Advanced Energy Thyro-S User manual

1
BUS MODULE MODBUS RTU
FOR THYROS, THYROA AND THYROAX
July 2014 DE/EN - V3

2
CONTACT INFORMATION
TECHNICAL QUERIES
Do you have any technical queries regarding the subjects dealt with in
these operating instructions?
If so, please get in touch with our team for power controllers:
Phone +49 (0) 2902 763-520
COMMERCIAL QUERIES
Do you have any commercial queries on power controllers?
If so, please get in touch with our team for power controllers.
Phone +49 (0) 2902 763-558
SERVICE
Advanced Energy Industries GmbH
Branch Oce Warstein-Belecke
Emil-Siepmann-Straße 32
D-59581 Warstein
Phone +49 (0) 2902 763-0
http://www.advanced-energy.com
COPYRIGHT
No part of these operating instructions may be transmitted, reproduced and/or copied by any electronic
or mechanical means without the express prior written permission of Advanced Energy.
© Copyright Advanced Energy Industries GmbH 2014.
All rights reserved.
FURTHER INFORMATION ON COPYRIGHT
Thyro-™, Thyro-S™, Thyro-A™, Thyro-AX™ are registered trademarks of Advanced Energy Industries GmbH.
All other company and product names are (registered) trademarks of the respective owners.

3
1. Introduction 5
1.1 General 5
1.2 Specific characteristics 5
1.3 Type designation 5
1.4 Warranty 5
2. Safety 7
2.1 Identification in the operating instructions 7
2.2 General danger information 8
2.3 Operator requirements 9
2.4 Personnel requirements 9
2.5 Intended purpose 9
2.6 Use of the device 10
2.6.1 Operation 10
2.6.2 Prior to installation/start-up 10
2.6.3 Maintenance, service, faults 10
2.6.4 Transport 10
3. Functions 11
3.1 Setpoint processing Thyro-S 11
3.2 Setpoint processing Thyro-A/Thyro-AX 12
3.3 Operating display 13
3.4 Additional functions for Thyro-S, Thyro-A and Thyro-AX 13
4. Operation 14
4.1 Selecting the bus address 14
4.2 Setting the communication parameters 14
4.3 Modbus-/J-bus log 15
4.3.1 Read holding registers (0x03) 16
4.3.2 Preset single register (0x06) 17
4.3.3 Preset multiple registers (0x10) 18
4.3.4 Report slave ID (0x11) 18
4.3.5 Exception response 19
4.4 Register allocation 19
4.4.1 Busmodule parameters 20
4.4.2 Controller parameters 21
CONTENTS

4
Fig. 1 Relay drive 13
Fig. 2 Block connecting diagram bus module 27
Fig. 3 Connecting plans Thyro-A/Thyro-AX 30
Fig. 4 Connecting plans Thyro-S 31
Tab. 1 Interpretation of master setpoints with Thyro-S 11
Tab. 2 Status of diagnosis LED 13
Tab. 3 Register allocation of bus module for J-Bus and Modbus RTU 19
Tab. 4 Bus module parameters 20
Tab. 5 Device types 20
Tab. 6 Bus module master 21
Tab. 7 Controller actual values 21
Tab. 8 Controller parameters 22-23
Tab. 9 Status and error flags 25-26
LIST OF ILLUSTRATIONS AND TABLES
4.5 Status and error communication 25
5. External connections 27
5.1 Power supply 27
5.2 Operating elements and terminal strips 28
6. Interfaces 29
6.1 System interface 29
6.2 Modbus interface 29
7. Connecting plans Thyro-A/Thyro-AX 30
8. Connecting plans Thyro-S 31
9. Special remarks 32
9.1 Installation 32
9.2 Commissioning 32
9.3 Service 32
10. Technical Data 33
11. Dimensional drawings 33
12. Accessories and options 34
13. Approvals and conformity 34

5
1. INTRODUCTION
The following operating instructions merely serve as a supplement and
apply only in connection with the operating instructions of the Advanced
Energy power controllers Thyro-S and Thyro-A of types H1 and H RL1, as well
as Thyro-A H RLP1 as well as Thyro-AX of types H RL2 and H RLP2. Particular
attention must be paid to the safety instructions included in them.
1.1 GENERAL
The bus module Modbus RTU can connect up to 8 power controllers of
type Thyro-A...1, Thyro-AX...2 or power switches of type Thyro-S…1 to a Mod-
bus master in any random order.
Several bus modules can be employed at one device. Each bus module
occupies one address on the Modbus.
The power supply of the bus module is provided by an external 24 V
d.c. power source (150 mA), which is fed into X11.1 (+) and X11.2 (ground)
(reverse battery protected). The 24 V d.c. supply must be ungrounded when
operating under SELV. Several modules can be operated at one power supply.
For EMC reasons, the earth connection to X11.3 must be as short as possible.
The Modbus connector with a 9-terminal standard allocation must be con-
nected to the socket X20.
1.2 SPECIFIC CHARACTERISTICS
• The bus module is a slave component
• Function control via LED
• 8 free digital outputs X1.5 to X8.5
• processing of actual values as oat number in physical units
• C-rail assembly
• When the bus module is linked to Thyro-AX, please be aware that data trans-
fer is the same as for Thyro-A whereas special features or other additional
parameters are excluded from this.
1.3 TYPE DESIGNATION
Bus module Modbus RTU Order No. 2000 000 842

6
1.4 WARRANTY
In the event of any claims in connection with the Modbus RTU, please contact
us immediately quoting:
- Type designation
- Works number/Serial number
- Reason for the complaint
- Environmental conditions of the device
- Operating mode
- Period of use
Goods and services are subject to the general conditions of supply for
products of the electrical industry, and our general sales conditions.
Claims in connection with supplied goods must be submitted within one
week of receipt, along with the delivery note. Advanced Energy will rescind
all obligations such as warranty agreements, service contracts, etc. entered
into by Advanced Energy or its representatives without prior notice if main-
tenance and repair work is carried out using anything other than original Ad-
vanced Energy spare parts or spare parts purchased fromAdvanced Energy.

7
2. SAFETY
2.1 IDENTIFICATION IN THE OPERATING INSTRUCTIONS
In these operating instructions, there are warnings before dangerous
actions. These warnings are divided into the following danger categories:
DANGER
Dangers that can lead to serious injuries or fatal injuries.
WARNING
Dangers that can lead to serious injuries or considerable damage to property.
CAUTION
Dangers that can lead to injuries and damage to property.
CAUTION
Dangers that can lead to minor damage to property.
The warnings can also be supplemented with a special danger symbol
(e.g.„Electric current“ or„Hot parts“), e.g.
risk of electric current or
risk of burns.

8
In addition to the warnings, there is also a general note for useful information.
NOTE
Content of note
2.2 GENERAL DANGER INFORMATION
DANGER
Failure to observe the safety regulations in the operating instructions for the
power controllers used risk of injury or damage to the device or plant.
> Observe all safety regulations in the safety chapter of the operating instruc-
tions for the power controllers used.
DANGER
Electric current
Risk of injury from live parts/risk of damage to the bus module.
> Never operate the device without the cover.
> Only carry out adjustments or wiring when the device is deenergised.
CAUTION
Risk of damage to the bus module
The current at terminals X1.5 to X8.5 may not exceed 120 mA.
> Check the connection data of the upstream relay.
NOTE
Communication faults
To avoid communication faults, observe the following points:
> Use shielded cables.
> Ensure grounding on the bus module (X1.7 to X8.7). Do not also ground on
the power controller.

9
2.3 OPERATOR REQUIREMENTS
The operator must ensure the following:
- That the safety regulations of the operating instructions are observed.
- That the accident prevention regulations valid in the respective coun-try of
use and the general safety regulations are observed.
- That all safety devices (covers, warning signs etc.) are present, in perfect
condition and are used correctly.
- That national and regional safety regulations are observed.
- That the personnel has access to the operating instructions and safety
regulations at all times.
- That operating conditions and restrictions resulting from the technical data
are observed.
- That, should abnormal voltages, noises, increased temperatures, vibra-
tion or similar occur, the device is immediately put out of operation and the
maintenance personnel is informed.
2.4 PERSONNEL REQUIREMENTS
Only qualied electro-technical personnel who are familiar with the
pertinent safety and installation regulations may perform the following:
- Transport
- Installation
- Connection
- Start-up
- Maintenance
- Testing
- Operation.
These operating instructions must be read carefully by all persons working
with or on the equipment prior to installation and initial start-up.
2.5 INTENDED PURPOSE
The device may only be used for the pupose for which it was intended,
as persons may otherwise be exposed to dangers (e.g. electric shock,
burns) and plants also (e.g. overload). The user must therefore observe
the following points:
- It is not permitted to make any unauthorised modications to the
unit or to use any spare parts or replacement parts not approved by Advan-
ced Energy, or to use the unit for any other purpose.

10
- The warranty obligations of the manufacturer are only applicable if these
operating instructions are observed and complied with.
- The device is a component that cannot function alone.
- Project planning must account for the proper use of the device.
2.6 USE OF THE DEVICE
2.6.1 OPERATION
- Only switch on the mains voltage at the machine when there is no danger to
persons, system or load.
- Protect the device against dust and damp.
- Ensure that the ventilation openings are not blocked.
2.6.2 PRIOR TO INSTALLATION/STARTUP
- If stored in a cold environment: ensure that the device is absolutely
dry. (Allow the device a period of at least two hours to acclimatise before
start-up.)
- Ensure sucient ventilation of the cubicle if mounted in a cubicle.
- Observe minimum spacing.
- Ensure that the device cannot be heated up by heat sources below it (see
chapter 10, Technical data).
- Ground the device in accordance with local regulations.
- Connect the device in accordance with the connection diagram.
2.6.3 MAINTENANCE, SERVICE, FAULTS
In order to avoid injuries and damage, the user must observe the following:
- Before all work:
> Disconnect the device from all external voltage sources.
> Secure the device against accidentally being switched back on.
> Use suitable measuring instruments and check that there is no voltage
present.
> Ground and short-circuit the device.
> Provide protection by covers or barriers for any neighbouring live parts.
- The device may only be serviced and repaired by trained electrotechnical
personnel.
2.6.4 TRANSPORT
- Only transport the device in the original packaging.
- Protect the device against damage, caused by jolts, knocks and contamina-
tion, for instance.

11
3. FUNCTIONS
3.1 SETPOINT PROCESSING Thyro-S
The setpoints via the bus (setpoints master) are interpreted as an operating
mode with Thyro-S as shown in table 1.
SETPOINT RETURN VALUE
(setpoint master) (total setpoint)
to 409 = OFF 0
to 1091 = 1/5 819
to 1706 = 1/3 1365
to 3071 = 1/2 2047
to 4096 = ON 4096
TAB. 1 INTERPRETATION OF THE MASTER SETPOINTS WITH Thyro-S
The setpoint processing continues to depend on how the bus module is
connected to the power controller. For Thyro-S dierent variations can
be realised as required. The connection of terminal X22.4 of Thyro-S
controls the procedures (Chapt. 8, Fig. 4).
• No connection to X22.4
The bus module is fully functional, only the analog signal of control terminal
X22.1, however, is used as a setpoint (ON / OFF).
• X22.4 has ground potential
Only the master setpoints are used by the bus module (graded as in table 1).
The controller’s terminal X22.4 can be directly connected to earth if an alter-
native operation is excluded.
• X22.4 is switched
• Thyro-S’s terminal X22.4 is connected to one of the terminals X1.1 to X8.1
of the bus module (Fig. 4).
With malfunctions on the bus line an automatic switchover takes place to
the corresponding signal of the setpoint input of Thyro-S.
• Thyro-S’s connection X22.4 is connected to one of the terminals X1.5 to
X8.5 of the bus module (Fig. 4). The controllers can then individually be
switched (selectively) via bus to„Hand”.
With malfunctions on the bus line the last setpoint is automatically retai-
ned.

12
• Digital outputs with free drives
If a terminal X1.5 to X8.5 of the bus module is not allocated, a relay with 24 V
d.c. coil can be connected for free use (Fig. 1). The free circuit is integrated.
The driver current is maximum 120mA per output.
Ventilation cabinets, auxiliary heating, circuit breakers or control lamps for
example, can be activated with this via the Modbus.
3.2 SETPOINT PROCESSING Thyro-A/Thyro-AX
The setpoint processing depends on how the bus module is connected to the
power controller. For Thyro-A/Thyro-AX dierent variations can be realised
depending on the requirements. The connection of terminal X22.1 of Thyro-
A/Thyro-AX controls the procedures (Chapt. 7, Fig. 3).
• No connection to X22.1
The bus module is fully functional, however, only the analog signal of con-
trol terminal X2.4 is used as the setpoint.
• X22.1 has ground potential
Only the master setpoint is accepted by the bus module as a setpoint. The
controller’s terminal X22.1 can be directly connected to earth if an alternati-
ve operation is excluded.
• X22.1 is switched
• The terminal X22.1 of Thyro-A/Thyro-AX is connected to one of the termi-
nals X1.1 to X8.1 of the bus module (Fig. 3).
With malfunctions on the bus line all controllers are automatically swit-
ched over to the respective analog signal of the setpoint input of Thyro-A/
Thyro-AX.
• The circuit X22.1 of Thyro-A/Thyro-AX is connected to one of the terminals
X1.5 to X8.5 of the bus module (Fig.3). Then each controller can be switched
individually (selectively) via bus to„Hand”.
With malfunctions on the bus line the last setpoint is automatically retai-
ned.
• Digital outputs with free drives
If a terminal X1.5 to X8.5 of the bus module is not allocated, a relay with 24
V d.c. coil can be connected for free use (Fig. 1). The free circuit is integrated.
The driver current is maximum 120 mA per output.
Ventilation cabinets, auxiliary heating, circuit breakers or control lamps, for
example, can be switched via the Modbus.

13
FIG. 1 RELAY DRIVE
3.3 OPERATION DISPLAY
STATUS LED MODBUS INDICATION
ON – Card error
BLINKS with 1 Hz OFF No bus signal present
BLINKS with 1 Hz ACTIVE Card error
OFF OFF Power supply absent
(also green LED o)
OFF ACTIVE Everything OK
TAB. 2 STATUS DIAGNOSIS LED
3.4 ADDITIONAL FUNCTIONS FOR Thyro-S, Thyro-A AND
Thyro-AX
By using a bus module, additional functions for the power controllers
Thyro-S, Thyro-A and Thyro-AX can be employed.
All the accessible parameters of both type ranges can be found in
columns S/A (abbreviation for Thyro-S and Thyro-A; these modications also
apply for Thyro-AX) under R/W in table 8.
The most important parameters are described in more detail in the
according power controller operating instructions. Here r = read,
i.e. can only be read, r/w = read and write possible.

14
4. OPERATION
The Modbus connection is lead through
a 9-pole sub-D bushing (X20). It provides
the data lines A and B as well as an electrically
isolated supply voltage (5 V, 80 mA).
4.1 SELECTING THE BUS ADDRESS
A device address, which only exists once in the system, must be set in a
switched-o state between 1 to 247 at the bus module via the switch
S501.1 to S501.7.
4.2 SETTING THE TRANSMISSION PARAMETERS
The settings which are required for communication assimilation can be
made via the DIP switch S502 (conguration switch). At the standard
setting all switches are open. The following table illustrates the function
of the switches. 0 represents an open switch and 1 a closed switch.
1 = CLOSED
0 = OPEN
1, 2, 4, 8, 16, 32, 64, 128 S 501
1 = CLOSED
0 = OPEN
S 502
PIN ALLOCATION OF THE
MODBUS SOCKET

15
S 502
SWITCH FUNCTION
12345678
0 0 0 4800 Baud
1 0 0 9600 Baud
0 1 0 19200 Baud
1 1 0 38400 Baud
0 0 1 57600 Baud
1 0 1 115200 Baud
0 1 1 230400 Baud
1 Parity
1 Even nOdd
1 2 Stopp-Bit
1 Long Break
x free
Baud rate: Works setting = 4800 Baud.
The baud rate can be set with the rst three switches. The transmission
rates of 4800 to 230 400 baud are sustained.
Parity: Works setting = no parity
This switch activates transmission with parity bit.
Even nOdd: Works setting = Odd
With activated parity bit it is possible to switch between Even and Odd
parity.
2 Stopp-Bit: Works setting = 1 Stopp Bit
This switch allows an additional Stopp Bit to be sent.
Long Break: Works setting = no extension
This switch allows the delay time between master inquiry and slave reply to
be increased by 3.5 bytes.
4.3 MODBUS/J BUS LOG
The transmission mode RTU (Remote Terminal Unit) is used for communica-
tion.
General telegram set up:

16
START ADDRESS FUNCTION DATA
BYTES
CRC END
Pause
>3,5 bytes
1 byte 1 byte x bytes 2 bytes Pause
>3,5 bytes
The following functions are sustained:
1. Read Holding Register
Reads one or more registers from the slave.
2. Preset Single Register
Changes a register in the slave.
3. Preset Multiple Regs
Changes several registers in the slave.
4. Report Slave ID
Reads the slave ID of the slave.
The individual registers as well as the calculations of the corresponding
register addresses are described in chapter 4.4. The J-bus register
address is always used (i.e. also with Modbus) within the telegrams.
4.3.1 READ HOLDING REGISTERS 0X03
With this telegram the master can read out one or more registers (function
code 0x03). The registers must lie in series.
Example:
Registers 72 + 128 (load voltage chapter 4.4, Controller 1) are to be read out
from the bus module with the address 100. (72 + 128 = 200, no overow into
high byte).
Inquiry:
ADDRESS FUNCTION REGISTER NUMBER CRC
100 3 0, 200 0, 2 76, 00
Response:
ADDRESS FUNCTION NO.
BYTES
DATA CRC
100 3 4 250, 184, 70, 23 13, 166
Error:
Should the address of the register to be read out lie outside the address
location, the reply Exception Response„ILLEGAL DATA
ADDRESS”is transmitted (see chapter 4.3.5).

17
Response:
ADDRESS FUNCTION ERROR CODE CRC
100 131 2 208, 238
If more than 120 registers are requested simultaneously the Exception
Response„ILLEGAL DATA VALUE” is transmitted (see Chapt. 4.3.5).
Response:
ADDRESS FUNCTION ERROR CODE CRC
100 131 3 17, 46
4.3.2 PRESET SINGLE REGISTER 0X06
With this telegram the master can change a register (function code 0x06).
Example:
Registers 6 + 256 (operating mode Thyro-A/Thyro-AX, Controller 2)
are to be changed to 2 (VAR) in the bus module with the address 100
(1 overow into high byte).
Inquiry:
ADDRESS FUNCTION REGISTER DATA CRC
100 6 1, 6 0, 2 224, 3
Response:
ADDRESS FUNCTION REGISTER DATA CRC
100 6 1, 6 0, 2 224, 3
Error:
Should the register’s address lie outside the address location or is
an attempt made to write on an address that cannot be changed, the
Exception Response responds by transmitting„ILLEGAL DATA
ADDRESS”(see Chapt. 4.3.5). This is also the case if the controller in
question is not connected!
Response:
ADDRESS FUNCTION ERROR CODE CRC
100 134 2 211, 190

18
4.3.3 PRESET MULTIPLE REGS 0X10
With this telegram the master can change one or more registers, whereby the
registers must lie in series.
Example:
The registers 24 (+25) + 384 (Pmax Thyro-A H RLP1/Thyro-AX H RLP2, Control-
ler 3) are to be changed to 10kW in the bus module with the address 100.
(24+3*128=408, 408-(1 x 256) = 152; 10000 = 39,16 (256 * 39 + 16 = 10000)
Inquiry:
ADDRESS FUNC
TION
REGISTER NUMBER
NO.
BYTES
DATA CRC
100 16 1, 152 0, 2 40, 0, 39, 16 3, 4
Response:
ADDRESS FUNCTION REGISTER NUMBER CRC
100 16 1, 152 0, 2 200, 46
Error:
Should the register’s address lie outside the address location, the
Exception Response„ILLEGAL DATA ADDRESS” is transmitted (see-
Chapt. 4.3.5).
Response:
ADDRESS FUNCTION ERROR CODE CRC
100 144 2 221, 222
Should there be registers which can only be read out, the change
requested is ignored.
4.3.4 REPORT SLAVE ID 0X11
With this telegram the master can read out the slave ID.
Example:
The ID is to be read out from the bus module with the address 100.
Inquiry:
ADDRESS FUNCTION CRC
100 17 235, 124

19
Response:
ADDRESS FUNC
TION
NO. BYTES SLAVE ID RUN STA
TUS
CRC
100 17 2 4 255 18, 116
4.3.5 EXCEPTION RESPONSE
With an incorrect inquiry an Exception Response is transmitted and the
inquiry is rejected.
ILLEGAL FUNCTION:
The function code received in the inquiry is not sustained by the slave.
ILLEGAL DATA ADDRESS:
The register address does not exist. It must be smaller than 1152. With
the inquiries„Read Holding Registers” and„Preset Multiple Regs”the
address comprises the register’s start address and the number of registers. So
that the following applies
Register + number <1152; 128+8x128.
ILLEGAL DATA VALUE:
The data in the inquiry are not permitted. For example the number of
registers to be read is too high (max. 120).
4.4 REGISTER ALLOCATION
The registers are split up into the following areas:
PARAMETERS REGISTER ADDRESSES
JBUS MODBUS
Bus module 0 - 127 40001 - 40128
Controller X1 128 - 255 40129 - 40256
Controller X2 256 - 383 40257 - 40384
Controller X3 384 - 511 40385 - 40512
Controller X4 512 - 639 40513 - 40640
Controller X5 640 - 767 40641 - 40768
Controller X6 768 - 895 40769 - 40896
Controller X7 896 - 1023 40897 - 41024
Controller X8 1024 - 1151 41025 - 41152
TAB. 3 REGISTER ALLOCATION OF THE BUS MODULE FOR JBUS AND MOD
BUS RTU

20
The index of the individual registers below corresponds to the oset
at the beginning of the area concerned. The corresponding register is
calculated as followed (for bus module parameters the Controller
No. equals 0):
J-bus: Register address = index + (128 * Controller No.)
Modbus: Register address = Index + (128 * Controller No.) + 40001
4.4.1 BUSMODULE PARAMETERS
General information can be read out via the bus module (participant
recognition). The parameters are thereby only addressed via the index num-
ber. Parameters for Thyro-A apply also to Thyro-AX.
MODULPARAMETER R/W
INDEX ADR. SYMBOL NAME VALUE RANGE COMBOOPT UNIT S A DEFAULT
0 GER_1 Device type at port 1 5, 9, 10, .. S, 1A, 2A,.. r r
1GER_2 Device type at port 2 5, 9, 10, .. S, 1A, 2A,.. r r
2GER_3 Device type at port 3 5, 9, 10, .. S, 1A, 2A,.. r r
3 GER_4 Device type at port 4 5, 9, 10, .. S, 1A, 2A,.. r r
4 GER_5 Device type at port 5 5, 9, 10, .. S, 1A, 2A,.. r r
5 GER_6 Device type at port 6 5, 9, 10, .. S, 1A, 2A,.. r r
6 GER_7 Device type at port 7 5, 9, 10, .. S, 1A, 2A,.. rr
7 GER_8 Device type at port 8 5, 9, 10, .. S, 1A, 2A,.. rr
8 res.
9 VERS_J Version year (Bus module) 0...9999 r r
10 VERS_M Version month (Bus module) 1...12 r r
11 VERS_T Version day (Bus module) 1...31 r r
12 res.
13 Number of act. val. from
which mean is taken
1...20 r/w r/w 1
14 Digital outputs Bit 0-7 r/w r/w 0
TAB. 4 BUS MODULE PARAMETERS
DEVICE TYPE H1 H RL1/H RL2 H RLP1/H RLP2
Thyro-S 1S 5 37 –
Thyro-A 1A/Thyro-AX 1A
9 41 297
Thyro-A 2A/Thyro-AX 2A
10 42 298
Thyro-A 3A/Thyro-AX 3A
11 43 299
TAB. 5 DEVICE TYPES
This manual suits for next models
2
Table of contents
Other Advanced Energy Control Unit manuals