2 System overview
© 2021 Interflex Datensysteme GmbH IF-4077-4 Zutrittsmanager 4
SSH Secure shell
1.7 Cable lengths and cable types
Cable Function Max. Length Recommended cable type
230 V AC power supply to power supply unit (if not
pre-installed)
NYM 3 x 1.5mm2
Network cabling: RJ45 patch cable, preferably shield
braiding
100 m From category 5
Cable to floating status contacts, control cable 100 m J-Y(St) Y 2 x 2 x 0.6mm2
J-Y(St) Y 2 x 2 x 0.8mm2
RS485 bus cable to parent or child devices 1200 m J-Y(St) Y 2 x 2 x 0.6mm2
J-Y(St) Y 2 x 2 x 0.8mm2
RS485 branch cable to bus cable 100 m J-Y(St) Y 2 x 2 x 0.6mm2
J-Y(St) Y 2 x 2 x 0.8mm2
Connecting cable between I/O controller board and
reader
100 m J-Y(St) Y 4 x 2 x 0.6mm2
J-Y(St) Y 4 x 2 x 0.8mm2
In long cables, voltage losses can impair the functionality of the connected device. Therefore, do not use
cables longer than specified in the table. Wire the +5 V and GND lines with two cores each for a cable
length > 50 m.
2 System overview
The IF-4077-4 access manager includes the following functions:
nOperation in conjunction with a host system for access control or time recording (e.g., IF-6020 or
IF-6040)
nConnection of 4 readers via 4 integrated I/O controller boards as well as up to 12 additional readers
via RS-485 interfaces on the IF-4072 controller.
nAccess control including door control and monitoring
nStorage of data required for offline operation, e.g. person records, day and week programs, and local
permissions
nOffline Mode: In offline mode, the access manager takes over the functions of the host system. It
checks and acknowledges booking permissions during identification procedures at readers.