Airstream Cumberland EXPERT LA User manual

M 890-00507 rev. 00 REV. 00
EXPERT LA
Temperature Controller
USER’S MANUAL
Main Menu
Alarm
Clean
Mode
Light
Open
Close
Open
Close
Open
Close
Open
Close
Open
Close
Open
Close
12
11
10
9
8
7
6
5
4
3
2
1
Min. Vent.
1
2
3
4
Misting
Cool cell
0-10V
Clock 1
Clock 2
Tunnel 2
Tunnel 1
Curtain 2
Curtain 1
Vent Door/
Inlet 2
Vent Door/
Inlet 1
StagesHeaters
Back
Page-
up
Page-
down
Adjust

2EXPERT LA rev.00
EXPERT LA
NOTICE
Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject
to change without notice due to further developments.

3
EXPERT LA rev.00
EXPERT LA
1. INTRODUCTION ........................................................ 6
1.1 Precautions ...........................................................................6
1.2 Symbols of the Manual.............................................................6
1.3 Controller’s Overview ..............................................................7
2. MOUNTING INSTRUCTIONS...................................... 10
2.1 Installing the Controller on the Wall ..........................................10
2.2 Connections.........................................................................10
2.2.1 Main Wiring .........................................................................................10
2.2.2 Alarm Connection .................................................................................10
2.2.3 Sensor Inputs ........................................................................................10
2.2.4 0-10V Output Connection......................................................................10
3. USER INTERFACE .................................................... 11
3.1 Location of the Controls ......................................................... 11
3.2 Parameter Adjustment ...........................................................12
3.3 Language Selection ...............................................................12
3.4 LED Meaning........................................................................13
4. INSTALLATION SETUP ............................................. 14
4.1 Setting the Time & Date......................................................... 14
4.2 Password ............................................................................14
4.2.1 Entering/Changing the Password.............................................................15
4.2.2 Retreiving a Lost Password ....................................................................15
4.3 Controller Programs .............................................................. 16
4.3.1 Program Selection & Settings.................................................................16
4.3.2 Copying & Pasting Programs ..................................................................17
4.4 Measuring Units....................................................................18
4.5 Installation Setup ..................................................................19
4.6 RH Compensation Setup .........................................................23
4.7 Probe Setup......................................................................... 24
4.7.1 Probe Activation ...................................................................................24
4.7.2 Probe & Water Meter Calibration............................................................25
4.7.3 Probe Assignment .................................................................................26
4.8 Relay Assignment ................................................................. 27
4.8.1 Assigning Relays to the Outputs .............................................................27
4.8.2Assigning Min.Ventilation Relays ............................................................28
4.9 Night Settings ......................................................................29
4.10 Clean Mode .........................................................................30
4.11 Test Mode........................................................................... 31
4.12 Version ...............................................................................31
TABLE OF CONTENTS

4EXPERT LA rev.00
EXPERT LA
5TEMPERATURE & PRESSURE SETTINGS ..................... 32
5.1 Temperature Set Point ...........................................................32
5.2 Static Pressure Set Points ......................................................33
5.3 Temperature Set Point Curve ..................................................34
5.3.1 Principle of operation.............................................................................34
5.3.2 Curve Settings ......................................................................................35
5.3.3 Curve Offset .........................................................................................36
6. VENTILATION & COOLING ....................................... 37
6.1 Minimum Ventilation ..............................................................37
6.1.1 Minimum Ventilation Cycles ..................................................................37
6.1.2 Minimum Ventilation Settings ................................................................37
6.1.3 Minimum Ventilation Curve ...................................................................38
6.1.4 Curve Settings ......................................................................................39
6.2 Fan Stages ..........................................................................40
6.2.1 Principle of Operation ............................................................................40
6.2.2 Stage 1 Ramping (Transition between Min. Vent. & Stage 1) ..................41
6.2.3 Fan Stage Settings ................................................................................42
6.2.4 0-10V Ventilation Outputs .....................................................................43
6.3 Natural Ventilation Curtains ....................................................44
6.3.1 Principle of Operation ............................................................................44
6.3.2 Natural Ventilation Settings ...................................................................45
6.3.3 Curtain Compensation ...........................................................................46
6.3.4 Stopping Fans in Natural Vent................................................................46
6.3.5 Purge ...................................................................................................47
6.4 Tunnel Doors....................................................................... 48
6.4.1 Pressure-based Tunnel Doors..................................................................48
6.4.2 Temperature-Based Tunnel Doors ...........................................................49
6.4.3 Tunnel Door Settings .............................................................................50
6.5 Vent Doors (Inlets) ................................................................51
6.5.1 Timer-based Vent Doors (Inlets) .............................................................52
6.5.1.1 Principle of Operation ......................................................... 52
6.5.1.2 Timer-based Vent Door (Inlet) Settings ................................. 53
6.5.1.3 Resetting the Actuator’s Position ......................................... 54
6.5.2 Static-Pressure-Based Vent Doors (Inlets)................................................55
6.5.2.1 Principle of Operation ......................................................... 55
6.5.2.2 Static-Pressure-Based Vent Door (Inlet) Settings..................... 56
6.6 0-10V Air Inlet .....................................................................57
6.7 Cool Cells ............................................................................59
6.8 Misting Output .....................................................................60
7. HEATING................................................................ 62
8. LIGHTS .................................................................. 63

88 EXPERT LA rev.00
EXPERT LA
Timer relays
Principle of operation 40
Timer settings 42
S
Screens (LED & LCD) 12
Sensors
see Probes
Set points
RH set point
see Relative Humidity
Static pressure set points
see Static Pressure
Temperature set points
see Temperature
Setup (Installation) 19–22
Simulation (temperature) 31
Spanish software 12
Static pressure (SP)
Current pressure level 72
Measuring units 18
Pressure alarms
Principle of operation 70
Settings 71
Probe history 73
SP Probe
Activation 25
Calibration 25
Static pressure set points
Activating pressure groups 20
Operation & settings 33
Symbols of the manual 6
T
Technical specifications 76
Temperature
Average room temperature
Current average T° 72
History 73
Probe assignment 26
Probe set 2 - probe assignment 26
Probe set in use 72
Inside temperature probes
Activation 24
Current probe readings 72
History 73
Probe assignment 26
Probe calibration 25
Outside temperature
Activation 24
Current probe reading 72
History 73
Outside T° set point 32
Probe calibration 25
Temperature alarms
Principle of operation 70
Settings 71
Temperature set points
Clean mode set point 32
Current set point 72
Night set point 32
Operation & settings 32–33
Outside T° set point 32
Set point curve 34, 36
Temperature simulation 31
Temperature units 18
Test mode 31
Time
Setting the time and date 14
Time format 18
Tunnel doors (pressure-based)
Activation 19, 20
Principle of operation 48
Probe set 2 50
Settings 50
Static pressure limits 33
Tunnel doors (temperature-based)
Activation 19, 20
Principle of operation 48, 49
Probe set 2 50
Settings 50
U
Units 18
User password 14
V
Variable fans
see Fan stages (0-10V Fans)
Vent door/inlet (pressure-based)
Activation 19, 20
Current position 72
Principle of operation 55
Relay assignment 27
Settings 56
Static pressure limits 33
Vent door/inlet (timer-based)
Activation 19, 20
Current position 72
Principle of operation 52
Relay assignment 27
Resetting the position 54
Settings 53
Ventilation
Fans
see Fans stages
Min. ventilation
see Minimum ventilation
Version (software) 31
W
Warning messages 75
Water meter
Activation 24
Calibration 25
Consumption history 73
Measuring units 18
Water spill alarm 70, 71
Whisker switch 21, 46
Wiring 10
Worksheets 80–85
5
EXPERT LA rev.00
EXPERT LA
9. CLOCK OUTPUTS .................................................... 66
10. RH COMPENSATION ................................................ 67
11. ALARMS................................................................. 69
11.1 Alarm Log ...........................................................................69
11.2 Alarm Conditions ..................................................................70
11.3 Alarm Settings .....................................................................71
12. MONITORING FUNCTIONS........................................ 72
12.1 Current Conditions ................................................................ 72
12.2 Run Time Histories ................................................................ 72
12.3 History Menus ......................................................................73
12.4 Animal Age & Count.............................................................. 74
12.5 Automatic Reminder .............................................................. 75
13. TECHNICAL SPECIFICATIONS ................................... 76
14. MEMORY CARD....................................................... 77
14.1 Principle of Operation ............................................................ 77
14.2 Access the Transfer Menu...................................................... 77
14.3 Configuration Transfer ...........................................................78
14.3.1 Installing a New Configuration ...............................................................78
14.3.2 Saving a Configuration on the Card ........................................................78
14.4 Firmware Update ..................................................................79
14.5 Erasing the Memory Card .......................................................79
15. WORKSHEETS......................................................... 80
15.1 Relay Assignment Template ....................................................81
15.2 Probe Assignment Worksheet..................................................84
15.3 Installation Setup Worksheet ...................................................85
INDEX ............................................................................ 86

6EXPERT LA rev.00
EXPERT LA
1. INTRODUCTION
1.1 Precautions
We strongly recommend installing
supplementary natural ventilation as
well as a backup thermostat on at least
one cooling stage (refer to the relay pan-
els’ wiring diagram to connect the ther-
mostat).
Although fuses at the input and outputs
of the controller protect its circuits in
case of an overload or overvoltage, we
recommend installing an additional pro-
tection device on the controller's sup-
ply circuit.
The room temperature where the con-
troller is located MUST ALWAYS RE-
MAIN BETWEEN 32°F AND 104°F
(0°C TO 40°C).
To avoid exposing the controller to
harmful gases or excessive humidity, it
is preferable to install it in a corridor.
DO NOT SPRAY WATER
ON THE CONTROLLER!
1.2 Symbols of the Manual
Caution.Readthefollowingtextcare-
fully. It contains important pieces of
information which, if ignored, may
cause the controller to operate im-
properly.
Payattention.Thefollowingtextcon-
tainsveryusefulinformation.
PresstheMainMenupush-button.
Press the proper menu selector.
87
EXPERT LA rev.00
EXPERT LA
History menus 73
Humidity see Relative humidity
I
Inlets
Static-pressure-based inlets
see Vent door/inlet (pressure-
based)
Timer-based inlets
see Vent door/inlet (timer-based)
Inlets (0-10V inlet output)
Activation 20
Principle of operation 57
Probe assignment 26
Settings 58
Inputs
Activation 24
List of available inputs 7
Installation setup 19–22
Installer password
see Password
L
Language selection 12
LCD screen
Backlight button 12
Contrast adjustment 12
Location 12
LEDs
LED display
Location 12
Unit selection 22
LED meaning 13
Lights
Activation 19
Operation & Settings 63–65
Using additionnal on/off lights 27
Liters 18
M
Main menu button 11
Marketed animals
History 73
Posting # of marketed animals 74
Measuring units 18
Memory card
Erasing the card 79
Transfer process 77
Menu selectors 11
Minimum ventilation
Activation 37
Principle of operation 37
Relay assignment 28
Settings 37
Minimum ventilation curves
Principle of operation 38
Settings 39
Misting output
Activation 21
Operation & settings 60–61
Relay assignment 27
RH compensation on the mist output
Activation 23
Principle of operation 67
Settings 68
Mortality
Entering new mortalities 74
History 73
Posting # of mortalities 74
Mounting instructions 10
N
Natural ventilation curtain
Outside T° compensation 46
Outside T° set point 32
Principle of operation 44
Probe assignment 26
Purge cycles 47
Settings 45
Shutoff fans
Principle of operation 46
Relay selection 27
Night
see Day/night
O
Outputs
Activation 19–22
List of available outputs 7
Number of outputs 21
Relay assignment 27
Outside RH
see Rel. Humidity (RH)
Outside T°
see Temperature
P
Parameter adjustment 12
Password
Default user level 22
Enable/disable the password 22
Entering/changing the password 14–15
Retreiving a lost password 15
Probe
Activation 24
Assignment 26
Calibration 25
Connection 10
Extension 10
Probe sets
Current probe set in use 72
Principle of operation 49
Probe assignment 26
Settings 50
Programs
Automatic program switch
Activation 21
Settings 16, 21
Copy/paste program settings 17
Current program in use 72
Enabling programs 21
Principle of operation 16
Program selection 16
Purge cycles
Activation 21
Operation & settings 47
R
Ramping (stage 1)
Activation 21
Principle of operation 41
Relative humidity (RH)
Inside RH sensor
Activation 24
Calibration 25
Current reading 72
History 73
Outside RH sensor
Activation 24
Calibration 25
Current reading 72
History 73
RH Compensation
Principle of operation 67
Settings 68
RH set point 68
Relays
Alarm relay 71
Relay assignment 27
Shutoff fan relays in natural ventilation
Principle of operation 46
Relay selection 27

86 EXPERT LA rev.00
EXPERT LA
INDEX
A
Age
see Animals
Alarms
Alarm conditions 69, 70
Alarm log 69
Reset the alarm log 22
Alarm relay 71
Alarm settings 71
Animals
Animal count
History 73
Posting changes to the animal
count 74
Enabling animal age functions 21
Starting a new group 74
B
Backup
Backup relay
Activation 21
Relay assignment 27
Making a backup of the controller
77
Buttons 11–12
C
Calibration
Probe calibration 25
Water meter calibration 25
Celsius units 18
Clean mode
Alarms 70, 71
Clean mode set point 32
Operation & settings 30
Clock
Display : AM/PM or 24hours 18
Setting the time and date 14
Clock outputs
Activation 19
Current status 72
Operation & settings 66
Relay assignment 27
Compensation
see Relative humidity compensation
Connections 10
Contrast (LCD screen) 12
Controller
Features 7
Firmware update 79
Installation setup 19–22
Location of the controls 11
Mounting instructions 10
Software
Language selection 12
Version 31
Technical specifications 76
Cool cells
Activation 21
Operation & Settings 59
Relay assignment 27
RH comp. on the cool cell output
Activation 23
Principle of operation 67
Settings 68
Copy & Paste function 17
Culled
History 73
Posting # of culled animals 74
Current conditions 72
Curtains
see Natural ventilation curtain
Curves
Minimum ventilation - On Time
curve
Principle of operation 38
Settings 39
Set point curve
Curve offset 36
Enable the curve function 21
Principle of operation 34
Settings 35
D
Date 14
Day / Night
Day/night times 29
Night set point
Principle of operation 32
Settings 32
Display
Red LED display
Location 11
Unit selection 22
E
Electrical specifications 76
English software 12
Evaporative pads
see Cool cells
F
Fahrenheit units 18
Fan stages
Activation 19
Current fan stage in use 72
Minimum ventilation
see Minimum ventilation
Principle of operation 40
Relay assignment 27
Settings 42
Timer relays
Principle of operation 40
Timer settings 42
Fan stages (0-10V fans)
Activating 0-10 V outputs 20
Operation & settings 43
Probe assignment 26
Feeders
Activation 19
Relay assignment 27
Run time alarm
Principle of operation 70
Settings 71
Run time history 72
Fire see Heaters
Firmware update
Principle of operation 79
Settings 79
G
Gallons 18
H
Heaters
Activation 19
Current status 72
Lo/Hi fire
Activation 19
Operation & Settings 62
Probe assignment 26
Relay assignment 27
RH compensation on heaters
Activation 23
Principle of operation 67
Settings 68
Run time history 72
Hi/Lo Fire see Heaters
7
EXPERT LA rev.00
EXPERT LA
1.3 Controller’s Overview
The EXPERT LA is an electronic device used for
environmental control in livestock buildings. It com-
bines sidewall, natural and tunnel ventilation into
one powerful system.
The EXPERT LA can control the following inputs
and outputs:
OUTPUTS:
4heating stages;
12 fan stages;
2tunnel doors;
2natural ventilation curtains;
2vent doors (inlets);
2clock outputs;
1misting output;
1cool cell output;
4feeders;
1backup relay;
1built-in 0-10V output to control an inlet or
variable-speed fans;
1 built-in 0-10V output to control lighting equip-
ment.
INPUTS:
8inside temperature sensors;
2outside temperature sensors;
1inside humidity sensor;
1outside humidity sensor;
1static pressure probe;
9water meters.
Refer to the wiring diagram enclosed
at the end of this manual to connect
sensorsandloads.

8EXPERT LA rev.00
EXPERT LA
MAIN FEATURES:
VERY LARGE LCD DISPLAY
A large LCD screen provides an efficient interface
for displaying, monitoring and adjusting the param-
eters.
3 CONTROLLER PROGRAMS
The controller allows using 3 different programs to
control the room temperature. It is thus possible to
activate a specific program, that uses particular
temperature settings, in accordance with the ani-
mal age for instance.
STATUS LEDS
Pilot lights that indicate the status of the control-
ler outputs are located on the faceplate of the con-
troller. These LEDs allow monitoring the system’s
operation without having to enter the building.
MINIMUM VENTILATION CYCLE
When ventilation is not required to reduce the room
temperature, fan outputs can run either continu-
ously or intermittently to reduce humidity levels
and supply oxygen to the room.
8 INDOOR TEMPERATURE SENSORS
Up to eight temperature sensors can be connected
to the controller to obtain an accurate reading of
the average room temperature and a faster reac-
tion time.
NATURAL VENTILATION CURTAINS
The controller can open 2 natural ventilation cur-
tains and stop all ventilation when the outside tem-
perature is sufficiently warm.
TUNNEL VENTILATION
When the room temperature rises, tunnel ventila-
tion reduces the actual temperature perceived by
the animals.
HUMIDITY CONTROL
The inside and outside relative humidity sensors al-
low controlling humidity levels in the room.
0-10V OUTPUT
The controller has 2 internal 0-10V outputs. The
first 0-10V output can either be used to control an
air inlet or variable-speed fans and the second out-
put can control lighting equipment.
CONTROL OF THE AIR INLET MOVEMENT
The movement of vent doors (inlets) can be coordi-
nated with the operation of the fans. This allows
the vent doors (inlets) to be adjusted correctly,
without the influence of uncontrollable factors such
as wind or air from adjoining rooms
HISTORY MENUS
History menus allow monitoring the sensor read-
ings and verify the run time of some outputs. The
controller comes with the following histories menus:
•Minimum and maximum sensor readings:
Ambient temperature ........... 60 days
Inside temperature sensors .... 10 days
Outside temperature sensor ... 75 days
Inside humidity sensor ........... 75 days
Outside humidity sensor ........ 75 days
Static pressure sensor........... 75 days
•Run time of each heater ........ 75 days
•Run time of each feeder ........ 75 days
•Daily water consumption ....... 75 days
ALARM MANAGEMENT
The controller provides alarms for high-low tem-
peratures, defective sensors and other system fail-
ures. It keeps in memory the 20 most recent alarm
conditions.
PASSWORD PROTECTION
A password can be enabled to restrict access to
the setup functions of the controller.
Program 1 Program 2 Program 3
# feeders ____ (0-4) ____ (0-4) ____ (0-4)
# heating stages ____ (0-4) ____ (0-4) ____ (0-4)
Use Heater Lo/Hi Fire? (Common to
all programs)
# fan stages ____ (0-12) ____ (0-12) ____ (0-12)
# clock output ____ (0-2) ____ (0-2) ____ (0-2)
# natural vent. curtains ____ (0-2) ____ (0-2) ____ (0-2)
# tunnel curtains ____ (0-2) ____ (0-2) ____ (0-2)
# light programs ____ (0-8) ____ (0-8) ____ (0-8)
# vent door / inlet ____ (0-2) ____ (0-2) ____ (0-2)
Use 0-10V output?
Vent door / inlet 1 Mode (Common to
all programs)
Vent door / inlet 2 Mode (Common to
all programs)
Close vents in natural?
Tunnel control (Common to
all programs)
# of Static P. Set points ____ (1-3) ____ (1-3) ____ (1-3)
0-10V Type (Common to
all programs)
0-10V Mode (Common to
all programs)
0-10V follows set point ? (Common to
all programs)
Curtain 1 compensation ?
Curtain 1 Whisker switch ? (Common to
all programs)
Curtain 2 compensation ?(Common to
all programs)
Curtain 2 Whisker switch ?
Ramping in stage 1 ?
Use purge ?
Use misting ?
Mist follows set point ? (Common to
all programs)
Use cool cell ?
Use backup relay ?
Number of outputs ? (Common to
all programs)
Use age ?(Common to
all programs)
Use Temp. curve ? (Common to
all programs)
Number of programs ____ (1 - 3) (Common to
all programs)
Switch program by age? (Common to
all programs)
Switch program by Out.T° ? (Common to
all programs)
Use password ?(Common to
all programs)
Use passsword level: (Common to
all programs)
Clear alarms ?(Common to
all programs)
Digit display (Common to
all programs)
ventilation inlet
Yes No Yes No Yes No
Yes No Yes No Yes No
Yes No Yes No Yes No
Yes No
Yes No
0-10V 10-0V
Yes No
Yes No Yes No Yes No
Yes No
Yes No Yes No Yes No
Yes No Yes No Yes No
16 32
Yes No
Yes No
Yes No
User 1
T°
SP
T°/SP
Yes No Yes No Yes No
Yes No Yes No Yes No
Temperature
Static pressure
Time
Time
Yes No Yes No Yes No
Yes No
Yes No
Yes No
User 2 Installer
Yes No
Static pressure
Static pressure
15.3 Installation Setup Worksheet

84 EXPERT LA rev.00
EXPERT LA
15.2 Probe Assignment Worksheet
PROGRAM 1
PROGRAM 2
PROGRAM 3
Output
1
2
3
4
5
6
7
8
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Room T°
Probe set 2
0-10V #1
Natural curtain 1
Natural curtain 2
PROBES
Output
1
2
3
4
5
6
7
8
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Room T°
Probe set 2
0-10V #1
Natural curtain 1
Natural curtain 2
PROBES
Output
1
2
3
4
5
6
7
8
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Room T°
Probe set 2
0-10V #1
Natural curtain 1
Natural curtain 2
PROBES
9
EXPERT LA rev.00
EXPERT LA
BACKUP BATTERY
A backup battery allows the unit to keep time in
case of a power failure.
OVERLOAD AND OVERVOLTAGE PROTECTION
Resettable fuses are provided at low-voltage inputs
of the controller to protect its circuitry in the case
of an overload or overvoltage.
COMPUTER CONTROL
The controller can be connected to a computer,
thus making it possible to centralize the manage-
ment of information and diversify control strate-
gies.
TEST MODE
A test mode allows you to simulate temperature
changes and verify controller performances.

10 EXPERT LA rev.00
EXPERT LA
2. MOUNTING INSTRUCTIONS
2.1 Installing the Controller on
the Wall
Fasten the two metal brackets on the mounting
holes located behind the controller using four
screws. Then, mount the enclosure on the wall us-
ing four other screws. Leave a clearance of at least
16” to the left of the enclosure to allow the cover
to be removed for maintenance.
2.2 Connections
2.2.1 Main Wiring
Refer to the wiring diagram enclosed with this
user's manual to connect the controller. Drill holes
at the bottom of the enclosure to pass the wires
and install watertight connectors to prevent water
from entering in the enclosure. Do not make any
holes at the side and top of the enclosure.
ALL WIRING MUST BE DONE BY AN
AUTHORIZEDELECTRICIANANDMUST
COMPLY WITH APPLICABLE CODES,
LAWS AND REGULATIONS. MAKE
SURE POWER IS OFF BEFORE DOING
ANY WIRING TO AVOID ELECTRICAL
SHOCKS AND EQUIPMENT DAMAGE.
2.2.2 Alarm Connection
There are two types of alarms on the market. One
type activates when current is cut off at its input;
the other type of alarm activates when current is
supplied at its input. For an alarm of the first type,
use the NC terminal as shown on the wiring dia-
gram. For an alarm of the second type, use the
NO terminal.
2.2.3 Sensor Inputs
Sensors operate at low voltage and are isolated
from the supply. Make sure that sensor cables
remain isolated from all high voltage sources. In
particular, do not route the sensor cables through
the same electrical knockout as other cables. Do
not connect the shield from the sensor cable to a
terminal or a ground.
Extending a sensor:
Each sensor can be extended up to 500 feet
(150 meters). To extend a sensor, use a shielded
cable of outside diameter between 0.245 and 0.260
in (6.22 and 6.60 mm) (the cable dimensions should
not be under 18 AWG) to ensure the cable entry is
liquid tight. Do not ground the shielding.
It is preferable to solder the cable joint to ensure a
proper contact between the two cables.
Donotrunsensorcablesnexttoother
power cables. When crossing over
other cables, cross at 90°.
Defective sensors:
An alarm is generated when a defective sensor is
detected. Defective sensors are identified in the
"Alarm Log" menu. Refer to chapter 12 for fur-
ther information on the alarms.
2.2.4 0-10V Output Connection
It is recommended to use a 18 to 22 AWG wire to
connect the devices to 0-10V outputs. This type
of output can be used to connect various devices
such as inlets, fans or lighting equipment.
PROGRAM 3
12345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Min. vent. on/off fans
Fan stage 1
Fan stage 2
Fan stage 3
Fan stage 4
Fan stage 5
Fan stage 6
Fan stage 7
Fan stage 8
Fan stage 9
Fan stage 10
Fan stage 11
Fan stage 12
Tunnel door 1 OPN
Tunnel door 1 CLO
Tunnel door 2 OPN
Tunnel door 2 CLO
Inlet 1 / Vent door 1 OPN
Inlet 1 / Vent door 1 CLO
Inlet 2 / Vent door 2 OPN
Inlet 2 / Vent door 2 CLO
Natural curtain 1 OPN
Natural curtain 1 CLO
Natural curtain 2 OPN
Natural curtain 2 CLO
Feeder relay
Backup relay
Misting
Cool cell
Time Clock 1
Time Clock 2
On/Off Lights
Output #:

PROGRAM2
12345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Min. vent. on/off fans
Fan stage 1
Fan stage 2
Fan stage 3
Fan stage 4
Fan stage 5
Fan stage 6
Fan stage 7
Fan stage 8
Fan stage 9
Fan stage 10
Fan stage 11
Fan stage 12
Tunnel door 1 OPN
Tunnel door 1 CLO
Tunnel door 2 OPN
Tunnel door 2 CLO
Inlet 1 / Vent door 1 OPN
Inlet 1 / Vent door 1 CLO
Inlet 2 / Vent door 2 OPN
Inlet 2 / Vent door 2 CLO
Natural curtain 1 OPN
Natural curtain 1 CLO
Natural curtain 2 OPN
Natural curtain 2 CLO
Feeder relay
Backup relay
Misting
Cool cell
Time Clock 1
Time Clock 2
On/Off Lights
Output #:
11
EXPERT LA rev.00
EXPERT LA
3. USER INTERFACE
3.1 Location of the Controls
•Menu selectors
Use these buttons to select a menu.
•Main menu short-cut key
This short-cut key provides access to the
main menu and allows seeing the current sta-
tus of each input and output on the main
screen. The main menu is automatically se-
lected after 4 minutes of inactivity.
Main
Screen
Menu
Selectors Menus LED
Display
Navigation
Buttons
Adjustment
Buttons Status
LEDs
Main menu
short-cut key Back
Page-
up Page-
down
Main Menu
Alarm
Clean
Mode
Light
Open
Close
Open
Close
Open
Close
Open
Close
Open
Close
Open
Close
12
11
10
9
8
7
6
5
4
3
2
1
Min. Vent.
1
2
3
4
Misting
Cool cell
0-10V
Clock 1
Clock 2
Tunnel 2
Tunnel 1
Curtain 2
Curtain 1
Vent Door/
Inlet 2
Vent Door/
Inlet 1
StagesHeaters
Back
Page-
up
Page-
down
Adjust
•Navigation buttons
Use these buttons to select an item displayed
in the main screen. In addition, the left and
right-arrow key are also used to move
through the display by pages (left = page-
up, right = page-down).
•Adjustment buttons
Use these buttons (+ or -) to modify the
value of the selected parameter.

12 EXPERT LA rev.00
EXPERT LA
•Back
Press BACK to return to the previous menu.
•Main LCD Screen
The large LCD screen is used to display the
various parameters and menus. The contrast
of the screen can be adjusted using the po-
tentiometer located behind the display. Open
the front panel to access the potentiometer.
•LED Display
This display shows the current reading of
chosen sensor(s). Refer to section 4.5 to
select what information needs to be shown
on the LED display.
•Status Leds
Status pilot lights indicate the current sta-
tus of the outputs. Refer to section 3.4 for
further information about these LEDs.
•Backlight button
Press this button to light up the LCD screen.
3.2 Parameter Adjustment
Use navigation buttons to select the desired pa-
rameter on the main screen. A parameter that
can be modified blinks when it is selected; non-
blinking parameters cannot be changed.
-
+
LCD CONTRAST
POTENTIOMETER
Backlight
Button
3.3 Language Selection
The user interface of the controller can be displayed
in multiple languages. Follow these steps to change
the language selection:
Select:
Main menu
More, Otros or Outros
English, Español or Português
•The controller automatically changes the lan-
guage display.
Pressandholdthe main menu
buttonfor5secondstoswitch
thelanguageselection.
Main menu
Monitoring
Program
Selection
Setup
Time/Date
Español
Português
User Settings
Use to navigate
81
EXPERT LA rev.00
EXPERT LA
15.1 Relay Assignment Template
PROGRAM 1
12345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Heater 4 Hi Fire
Heater 4
Heater 3 Hi Fire
Heater 3
Heater 2 Hi Fire
Heater 2
Heater 1 Hi Fire
Heater 1
Min. vent. on/off fans
Fan stage 1
Fan stage 2
Fan stage 3
Fan stage 4
Fan stage 5
Fan stage 6
Fan stage 7
Fan stage 8
Fan stage 9
Fan stage 10
Fan stage 11
Fan stage 12
Tunnel door 1 OPN
Tunnel door 1 CLO
Tunnel door 2 OPN
Tunnel door 2 CLO
Inlet 1 / Vent door 1 OPN
Inlet 1 / Vent door 1 CLO
Inlet 2 / Vent door 2 OPN
Inlet 2 / Vent door 2 CLO
Natural curtain 1 OPN
Natural curtain 1 CLO
Natural curtain 2 OPN
Natural curtain 2 CLO
Feeder relay
Backup relay
Misting
Cool cell
Time Clock 1
Time Clock 2
On/Off Lights
Output #:

80 EXPERT LA rev.00
EXPERT LA
15. WORKSHEETS
CLIENT
Name: _______________________________________________
Address: _______________________________________________
_______________________________________________
_______________________________________________
City: _______________________________________________
Tel.: _______________________________________________
Fax: _______________________________________________
E-mail: _______________________________________________
INSTALLER
Name: _______________________________________________
Address: _______________________________________________
_______________________________________________
_______________________________________________
City: _______________________________________________
Tel.: _______________________________________________
Fax: _______________________________________________
E-mail: _______________________________________________
13
EXPERT LA rev.00
EXPERT LA
3.4 LED Meaning
Solid LED: An alarm condition is active.
A corrective action is required.
Flashing LED: An alarm condition occurred
but no longer exists.
CLEAN MODE Solid LED: Clean mode is active.
Solid LED: Lights are ON.
Open Solid LED: tunnel door #2 is opening.
Close Solid LED: tunnel door #2 is closing.
Open Solid LED: tunnel door #1 is opening.
Close Solid LED: tunnel door #1 is closing.
Open Solid LED: natural ventilation curtain #2 is opening.
Close Solid LED: natural ventilation curtain #2 is closing.
Open Solid LED: natural ventilation curtain #1 is opening.
Close Solid LED: natural ventilation curtain #1 is closing.
Solid LED: vent door (inlet) #2 is opening.
Flashing LED: the controller opens vent door (inlet) #2 to reset the
actuator's position.
Solid LED: vent door (inlet) #2 is closing
Flashing LED: the controller closes vent door (inlet) #2 to reset the
actuator's position.
Solid LED: vent door (inlet) #1 is opening.
Flashing LED: the controller opens vent door (inlet) #1 to reset the
actuator's position.
Solid LED: vent door (inlet) #1 is closing
Flashing LED: the controller closes vent door (inlet) #1 to reset the
actuator's position.
Solid LED: fan stage #x is active.
MINIMUM VENTILATION Solid LED: minimum ventilation cycles are active.
Solid LED: heating output #x is active.
Solid LED: the misting output is active.
Solid LED: the cool cell output is active.
Solid LED: 0-10V output #1 is active.
Solid LED: clock output #x is active.
MEANING
CURTAIN 2
CURTAIN 1
TUNNEL 2
TUNNEL 1
ALARM
VENT DOOR /
INLET 1
Open
Close
LED
0-10V OUTPUT
CLOCK 1-2
COOL CELL
LIGHTS
MISTING
STAGES 1-12
HEATERS 1-4
Open
VENT DOOR /
INLET 2
Close

14 EXPERT LA rev.00
EXPERT LA
4.INSTALLATION SETUP
4.1 Setting the Time & Date
Select:
Main menu
Time / Date
•Press the right-arrow key once. The current
day of the week flashes on the display.
•Use the adjustment buttons to adjust the day
of the week.
•Press the right-arrow key to step to the next
parameter.
•Proceed in similar fashion to set the whole
time and date.
Main menu
Time/Date
Time and Date
Use to navigate
Wed May 12 200X
12 : 12 : 12 AM
4.2 Password
The controller has three levels of password access:
User 1 password [1-1-1-1]
This password provides access to temperature set
points, minimum ventilation settings and to the ani-
mal count menu. If many password levels are used,
the controller automatically selects this user level
after 15 minutes of inactivity.
User 2 [2-2-2-2]
This password provides access to all menus except
for installation setup menus. This password can be
modified as explained below.
Installer password [0-6-1-0]
This password provides access to all functions of the
controller. It can be modified as explained below.
Using passwords is optional. Refer to the Installa-
tion Setup section of this manual to enable or dis-
able passwords (section 4.5).
Default installer password
0 - 6 - 1 - 0
User 1 Password
1 - 1 - 1 - 1
User 2 Password
2 - 2 - 2 - 2
Refer to the Installation Setup
menutoenable/disablethepass-
wordprotection(seesec.4.5).
79
EXPERT LA rev.00
EXPERT LA
14.4 Firmware Update
Firmware Files (*.fir)
The controller’s firmware contains instructions and
data responsible for controlling the controller. When
a new firmware version is available, you can install
it in your controller by downloading a firmware file
(*.fir) from the card. Upgrading the firmware will
not affect your parameter settings.
•Access the transfer menu as explained in
section 14.2 and select the “Memory card
to controller” menu.
•Press and hold the up- and down-arrow keys
simultaneously for 3 seconds. The Firmware
Update menu is displayed.
•Read the warning message carefully then
press Next.
•Select the proper firmware file (*. fir) on
the main screen. The icon indicates which
files can be used for the transfer.
Main Menu
Card/Ctrl
Firmware
Next
Exit
FIRMWARE UPDATE
WARNING!!!
It is extremely important
to ensure that the AC power
source is not interrupted
during this process.
This unit may render
inoperable if power fails
during this update.
To continue this process,
press NEXT.
Main Menu
Card/Ctrl
Firmware
Select
Exit
FIRMWARE UPDATE
File_name.cfg
atm_0_7_30.bin
atm_0_7_30.fir
•Press “Select” to get information about the
selected firmware file (*.fir).
•Press “Yes” to install the selected firmware
or select “No” to go back to the previous
menu.
•Once the transfer is over, press Exit then re-
move the memory card from the connector.
Main Menu
Card/Ctrl
Firmware
Yes
No
FIRMWARE UPDATE
Install this firmware?
Name = Atm Advanced
Version= x.y.zz
ReleaseDate=2006-01-01
ModelVersion=0x111A
14.5 Erasing the Memory Card
Follow this procedure to delete all the content of
the memory card.
•Access the transfer menu as explained in
section 14.2 and select the “Controller to
Memory card” menu.
•Press “Erase card” to delete all files that are
stored on the card.
•Once the card is erased, press Exit then re-
move the memory card from the connector.
Mem.Card
Ctrl/card
Complete
Erase card
Exit
Controller to Memory card

78 EXPERT LA rev.00
EXPERT LA
14.3.1 Installing a New Configuration
The following procedure shows how to install a new
configuration in your controller. You can choose to
install the whole new configuration or to install a
specific component of it.
•Access the transfer menu as explained in
section 14.2 and select the “Memory card
to controller” menu.
•Select the proper configuration file (*. cfg)
on the main screen. The icon indicates
which files can be used for the transfer.
•Press the button that corresponds to the
component(s)you want to install:
Complete (all components)
Software (screen menus)
User data (parameter settings)
•Once the transfer is over, press Exit then re-
move the memory card from the connector.
14.3.2 Saving a Configuration on the Card
The following procedure shows how to save your
controller’s configuration into the memory card.
This will create a configuration file (*.cfg) on the
card.
•Access the transfer menu as explained in
section 14.2 and select the “Controller to
Memory card” menu.
•The name of the configuration file (*.cfg) is
shown at the top of the screen and the table
at the bottom gives information about the
memory card. Press “Complete” to save your
controller’s configuration on the card.
•Once the transfer is over, press Exit then re-
move the memory card from the connector.
Mem.Card
Card/ctrl
Complete
Software
User Data
Exit
Memory card to controller
File_name.cfg
atm_0_7_30.bin
atm_0_7_30.fir
Mem.Card
Ctrl/card
Complete
Erase card
Exit
Controller to Memory card
File_name.cfg
MS300
Total : 8192 KB
Used : 0 KB
Free : 8192 KB
14.3 Configuration Transfer
Configuration Files (*.cfg)
Configuration files are a set of instructions that
tells the controller what to do. These files are di-
vided into two parts:
1) Software (screen menus)
2) User data (parameter settings)
You can save your controller’s configuration on the
card or you can install a new configuration into
your controller. Note that it is now possible to in-
stall a specific component of the configuration with-
out affecting the other component. For instance,
you can upload new controller software without
affecting your parameter settings.
15
EXPERT LA rev.00
EXPERT LA
4.2.1 Entering/Changing the Password
Select:
Main menu
Setup *
User
Password
*A password may be required to access this menu.
•Use the adjustment buttons to set the first
number of the password then press the right-
arrow key. Proceed the same way to enter
all numbers of the password then press the
right-arrow key. The user is then identified.
•If the installation password or user 2 pass-
word is posted, the prompt “Change Pass-
word” appears on screen. Use the adjust-
ment buttons to set the new password code.
IMPORTANT
Chooseaneasy-to-remember
passwordandwrite itdown
in a safe place!
•Use the adjustment buttons to confirm the
new installer password then press the right-
arrow key to confirm the new password.
4.2.2 Retreiving a Lost Password
Follow these steps to retrieve a lost password:
Select:
Main menu
Setup *
User
Password
User Password**
*If the controller prompts for a password, enter the factory
password (contact your dealer).
** This tab is only accessible from the factory level.
•The actual password of all user levels are
displayed on screen.
Main menu
Setup
User
Password
Password
Use to navigate
Current mode Installer
Change User 0 * * *
Change Password * * * *
Main menu
Setup
User
Password
User Passw.
User Passwords
Use to navigate
User 1: 1111
User 2: 2222
Installer: 0000

16 EXPERT LA rev.00
EXPERT LA
4.3 Controller Programs
Program definition
Programs are an assembly of settings (tempera-
ture settings, relay assignment, probe assignment,
etc.) that can be enabled at different moment of
the breeding process. In all, the controller can use
3 different programs.
Automatic program selection
The controller can automatically switch the pro-
gram selection when the animals reach a certain
age and/or as a function of outside temperature.
Refer to the Installation Setup section of this
manual to enable or disable the automatic program
switch (see section 4.5).
Refer to the Installation Setup section of this
manual to set the number of programs in use
and to enable or disable the automatic
program switch (section 4.5).
Program selection
When a program is selected, all parameter settings
displayed on screen are related to this program.
Makesuretherightprogramisselected
beforeadjustinganyparameter.
4.3.1 Program Selection & Settings
The controller can automatically switch the pro-
gram selection when the animals reach a certain
age and/or as a function of outside temperature. If
the automatic program switch option is enabled in
the Installation setup (sec. 4.5), you must indicate
the moment at which each program starts.
Select:
Main menu
Setup*
Program
*A password may be required to access this menu (sec. 4.2).
Program #x above:
If the program switch is based on the ani-
mal age, select the day at which programs
2 and 3 start; if the switch is based on the
outside temperature, select the outside tem-
perature above which each program starts.
Note that program 1 is automatically used
when the animal age (or outside tempera-
ture) is lower than the value defined for pro-
grams 2 and 3.
Main menu
Setup
Prog.Select
Program Settings
Use to navigate
Program 2 above day: 10
Program 3 above day: 20
Program 2 above Out T: 50.0
Program 3 above Out T: 75.0
Show Settings :Program 1
[ or ]
Running Program: Program 1
77
EXPERT LA rev.00
EXPERT LA
14. MEMORY CARD
14.1 Principle of Operation
The memory card allows you to upgrade the firm-
ware or software of your controller without loos-
ing your parameter settings (firmware and/or soft-
ware upgrade). The card can also be used to make
a backup of your controller settings or to copy these
settings on another controller of the same type.
Various kind of files can be stored on the card:
configuration files (*.cfg files) and/or firmware files
(*.fir and *.bin files). Refer to section 14.3 to load
or save a configuration file; refer to section 14.4
to upgrade the firmware.
14.2 Access the Transfer Menu
1. Unscrew the screws located on the
controller's front panel then open the panel.
2. Insert the memory card in the connector lo-
cated on the electronic board located on the
back of the front panel (see illustration).
3. Close the front panel then simultaneously
press the up- and down-arrow keys for 3 sec-
onds to display the transfer menu.
Select the desired transfer menu:
Memory Card Controller
or
Controller Memory Card
Exit
Memory card Menu
Memory card Controller
Controller Memory card
Front
Panel
Cover
Connector
Memory
Card

76 EXPERT LA rev.00
EXPERT LA
13. TECHNICAL SPECIFICATIONS
Type .................................................... EXPERT LA
Main supply fuse F25 .............................. 1A, fast-blow
Mains supply/frequency ........................... 120/240 VAC, 50/60Hz
0-10V outputs ....................................... 0-10Vdc, 30mA source max.
Precision on 0-10V outputs ...................... ±1 %
14Vdc output ........................................ 14 VDC ±10%, regulated, 250 mA max.
Alarm contact ....................................... ON/OFF output, 24VDC or AC, 0.15A.
Housing ................................................ IP54, plastic casing
Operating temperature ............................ 32 to 104°F (0 to 40 °C)
Storage temperature............................... 5 to 122 °F (-15 to 50 °C)
Ambient relative humidity ........................ max. 95%
RH input ............................................... 4-20 mA
Outside RH input .................................... 0-2.5V DC
Temperature inputs................................. 1K @ 77 °F (25 °C), NTC
17
EXPERT LA rev.00
EXPERT LA
Show settings of:
Even when a program is running you can still
display parameter settings of other programs
without changing the program in use. Se-
lect the desired program to be displayed on
screen.
Only programs that are enabled in the Installation
Setup are available (see sec. 4.5).
Running program:
This message is shown when the program
selection is made manually (i.e., it is not se-
lected as a function of the day and/or out-
side temperature). Select the running pro-
gram.
Only programs that are enabled in the Installation
Setup are available (see sec. 4.5).
The day number refers to
theanimalage.
4.3.2 Copying & Pasting Programs
Use the copy-paste function to duplicate all param-
eter settings associated to a program onto another
program. This avoids repeating the same program-
ming sequence several times.
Select:
Main menu
Setup*
Copy/Paste
*A password may be required to access this menu (sec. 4.2).
•Copy From:
Select the source program. The one that will
be duplicated.
•Copy to:
Select the target program. The one on which
the copied program will be pasted.
•Once a different source and target programs
are selected, the message "Confirm?" is dis-
played. Select “Yes” to start the program
duplication. The message " Copy in
progress" is displayed. Wait until the data
transfer is over.
Main menu
Setup
Copy/paste
Program Settings
Use to navigate
Copy From: Program 1
Copy to: Program 2
Confirm? No

18 EXPERT LA rev.00
EXPERT LA
4.4 Measuring Units
Select the measuring units as follows:
Select:
Main menu
Setup*
User
Units
*A password may be required to access this menu (sec. 4.2).
•Select the proper measuring units:
Time display:AM/PM / 24 hours.
Temperature units:
Celsius (Deg C) or Fahrenheit (Deg F).
Water: Gallons / Liters.
Static Pressure
Inches of water (“WC) or Pascal (Pa).
Measuringunitsarecommontoall
programsofthe controller.
Main menu
Setup
User
Units
Unit Selection
Use to navigate
Time Display AM/PM
Temperature Deg F
Water Liter
Static Pressure “WC
75
EXPERT LA rev.00
EXPERT LA
12.5 Automatic Reminder
The controller can display warning messages at
regular intervals. The automatic reminder allows
you to associate a warning message to a servicing
activity for instance then decide the frequency at
which this servicing activity must be performed. In
all, the controller can display 3 different warning
messages.
When a warning message is active, the word
“Warning” is displayed on screen, along with the
message number.
Settings
Select:
Main menu
Setup*
User
Warning
*A password may be required to access this menu (sec. 4.2).
Itissuggestedtowritedownthemean-
ing and frequency of warning mes-
sages1-3:
Warning # Meaning Frequency
warning 1 every _____ days
warning 2 every _____ days
warning 3 every _____ days
•Set the following parameters:
Show warning 1-3 every
Select the frequency at which each warn-
ing message is displayed (1 to 450 days);
select “Off” to disable a warning message.
Clear Warning #x ?
This menu appears when the timer of a
warning message has elapsed. Select “Yes”
to reset the timer of a warning message.
Main menu
Setup
User
Warning
Warning message settings
Use to navigate
Show Warning1 every 10 days
Show Warning2 every 100 days
Show Warning3 every Off days
Clear Warning 1? Yes

74 EXPERT LA rev.00
EXPERT LA
12.4 Animal Age & Count
Animal age
Some parameters of the controller can automati-
cally change over time as the animals grow up
(curves, programs & tunnel door). Using age-based
parameters is optional, refer to section 4.5 to en-
able or disable the animal age function.
Animal count
(current count / mortality / culled / marketed)
At the beginning of a group, the user must specify
the initial number of animals. Afterwards, the user
can specify the number of mortalities, culled, and
marketed animals as it occurs.
ALL histories of the controller are
reset when a new group starts.
Settings
Select:
Main menu
Age/Mortality*
•Accessible if age-based functions are enabled in the Installa-
tion Setup (section 4.5)
•Set the following parameters:
•Animal age
The animal age can be adjusted from -5 days
to 450 days. Negative day values are used
to prepare the house before letting the ani-
mals in.
•Initial count
Enter the initial number of animals in the
room.
•Current count
The current count is automatically adjusted
as mortalities or culled animals are posted.
•Starting a new group
Select “Yes” to start a new group. This will
reset the animal age.
ALL histories of the controller
are reset when a new group
starts.
•New mortalities
Post the number mortalities as mortality
occurs. Once it is validated, the parameter
value automatically goes back to “0”. The
posted value is added to the total mortality
count and removed from the current animal
count.
•New culled
Post the number culled animals as it occurs.
Once it is validated, the parameter value au-
tomatically goes back to “0”. The posted
value is added to the total culled count and
removed from the current animal count.
•New marketed
When new pigs are sold, post the number
marketed animals. Once it is validated, the
parameter value automatically returns to
“0”. The value is added to the total mar-
keted animal count.
Main menu
Age/Mortal.
Age & Mortality
Use to navigate
Animal Age 1day
Initial Count 500
Current Count 500
Start New Group? No
New Mortality 0
Today’s Mortality 0
Total Mortality 0
New Culled 0
Today’s Culled 0
Total Culled 0
New Marketed 0
Today’s Marketed 0
Total Marketed 0
19
EXPERT LA rev.00
EXPERT LA
4.5 Installation Setup
The following section shows how to customize the
controller for your particular application. It explains
how to enable and set the outputs of your control-
ler. Normally, this setup needs to be done only once.
Select:
Main menu
Setup*
User
Installation
*A password may be required to access this menu (sec. 4.2).
Hint: use the right and left arrow key
to move up and down through the
displaybypages.
•Set the following parameters:
Number of feeders
The controller has 4 inputs that are used to
monitor the run time of feeder motors. En-
able the proper number of feeder inputs (0
to 4 feeders).
Number of heating stages
Enable the proper number of heating stages
(0 to 4 heating stages).
Use Heater Lo/Hi Fire?
Select “Yes” to activate the heating out-
puts’ Lo & Hi fire option. This function al-
lows doubling the number of heating stages.
[This parameter is common to all programs].
Number of fan stages
Enable the proper number of fan stages
(0 to 12 fan stages).
The number of fan stages is limited by the stage
number that signals the beginning of tunnel venti-
lation. Refer to section 6.4 to select the first tun-
nel stage.
Main menu
Setup
User
Install.
Installation
Use to navigate
# Feeders 4
# Heater stages 4
Use Heater Lo/Hi Fire? Yes
# Fan stages 8
# Clocks 2
# Natural Curtain 2
# Tunnel Curtain 2
# Light Programs 3
# Vent Doors/Inlets 2
Use 0-10V Output Yes
Vent Door/Inlet 1 Mode Time
Vent Door/Inlet 2 Mode S.P.
Close Vents in Natural No
Number of clock outputs
Enable the proper number of clock outputs
(0 to 2 clock outputs).
Number of natural ventilation curtains
Enable the proper number of natural ventila-
tion curtains (0 to 2 natural vent. curtains).
Number of tunnel curtains
Enable the proper number of tunnel curtains
(0 to 2 tunnel curtains).
Number of light programs
Enable the proper number of light programs
(0 to 8 light programs). Note that lighting pro-
grams are based on the animal age. Conse-
quently, enabling a light program automati-
cally enables age-based functions.
Number of vent doors
Enable the proper number of vent doors (in-
let) outputs (0 to 2 outputs).

20 EXPERT LA rev.00
EXPERT LA
0-10V output
Select “Yes” to enable the 0-10V output.
This output can either be used to control an
air inlet or a variable fan stage.
Vent door/inlet 1-2 mode
Vent doors (inlets) can operate in two dif-
ferent ways:
Accessible if a vent door (inlet) output is enabled
above.[This parameter is common to all programs].
1. Time
The vent door (inlet) opens or closes in
timer mode, as a function of tempera-
ture.
2. Static pressure (S.P.)
The vent door (inlet) opens or closes as a
function of static pressure.
Close vents in natural
Select “Yes” for vent doors (inlets) to close
when the controller enters in natural venti-
lation.
Accessible if natural ventilation curtains and vent
doors/inlets are enabled.
Tunnel control
Does the tunnel door opens and closes ac-
cording to the static pressure level (S.P.) or
according to the room temperature.
Accessible if the tunnel curtain is activated above.
The static pressure option is only available if the
static pressure sensor is activated in section 4.7.1.
Number of static pressure set points
The controller can use up to 3 groups of
static pressure set points and each group
starts at a user-defined fan stage.
Accessible if at least one air inlet output (inlet,
vent door or tunnel curtain) operates according to
the static pressure level.
0-10V Type
Select the type of signal used by the
0-10V output (0-10V or 10-0V).
Accessible the 0-10V output is enabled above.
[This parameter is common to all programs].
0-10V mode
Select the function of the 0-10V output:
Accessible if the 0-10V output is enabled above.
[This parameter is common to all programs].
-0-10V ventilation output
When it is used for ventilation, the
0-10V output runs similarly as a vari-
able-speed fan stage and uses indepen-
dent temperature settings.
-0-10V inlet
When it is used as an air inlet, the
0-10V output opens and closes an ac-
tuator as a function of the ventilation
level.
0-10V output follows set point
Operating temperatures of the 0-10V out-
put can either be related to the set point –
which means the controller automatically
adjusts them when the set point changes –
or they can be set as absolute values.
Select “Yes” if they follow the set point or
select “No” if they set as absolute values.
Accessible if the 0-10V output is enabled above.
[This parameter is common to all programs].
Curtain compensation
Select "Yes" to enable a compensation on the
opening of natural ventilation curtains as a
function of the outside temperature.
Accessible if natural ventilation curtains are en-
abled above and if an outside temperature sensor
is enabled in section 4.7.1.
Main menu
Setup
User
Install.
Installation
Use to navigate
Use 0-10V Output Yes
Vent Door/Inlet 1 Mode Time
Vent Door/Inlet 2 Mode S.P.
Close Vents in Natural No
Tunnel Control SP
#Static.P Set Points 3
0-10V Type 0-10V
0-10V Mode Ventil.
0-10V Follow SetP Yes
Use Curtain 1 Compens? Yes
Use Curtain 1 Whisker? Yes
Use Curtain 2 Compens? Yes
Use Curtain 2 Whisker? Yes
73
EXPERT LA rev.00
EXPERT LA
12.3 History Menus
History menus give a daily record of probe read-
ings and of the animal count. These pieces of infor-
mation are logged into history menus at midnight.
Refer to section 13.2 to consult run time histories
(for heaters, water consumption and feeders).
Select:
Main menu
History
Select the desired type of history:
•Ambient temperature
This menu contains the daily minimum and
maximum readings of the room temperature
of the past 60 days.
•Probe temperature
This menu contains the daily minimum and
maximum temperature readings of each tem-
perature probe for the past 10 days.
•Outside temperature
This menu contains the daily minimum and
maximum readings of outside temperature
probes for the past 75 days.
Accessible if an outside temperature sensor is en-
abled (section 4.7.1).
•Inside relative humidity (RH)
This menu contains the daily minimum and
maximum inside humidity readings of the
past 75 days.
Accessible if the inside humidity sensors is enabled
(sec. 4.7.1).
•Outside relative humidity (RH)
This menu contains the daily minimum and
maximum outside humidity readings of the
past 75 days.
Accessible if the outside humidity sensors is en-
abled (sec. 4.7.1).
•Static Pressure
This menu contains the daily minimum and
maximum static pressure readings of the
past 75 days.
Accessible if a static pressure sensor is enabled
(sec. 4.7.1).
•Mortality / Culled / Marketed
These menus contains the daily count of
mortalities, culled, and of marketed animals
of the past 75 days.
Accessible if age-based functions are enabled (sec-
tion 4.5).
•Water
This menu shows the daily water consump-
tion and the consumption of the past 75
days.
Main menu
History
Ambient T°
Probe T°
Outside T°
Inside RH
Outside RH
Static P.
Mortality
Culled
Marketed
History Menu
Table of contents
Other Airstream Controllers manuals