailable
7 10 1 1 WAGO analogue output module unavailable
7 11 1 1 WAGO incorrect amount digital-input modules
Install WAGO I/O module or remove mod-
ule from the configuration
7 12 1 1 WAGO incorrect amount digital-output modules
7 13 1 1 WAGO incorrect amount relay modules
7 14 1 1 WAGO incorrect amount digital-input modules
# = Channel number 1..16 $= Sensor address 1..16
17

ACO AUTOMATION COMPONENTS DIGISYS interchange and evaluation unit
7.5 Connection / wiring
The I/O modules must be inserted in a determined sequence on a carrier rail (35x7.5 mm):
WAGO Module type
Amount
Field bus controller PROFIBUS DP / V1 with ACO/LMT soft-
ware
1750-833
0 to 4 750-402 4-channel digital input terminal 3ms
0 to 4 750-504 4-channel digital output terminal
2-channel analogue output terminal 4..20mA or2-channel ana-
logue output terminal 0..10 V
0 to 8 750-554750-550
0 to 8 750-513 Relay output terminal 250V AC, 30V DC, 2A AC/DC
1750-653 000-020 Serial interface RS-485 with sensor bus
1750-600 End terminal
Electric shock!
DANGER Connection of the plant and all tasks to the electrical equip-
ment may only be carried out by an electrical specialist.
Examples of wiring:
6
X10
2
4
S
3
8
S
ADDRESS
X1 3
M
7
M
+-AB
GPROFIBUS A H
1
2
USR
I/O
RxD
+
6
RxD
-
TxD
BF
DIA
BUS
24V 0V
+
1
RUN
-
5
TxD
+ -
J5
4
PROFIBUS-DP
A controller PROFIBUS DP
G RS485 interface
H end terminal
J terminal block
1 PROFIBUS cable/plug
2 PROFIBUS address
3 configuration interfaces
4 connection power pack 24V DC
5 terminating resistor120 ohm
6 bus cable sensor bus
+ - power supply sensors
A B data signal
shield
18
Other manuals for DMMS
1
This manual suits for next models
1
Table of contents
Other ACO Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

System Sensor
System Sensor PC4RLA Installation and maintenance instructions

HP
HP 4154A Operation and service manual

Cisco
Cisco TelePresence VCR MSE 8220 Getting started

Chauvin Arnoux
Chauvin Arnoux C.A 6531 user manual

Teledyne
Teledyne HVG-2020B instruction manual

Integrated control
Integrated control Temp Minder Color installation manual