ESM-4410, ESM-7710, ESM-9910
Digital, ON/OFF Temperature Controller Unit
- ON/OFF control form
-3D
- Selectable heating and cooling function
- Operating type selection with hysteresis
- Adjustment of temperature offset value
- Minimum pulling time adjustment for control outputs
- Set value low limit and set value high limit boundaries
- Password protection for programming mode
igits display
- NTC Input or,
PTC Input or,
J type thermocouple or,
K type thermocouple or,
PT-100, PT1000, 2-wire or 3-wire temperature input
( It must be determined in order )
ESM series temperature controllers are designed for measuring and
controlling temperature. They can be used in many applications with On/Off
control form and heating and cooling selection.
They are mainly used in glass, plastic, petro-chemistry, textile, automotive and
machine production industries.
SPECIFICATIONS
INPUT
NTC:
PTC:
Thermocouple(TC):
Thermoresistance(RTD):
Measurement Range:
Accuracy:
Cold Junction Compensation:
Sensor Break Protection:
Sampling Cycle:
CONTROL
Control Form:
ON/OFF hysteresis:
NTC (10k @ 25°C)
PTC (1000 @ 25°C)
J, K (IEC 584.1) (ITS90)
2 or 3-wire PT100, PT1000 (IEC 751) (ITS90)
It is in ordering information
± 1% of full scale
Automatically ±0.1°C/1°C
Upscale
3 samples per second
ON/OFF
It can be configured for two control outputs
W
W
OUTPUT
Output-1 :
Output-2 :
Relay (7A@250V at resistive load ) or
SSR Driver Output ( )
Relay (7A@250V at resistive load ) or
SSR Driver Output ( )
Outputs that are on the device can be used as process or alarm output.
V
V
Maximum 10 mA@ 5 V
Maximum 10 mA@ 5 V
Z
Z
DISPLAY
Process Display :
ESM-4410 :
ESM-7710 :
ESM-9910 :
LED Display :
Device with 1 Output :
Device with 2 Outputs :
10 mm Red 3 digits LED Display
14 mm Red 3 digits LED Display
20 mm Red 3 digits LED Display
SET(Green), OUT(Red), PROG(Red)
SET1(Green), SET2(Green), OUT1(Red),
OUT2(Red), PROG(Red)
Electrical Wiring
1-Insert the unit in the panel
cut-out from the front side.
2- Insert the mounting clamps
to the holes that located top
and bottom sides of device and
screw up the fixing screws until
the unit completely immobile
within the panel
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during
shipment is recommended before installation. It is your responsibility to
ensure that qualified mechanical and electrical technicians install this
product.
If there is danger of serious accident resulting from a failure or defect in
this unit, power off the system and the electrical connection of
the device from the system.
The unit is normally supplied without a power switch or a fuse. Use
power switch and fuse as required.
Be sure to use the rated power supply voltage to protect the unit against
damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric
shock and trouble with the unit can be prevented.
separate
Installation
Before beginning installation of this product, please read
the instruction manual and warnings below carefully.
c
Introduction Brochure. ENG ESM-xx10 01 V03 10/11
Note-1:Output-2 exists in only ESM-7710 and ESM-9910 Devices
DIMENSIONS
ESM-4410
84 mm / 3.31 inch
48 mm/ 1.89 inch
Maximum 5 0.2 inchmm /
11±1mm/0.43 inch
ESM-7710
72mm / 2.83 inch
72mm / 2.83 inch
Maximum 15 0.59 inchmm /
84 mm / 3.31 inch
11.5±1mm/0.45 inch
ESM-9910
96mm / 3.78 inch
96mm / 3.78 inch
12 ± 1 mm / 0.47 inch 84 mm / 3.31 inch
Maximum 15 0.59 inchmm /
ESM-7710
SET
SET
OUTPROG
P
48 mm/ 1.89 inch
ESM-4410
SET
SET
OUT PROG
P
PANEL MOUNTING 12
Never attempt to disassemble, modify or repair this unit.
Tampering with the unit may results in malfunction, electric shock
or fire.
Do not use the unit in combustible or explosive gaseous
atmospheres.
During the equipment is putted in hole on the metal panel while
mechanical installation some metal burrs can cause injury on
hands, you must be careful.
Montage of the product on a system must be done with it’s own
fixing clamps. Do not do the montage of the device with
inappropriate fixing clamp. Be sure that device will not fall while
doing the montage.
It is your responsibility if this equipment is used in a manner not
specified in this instruction manual.
ON / OFF TEMPERATURE CONTROL UNITS
ESM-XX10
1
TC
N
L
PT1000
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
234567
NO
C
CAT II
Yc
ESM- 0441
OUTPUT
7A@250VV
230VV
115VV
24VV
PTC, NTC
24 V W
Output
1A T FuseV
Supply
Voltage
Switch
ESM-9910 (96x961/4DIN)
ABCD E FGHI /
/
UVWZ/
/
1000200
12
05
09
J ,Fe CuNi IEC584.1(ITS90)
PTC (Note-1)
Input Type
BC Scale(°C)
-50°C 150°C
0°C 800°C
-50°C 400°C
PT 1000, IEC751(ITS90)
10 K ,NiCr Ni IEC584.1(ITS90)
99.9°C
0°C 999°C
PT 1000, IEC751(ITS90) -19.9°C
PTC (Note-1)
15 -19.9°C 99.9°C
03
13
14
Note-1: If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason,
If input type is selected as PTC, sensor type (V = 0, 1 or 2) or
If input type is selected as NTC, sensor type (V = 0, 3 or 4) must be
declared in ordering information.
ESM-7710 (72x721/4DIN)
ESM-4410 (48x481/4DIN)
ESM-9910 ESM-7710 ESM-4410
3
24 V ( - %15, + %10 ) 50/60 HzW
Supply Voltage
A
2
4
5
9
24 V ( ± %15 ) 50/60 HzV
115 V ( ± %15 ) 50/60 HzV
230 V ( ± %15 ) 50/60 HzV
Customer
18 -50°C 100°C
NTC (Note-1)
19 -19.9°C 99.9°C
NTC (Note-1)
2
Relay Output(7A@250V at resistive load,1NO+1NC)V
Output-1
E
1
SSR Driver Output (Maximum 10 mA@ 5 V )Z
02
For ESM9910; Relay Output(7A@250V at resistive load,1NO+1NC)
For ESM7710; Relay Output(7A@250V at resistive load,1NO)
V
V
Output-2
FG
01
SSR Driver Output (Maximum 10 mA@ 5 V )Z
None
00
-19.9°C 99.9°C
PT 100 , IEC751(ITS90)
400°C
PT 100 , IEC751(ITS90) 0°C
Temp.Sensor which is given with ESM-xx10
V
NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
1.5 m cable for cooling application)
3
None
0
PTC-M6L40.K1.5(PTC Air probe with 1.5 m silicon cable)
1
PTCS-M6L30.K1.5.1/8”(PTC Liquid probe with 1.5 m silicon cable)
2
NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
4
Customer
9
POWER SUPPLY
230
115
V ( ±15% ) 50/60 Hz - 3 VA
V ( ±15% ) 50/60 Hz - 3 VA
24 V ( ±15% ) 50/60 Hz - 3 VA
-3VA
(Supply voltage must be determined in order)
V
V
V
24 V ( - %15, + %10 ) 50/60 HzW
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS
Operating Temperature :
Humidity :
Protection Class :
0...50°C
0-90%RH (none condensing)
IP65 at front, IP20 at rear
ESM-4410 160 gr 48x48 mm, Depth:95 mm 46x46mm
DEVICE WEIGHT DIMENSION PANEL CUT-OUT
ESM-7710 210 gr 72x72 mm, Depth:95.5 mm 69x69mm
ESM-9910 280 gr 96x96 mm, Depth:96 mm 92x92mm
N
L
CAT II
Yc
ESM- 0991
TC
PT1000
NO NCC
OUTPUT-1
7A@250VV
1234567891011
NO NCC
OUTPUT-2
7A@250VV
PTC, NTC
230VV
115VV
24VV
24 V W
Supply
Voltage
Switch
1A T FuseV
Output-2
Note-1
Output-1
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
PT100
N
L
CAT II
Yc
ESM- 0771
TC
PT1000
12345678910
OUTPUT-2 OUTPUT-1
PTC, NTC
230VV
115VV
24VV
24 V W
Supply
Voltage
Switch
1A T FuseV
Output-2
Note-1
Output-1
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
SSR Driver Out
Max.
10mA@5V Z
SSR Driver Out
Max.
10mA@5V Z
PT100
N
L
CAT II
Yc
ESM- 0771
TC CNO NO NCC
12345678910
OUTPUT-2
7A@250VVOUTPUT-1
7A@250VV
PTC, NTC
230VV
115VV
24VV
24 V W
Supply
Voltage
Switch
1A T FuseV
Output-2
Note-1
Output-1
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
PT1000
PT100
N
L
CAT II
Yc
ESM- 0991
TC
PT1000
OUTPUT-1
1234567891011
OUTPUT-2
PTC, NTC
230VV
115VV
24VV
24 V W
Supply
Voltage
Switch
1A T FuseV
Output-2
Note-1
Output-1
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
PT100
SSR Driver Out
Max.
10mA@5V Z
SSR Driver Out
Max.
10mA@5V Z
ESM 9910 with SSR Outputs:
ESM 9910 with Relay Outputs:
ESM 7710 with SSR Outputs:
ESM 7710 with Relay Outputs:
ESM 4410 with Relay Output:
ESM 4410 with SSR Output:
1
TC
N
L
PT1000
23456 7
CAT II
Yc
ESM- 0441
OUTPUT
230VV
115VV
24VV
PTC, NTC
24 V W
Output
1A T FuseV
Supply
Voltage
Switch
PT100
SSR Driver Out
Max.
10mA@5V Z
Temperature
Sensor Input
(TC, PTC, NTC
PT100 or PT1000)
PT100