manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADEMCO
  6. •
  7. Transmitter
  8. •
  9. ADEMCO 5817CB User manual

ADEMCO 5817CB User manual

K5623V1 4/01
ADEM CO LIM ITED W ARRANTY
Alarm Device Manufacturing Company,a Division of PittwayCorporation,and its divisions,
subsidiaries and affiliates ("Seller"),165 Eileen Way,Syosset,New York 11791,warrants its
products to be in conformancewith its ow n plans and specificationsand to be free from defects
in materials and workm anship undernormaluse and service for24 m onthsfrom the date stam p
controlon the productor,forproducts nothaving an Ademcodate stam p,for12 m onths from
date of original purchase unless the installation instructions or catalog sets forth a shorter
period, in w hich case the shorter period shallapply. Seller's obligation shallbe limited to
repairing orreplacing,atits option,free ofcharge formaterials orlabor,any productwhich is
proved not in com pliance w ith Seller's specifications or proves defective in m aterials or
workm anship undernormaluse and service.Seller shallhave no obligation underthis Limited
Warranty or otherwise ifthe productis altered or improperly repaired or serviced by anyone
otherthan Ademcofactory service.Forwarranty service,return producttransportation prepaid,
to AdemcoFactory Service,165 Eileen Way,S yosset,New York 11791.
THERE ARENO W ARRANTIES,EXPRESS OR IMPLIED,OFM ERCHANTABILITY,OR
FITNESS FO R A PARTICULAR PURPOSE OR OTHERW ISE, WHICH EXTEND
BEYOND THE DESCRIPTION ON THE FACE HEREOF.IN NO CASE SHALL SELLER
BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAM AGES
FOR BREACH OF THIS OR ANY OTHER W ARRANTY,EXPRESS OR IMPLIED,OR
UPON ANY OTHER BASIS O F LIABILITY W HATSOEVER,EVEN IF THE LOSS OR
DAM AGEIS CAUSED BY THE SELLER'S OW N NEGLIGENCEOR FAULT.
Seller does notrepresent thatthe products itsells maynotbe com prom ised or circum vented;
thatthe products willpreventany personal injury orproperty loss by burglary,robbery,fire or
otherwise; or that the products w ill in allcases provide adequate w arning or protection.
Custom erunderstands thata properly installed and maintained alarm mayonly reduce the risk
ofa burglary,robbery,fire orotherevents occurring withoutproviding an alarm,butitis not
insurance or a guarantee thatsuch w illnotoccur or thatthere w illbe no personal injury or
property loss as a result.CONSEQUENTLY,SELLER SH A LL HAVE NO LIABILITY FO R
ANY PERSONAL INJURY,PROPERTY DAMAGE OR OTHER LOSS BASED ON A
CLAIM THE PRODUCT FAILED TO GIVE W ARNING.HOW EVER,IF SELLER IS
HELD LIABLE, W HETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR
DAM AGE ARISING UNDER THIS LIMITED W ARRANTY OR OTHERW ISE,
REGARDLESSOFCAUSE OR ORIGIN,SELLER'S MAXIMUM LIABILITY SH A LL NOT
IN ANY CASE EXCEED THE PURCHASE PRICE OFTHE PRODUCT,WHICH SHALL
BE THE COM PLETE AND EXCLUSIVE REMEDY AGAINST SELLER.This w arranty
replaces any previous warranties and is the only warranty madeby Seller on this product.No
increase or alteration, written or verbal,of the obligations of this L imited W arranty is
authorized.
FCC NOTICE
FCC ID: CFS 8DL 5817CB
This device complies with Part 15 of FCC rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference. (2)
This device must accept any interference received, including interference that may
cause undesired operation.
ALARM DEVICE MANUFACTURING COMPANY
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, New York 11791
Copyright © 2000 PITTWAY CORPORATION
¬.895694,l#
®
K5623V1 4/01
5817CB
WIRELESS COMMERCIAL
/
HOUSEHOLD TRANSMITTER
INSTALLATION INSTRUCTIONS
GENERAL INFORMATION
The 5817CB is a universal contact-monitoring transmitter that can be used with household
and commercial fire and burglary-initiating devices such as door/window contacts, motion
and glassbreak detectors, sprinkler water flow switches, tamper switches, post indicator
valves, manual pull stations, and remote duct detectors. Upon activation, it emits an RF
signal to a control panel that sends a burglary or fire alarm to a central station. The 5817CB
has three unique input loops (zones). The first loop (primary loop) is supervised and typically
used for high-priority alarm reporting such as commercial fire or burglary. It requires a
470K ohm end-of-line resistor to be placed across the sensor. The second loop is the built-in,
normally closed reed switch (used in conjunction with a magnet, as described below). The
third loop is another normally closed household burglary loop. All three loops may be used. A
fourth (automatically enrolled) loop contains two tamper switches to protect the 5817CB
transmitter. A built-in cover tamper switch is activated when the cover is removed. A unit
tamper switch is activated if the unit is separated from its mounting plate.
The 5817CB has its own unique serial number permanently assigned during manufacture.
You must "enroll" this transmitter serial number in the control panel at some point prior to
its usage in the alarm system. Refer to the control panel's installation instructions for
further details. Note: During programming of the control panel, program the 5817CB
transmitter as Input Type "RF" (i.e., supervised RF) (mandatory for UL installations).
MOUNTING
For proper orientation of the unit in relation to its wall mounting plate and the loop wiring,
read all of this section before installing the unit. Before mounting the transmitter
permanently, conduct Go/No Go tests (see control's instructions) to verify adequate signal
strength from location. When a satisfactory location is found, remove the battery and proceed
with installation.
The following mounting instructions assume that the unit will be mounted as shown in the
diagrams. The unit may, however, be installed in any direction, as long as the relationship of
the unit to its mounting plate is maintained.
The mounting plate, installed as described below, enables easy removal of the unit for
servicing, should it become necessary.
1. Remove the transmitter's cover by inserting the flat blade of a small screwdriver into
the pry-off slot at the bottom end of the unit on the right side closest to the cover's
decorative ribs and twisting.
2. Disengage the supplied mounting plate from the unit by inserting the blade of a
small screwdriver into the mounting plate release hole (see Diagram 2) and pushing the
locking tab out (see Diagram 1). Slide the mounting plate downward along the case back.
Note: For this application, the alignment guide strip along one edge of the mounting
plate serves no function and may be broken away, if desired.
3. If concealed wiring is to be used, feed the wires through the concealed wiring entry
hole at one corner of the plate (surface wiring is mentioned in Step 5 below).
4. Install the mounting plate, with its case-holding posts pointing up, in the location
selected, as described in the control unit's installation instructions. Use the two flat-head
screws supplied. Note: To ensure proper operation of the unit's back tamper (when it is
separated from the mounting plate), the screws must be anchored to a wall stud or other
solid wood material.
5. If surface wiring is to be used, remove the knockout slot in the case back (located
across from loop 3 terminal block). Surface wiring should enter through this knocked
out space provided. Do not connect the wiring to the terminal block(s) yet.
www.PDF-Zoo.com
firealarmresources.com
- 2 - - 3 -
6. Attach the case back to the mounting plate by sliding the keyhole slots in the case
back down onto the mounting plate's holding posts. The locking tab will click as the case
back locks in place. To disengage the unit from an installed mounting plate, insert a
small screwdriver into the mounting plate release hole, push down to retract the locking
tab, and push upward on the unit to disengage from posts.
7. Set the DIP switch (after the control panel has enrolled the transmitter's input IDs) for
the desired primary loop characteristics, as described in the table below.
PRIMARY LOOP OPTIONS TABLE
DIP SWITCH POSITION
SWITCH
SETTING 1 2 3 4
ON REPEATING
TRANSMISSION
(every 4 sec.)
UPON PRIMARY
LOOP FAULT
Use for high priority
alarm, such as fire.
OFF SINGLE
TRANSMISSION
PER PRIMARY
LOOP CHANGE-
OF-STATE
SWITCH MUST
ALWAYS BE
IN THE
ON
POSITION
SWITCH MUST
ALWAYS BE
IN THE
ON
POSITION
SWITCH MUST
ALWAYS BE
IN THE
OFF
POSITION
Notes: a. In order for the control panel to enroll the transmitter, the DIP switches must
be set to OFF – ON – ON – OFF (see Diagram 2).
b. The Auxiliary loops are not affected by the DIP switch settings.
UL REQUIREMENT
1. If using one of the panel revisions shown in the following table, and programming the
5817CB as an Entry/Exit zone, you must enroll the tamper loop (loop 4) as a separate
zone, programmed for 24-hour response (e.g., zone type 5 Trouble-by-day/Alarm-by-
night).
Model # Rev. EPROM P/N
FA1600C 8 (WAVIS150FA-18)
Vista-32FB 3 (WAVIS32FB-13)
Vista-128FB 4 (WAVIS128FB-14)
Vista-128B 3 (WAVIS128B-13)
2. For UL Commercial Burglary installations, this transmitter must be used in conjunction
with the 5881ENHC RF Receiver.
WIRING CONNECTIONS
Connect the loop wiring to the unit's terminals before installing the battery (see Diagram 2).
Notes:a. Primary loop 1 is a supervised loop and must have an end-of-line (EOL)
resistor (470K ohms, supplied) placed across the last sensor. Additionally, for
Primary loop 1, a contact device may not be installed more than 20 feet from the
transmitter.
b. If loop 2 is not going to be used, the magnet is not necessary.
c. If loop 3 is not going to be used, no connection is needed across its terminals.
For UL household burglary and fire installations, the loop 3 contact device (if
used) may not be more than 3 feet from the transmitter.
BATTERY INSTALLATION/REPLACEMENT
1. Remove the transmitter's cover as described in Mounting Step 1.
2. Observe correct polarity and insert the battery provided into the battery holder
(see Diagram 2). Take care not to bend the antenna.
Note:Replace battery
only with: Duracell DL123A, Sanyo CR123A,
Panasonic CR123A, Ademco 466, Varta CR123A, or Tekcell CR123A.
CAUTION: Risk of fire, explosion, and burns. Do not recharge, disassemble,
heat above 212°F (100°C), or incinerate. Dispose of used batteries
promptly. Keep away from children.
3. To replace the cover, engage the hooks along the top edge and snap shut.
SPECIFICATIONS
Dimensions 1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm)
Battery 3V Lithium (see BATTERY INSTALLATION/REPLACEMENT).
UL Listings:
Commercial Fire ......................................UL864
Household Fire......................................... UL985
Household Burg .......................................UL1023
Commercial Burg..................................... UL365, UL609, UL634, UL1610
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing
by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user, as well as acquainting the user with the proper operation
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to insure the system's
operation at all times.
FOR DETAILS ON LIM ITATIONS OF THE ENTIRE ALARM SYSTEM , REFER TO THE
CONTROL PANEL'S
INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL W ITH
WHICHTHISDEVICE IS USED.
5817CB-001-V0
MOUNTING
PLATE
HOLE CASE
HOLDING
POSTS
CONCEALED
WIRING
ENTRY
HOLE
MOUNTING
PLATE HOLES
TAMPER SWITCH
HOLD DOWN
LOCKING
TAB
Diagram 1. Mounting Plate
+
–
BATTERY
5817CB-002-V1
DIP
SWITCH
COVER
HOLDING
SLOTS (2) ANTENNA
COVER
TAMPER
SWITCH
COVER
PRY-OFF
POINT
MOUNTING
PLATE
RELEASE
1/2"
MAX.
N.O.
CONTACT
DEVICE
N.C.
CONTACT
DEVICE
LOOP 3
TERMINALS
(AUX)
ALIGN MAGNET
WITH MARKS ON
CASE (2 PLACES)
MAGNET
(OBTAIN
SEPARATELY)
LOOP 2
REED SWITCH
(AUX)
PRIMARY
LOOP 1
TERMINALS
DIP SWITCH FOR PRIMARY LOOP OPTIONS
(SEE SETTINGSTABLE)
SHOWN SET FOR: 1. SINGLE TRANSMISSION
NOTE:SW2 MUST BE ON
ON
OFF
ON
1 2 3 4
WHITE AREA
INDICATES
SWITCH HANDLE
THE DIP SWITCHES MUST BE
SET AS SHOWN DURING
ENROLLMENT BYTHE CONTROL
SLOT FOR
CONCEALED
WIRING ACCESS
SW3 MUST BE ON
SW4 MUST BE OFF
EOLR 470K ohms
Diagram 2. Transmitter, Cover Removed
NOTE: For UL commercial and household fire
installations, only one initiating device may be
connected to this transmitter. For UL commercial
burglary installations, multiple initiating devices
may be used as long as the devices all service
the same function such as door/window contacts,
motion or glassbreak detectors. All initiating
devices must be located within the same room.
www.PDF-Zoo.com
firealarmresources.com

Other ADEMCO Transmitter manuals

ADEMCO 5818 User manual

ADEMCO

ADEMCO 5818 User manual

ADEMCO 5805-4 User manual

ADEMCO

ADEMCO 5805-4 User manual

ADEMCO 5804 User manual

ADEMCO

ADEMCO 5804 User manual

ADEMCO 5817 User manual

ADEMCO

ADEMCO 5817 User manual

ADEMCO 413 User manual

ADEMCO

ADEMCO 413 User manual

ADEMCO 5817CB Assembly instructions

ADEMCO

ADEMCO 5817CB Assembly instructions

ADEMCO 5804BDV User manual

ADEMCO

ADEMCO 5804BDV User manual

ADEMCO 5816TEMP User manual

ADEMCO

ADEMCO 5816TEMP User manual

ADEMCO 5817CB User manual

ADEMCO

ADEMCO 5817CB User manual

ADEMCO Ademco 5802WXT User manual

ADEMCO

ADEMCO Ademco 5802WXT User manual

ADEMCO 5817CB User manual

ADEMCO

ADEMCO 5817CB User manual

ADEMCO 5819 Operation and maintenance manual

ADEMCO

ADEMCO 5819 Operation and maintenance manual

ADEMCO 5879 Assembly instructions

ADEMCO

ADEMCO 5879 Assembly instructions

ADEMCO 5869 Assembly instructions

ADEMCO

ADEMCO 5869 Assembly instructions

ADEMCO 5820 Assembly instructions

ADEMCO

ADEMCO 5820 Assembly instructions

ADEMCO 5817CB Assembly instructions

ADEMCO

ADEMCO 5817CB Assembly instructions

ADEMCO 5716 User manual

ADEMCO

ADEMCO 5716 User manual

ADEMCO 5819WHS - Ademco Wireless Shock Processor User manual

ADEMCO

ADEMCO 5819WHS - Ademco Wireless Shock Processor User manual

ADEMCO 5804H User manual

ADEMCO

ADEMCO 5804H User manual

ADEMCO 5802WXT User manual

ADEMCO

ADEMCO 5802WXT User manual

ADEMCO 5816MN User manual

ADEMCO

ADEMCO 5816MN User manual

Popular Transmitter manuals by other brands

Converters.TV CH-1107TX Operation manual

Converters.TV

Converters.TV CH-1107TX Operation manual

CYP PUV-3090TX-UEA Operation manual

CYP

CYP PUV-3090TX-UEA Operation manual

Transmitter Solutions STINGER2 318ALD21V2 manual

Transmitter Solutions

Transmitter Solutions STINGER2 318ALD21V2 manual

Greystone Energy Systems TE500AS Series installation instructions

Greystone Energy Systems

Greystone Energy Systems TE500AS Series installation instructions

Endress+Hauser iTEMP TMT71 operating instructions

Endress+Hauser

Endress+Hauser iTEMP TMT71 operating instructions

SICK TRANSIC111LP operating instructions

SICK

SICK TRANSIC111LP operating instructions

CYP PUV-1510RXWP Operation manual

CYP

CYP PUV-1510RXWP Operation manual

Vega VEGABAR 86 Quick setup guide

Vega

Vega VEGABAR 86 Quick setup guide

Emerson Rosemount 2051 Reference manual

Emerson

Emerson Rosemount 2051 Reference manual

UniKit UX400 manual

UniKit

UniKit UX400 manual

Aplisens AS-dP user manual

Aplisens

Aplisens AS-dP user manual

Transmitter Solutions Stinger2 31LID21V2 manual

Transmitter Solutions

Transmitter Solutions Stinger2 31LID21V2 manual

Pyramid 915 MHZ user guide

Pyramid

Pyramid 915 MHZ user guide

DLO TuneStik user manual

DLO

DLO TuneStik user manual

FMUser CZH-T200 user manual

FMUser

FMUser CZH-T200 user manual

Eldat RT31 quick start guide

Eldat

Eldat RT31 quick start guide

Audio Authority 2801 user manual

Audio Authority

Audio Authority 2801 user manual

Omega Engineering HX92B Series user guide

Omega Engineering

Omega Engineering HX92B Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.