Alderon Industries Check It Series User manual

Introduction
Description of Operation
3 Float:
With both “HOA” switches in “Auto” and the pump selector switch in “ALT”: On water rise, the “off” float will
close and when the level closes the “lead” float, pump 1 will start and pump down to the “off” float. The
panel will alternate so on the next cycle pump 2 will activate. If the level reaches the “lag” float, both
pumps and the alarm will activate and pump down to the “off” float. Alarm turns off at the “off” level. For a
pump up application the floats are reversed (see float configurations Fig. #A on page 4).
4 Float:
With both “HOA” switches in “Auto” and the pump selector switch in “ALT”: On water rise, the “off” float will
close and when the level closes the “lead” float, pump 1 will start and pump down to the “off” float. The
panel will alternate so on the next cycle pump 2 will activate. If the level reaches the “lag” float, both
pumps will activate and pump down to the “off” float. If the reaches the “alarm” float the alarm will
activate. Alarm turns off when the alarm float is “off”. For a pump up application the floats are reversed
(see float configurations Fig. #B on page 4).
Before proceeding with the installation or operation of the control panel read all instructions thoroughly,
as well as comply with all Federal, State and Local Codes, Regulations and Practices. The control panel
must be installed by qualified personnel familiar with all applicable local electrical and mechanical codes.
Refer to the National Electrical Code (NFPA 70). Failure to properly install and test this product can result
in personal injury or equipment malfunction. All conduit connected to the panel must be sealed with
conduit sealant to prevent moisture or gases from entering the panel. NEMA 1 enclosures are for indoor
use only while NEMA 4X panel enclosures may be used indoor or outdoor. Refer to panel model name-
plate on inside of door for enclosure rating. Note: If options are ordered that affect the number of floats,
refer to the panel schematic for complete information.
Safety Guidelines
1. DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE,
ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES. CONTROL PANEL SHOULD ONLY BE USED IN
WATER AND WASTEWATER APPLICATIONS THAT ARE NOT RATED AS A HAZARDOUS LOCATION.
2. DO NOT WORK ON THE CONTROL PANEL WITH LIVE VOLTAGE APPLIED TO THE CONTROL PANEL
WITH WET HANDS OR WHEN STANDING ON A WET SURFACE.
3. DISCONNECT ALL ELECTRICAL SERVICE BEFORE WORKING ON OR HANDLING THE CONTROL
PANEL
4. INCOMING VOLTAGE MUST MATCH THE CONTROL PANEL VOLTAGE. REFER TO THE PANEL SCHE-
MATIC FOR COMPLETE INFORMATION.
Alarm Systems Control Panels Float Switches Leak Detection Systems Page 1 of 4
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
P/N: 100836
Operation, Maintenance and Installation Manual
1 Phase Duplex
Check It™Panel
Circuit Board Command Center:
The control panel is equipped with a circuit board and control command
center. There are two “HOA” switches, a pump selector switch and a Check It
switch. Two green power “on” indicators provide visual indication for the
control and alarm fuses. Fuses must be replaced with 1 amp fast acting 5mm
x 20mm fuses. 4 red level indicators are provided for level indication of the
off, lead, lag and alarm switches.
HOA switch:
Placing the HOA switch in “H” (hand mode) will activate the pump. In the “O” (off) mode the
pump will not activate. Placing the switch in “A” (automatic) mode, will activate the pump
with the level switches. Place the switch in “A” mode when installation is complete and normal
operation is desired.
Pump selector switch:
Placing the switch in “ALT” will allow the panel to automatically alternate the pumps on
successive cycles. If a pump needs to be taken out of service, place the switch to the pump
that will remain in service. I.E. if pump 2 is out of service, place the switch to “P1” so the panel
will activate pump 1 on each cycle. Note: If the level reaches the lag/alarm or alarm switch
level the alarm will activate. For applications where alternation is not desired and a lag pump
operation is required, consult factory for further information. When a pump is selected with
the pump selector switch only that pump will activate (simplex mode).
Check It switch:
Use the Check It switch to verify panel operation and float status. To check panel operation
place the pump selector switch to “Alt” and the HOA switches to “A”. Press and hold the Check
It switch – one pump should activate. De-Press the Check It switch and Re-Press again and the
other pump should activate. The panel will alternate the pumps each time the Check It switch
is pressed.
Use the Check It switch to verify float status. In normal operation the float status LED’s activate when the
level switch “closes”. If the floats are activated out of sequence (I.E., “off” float is not activated but the
“lead” float is activated) the LED for the “lead” switch will not illuminate. Use the Check It switch to deter-
mine exact status of each float. When the Check It switch is pressed and held, the circuit will automatically
give true indication of which level switches are “closed” or “opened”. You can perform this test with the
“HOA” switch in either the “O” (off) or “A” (auto) modes.
Alarm Systems Control Panels Float Switches Leak Detection Systems Page 2 of 4
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
P/N: 100836
Operation, Maintenance and Installation Manual
1 Phase Duplex
Check It™Panel
Alarm Mode Configurations:
All “e” (economy) series control panels will only have a combination “test-normal-silence” switch where
automatic alarm reset is the only alarm configuration. When the panel goes into alarm, press the switch to
“silence” and the buzzer will turn off but the alarm indicator will remain on until the lag/alarm or alarm
level switch deactivates and automatically resets the alarm system.
All other Check It series control panels employ separate “test” and
“silence” switches. These panels can be field modified to have a “manual”
alarm reset. Refer to figure for placement of an 18 AWG jumper wire to
convert the panel from automatic reset to MANUAL reset. In the Manual
Reset mode and when the panel goes into alarm, the panel will remain in
alarm even if the alarm level switch is “opened” until the “silence” switch
is activated. This feature allows alarms to be manually acknowledged
before the alarm is cleared. In the event of a power failure, the alarm is
also cleared.
Use 18 AWG wire approximately 4” long. Strip off ¼” outer insulation. Insert jumper wire into the 2 posi-
tion wire port (one wire per port). To remove jumper wire, press small screw driver or pointed object onto
the “white” port block and remove wire as the wire is held in place by a spring cage terminal device.
Circuit Board Terminal Blocks:
The Check It series control panel uses two terminal blocks. A 10 position main terminal block is for power
and level switch connections. A separate 3 position terminal block are for dry auxiliary contacts. A 5 amp,
120 VAC max load can be applied to the auxiliary terminals. The auxiliary contacts are Form C, Single Pole,
Double Throw. (Common, Normally Open, Normally Closed). Contacts change state when in alarm condi-
tion.
10 position terminal block Auxiliary Contact terminal block
WARNING! When using the manual alarm reset feature you
must use a four float system. If you’re using a 3 float system, add a fourth float and remove the yellow jumper
wire between the lag and alarm terminals to avoid dry pumping.
Alarm Systems Control Panels Float Switches Leak Detection Systems Page 3 of 4
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
P/N: 100836
Operation, Maintenance and Installation Manual
1 Phase Duplex
Check It™Panel
1
. Determine mounting location for the control
panel. Attach the 4 mounting feet to the control
panel enclosure. If splicing is required between the
level switches and the panel, we recommend an
Alderon Junction box. CAUTION! Use conduit
sealant and waterproof wire nuts for connections.
Make sure all connections are water tight.
2. Determine conduit entrance locations on
control panel and install per local codes. Check
schematic and determine number of power sources
required. Use conduit sealant on all conduits to
prevent moisture and gases from entering control
panel.
3. Connect control/alarm and pump power
conductors to the proper terminals. The schematic
and terminal blocks will be labeled for proper
connection.
4. Verify correct panel operation after installa-
tion of panel, power and level switches are complete.
Installation of the Control Panel:
Float switches are most commonly used, but the
Check It series control panels can be used with any
dry contact type level or pressure switch. Illustra-
tions show float switches and installed for pump
down applications. Reverse float order for Pump Up
applications. Refer to float switch instuctions for
mounting of pipe clamp or weighted floats.
Mounting Level Switches:
Fig. #A
3 float configuration
Fig. #B
4 float configuration
Stop Float
Lead Pump
Start Float
Lag Pump Start
& Alarm Float
Stop Float
Lead Pump
Start Float
Lag Pump
Start Float
Alarm Float
Incoming Power Configurations:
The Check It series control panels may be ordered with or without circuit breakers. In either case the
incoming power for each pump is separated at the incoming power terminal block. For panels without
circuit breakers individual branch circuit breakers must be wired into the control panel. For panels with
circuit breakers either one or two power sources may be wired to the control panel. Illustration below
shows how to connect power for one or two incoming pump power sources.
1 Incoming Power Circuit
Install jumper wires:
12 AWG for pumps up to 25 Amps
10 AWG for pumps up to 30 amps
Incoming Power
for both pumps
2 Incoming Power Circuits
Pump 1
Incoming Power
Pump 2
Incoming Power
Alarm Systems Control Panels Float Switches Leak Detection Systems Page 4 of 4
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
P/N: 100836
Operation, Maintenance and Installation Manual
1 Phase Duplex
Check It™Panel

This manual suits for next models

1

Other Alderon Industries Control Panel manuals

Alderon Industries FLEX User manual

Alderon Industries

Alderon Industries FLEX User manual

Alderon Industries WaterPro VA02A User manual

Alderon Industries

Alderon Industries WaterPro VA02A User manual

Alderon Industries Check It Panel User manual

Alderon Industries

Alderon Industries Check It Panel User manual

Alderon Industries Power Post PPCP Series User manual

Alderon Industries

Alderon Industries Power Post PPCP Series User manual

Popular Control Panel manuals by other brands

LEGRAND 67206 user guide

LEGRAND

LEGRAND 67206 user guide

weintek cMT-iPC10 series Installation instruction

weintek

weintek cMT-iPC10 series Installation instruction

KitchenAid KESS300B reference guide

KitchenAid

KitchenAid KESS300B reference guide

Intermatic T30000R SERIES Installation, operation & service manual

Intermatic

Intermatic T30000R SERIES Installation, operation & service manual

WhisperPower WhisperTouch WP-TOUCH 5 User & installation manual

WhisperPower

WhisperPower WhisperTouch WP-TOUCH 5 User & installation manual

urmet domus 1067/032A installation manual

urmet domus

urmet domus 1067/032A installation manual

ergolutions 10001 manual

ergolutions

ergolutions 10001 manual

Electronics Line infiniti user manual

Electronics Line

Electronics Line infiniti user manual

NAPCO Gemini GEM-P1664EX datasheet

NAPCO

NAPCO Gemini GEM-P1664EX datasheet

GE Security Simon XT user guide

GE Security

GE Security Simon XT user guide

Panduit Atlona AT-ANC-180D manual

Panduit

Panduit Atlona AT-ANC-180D manual

Notifier NFS-3030/E Operation manual

Notifier

Notifier NFS-3030/E Operation manual

Extron electronics RCP 101 EU Setup guide

Extron electronics

Extron electronics RCP 101 EU Setup guide

DSC Power Series quick guide

DSC

DSC Power Series quick guide

Microm FX-400 Installation and operation manual

Microm

Microm FX-400 Installation and operation manual

Gems CP16BXXX1 series Operation manual

Gems

Gems CP16BXXX1 series Operation manual

iSMA CONTROLLI FP-2B-B user manual

iSMA CONTROLLI

iSMA CONTROLLI FP-2B-B user manual

RIB KS2 12-24V Assembly instructions

RIB

RIB KS2 12-24V Assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.