OAM II Transmitter Dierential Pressure Airow & Temperature Measurement System 1017-1 - 12/17 6
1.3 SPECIFICATIONS
Channel 2 transducer: 316 stainless steel ¼” NPT
compression ttings for channel 2 Dual mode or as the
maximum pressure port Split Min/Max mode
Temperature: 3-wire RTD terminal block connections
TEMPERATURE LIMITS
Standard operating range: +32 to 120 ºF
Extended operating range: -40 to 120 ºF (requires
optional NEMA4 enclosure heater)
Storage temperature range: -20 to 180 ºF
POWER SUPPLY REQUIREMENTS
24VAC (20-32VAC RMS) or 24VDC (20-40VDC)
Power Consumption
Standard:18VA @ 24VAC; 13W @ 24VDC
With heater: 40VA @ 24VAC; 35W @ 24VDC
DISPLAY
3.5” diagonal color graphic LCD with eld programmable
menu driven user interface accessed via four button
membrane keypad.
PROGRAMMING
Factory programmed for specic application. Field
programming available through the user interface/display.
MEMORY
Nonvolatile FLASH memory retains all program
parameters in the event of power loss.
ANALOG OUTPUTS
Three analog outputs are provided: Depending on the
operating mode, they can report ow, temperature and/or
differential pressure.
Field congurable via user interface/display as: 4-20mA,
0-10 VDC or 0-5VDC
COMMUNICATION PROTOCOLS (Field congurable via
user interface/display)
BACnet MS/TP (Default)
MODBUS RTU
NETWORK CONFIGURATION & ADDRESSING
RS485 unit load: ⅓
Recommended maximum number of devices per segment: 32
Baud Rates: 9600, 19200, 38400, 57600, 76800, or 115200
(Default: 38400)
Device Address Range: 1 – 255 (1 - 247 MODBUS)
(Default: 1)
BACnet Device Instance Range: 1 – 4,194,303 (Default 1)
BACnet Max Master Range: 1 – 127 (Default 127)
MODBUS Parity: None, Even, Odd (Default: Even)
APPROVALS
FCC Part 15 Subpart B, Class A Device
SENSING METHOD
Differential pressure is measured across a xed inlet
resistance along with temperature. Sensor readings are
used to calculate and report velocity, volumetric ow and
temperature data. The xed inlet resistance must produce at
least 0.06” w.c. pressure drop at 600 FPM face velocity.
MEASUREMENT MODES
Low Flow Mode: provides a single differential pressure
signal connection
Extended Mode: provides a single differential pressure
signal connection operating over an extended ow range
Min/Max (Split) Mode: provides two differential pressure
signal connections, one for the minimum OA inlet, and
the other for the maximum OA inlet.
Dual Mode: provides separate air ow measurement
channels for OA feeding two separate air handlers.
ACCURACY
Airow
±5% of actual airow over the specied operating
range above 150 FPM. Requires an optional enclosure
heater to maintain accuracy when operating at ambient
temperatures below 32 °F.
Temperature
±2° F from -50 to 120 °F
OVERALL FLOW RANGE (≥ 100 FPM)
Low ow operating mode: 6:1 turn-down
Extended operating mode: up to 24:1 turn-down
Min/Max (Split) operating mode: 6:1 turn-down for each
channel
Dual operating mode: 4:1 turn-down for each channel
AVAILABLE TRANSDUCERS (max. pressure in inches
w.c.) 0.1, 0.25, 0.5, 1.0. 2.0, 5.0 and 10
AVAILABLE SENSOR TYPES
Uni-sensor
316 stainless steel combination reference and inlet
airow pressure sensors.
Temperature
316 stainless steel 3-wire 100 Ohm Platinum RTD with
¼” NPT mounting hardware
ENCLOSURE
Standard: NEMA 1 aluminum with hinged cover
Optional: NEMA 4 with display window and heater
AIRFLOW SENSOR CONNECTIONS
Channel 1 transducer: 316 stainless steel ¼” NPT
compression ttings used for low ow, Extended or
channel 1 Dual mode or as the minimum pressure port for
Min/Max (Split) mode