Alpha Outback Energy Alpha FXM 650 User manual

Alpha FXM 650, 1100 and 2000
USER MANUAL

Table of Contents
1. Safety .................................................................................................................................................. 3
1.1 Safety Symbols ...................................................................................................................................... 3
1.2 General Warnings and Cautions ............................................................................................................ 4
1.3 Certifications and Compliances .............................................................................................................. 5
2. General Description ............................................................................................................................ 6
2.1 Overview ................................................................................................................................................ 6
2.2 Front Panel ............................................................................................................................................ 6
3. Site Planning ..................................................................................................................................... 10
3.1 Safety Precautions ............................................................................................................................... 11
3.2 Communicating with the Alpha FXM .................................................................................................... 11
3.3 Electromagnetic Compatibility (EMC)
Requirements
............................................................................ 13
4. Unpacking Alpha FXM .........................................................................................................................13
5. Installation ...........................................................................................................................................14
5.1 Tools and Equipment Required for Installation ..................................................................................... 14
5.2 Mounting the Alpha FXM ...................................................................................................................... 14
5.3 Wiring the External Batteries ............................................................................................................... 16
5.4 UATS and (UGTS) Option .................................................................................................................... 18
6. Operating the Alpha FXM ..................................................................................................................19
6.1 Switching the Alpha FXM On and Off .................................................................................................. 19
6.2 Operating from the Control Panel Interface ......................................................................................... 20
6.3 Operating via the FXM Communication Module (Intranet or Internet) ................................................. 31
6.4 The Alpha UPS Monitor Interface ........................................................................................................ 58
6.5 HyperTerminal Interface ....................................................................................................................... 63
7. Maintenance.....................................................................................................................................75
7.1 Upgrading the FXM Firmware .............................................................................................................. 75
7.2 Testing and Replacing the Batteries ..................................................................................................... 77
7.3 Preventative Maintenance.................................................................................................................... 81
Page 1 to 95

8. Troubleshooting ................................................................................................................................83
8.1 Procedure ............................................................................................................................................. 83
9. Specifications ....................................................................................................................................86
10. Warranty .............................................................................................................................................89
11. Emergency Shutdown Procedure .....................................................................................................90
Appendix A - Peukert Number and Battery Capacity ............................................................................ 91
A.1 Introduction........................................................................................................................................... 91
A.2 Determining the Peukert’s Number and Peukert’s Capacity ................................................................ 91
A.3 Determining Peukert’s Capacity for Series Parallel Combinations ...................................................... 91
A.4 Example ............................................................................................................................................... 92
A.5 Using the Spreadsheet ......................................................................................................................... 93
Appendix B - Types of Triggers .............................................................................................................. 94
B.1 Edge trigger.......................................................................................................................................... 94
B.2 Level
Toggle
......................................................................................................................................... 94
Page 2 to 95

1. Safety
SAVE THESE INSTRUCTIONS: This manual contains important safety instructions that must be followed during the
installation, servicing, and maintenance of the product. Keep it in a safe place. Re- view the drawings and
illustrations contained in this manual before proceeding. If there are any questions regarding the safe installation or
operation of this product, contact Alpha an Outback Energy GmbH or the nearest AOE representative. Save this
document for future reference.
1.1
Safety Symbols
To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following
symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention.
The use of ATTENTION indicates specific regulatory/code requirements that may affect the placement of equipment
and /or installation procedures.
NOTE:
A NOTE provides additional information to help complete a specific task or procedure. Notes are
designated with a checkmark, the word NOTE, and a rule beneath which the information appears.
CAUTION!
CAUTION indicates safety information intended to PREVENT DAMAGE to material or equipment. Cautions
are designated with a yellow warning triangle, the word CAUTION, and a rule beneath which the information
appears.
WARNING!
WARNING presents safety information to PREVENT INJURY OR DEATH to personnel. Warnings are
indicated by a shock hazard icon, the word WARNING, and a rule beneath which the information appears.
HOT!
The use of HOT presents safety information to PREVENT BURNS to the technician or user.
Page 3 to 95

1.2
General Warnings and Cautions
You must read and understand the following warnings before installing the Alpha FXM and its components. Failure
to do so could result in personal injury or death.
Read and follow all instructions included in this manual.
Do not work alone under hazardous conditions.
Only qualified personnel are allowed to install, operate and service this system and its components.
Use proper lifting techniques whenever handling equipment, parts, or batteries.
Always assume electrical connections or conductors are live. Switch off all circuit breakers and double-
check connections with a voltmeter before performing installation or maintenance.
Place warning label(s) on the utility panel to tell emergency personnel a UPS is installed.
The Alpha FXM uses more than one live circuit. AC power may be present at the outputs even if the system
is disconnected from line or battery power.
The Alpha FXM surface can be very hot to the touch.
Battery installation and servicing should be done or supervised by personnel knowledgeable about
batteries and their safety procedures.
If electrolyte splashes on your skin, immediately wash the affected area with water. If electrolyte gets into
your eyes, wash them for at least 10 minutes with clean running water or a special neutralizing eye wash
solution. Seek medical attention at once.
Neutralize spilled electrolyte with special neutralizing solutions in a “spill kit” or a solution of 1 lb. (0.45 kg)
of baking soda (bicarbonate of soda) in 1 gallon (3.8 L) of water.
Be extra cautious when connecting or adjusting battery cabling. An improperly connected battery cable or
an unconnected battery cable can result in arcing, fire, or explosion.
Use new batteries when installing a new unit. Verify that all batteries are the same type with identical date
codes.
Always replace batteries with ones of identical number, type and rating. Never install old or untested
batteries. One sealed lead-acid battery is rated to a maximum voltage of 12 Vdc.
A battery that shows signs of cracking, leaking or swelling must be replaced immediately by authorized
personnel using a battery of identical type and rating.
Keep the chassis area clear and dust-free during and after installation.
Keep tools away from walk areas where you or others could fall over them.
Wear safety glasses when working under any conditions that might be hazardous to your eyes.
Do not work on the unit or connect or disconnect cables during periods of lightning activity.
Do not smoke or introduce sparks in the vicinity of a battery.
Never open or damage the batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic
and hazardous to the environment.
Page 4 to 95

A battery can present a risk of electrical shock and high short-circuit current. The following precautions
should be observed when working on batteries:
a.
Remove watches, rings, or other metal objects.
b.
Use tools with insulated handles.
c.
Wear rubber gloves and boots.
d.
Do not lay tools or metal parts on top of batteries.
e.
Disconnect the charging source before connecting or disconnecting battery terminals.
f.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source from
the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if the grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
Never let live battery wires touch the Alpha FXM, the enclosure or any other metal objects. This can cause
a fire or explosion.
Never dispose of batteries in a fire. The batteries may explode. Follow the manufacturer’s directions and
check with your local jurisdictions for safe battery disposal.
Before attaching the batteries to the Alpha FXM, make sure that the polarity is correct.
If the batteries have been in storage for more than 3 months, recharge them for at least 24 hours and then
test them with a load before installation.
Each AlphaCell™ battery has a date code, found on the warning label, which must be recorded in the
maintenance log. If non-Alpha batteries are used, see the manufacturer’s documentation for date code type
and placement.
1.3
Certifications and Compliances
The Alpha FXM has been designed, manufactured, and tested to the requirements of the following national and
international safety standards:
CAN/CSA-C22.2 No. 107.3-05 – Uninterruptible Power Systems; additional requirements (RD): CAN/CSA-
C22.2 No. 60950-1-03 - Information Technology Equipment - Safety.
UL 1778 (Edition 4) – Uninterruptible Power Systems; additional requirements (RD): UL 60950-1 (Edition 1)
- Information Technology Equipment - Safety.
FCC CFR47 Part 15 Class A – This equipment has been tested and found to comply with the limits for a
Class A digital device pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
Industry Canada - This Class A digital device apparatus complies with Canadian ICES-003.
Industry Canada - Cet appareil numrique de la Classe A est conforme la norme NMB-003 du Canada.
Page 5 to 95

2
4
6
5
9
14
12
1
3
7
8
10
C6
11
13
1
4
6
5
8
10
12
2
3
7
9
1
1
13
14
2. General Description
2.1
Overview
The Alpha FXM is available in 3 models – FXM 650, FXM 1100 and FXM 2000. The FXM 650 and the FXM
1100/2000 look different, but all of the front panel connectors and circuit breakers operate in the same way. How-
ever the circuit breakers for each unit have different ratings. See Chapter "9. Specifications" for details. All units
operate in the same way unless stated otherwise in this manual.
FXM 650-24Vdc – with a 24 Vdc battery string voltage.
FXM 650-48Vdc – with a 48 Vdc battery string voltage.
FXM 1100-48Vdc – with a 48 Vdc battery string voltage.
FXM 2000-48Vdc – with a 48 Vdc battery string voltage.
2.2
Figure 1 shows the front panel connectors and circuit breakers, which are described in detail in the following
sections.
Figure 1 — FXM 650 (top) and FXM 1100/2000 front panel description
Page 6 to 95
Front Panel

8
6
Battery breaker
This circuit breaker provides over-current protection and is used as an on/off switch for the
battery power. It must be switched on for proper Alpha FXM operation.
Battery connector
The battery connector connects the external batteries to the Alpha FXM.
Replaceable fan assembly
This microprocessor-controlled fan turns on at a programmable temperature to lower the Alpha
FXM internal temperature. It must not be blocked. An Alarm is generated if the fan fails; a failed
fan can be replaced in the field.
RJ45 communication module connector
The RJ-45 connector is the Alpha FXM Ethernet connector.
LCD control panel and menu navigation buttons
The LCD control panel together with the cancel, scroll and select buttons are used to monitor and
control the Alpha FXM.
Battery voltage test points
These test points accept 2 mm diameter test probe tips. The battery circuit breaker must be on to
measure the voltage.
The battery voltage test points are not to be used as a power outlet.
RS-232
This DE-9 connector allows a straight-through DE-9 to DE-9 connector cable to be used to
connect the Alpha FXM to a computer for remote control and monitoring.
Battery temperature sensor connector
The battery charging voltage is temperature dependant when compensation is not set to 0
mV/°C/cell. A battery temperature sensor connects to the Alpha FXM so the Alpha FXM
microprocessor can adjust the charging volt- age for optimum charging. Refer to "UPS
Maintenance > Battery" on page 38.
The sensor MUST be attached to the Alpha FXM for normal operation. If the sensor is not
attached, a “Temperature Probe Unplugged” alarm appears on the LCD.
4
Page 7 to 95
1
2
3
5
7

9
+48Vdc, 500mA (FXM
1100/2000, 650- 48) or
+24Vdc (FXM
650-24) from the
external batteries.
Contacts C1 to C6
Contacts C1 to C5 allow the Alpha FXM to be connected to an external monitoring panel or to
traffic control equipment.
The factory default settings can be reprogrammed to meet your requirements. Each contact can
only be programmed for one function at a time and cannot show multiple conditions. See "UPS
Maintenance > Relay & Load Shed" on page 41 and section 6.5.7 on page 66 for the
HyperTerminal interface.
For Contact C6, the default factory configuration is +48 Vdc output (FXM 650-24 is +24 Vdc), but
it can be factory configured as a dry contact. Figure 2 shows the contact’s layout while Figure 3
shows the +48 Vdc or +24 Vdc terminal block layout.
Figure 2 — Contact Layout (Standard for C1 to C5, Factory Option for C6)
C1: The C1 contact is energized when line power is unqualified and the Alpha FXM
provides backup battery power to the load(s). It can be used to generate an “On Battery”
contact.
C2, C3: These contacts are energized when the battery drops below a pre-set voltage
level. They can be used to generate a Low Battery alarm. To change the pre-programmed
level to match the batteries used and the actual operating conditions, see Low Battery
Warning in "UPS Maintenance > Battery" on page 38.
C4: This contact is energized after the Alpha FXM has been in Inverter mode for 2 hours.
To change the pre-programmed 2 hours to match your operating conditions, see Load
Shed Timer Configuration in "UPS Maintenance > Relay & Load Shed" on page 41.
C5: The C5 contact is energized when any alarm is generated—see "Table P — Alarm
Submenu" on page 78.
C6: The factory default layout for the C6 contact is a relay that is energized when the
Alpha FXM is in Line or Inverter modes and is de-energized when in Standby mode. It
provides 48 Vdc (500 mA) from the external batteries to an external fan or other
equipment. C6 can be factory-configured as a dry contact.
Figure 3 — 48 Vdc Contact Layout (De-energized Shown, Factory Default for C6)
The contacts have
a maximum rating
of 1A at 250V.
Microprocessor
Normally
Open (NO)
Normally
Closed (NC)
UPS
Interior
Common (C)
Microprocessor
Contact C6
16
17
18
Page 8 to 95

11
Microprocessor
48Vdc from the
external batteries
Optically isolated user inputs C7 and contacts C8
The optically isolated user inputs are used to attach an external switch panel for remote control of
the Alpha FXM or to allow the Alpha FXM to control optional Alpha Off-Line Automatic Transfer
Switch (ATS).
User Input (C7): This relay has three contacts that are used to control the Alpha FXM:
19 (S1): Shorting this contact starts the Alpha FXM self test. See "UPS Maintenance > Battery" on
page 38.
20 (S2): Shorting this contact activates an alarm. See "UPS Maintenance > User Input" on page
46.
21 (S3): Shorting this contact disables the AC output. There is no AC output power, but the Alpha
FXM is still energized. A manual restart is required to put the Alpha FXM back to normal
operation.
22 (C): Isolated return for contacts S1, S2 and S3.
Figure 4 — User Input Layout
ATS (C8): When the Alpha FXM is in the Inverter mode, this normally open relay closes sending
48 Vdc (FXM 650-48, 1100, 2000) or 24 Vdc (FXM 650-24) from the external batteries to this dry
contact (Figure 5). If the op- tional Alpha Off-Line Automatic Transfer Switch (ATS) is connected, it
will cause the ATS to switch the load from line power to the Alpha FXM battery backup power.
Figure 5 — ATS Layout
Status and Alarm LEDs Status:
Green LED solidly illuminated: the Alpha FXM is in Line mode and line power is provided to the
load. Green LED flashing: the unit is in Inverter mode and backup battery power is provided to the
load.
Alarm:
Red LED solidly illuminated: fault in the Alpha FXM. (See "Table Q — Fault Submenu" on page
79.) Red LED flashing indicates an alarm. (See "Table P — Alarm Submenu" on page 78.)
19
S1: Self Test
20
S2: Alarm
21
S3: Shutdown
22
Common
48Vdc from the
external batteries
+
Contact C8
23
24
Page 9 to 95
10

13
AC Input Circuit Breaker
This circuit breaker is an on/off switch for the line power into the Alpha FXM that also provides
input protection. It must be switched on for proper Alpha FXM operation.
Input Terminal Block
This terminal block is the Alpha FXM AC line power input.
Output Terminal Block
This terminal block is the Alpha FXM AC power output.
3. Site Planning
WARNING!
Restricted Access: The Alpha FXM must be installed in a restricted area accessible only
by qualified service personnel.
The Alpha FXM is intended for permanent AC connection only. The only exception is the FXM650(U) model.
The Alpha FXM must be correctly grounded for proper operation. Older facilities may have inadequate
electrical grounding. Inspection must be performed by a qualified electrician before installation to ensure
that grounding meets the local electrical code.
The utility line attached to the Alpha FXM input MUST be protected by a circuit breaker certified for this use
in accordance with the local electrical code. The UPS must be connected only to a dedicated branch circuit.
The UPS equipment that is powered by this service panel requires the neutral to be permanently bonded to
the ground. Always disconnect the batteries before servicing the circuit breaker panel.
The input and output lines to and from the Alpha FXM MUST have disconnect devices attached.
The Alpha FXM is suitable for installations in Network Telecommunication Facilities and locations where the National
Electrical Code applies.
Grounding: The Alpha FXM is suitable both for installation as part of a common bonding network and an isolated
bonding network.
For installations above 1400 m (4500 ft) elevation, additional cooling may be needed to reduce the operating
temperature of the Alpha FXM. The maximum allowable operating temperature must be reduced by 2°C (3.5
°F) for every 300 m (1000 ft) above 1400 m (4500 ft).
Page 10 to 95
12
14

3.1
Safety Precautions
Install the Alpha FXM on a surface that can support its weight. See Chapter "9. Specifications".
The input wiring must reach a suitably grounded power outlet and the load wiring must reach the Alpha FXM
output terminal blocks.
Place the Alpha FXM in a properly sheltered location or inside a weather-proof enclosure to protect the
electronics from water, dust and other possible contamination.
Alpha and Outback Energy offers a wide range of outdoor enclosure systems. Visit our website at
www.alpha-outback-energy.com, or call customer service for more information.
Backup Generator (If used)
Use Generator mode so that noise tolerance is increased to accept the fluctuations created by a genera- tor.
See Sense Type in Table B on page 24 .
Use a generator with electronic speed and voltage controls which produces less than 10% voltage to- tal
harmonic distortion (THD). Mechanical governors can force the Alpha FXM to run continuously in the Inverter
mode.
Before installation, make sure the generator’s output voltage is compatible with the Alpha FXM input volt-
age requirements. To make sure the system runs smoothly, use a generator that supplies twice as much
power as drawn by the total load.
3.2
Communicating with the Alpha FXM
There are several ways you can communicate with the Alpha FXM UPS:
1. Using the control panel.
2. Using an RS-232 interface, you can access the UPS command line system with Windows HyperTerminal or
other terminal emulation program.
3. Using an RS-232 serial connection via the Alpha UPS Monitor installed on your computer. The Alpha UPS
Monitor software can be downloaded from www.alpha-outback-energy.com.
4. Using the optional factory-installed FXM communication module, you can communicate with the Alpha FXM
over a company intranet or the internet using a web browser or with SNMP communications.
Page 11 to 95

Figure 6 — Alpha FXM Communication Options
Page 12 to 95

3.3
Electromagnetic Compatibility (EMC) Requirements
Observe the following EMC requirements when setting up the Alpha FXM and its internal equipment:
All AC mains and external supply conductors must be enclosed in a metal conduit or raceway when
specified by local, national, and/or other applicable government codes and regulations.
The customer facilities must provide suitable surge protection.
4. Unpacking Alpha FXM
WARNING!
The Alpha FXM is heavy, up to 16 kg (35 lb). Use proper lifting techniques. The lifting and moving should be
done by at least two people to avoid injury.
Follow these guidelines for unpacking the Alpha FXM.
1. Select a suitable area for unpacking.
2. Store all the packing material and boxes for possible equipment returns.
3. Compare the packing slip and the list of parts with the items you received: make sure the standard items as
well as purchased options are included:
Standard items
1 Alpha FXM
1 Alpha FXM operator manual
8 Terminal blocks and labels for the dry contacts
1
Temperature sensor cable
Purchased options
Batteries, if ordered from AOE, will be shipped separately.
Enclosure (with optional mounting hardware kit)
Battery heating mats
Network Interface card
In-line fuse
4. If the list of parts on your packing slip does not match the items you received, or any items appear
damaged, immediately notify your carrier agent and the supplier who prepared your shipment.
Page 13 to 95

5. Installation
WARNING!
The Alpha FXM module MUST be correctly grounded for proper operation.
The input and output lines to and from the Alpha FXM MUST have disconnect devices attached.
The Alpha FXM must be installed in a restricted area accessible only by qualified service personnel.
Once the installation location has been planned and prepared, you are ready to install the Alpha FXM. There are
three steps to setting up the Alpha FXM:
1. Mounting the Alpha FXM
2. Wiring the external batteries
3. Wiring the Alpha FXM
5.1
Tools and Equipment Required for Installation
DC voltmeter.
Labels or masking tape and marker.
Torque wrench for input/output terminal blocks.
Slot head screwdriver to fit the terminal blocks.
Minimum #10 AWG copper wire for input/output terminal blocks.
High strength, flame-proof tape such as duct tape.
Battery terminal corrosion inhibitor such as NOCO Company NCP-2 or Sanchem Inc. No-Ox ID Grease “A”.
5.2
Mounting the Alpha FXM
The Alpha FXM can be placed on a shelf with no other parts needed. Any version of the FXM can be rack or wall
mounted or secured to a shelf, such as on an outdoor enclosure shelf, with the optional mounting brackets as
shown in the figure below The brackets and the screws to attach them to the Alpha FXM case are available from
Alpha and Outback Energy (part number 740-697-21).
Page 14 to 95

CAUTION!
Terminal block covers and the battery harness restraining bracket MUST be used and are available from
Alpha and Outback Energy (part number 740-698-21). If the Alpha FXM end application is mounted inside an
enclosure or in an area restricted to authorized personnel, then the covers and bracket may or may not be
needed.
To meet NEBS Level 1 specifications when you are installing this unit in a rack or frame, do the following:
1. Before installation, clean all attachment points on the Alpha FXM, rack and mounting brackets and bring
them to a bright finish. Then coat them with an anti-oxidant such as Sanchem Inc. No-Ox ID “A-Special
Electrical Grade” or equivalent.
2. Attach the mounting brackets with the thread forming screws and the paint piercing washers provided with
the brackets to insure adequate grounding between the Alpha FXM chassis and the rack.
Figure 7 — Mounting the Alpha FXM Mounting brackets position for rack mounting. Rotate to fit either 19" or 23"
racks.
For the FXM 1100/2000 units only, the control panel and the power connection panel can be rotated to suit your
needs. To rotate either one, unscrew the screws in each corner, remove the panel, rotate it and reinstall the screws.
CAUTION!
Use care to avoid damaging or pulling out the wires or the ribbon cables when rotating the panels.
Page 15 to 95

5.3
Wiring the External Batteries
WARNING!
The batteries must be installed by qualified personnel trained in the safe use of high-energy power
supplies and their batteries. Refer to the safety section in this manual.
Use new batteries when installing a new unit. Verify that all batteries are the same type with identical date
codes.
For the FXM 650-24, the battery string is 24 Vdc. For the FXM 650-48/1100/2000, the battery string is 48
Vdc.
If you are making your own battery wiring harness, use at least 10 AWG (for FXM 650/1100) or 8 AWG
(FXM 2000) wires.
The battery return connection is to be treated as an Isolated DC return (DC-I) as defined in GR-1089-
CORE.
5.3.1
Procedure
NOTE: The optional in-line fuse option shown in Figure 8 on page 18, is available as part number SPB98-645- 1,
Kit, Fuse Upgrade, 100A.
1. For FXM 650-48/1100/2000 (48 V battery string), number the batteries from 1 to 4 with labels or tape. For
FXM 650-24 (24 V battery string), number the batteries from 1 to 2 with labels or tape.
2. Coat the battery terminals with the corrosion inhibitor.
3. Connect the batteries as shown in Figure 8 on page 18. If used, install the in-line fuse as shown.
4. Connect the black battery cable to the negative terminal of the battery string, and the red battery cable to
the positive terminal of the battery string.
5. When the batteries are wired, measure the voltage at the battery connection terminals. It should read
between 42 and 54V for the FXM 650-48/1100/2000 or 21 and 27V for the FXM 650-24.
6. Note the polarity and ensure it is correct.
7. Ensure that the DC breaker if OFF.
8. Connect the external batteries to the Battery connector—location in Figure 1.
9. Route the sensor end of the battery temperature cable to the batteries.
10. Attach the battery temperature sensor to the body of the battery, about 2 to 3" (5 to 7.5 cm) from the base
of the battery.
11. If multiple battery strings are used, repeat steps 1 to 4 as required.
2
Page 16 to 95

Figure 8 — External Battery Wiring (for 48 Vdc string (top) and 24 Vdc string)
CAUTION!
Torque the battery terminals according to the manufacturer’s specifications on the battery name plate or
data sheet.
5.3.2
Wiring the Alpha FXM
WARNING!
Make sure the line power is off. Switch off all circuit breakers on the Alpha FXM before making any
electrical connections.
If stranded wires are used to connect the input and output terminal blocks, ferules or equivalent crimping
terminals must be used.
Page 17 to 95

5.3.3
Procedure
1. If used, connect the following ports (see Figure 1 on page 7 for location of numbered elements):
Ethernet port .
RS-232 port .
Dry contacts .
User inputs .
2. Connect the load to the Alpha FXM Output terminal block 14 . Torque to 1.4 N-m (12 lb-in).
3. Connect the line power to the Alpha FXM AC Input terminal block 13 . Torque to 1.4 N-m (12 lb-in).
4. If needed, attach the terminal block covers and battery harness-restraining bracket.
WARNING!
Before proceeding, verify that the line wire is attached to the line terminal block, the ground wire is
attached to the ground terminal block, and the neutral wire is attached to the neutral terminal block to
prevent accidental shocks or electrocutions.
5.4
UATS and (UGTS) Option
The Universal Automatic Transfer Switch (UATS) and Universal Generator Transfer Switch (UGTS) are the next
generation of Automatic Transfer Switch (ATS) and Generator Transfer Switch (GTS) products. They are optional
add-on switching units specifically designed for the FXM UPS family (FXM 650, 1100 and 2000), the Micro UPS
family (Micro 300 and 1000) and the Alpha FXM350/ Micro350 UPS. These switching units provide power and/or
bypass capacity (automatic or manual) so that the operator may safely disconnect the UPS from line or generator
power for easy removal and servicing. In bypass mode, the loads are directly connected to the line or generator
power without any conditioning. Depending on the use of one and/or the other, the UATS/UGTS allows the use of
up to 3 different back-up sources (line, batteries and generator). Refer to the UATS/UGTS Installation Manual
(Alpha P/N 020-165-B0) for details.
WARNING!
Make sure you have read and understood the instructions given in the UATS/UGTS Installation Manual
before making any connection to the supply.
Page 18 to 95

6.
Operating the Alpha FXM
6.1
Switching the Alpha FXM On and Off
Under normal operation, the Alpha FXM is always powered ON to supply uninterruptible power to the load.
Switching off the Alpha FXM will disconnect the power supply to the load. If for any reason you need to switch off
the Alpha FXM while maintaining power to your critical load, make sure that you have a plan that provides an
alternate source of power.
6.1.1
Switch Off Procedure
1. Switch off the AC input circuit breaker.
2. Switch off the battery circuit breaker.
The status LED turns off and the LCD panel goes blank. The Alpha FXM is now switched off and no backup
power is supplied to the load.
6.1.2
Switch On Procedure (LINE mode)
Before you put the Alpha FXM back into commission, make sure that the line is qualified and the batteries are fully
charged.
1. Switch on the battery circuit breaker. The LCD displays STANDBY and the fan turns on for about a minute.
If the temperature is below –15ºC, the LCD display may not function. See Chapter "8. Troubleshooting".
2. Switch on the AC input circuit breaker. The Alpha FXM qualifies the line power. The LCD displays
RETRAN, then shows LINE, BUCK or BOOST. The status LED illuminates.
3. If there is no line power, the Alpha FXM remains in the STANDBY mode until the line power is qualified. To
provide backup battery power to the load, perform a manual start by using the Inverter command: From
the Control Menu, scroll till the LCD displays Inverter, press Select and select ON. (See Figure 11 on page
23).
The Alpha FXM uses auto-frequency detection. When it is first switched on, it senses the line frequency and
adjusts its output frequency to match that of the input. The load should be receiving power, If not, perform
trouble- shooting.
6.1.3
Switching the Alpha FXM from Line mode to Inverter mode
You can force the Alpha FXM to operate in the Inverter mode by manually switching off the input circuit breaker.
Doing so will effectively disconnect any line power to the Alpha FXM, simulating a power outage which triggers
the Alpha FXM to switch to the inverter mode of operation.
Procedure
1. Switch off the input circuit breaker. The LCD shows INVERTER, the status LED starts flashing to show that
the Alpha FXM is running on backup battery power. Confirm that the load is receiving power.
Page 19 to 95
This manual suits for next models
2
Table of contents
Other Alpha Outback Energy UPS manuals

Alpha Outback Energy
Alpha Outback Energy Tetrex 500 User manual

Alpha Outback Energy
Alpha Outback Energy CableUPS XM3V-HP User manual

Alpha Outback Energy
Alpha Outback Energy FXM 350 Series User manual

Alpha Outback Energy
Alpha Outback Energy Tri Power X33 HE User manual

Alpha Outback Energy
Alpha Outback Energy Sentra XL User manual

Alpha Outback Energy
Alpha Outback Energy Continuity 1000 User manual

Alpha Outback Energy
Alpha Outback Energy Continuity 6K User manual

Alpha Outback Energy
Alpha Outback Energy Tri Power X33 SE Series User manual