Alpha 3.022144 Guide

Alpha Climatic Programmable Modulating Boiler Energy Manager
Part No 3.022144 (Hard Wired)
Part No 3.022143 (Radio Frequency)
Installation and User Instructions

2
1. Description
The Alpha Climatic energy manager is a programmable modulating room thermostat capable of controlling time and temperature for heating
varying the primary flow temperature depending on the room temperature.
The controller also allows remote control of the hot water function and other boiler features.
Connection to the boiler is via a two core cable to the low voltage bus connection for hard wired version or via an integrated RF receiver for
the RF version.
2. Mounting of the Controller
The controller must be mounted in a position where it can not be influenced by direct sunlight, any device which might emit heat, near a door,
window or be obstructed by curtains. It must be installed approximately 1.5m from the floor and any radiators within the same room must not
have thermostatic radiator valves or any other thermostatic control fitted to them.
Fig 1

3
3. Fixing the Programmer to the Wall
Using a small screwdriver press down on the tab at the top of the controller (4) and separate the front control panel from the rear case.
Hold the rear casing in its chosen position level against the wall and mark the fixing holes.
Drill two 5mm holes in the wall, insert the wall plugs provided and fix the rear case to the wall using the 30mm screws.
Connect the boiler data wire to the + and – terminals in the rear casing (hard
wired only).
Re-fit the front control panel, lower the control cover (1) and secure the
control panel using the two 10mm screws provided (3).
Note; If an RF controller is being used then the data wire is not required but
two AA batteries must be fitted.
Fig 2
Installing the batteries (RF controller only)
Using a small screw driver un-clip the bottom of the battery cover (2) and
remove. Insert two Size AA batteries in the position shown in the back of the
battery compartment and refit the battery cover
Note; The RF Climatic must not be programmed until the receiver unit is
connected to the boiler and RF communication is established.
Fig 2

4
4. Connecting the Climatic Controller (Hard Wired)
Gain access to the boiler terminal block as described in the boiler installation and service instructions section 4.10. Pass the wire from the
Climatic controller through the rubber grommet in the terminal block cover and connect it to terminals 12 and 13 (BUS). Secure the wire
under the cable clamp and re-assemble in reverse order.
Installing the receiver (RF models only)
Gain access to the boiler terminal block as described in the boiler installation and service instructions section 4.10. Remove the screws from
the fixing posts in the back of the control panel, position the receiver and re-fit the screws to secure it in place. Connect the wires from the
receiver terminal to the BUS connection on the boiler terminal block. See fig 3. Tuck the wire behind the tabs on the PCB cover and re-
assemble in reverse order.
Note: Remove the link between terminals 1 and 2 when connecting either Climatic heating controller.
Fig 3

5
5. Control button functions.
1. Mode selection switch
2. Reset, previous display
3. Heating/Cooling on-off temperatures
4. Reset remote settings
5. Programming menu selection
6. Menu selection
7. DHW temperature set
8. CH temperature set
9. Information e.g. flow temperature
10. Auto/Manual override
11. Scroll/temperature adjust
12. Scroll/temperature adjust
Fig 4

6
6. Display Symbol Descriptions
Symbol Description Symbol Description
DHW and heating on Outside temp. display
DHW only Inside temp. display
Cooling and DHW modes enabled Remote phone activation
Request for heating or cooling Holiday mode
Cylinder heating in progress (if present) Indicates it is possible to adjust a parameter using
buttons 11 and 12
Request for DHW 000:000 Describes current status
Request for Heating Anomaly or Fault
Reset/escape to previous screen Solar active
Displays room temp. and numerical date External probe connected
Functioning in wireless mode (RF models only) Battery condition low (RF models only)

7
7. Climatic RF Boiler Communication
The communication between the remote and the boiler mounted receiver is identified with the symbol.
There are three possible conditions shown via this symbol:
1. Symbol not present - No compatible connection between devices.
2. Symbol flashing - Connection with communication error
3. Symbol permanent - Communication OK
8. Programming
a. Set Time
Turn the mode selection switch to CH/DHW on .
Press the button to enter the time setting mode, then press OK and the hour will flash.
Using the +/- buttons adjust the time to the correct hour then press OK, the minutes will now flash, using the +/- buttons adjust the minutes
then press OK. The day of the week will flash, using the +/- buttons set to the correct day of the week and press OK then ESC to get back to
main menu.
b. Set Heating Programme
Press the button and TIME will appear, press + and CH PRG will flash, press OK and MONDAY will appear.
Using the + button you can programme individual days or blocks of days then press OK.
On 1 will be displayed and the time will flash, using the +/- buttons you can select the time you wish the heating to turn on followed by OK,
then using the +/- buttons you can set the time you wish the heating to turn off. Press OK and the next on period will appear, repeat the
previous procedure for the next on-off periods for the rest of the day to a maximum of four on periods. After one minute the display will return
to main menu or keep pressing ESC.
NOTE; if four on / off periods are not required then set the unused periods on off times the same.
E.g. on 23:00 off 23:00.

8
c. Set Hot Water Programme
Note; The hot water programmes only need to be set when a hot water storage cylinder is present.
Press the button and TIME will appear, press + twice and HW PRG will flash, press OK and MONDAY will appear.
Using the + button you can programme individual days or blocks of days then press OK.
On 1 will flash on the display with a time below it, using the +/- buttons you can select the time you wish the hot water to turn on followed by
OK, then using the +/- buttons you can set the time you wish the hot water to turn off. Press OK and the next on period will appear, repeat
the previous procedure for the next on-off periods for the rest of the day to a maximum of four on periods. After one minute the display will
return to main menu or keep pressing ESC.
NOTE; if four on off periods are not required then set the unused periods on off times the same.
E.g. On 23:00 off 23:00.
d. Setting the Temperature
Note; There are two temperature settings, comfort which is the heating on setting and economy which is the heating off setting. The comfort
temperature is the room temperature required during the heating on period. The economy temperature is the minimum allowable room
temperature, e.g. if the economy temperature is set to 10ºc and the temperature drops below this during a heating off period the boiler will
switch on to maintain the 10ºc setting.
Press the button and the word COMFOR will appear with the temperature flashing above and a symbol. Using the +/- buttons set
the temperature as required then press OK to store.
Press the button twice and the word ECONOM will appear with the temperature flashing above and a symbol. Using the +/- buttons
set the temperature as required then press OK to store.

9
9. a. Mode Selection
The mode selection switch (1) has five settings.
a. In this mode the control is switched off but the boiler frost protection is still active.
b. In this mode the control is switched off but provides frost protection for its immediate location.
c. This mode provides hot water only (summer setting).
d. This mode provides hot water and timed and temperature controlled heating (winter setting).
e. This mode is used in conjunction with an air conditioning unit to provide summer cooling control.(Hot Water is also active)
b. Central Heating Temperature setting (8)
The central heating temperature setting adjusts the primary heating water temperature to the user’s requirement. When the dial is turned the
temperature setting is displayed on the screen.
The primary flow temperature might not reach the temperature set by the user when in operation because the programmer will control the
boiler output to give optimum performance to reach the required room temperature setting.
c. Domestic Hot Water Temperature Setting (7)
The domestic hot water temperature setting adjusts the temperature of the water delivered to the hot tap to the user’s requirement. When the
dial is turned the temperature setting is displayed on the screen.
d. Continuous Override
The override function is used to manually control the boiler, press the button and use the +/- buttons to set the desired room
temperature. To turn off the manual override press the button.

10
e. Temporary Override
To access Temporary override press the +/- buttons to set the desired temperature and the symbol will flash in the top right hand corner
of the display. The room temperature will be maintained until the next timed on or off period or press the button to come out of
temporary override.
f. Room Frost Protection
If the temperature in the room where the programmer is installed drops to 5ºC the boiler will operate at minimum heating output until the
room temperature has been raised to 5.6ºC.
g. External Probe (optional)
If an external temperature probe is fitted it is possible to set a flow temperature correction curve according to the outside temperature. By
turning the CH temperature dial you can scroll from 0 to 9, each number corresponds to a line on the graph. Each number corresponds to a
line on the graph in fig 5. e.g. line 6 will give a flow temperature of 60ºC when the external temperature is 10ºC.
Fig 5
TE = External Temperature
TM = Heating Flow Temperature (values in brackets are for Low Temp Circuits)

11
h. Cooling Mode
In this mode the programmer can be used to control an air-conditioning unit, turn the selector to to enable.
NOTE; to use this function some boilers will need to have a relay PCB kit added. For more information please contact Alpha Heating
Innovation.
If fitted; the cooling programming for time and temperature is the same as for heating with the selector 1 (fig 4) in the cooling position.
i. Information
Pressing the INFO button allows the user to scroll through a menu showing various temperatures and the functioning state of the
programmer.
With each press of the INFO button a value will be displayed e.g. DHW T 50ºC, if a value is not present a “- -“will be displayed. The display
of the INFO is subject to the boiler model and the method of connection of the programmer.
To get return to the main menu press ESC button or wait for 60 seconds.
The displayed parameters are as follows;
EXT T: External temperature (if external probe is fitted).
HF TMP: Primary flow temperature.
HR TMP: Primary return temperature.
DWIN T: DHW input temperature.
DHW T: DHW output temperature.
PAN T: Solar collector temperature.
CH PRS: Primary system pressure.
SERVIC: Days remaining before a boiler service is required.
VER “X”: “X” identifies the type of communication protocol with the boiler in use:
VER PI = IMG-Bus.
The display shows the software version of the programmer remote control.
ZONE: Not used on the model.

12
j. Faults Diagnostics and Errors
The Climatic remote control continually controls the functioning of the boiler and signals any anomalies, stating the corresponding error code
on the display.
The error codes are listed in the boiler installation manual.
If a fault occurs it will be displayed as “ERR-XX” where the “XX” represents a number that identifies the code as well as a flashing
symbol.
The climatic also checks its own functioning state, indicating any malfunction.
Code Description
ERR>CM (Climatic Display) Communication error between the Alpha Climatic remote controller or receiver and the boiler.
ERR>TP (Climatic Display) Error in reading the room temperature or value measured off scale (below 0ºC or over 50ºC)
E51 (Boiler display) Communication error between the Alpha Climatic remote controller and receiver. (Climatic RF only)
k. Reset Errors
In the event of a resettable boiler lock out RESET will flash on the display. By pressing and holding the reset button (ref 2 fig 4) for 5
seconds, it is possible to reset the boiler.
It is possible to reset the boiler up to 5 times then one hour must elapse until one more attempts can be made.
l. Reset Climatic Remote Control
By pressing the reset button (ref 4 fig 4) the climatic remote control hardware can be reset without losing the user setting, such as time, date
and timed programmes.

13
m. Special Functions
By pressing the MENU button, a list of options can be accessed, by pressing the +/- buttons you can scroll through the various options and to
select press OK.
n. Language
Allows the user to choose between Italian and English.
o. Regult (management of regulation parameters)
This allows you to customise the functioning parameters.
CH MIN allows adjustment of the minimum central heating flow temperature. This value is used to calculate the curves used for the external
probe. Values that are too high can cause flow temperatures that are too high on average for room central heating.
OFFSET (regulation constant), constant that can be regulated from -15ºC to +15ºC and which in the presence of the optional external probe
modifies the set flow temperature (see fig 5) set as standard at 0ºC.
NOTE; if the self leaning function is enabled the offset value could be modified automatically.
BUILD (dimension and build inertia), adjustable from 1 to 20, default setting is 10.It establishes the reaction speed of the system depending
on the type of system present.
Example:
AUTO A (self learning), defines the activation of self learning, as per standard set at OFF. This function allows the Climatic remote control to
vary the offset, adapting it to the room in which it is installed.
Value System Type
5 System with little heat inertia e.g. Fan Assisted Radiators
10 System with normal inertia e.g. Standard Radiator system
15 System with high heat inertia e.g. Under-floor Heating

14
p. Holiday Mode
During winter mode function it is possible to deactivate both the hot water and central heating for a defined number of days (1 to 99). When
the set number of days has past normal function will resume.
When the holiday mode is set a flashing will be displayed and the number of days it is enabled for.
To set the holiday mode press OK then the + button until HOLIDY appears then OK to accept. Off will be displayed and by pressing the +
button the number of days can be set, press OK then ESC once to get to main menu and the symbol and set number of days will flash
at the bottom of the screen.
This function can be deactivated by pressing the button.
In the event of remote telephone activation the Climatic controller will revert back to normal operation omitting the holiday program.
NOTE; the frost protection function is still active during holiday mode.
q. Legion (anti-Legionella function)
The anti-Legionella function raises the temperature of the hot water storage cylinder to the maximum boiler set temperature for 20 minutes to
kill Legionella bacteria.
It is possible to set this function once a day at 2am (ON 24H), every Monday at 2am (ON 7 DAYS) or deactivate it (OFF standard function).
NOTE; this function must only be activated when a cylinder is present and a thermostatically controlled blending valve should be fitted to the
cylinder hot water outlet.

15
10. Technical Characteristics:
a. Alpha Climatic HW
• Dimensions (LxHxD):.................................................................................................................... 142 x 103 x 31
• Power Supply:............................................................................18V nominal via twin-wire communication Bus
• IMG_BUS protocol maximum power supply voltage: ..............................................................................18 Vdc.
• IMG_BUS protocol maximum input:.........................................................................................23 mA - 250 mW.
• Functioning room temperature:............................................................................................................ 0 - +40°C
• Warehouse temperature:...................................................................................................................-10 - +50°C
• Protection rating according to EN 60730:......................................................................................................... II
• Protection rating according to EN 60529:....................................................................................................IP 20
• Connection technique:……………………………………………………………………………… 2 polarised wires
• Load reserve time:.......................................................8 hours for hourly count (with at least 2 hours of charge)
• Connection cable max. length:....................... 50 m (with cable of 2x0.75mm2) (0.5 ÷mm2 min - 1.5 mm2 max)
• Precision indication room temp.:...............................................................................................+/- 0.5°C a 25°C*
• NTC room temp. sensor:....................................................................................................................50 k at 25°C
• Clock indication diversion...................................................................................................... +/- 15 minutes/year
* = the indication of the room temperature can be affected by the point of installation of the remote control (e.g.
hot wall, cold wall, height from the ground, etc.)

16
b. Alpha Climatic RF
Receiver Data:
• Base Power Supply:........................................................................................18V nominal via Twin-wire communication bus
• RF communication:............ backbone 868,4 MHz, GFSK modulation, cover 30-100 m (depending on the environment)
• IMG_BUS protocol maximum power supply voltage:.....................................................................................................18 Vdc.
• IMG_BUS protocol maximum input:.............................................................................................................. 23 mA - 250 mW.
• Power and duty cycle:.................................Power Tx < 10 dBm, duty cycle < 0.1%in one hour (in normal functioning mode)
• Connection technique:.............................................................................................................................2 non-polarised wires
• Connection cable (supplied):..............................................................................................280 mm (with cable of 2x0.35mm2)
Controller Data:
Dimensions (LxHxD):............................................................................................................................................. 142 x 103 x 31
• Power Supply:..........................................................................................................................................2 x 1.5 V, AA batteries
• Functioning room temperature:.................................................................................................................................... 0 - +40°C
• Warehouse temperature:...........................................................................................................................................-10 - +50°C
• Protection rating according to EN 60730:.................................................................................................................................. II
• Protection rating according to EN 60529:............................................................................................................................IP 20
• Precision indication room temp.:......................................................................................................................+/- 0.5°C a 25°C*
• NTC room temp. sensor:..........................................................................................................................................50 k at 25°C
• Clock indication diversion........................................................................................................................... +/- 15 minutes/year
* = the indication of the room temperature can be affected by the point of installation of the Alpha Climatic remote control (e.g.
hot wall, cold wall, height from the ground, etc.)

17
c. Factory Settings
•Central Heating Comfort Temperature ……………………………………………………………………..…… 20.0 ºC
•Central Heating Economy Temperature ………………………………………………………………………….16.0 ºC
•Cooling Comfort Temperature ……………………………………………………………………………...………..25 ºC
•Cooling Economy Temperature……………………………………………………………………………………… 40 ºC
•Room Temperature in Manual ………………………………………………………………………….……………20 ºC
•Anti Freeze ……………………………………………………………………………………..………….…………..5.0 ºC
•Holiday Program……………………………………………………………………………….……….…. HOLIDY = OFF
•Offset ………………………………………………………………………………………………..………OFFSET = 0 ºC
•Building Inertia …………………………………………………………………………………………………..BUILD = 10
•Self Learning ………………………………………………………………………………………..………AUTO A = OFF
•Room Probe……………………………………………………………………………………………………… AMB = ON
•Reading Correction……………………………………………………………………………………… AMB CR = 0.0 ºC
•Reduction …………………………………………………………………………………………………..REDUCT = OFF
•Modulation ………………………………………………………………………………………...………….MODUL = ON
•Telephone Control ………………………………………………………………………………………….REMOTE = ON
•Anti-Legionella……………………………………………………………………………………………… LEGION = OFF

18

19

20
Doc No 1.031200 Rev 15.035774/001
Alpha Therm Limited.
Nepicar House, London Road, Wrotham Heath,
Sevenoaks, Kent TN15 7RS
Tel: 0844 871 8764
Email: info@alpha-innovation.co.uk
Website: www.alpha-innovation.co.uk
These instructions have been carefully prepared but we
reserve the right to alter the specification at any time in the
interest of product improvement.
© Alpha Therm Limited 2011.
This manual suits for next models
1
Table of contents
Other Alpha Remote Control manuals