manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Alderon Industries
  6. •
  7. Control Panel
  8. •
  9. Alderon Industries Power Post PPCP Series User manual

Alderon Industries Power Post PPCP Series User manual

QUICK START GUIDE
Power Post™Control Panel
Pump Connection Center | Timed or Demand Dose, Integrated Alarm
15 Amp, 120/240VAC | PPCP Series (Models: PPRS-0001 and PPRS-0002)
Safety Guidelines
Step 2: Remove / Install Bottom Cover Step 4: Installing Wire into WAGO
Before proceeding with the installation or operation of this product,
read all instructions thoroughly, as well as complying with all federal,
state and local codes, regulations, and practices. This product must
be installed by qualied personnel familiar with all applicable local
electrical and mechanical codes. Refer to the National Electrical Code
(NFPA 70). Failure to properly install and test this product can result in
personal injury or equipment malfunction.
WARNING
Step 1: Install Post
QSG00292_Rev07_PPCP_Power Post Control Panel | May 31, 2022 7:41 AM
Before making wire connections and terminations, carefully read this
step for proper functions of both types of WAGO connectors.
WARNING: Improper use of the connectors will cause damage, DO
NOT use mechanical tools to open or close, hand usage only.
Wire Termination - Splice Connector WAGO (Fig. 1):
1) Lift tab(s) upward.
2) Insert wire(s) into slot.
3) Press tab(s) downward.
4) Make sure wire(s) are secured.
Wire Connection - Quick Snap Terminal WAGO (Fig. 2):
1) Press tab(s) outward. DO NOT open past 40° angle
2) Insert wire(s) into slot.
3) Press tab(s) inward.
4) Make sure wire(s) are secured.
Determine location for the post in the
ground near a tank and drill access
holes for the float switch cables using
the customer supplied conduit/fittings or
Alderon’s riser connection kit. Route the
cables through access holes and wire as
described in step 5. Run the direct burial
power wires underneath the bottom of
the post as shown in the diagram.
Note: Seal all conduits to prevent moisture and gases
from entering the post per local codes.
Direct
Burial
Wires
Remove the bottom enclosure cover screw, slide directly downward until
the sound chamber is cleared (2A) and pull directly away (2B). To install,
line up the bottom enclosure cover with the grooves (2B), then slide directly
upward (2A) until it meets the top of the enclosure so the screw hole is
lined up and replace the screw at the bottom of the enclosure.
Step 3: Remove / Install Post Cap
Remove Post Cap:
1) Remove Screws and Lift Cap Upwards
Install Post Cap:
1) Position text FRONT (with arrows) Forward
3) Align Fastener Holes
4) Fasten Screws to Secure Cap to Post
(Fig. 1) (Fig. 2)
TO OPEN
WAGO
TO CLOSE
WAGO
TO OPEN
WAGO
TO CLOSE
WAGO
FRONT
2A 2B
Alderon Industries™ | Patent Pending
Step 5: Wiring and Piggyback Plug Connections
Step 6: Testing and Backll
(120VAC Example Shown)
5B
5A
OPTIONAL PIGGYBACK PLUG CONNECTIONS
1) Plug the male end of the piggyback plug on the in-line pump switch power
cable into the pre-installed female power receptacle inside the post (5A).
2) Plug the male end of the pump power cable into the female end of
the piggyback plug on the in-line pump switch power cable (5B) from #1.
Make sure all steps of the installation and wiring process is completed
and there is power to the product.
1) TEST ALARM LEDs and BUZZER
Press the test/silence pushbutton, lifetime pump run event counter
statistic should display, then alarm LEDs should illuminate while
cycling between red, green, blue, and off. The OLED screen should
display a TESTING (COLOR) event for respective LEDs after event
statistic is displayed. Last, the buzzer should annunciate and OLED
screen should display a TESTING BUZZER event.
2) TEST ALARM FLOAT SWITCH
Activate the alarm oat switch, the red LEDs should illuminate,
ashing and the buzzer should annunciate. The OLED screen should
display a HIGH LEVEL ALARM event.
3) TEST ALARM SILENCE
Press the test/silence pushbutton on the front of the enclosure while
the alarm oat switch is activated. The red LEDs should keep ashing
and the buzzer should silence.
4) TEST FILTER SWITCH
Activate the lter switch, the amber LEDs should illuminate, ashing
and the buzzer should annunciate. The OLED screen should display a
FILTER ALARM event.
5) TEST PUMP AND CONTROL/IN-LINE PUMP FLOAT SWITCH
Make sure the tank has water to perform the testing. Activate the
control/in-line pump oat switch, the blue LEDs should illuminate and
the OLED screen should display a PUMP RUN event and the pump
amps are displayed.
6) RECOMMENDED SYSTEM SETTINGS
Alderon™ recommends changing the factory settings for: high amp
level, extended pump run time, and gallons per minute.
7) TEST WEEKLY
To ensure the product is functioning properly, test once a week.
BACKFILL: After installation and testing, backll with dirt/soil.
Menu System - Main Menu
1.0 | MAIN MENU - HOA Pump Mode
From HAND/OFF AUTO screen, press right
arrow key for menu to view system override
options. Press down arrow key to the
RESETBLE HISTORY screen.
2.0 | MAIN MENU - Resettable History
From the RESETBLE HISTORY screen,
press right arrow key for menu. Press down
arrow key to the SETTINGS screen.
3.0 | MAIN MENU - Settings
From the SETTINGS screen, press right
arrow key for menu to enter password and
program system settings. Press down arrow
key to the LIFETIME HISTORY screen.
4.0 | MAIN MENU - Lifetime History
From the LIFETIME HISTORY screen, press
right arrow key for menu. Press down arrow
key to the MODEL / FIRMWARE screen.
5.0 | MAIN MENU - Model/Firmware
From the MODEL/FIRMWARE screen, press
down arrow key to bring you back to the
HAND/OFF AUTO screen.
Note: The down arrow key will cycle through
the menu options until a specic option is
selected using the right arrow key.
The wiring diagram shows 10 terminals on the quick snap terminal blocks
that consists of ve pairs of connections. Make sure to read and review
the connector examples on page 7 for proper installation prior to wiring.
Note: The quick snap terminal blocks, are herein referred to as “terminal”
for instruction purposes. The installation example shown is for 120VAC,
for 240VAC installation the neutral (N) wire would be replaced by line
connection (L2) and white wire would include a red band to indicate the
wire is hot.
1) The rst cable grip, starting at the right, has a cable grip divider
allowing for two power sources to be brought into the enclosure.
The right side of the cable grip is used for the pump power
(attached in series). The line wire is connected to terminal 9 and
neutral wire is terminated by the two-position Wago connector.
The left side of the cable grip is used for the alarm/control power,
which is connected to terminals 7 and 8. Terminal 7 is the neutral
(N) connection and terminal 8 is the line connection (L1). The
pump and alarm/control power ground wires are terminated using
the three-position Wago connector. After bringing in the cables,
rmly tighten the cable grip by twisting clockwise until securely
fastened.
2) The female receptacle comes pre-installed in the middle cable
grip. The line wire is connected to terminal 10, neutral wire is
terminated by the two-position Wago connector, and ground wire
is terminated by the three-position Wago connector.
3) The third cable grip has cable grip dividers allowing for three
sensor connections. The pump control oat switch is connected
to terminals 1 and 2. The lter switch is connected to terminals 3
and 4. The high level alarm oat switch is connected to terminals
5 and 6. After bringing in the cables, rmly tighten the cable grip
by twisting clockwise until securely fastened.
4) NEVER leave ground wire(s) exposed, use provided Wago
connector for wire termination.
BLACK
BLACK
BLACK
BLACK
WAGO WAGO
GROUND
WHITE/RED
WHITE
WHITE/RED
WHITE
BLACK
WHITE
GROUND
9
10
7
8
BLACK
WHITE
1
2
3
4
5
6
Power Wiring
(steps 1 and 2)
Alarm/Control
Power
7
8
N/L2
L1
Pump Power
9
10
Factory Wired
L1
Alarm Wiring
(step 3)
Filter Switch
Alarm Float Switch
1
2
3
4
5
6
Pump Control
Switch
MAIN MENU - System Normal
From SYSTEM NORMAL screen, press the
MENU button to access main menu and
HAND/OFF AUTO will appear. Pressing
MENU button from a blank screen will also
access the main menu.
3.0 | Main Menu - Settings Part II
Right arrow key from SETTINGS screen for menu, down arrow key to scroll.
3.8 Dose Setting (factory set to Timed Dosing)
i. Demand Dose?, press MENU for Demand Dose
ii. Timed Dose?, press MENU for Timed Dose
3.9 Float Setting** (factory set to Float Input)
i. In-line Float?, press MENU for In-line Float
ii. Float Input?, press MENU for Float Input
3.10 Dose Off Time Setting*(factory set to 10 seconds)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.11 Dose On Time Setting*(factory set to 5 seconds)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.12 Peak Off Time Setting*(factory set to 10 seconds)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.13 Peak On Time Setting*(factory set to 5 seconds)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.14 Minimum Peak Dose Cycles Setting*(factory set to 1)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
CAUTION:
Alderon™ recommends changing factory settings to customize the
system per application for desired operation.
2.0 | Main Menu - Resettable History
From the RESETBLE HISTORY screen,
press right arrow key to access the menu for
event statistics and then press down arrow
key for the available events within this menu.
2.1 Pump Run Stats
2.2 Extended Pump Run Stats
2.3 High Amp Stats
2.4 Pump Float Stats
2.5 Relay Stats
2.6 Dose On Stats*
2.7 Peak On Stats*
2.8 High Level Alarm Stats
2.9 Filter Alarm Stats
2.10 Pump Fail Stats
2.11 Relay Fail Stats
2.12 System Fail Stats**
2.13 Power Loss Stats
Press right arrow key for the individual
stats of each event type listed above and
data stored in the system. Each resettable
history event stat has a clear history
function. The non-volatile memory allows all
settings and statistics to be retained during
power outages.
Note: The down arrow key will cycle through
all the resettable history menu options until
a specic option is selected using the right
arrow key as displayed on the screen. Press
the left arrow key to exit from any screen.
Press the test/silence pushbutton to exit the
menu system.
(*) Indicates Timed Dosing only
(**) Indicates Demand Dosing only
3.0 | Main Menu - Settings Part I
Right arrow key from SETTINGS screen for menu, down arrow key to scroll.
3.1 Password (factory set to 1919)
i. Password 0000 will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to accept password; press left arrow to exit
vi. Incorrect entry will exit user to the settings menu
Note: To change password, use up/down arrows until password screen reappears,
then enter numeric values between 0000-9999, press MENU to save.
3.2 Normal LED Setting (factory set to LED On)
i. Normally LED Off?, press MENU to turn LED off
ii. Normally LED On?, press MENU to turn LED on
3.3 Pump Run LED Setting (factory set to LED On)
i. Pump Run LED Off?, press MENU to turn LED off
ii. Pump Run LED On?, press MENU to turn LED on
3.4 Silence Time Setting (factory set to 24 hours)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.5 Extended Pump Run Time Setting (factory set to 30 minutes)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.6 High Amp Level Setting (factory set to 15 Amps)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.7 Gallons Per Minute Setting (factory set to Zero)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
3.15 End Dose Setting*(factory set to Stop Dose)
i. Finish Dose?, press MENU for Finish Dose
ii. Stop Dose?, press MENU for Stop Dose
3.16 Buzzer Delay*(factory set to 20 seconds)
i. The current setting will appear on the screen
ii. Up or down arrow, increase/decrease selected digit
iii. Right arrow, moves cursor to the right (blinking)
iv. Press MENU to save changes; press left arrow to exit
(*) Indicates Timed Dosing only OR (**) Indicates Demand Dosing only
OR
OR
OR
OR
OR
Power Post™Control Panel - Features
1Power On Indicator - Green LEDs illuminate inside top cover of enclosure cover,
power on indicators can be disabled in system settings
2Alarm Beacon - Alarm LEDs (various colors) illuminate inside the top cover of
enclosure cover
3Pump Run Indicator - Blue LEDs illuminate inside top cover of enclosure cover, pump
run indicators can be disabled in system settings
4System LED Indicators - Multiple color indicators will illuminate inside top cover of
enclosure cover for visual indication of various system events and/or alarm conditions
5OLED Display Screen - Displays system functions in addition to LED indicators
6 Menu Keypad - Toggle for system functions, program settings, and view statistics
7Test/Silence Pushbutton -
Quick access to lifetime pump run event counter statistic,
test or silence the alarm, or exit the menu system
8Alarm Buzzer - Annunciates to indicate an alarm event
9Quick Snap Terminal Blocks - Fast and easy connections for system wiring
10 Control Relay - Controls current through pump circuit and is removable, ideal for
systems with high usage environments
11 Vented Post Cap -
Allows airow, prevents build up of gases/condensation inside post
12 QR Code (not shown) - Scan for additional product information (alderonind.com)
13 Sound Chamber - Maximum buzzer output, protects from water intrusion
14 Cable Grips - Pre-installed for easy installation
15 Pump Power Receptacle (not shown) - Pre-installed, female, 15A, available in either
120VAC or 240VAC (voltage depends on model/part number)
16 Post - Provides wire routing access for system power, pump power, oat switch, and
sensor cables while protecting from water intrusion
Included with Product
Specications
▪ (1) Power Post™; junction box and cable grips pre-installed on post
▪ (1) Pre-installed, female, 15A, pump power receptacle
(120VAC or 240VAC, voltage depends on model/part number)
▪ (2) Wago connectors
FCC Part 15: NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pur-
suant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures: increase the separation between the equipment and
receiver, connect the equipment into an outlet on a circuit different from that to which the receiver is connected, consult the
dealer or an experienced radio/TV technician for help. Caution: changes / modications not approved by Alderon Industries
could void the user’s authority to operate the equipment.
Customer Support
Online
alderonind.com
Email
[email protected]
QR Code
Scan code for full product details
4.0 | Main Menu - Lifetime History
From the LIFETIME HISTORY screen,
press right arrow key to access the menu for
event statistics and then press down arrow
key for the available events within this menu.
4.1 Pump Run Stats
4.2 Extended Pump Run Stats
4.3 High Amp Stats
4.4 Pump Float Stats
4.5 Relay Stats
4.6 Dose On Stats*
4.7 Peak On Stats*
4.8 High Level Alarm Stats
4.9 Filter Alarm Stats
4.10 Pump Fail Stats
4.11 Relay Fail Stats
4.12 System Fail Stats**
4.13 Power Loss Stats
Press right arrow key for the individual stats
of each event type listed above and data
stored in the system. The lifetime statistics
are non-resettable and are displayed in Title
Case format for visual separation from the
resettable statistics, which are displayed
in UPPERCASE format. The non-volatile
memory allows all settings and statistics to
be retained during power outages.
Note: The down arrow key will cycle through
all the lifetime history menu options until a
specic option is selected using the right
arrow key as displayed on the screen. Press
the left arrow key to exit from any screen.
Press the test/silence pushbutton to exit the
menu system.
(*) Indicates Timed Dosing only
(**) Indicates Demand Dosing only
1 2 34
5
12
6
7
8
10
13
99
11
14
16
10
1Base Model (Power Post™ Control Panel) 3Alarm Options (15' Alarm Float, 15' Filter Switch) 5In-Line Pump Switch Options (15A, 15' Wide Angle)
2Pump Voltage (120VAC Pump) 4Pump Control Float Options (15' Wide Angle) 6Riser Kit/Access Options (2.5" Riser Connection Kit)
PPCP1315A2
1 2 3 4 5 6
Model Number Nomenclature
Alarm Power: 120VAC, 60Hz
(240VAC, 60 Hz available; consult factory)
Power Consumption: 14 Watts maximum (alarm condition)
Enclosure: Outdoor, rated Type 3R
Certifications: FCC Part 15 (US/Canada), CSA (US/Canada)
Pump Power Receptacle: 120VAC or 240VAC, 15A, 60Hz
Pump Power: 120VAC or 240VAC, 13A or 15A, 60Hz
(voltage/amps depends on model/part number)

This manual suits for next models

2

Other Alderon Industries Control Panel manuals

Alderon Industries WaterPro VA02A User manual

Alderon Industries

Alderon Industries WaterPro VA02A User manual

Alderon Industries Check It Panel User manual

Alderon Industries

Alderon Industries Check It Panel User manual

Alderon Industries Check It Series User manual

Alderon Industries

Alderon Industries Check It Series User manual

Alderon Industries FLEX User manual

Alderon Industries

Alderon Industries FLEX User manual

Popular Control Panel manuals by other brands

tau MEC 1000 installation guide

tau

tau MEC 1000 installation guide

Mitsubishi Electric E1000 series Service and maintenance manual

Mitsubishi Electric

Mitsubishi Electric E1000 series Service and maintenance manual

Beckhoff CPX29 0000 Series Installation and operating instructions

Beckhoff

Beckhoff CPX29 0000 Series Installation and operating instructions

Bentel Security Academy8L manual

Bentel Security

Bentel Security Academy8L manual

Lennox OLT-1X user manual

Lennox

Lennox OLT-1X user manual

Risco LightSYS Quick user guide

Risco

Risco LightSYS Quick user guide

Vimar By-Me 21509 instruction manual

Vimar

Vimar By-Me 21509 instruction manual

Side-Power 8940 installation guide

Side-Power

Side-Power 8940 installation guide

Intermatic T30000R SERIES Installation, operation & service manual

Intermatic

Intermatic T30000R SERIES Installation, operation & service manual

GROUP SCS EV-100 instruction manual

GROUP SCS

GROUP SCS EV-100 instruction manual

PEMTECH PT750 Series W Operator's manual

PEMTECH

PEMTECH PT750 Series W Operator's manual

See Water WS Series Installation and operator's manual

See Water

See Water WS Series Installation and operator's manual

SJE Rhombus 123 Installation Instructions and Operation/Troubleshooting Manual

SJE Rhombus

SJE Rhombus 123 Installation Instructions and Operation/Troubleshooting Manual

Autonics LP-A Series product manual

Autonics

Autonics LP-A Series product manual

Bentel Security KYO 320 installation manual

Bentel Security

Bentel Security KYO 320 installation manual

Brähler Systems DIGIMIC CS quick start guide

Brähler Systems

Brähler Systems DIGIMIC CS quick start guide

Satel Versa user manual

Satel

Satel Versa user manual

Bosch DS7400XiV4-EXP reference guide

Bosch

Bosch DS7400XiV4-EXP reference guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.