•Field-pluggable microBlox input modules allow you to change input types on
this carrier, usually without recalibration. Modules are over-molded and
RoHS compliant, and offer superior shock, moisture, and dust protection.
•Channel has dual alarm outputs that is configured using Bluetooth wireless
technology. Two carrier models are available—one with mechanical relays
(5A/250VAC/30VDC), one with solid-state relays (1A/200Vpk AC/DC).
•Free Bluetooth wireless technology Configuration App with Android™ or iOS™
support, no additional software required.
•16-character Password Protection for Bluetooth wireless technology access.
•Designed, hardened, and thoroughly tested for use in Harsh Environments.
•CE Approved & UL/cUL Class I, Division 2 Approvals.
•FCC Conformity Class B.
•ATEX / IECEx Certified for Explosive Atmospheres.
II 3 G Ex nA nC* IIC T4 Gc -40oC ≤Ta ≤+75oC (* for Model uBTA-P-MR)
DEMKO 18 ATEX 2086X and IECEx UL 18.0092X
•Designed and manufactured for High Quality/High Reliability with AS9100
(Aerospace Quality)/ISO9001.
•Carrier includes both 0-5V/1-5V and 0-20mA/4-20mA transmitter outputs.
•Better than ±0.1% alarm and transmitter output accuracy.
•Wide ambient temperature operation from -40°C to +75°C.
•All I/O and power ports are transient protected.
•Wide-range isolated DC power input from 6-32V.
•LED indicators for Bluetooth wireless technology link, power, and each relay
aide trouble-shooting.
•High 1500VAC Safety Isolation between field input, transmitter output, relay
contacts (including between contacts), and power. Individually isolated for
common-mode voltages up to 250VAC, or 354V DC off DC power ground, on a
continuous basis (will withstand 1500VAC HIPOT/dielectric strength test for
one minute without breakdown). This complies with test requirements of
ANSI/ISA-82.01-1988 for voltage rating specified.
•Shock (25G) and Vibration Immunity (4G) - Conforms to: IEC 60068-2-6: 10-
500 Hz, 5G, 2 Hours/axis, for sinusoidal vibration; IEC 60068-2-64: 10-500 Hz,
5G-rms, 2 Hours/axis, for random vibration, and IEC 60068-2-27: 30G, 11ms
half-sine, 18 shocks at 6 orientations and 50G, 3ms half-sine, 18 shocks at 6
orientations, for mechanical shock.
•EMC (Electromagnetic Compatibility) –Min Immunity per BS EN 61000-6-1
(2007); CE marked, per EMC Directive 2014/30/EU. Electrostatic Discharge
Immunity (ESD), per IEC 61000-4-2; Radiated Field Immunity (RFI), per IEC
61000-4-3 and ETSI EN 301 489; Electrical Fast Transient Immunity (EFT), per
IEC 61000-4-4; Surge Immunity, per IEC 61000-4-5. Conducted RF Immunity
(CRFI), per IEC 61000-4-6.
•Emissions - This is a Class B Product with Emissions per BS EN 61000-6-3
(2007+A1:2011) and Spurious Emissions per ETSI EN 300 328. Enclosure Port,
per CISPR 16. Low Voltage AC Mains Port, per CISPR 16.
•Installation Category - Suitable for installation in a Pollution Degree 2
environment with an Installation Category (Over-voltage Category) II rating
per IEC 1010-1 (1990).