Altronics CD200 User manual

ALTRONIC CD200
IGNITION SYSTEM
www.altronicinc.com
FORM CD200 II 5-07
www.altronicinc.com 1
1.0 DESCRIPTION
1.1
This manual provides installation and operating instructions for the
Altronic CD200 ignition system. It is recommended that the user
read this manual in its entirety before commencing operations.
1.2
The Altronic CD200 ignition system consists of these basic components:
•CD200 Unit - 791070-x or 791080-x (see FIG. 1 and FIG. 2)
•Magnetic Pickup Sensor (one per system)
•Input Harness (one per system)
•Output Harness (one or two per system)
•Ignition coils (one per cylinder)
1.3
The system requires a battery or a suitable power supply
with a nominal 12 Vdc or 24 Vdc (see FIG. 3). The CD200
unit steps up the DC supply voltage to charge an en-
ergy storage capacitor and contains a microproces-
sor and solid-state switching devices to release the
stored energy to the ignition coils in programmed,
timed sequence according to the application. Holes
(one per cylinder) in a special timing disc signal the
position of the engine crankshaft to the electronic
circuitry in the CD200 unit. One additional hole trails
after the last cylinder hole; this is the index signal that
another revolution has started. Ignition timing may be
varied by means of a manual switch, an analog timing signal
and/or engine RPM.
1.4
TheCD200systemcanoperateasasingle-ringordouble-ring
(ringonexhauststroke)systemuptotwelve(12)cylinders.These
instructionsdetail4-,6-,8-,10-and12-cylinder,single-ringap-
plications using CD200 units 791070-6, 791070-8, 791070-12, and
791080-6, 791080-8.
1.5
As shipped from the factory, the CD200 is in the auto-detect mode
and is set up for a trigger disc running at camshaft speed (see SEC-
TION 9.4). The setup is programmable by the use of the PC compatible
CD200 terminal program (FIGS. 14 & 15) provided on a CD delivered
with the unit. The programming of the unit is done via the RS-485
Modbus compatible communications port.
INSTALLATION INSTRUCTIONS
DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO
IMPROPER OPERATION OF THE MACHINE WHICH COULD
CAUSE PERSONAL INJURY TO OPERATORS OR OTHER
NEARBY PERSONNEL.
WARNING:

FORM CD200 II 5-07
2
INSTALLATION INSTRUCTIONS
NOTE: If possible, keep the
original shipping container.
If future transportation or
storage of the ignition is
necessary, this container will
provide the optimum protection.
2.0 CD200 UNIT
2.1
Select a location for the CD200 unit that will be at least 24 inches
(600 mm) away from the ignition coils and spark plug leads. In ad-
dition, the mounting location must be relatively cool, preferably
onebenettingfromtheenginefanstream(ifany);theoutsidecase
temperature of the CD200 unit should not exceed 185°F. (85°C.) in
continuous operation.
2.2
Secure the CD200 unit to a suitable mounting bracket with four 1/4
inch (6 mm) screws. Refer to FIG. 1 or FIG. 2 for CD200 unit dimen-
sions.
3.0 PICKUP SENSOR – CAMSHAFT DISC
3.1
A disc with the appropriate hole pattern must be prepared for
mounting at CAMSHAFT speed. The disc must be of magnetic ma-
terial and 4.0" (100 mm) diameter or larger. FIG. 4 details the hole
spacing depending on the number of engine cylinders. Note the di-
rection of rotation of the disc. The angular spacing is extremely im-
portant as this establishes the basic timing accuracy of the system.
3.2
Locate a suitable mounting position for the pickup sensor in order
to sense the holes in the rotating disc. Secure the pickup to a rigid
bracket or surface. See FIG. 4 for the dimensions of the 3/4"-16 pick-
up sensors.
3.3
Set the engine with no. 1 cylinder in the most advanced timing posi-
tion. Noting the direction of rotation, set the drilled disc opposite
the pickup in the position shown in FIG. 4.
3.4
Adjust the tightening nut holding the pickup sensor to maintain an
airgapasspeciedbelow:
•For magnetic pickups 791015-1 and 791016-2, the gap shall be
set to .020" ± .005" (0.50 mm ± 0.12 mm).
•For magnetic pickups 791035-2 and 791041-3 (12 mm thread),
the gap shall be set to .014" ± .004" (0.35 mm ± 0.10 mm).
The center of the pickup face must line up with the center of each
drilled hole as the disc rotates.
3.5
Plug the 2-pin pickup connector fully into the mating connector of
the CD200 wiring harness.
NOTE: Keep the pickup
sensor wires at least 2"
(50 mm) away from the coil
primary wires and at least
8" (200 mm) away from the
spark plug leads.
NOTE: Some MAN engines
have a 12 mm thread port;
use Altronic pickup 791035-2
or 791041-3.

www.altronicinc.com 3
ALTRONIC CD200 IGNITION SYSTEM
4.0 IGNITION COILS
4.1
USE ONLY THE ALTRONIC COILS INDICATED HERE:
•UNSHIELDED: 501061, 591010, 591040
•FLANGE: 591012, 591018
•SHIELDED: 501061-S, 591010-S
•INTEGRAL: 591007, 591011A, 591011B
4.2
Mount the ignition coils as close to the spark plugs as possible keep-
ing the high-tension lead length to a minimum but also keeping
temperatures below 200°F. (95°C.) during operation.
5.0 PRIMARY WIRING
5.1
The CD200 system requires a battery or other DC power source
providing 12-28 Vdc for running and a minimum of 8 volts for en-
gine starting. Refer to FIG. 3 for details of the connection to the DC
power source.
5.2
Primary wiring hookup is shown in the wiring diagrams – FIGS. 5
THROUGH 11.
Usethetablesbelowtorecordtheactualringorderandwiring.
791070-6, 791070-8* A B C D E F H* K*
ENGINE CYL. NO.
791080-6, 791080-8* A B C D E F H* I*
ENGINE CYL. NO.
791070-12 A1 A2 B1 B2 C1 C2 D1 D2 E1 E2 F1 F2
ENGINE CYL. NO.
The common coil ground lead on -6 and -8 units is the J harness
lead. On -12 units, the common coil ground leads are J1 and H2.
WIRING DIAGRAMS:
FIG. 5 — 4-CYLINDER
FIG. 6 — 6-CYLINDER
FIG. 7 — 8-CYLINDER
FIGS. 8–11 — 12-CYLINDER
NOTE: With unit 791070-12,
follow FIG. 10 if the rst
engine ring angle is 60
degrees or less (for example,
30°–90°). Use FIG. 11 if the
rst engine ring angle is
greater than 60 degrees
(for example, 90°–30°).
See section 9.20 for pro-
gramming the slave ring
angle with unit 791070-12.
THE HOOKUP SHOWN IS FOR THE MOST COMMON ENGINE
FIRING ORDER. CONNECT TO THE IGNITION COILS ACCORD-
ING TO THE ACTUAL ENGINE FIRING ORDER.
WARNING:

FORM CD200 II 5-07
4
INSTALLATION INSTRUCTIONS
5.3
All connections at unshielded coils should be made using ring-type
terminalsspeciedfor16AWG (1.5 sq.mm)wireand#10(5mm)
stud size. Terminals should either be soldered to the wire or at-
tached with an appropriate staking tool. Protect primary wiring
from physical damage, vibration and temperatures in excess of
200°F. (95°C.).
5.4
For details of the hookup for the analog timing signal, see FIG. 12.
5.5
Be sure the multi-pin harness connectors are fully plugged into the
mating receptacles connected to the CD200 unit.
6.0 SHUTDOWN WIRING
6.1
The CD200 system is shut-off by interrupting the DC power to the
unit; use a switch or relay with contacts rated 24 VDC, 10 amps -
refer to FIG. 3.
6.2
TheCD200canalsobeshutdownbyusingtheG-leadoftheoutput
harness. To shutdown the unit, connect the G-lead of the output
harness to ground. The CD200 will draw about 0.1 ampere from the
power source when shutdown.
7.0 SECONDARY WIRING
7.1
Withunshieldedcoils,sparkplugleadsshouldbefabricatedfrom
7 mm, silicone insulated, ignition cable with suitable terminals and
silicone spark plug boot.
7.2
Keep spark plug leads as short as possible and at least 2 inches (50 mm)
away from any grounded engine part. In deep spark plug wells, use
rigid, insulated extenders projecting out of the well.
7.3
Theuseofaclear,siliconegrease(suchasDowCorningDC-4,G.E.
G-623orGCElectronicsZ5)isrecommendedforallhigh-tension
connections and boots. This material helps seal out moisture and
prevent corrosion from atmospheric sources.
NOTE: Keep the primary
wiring at least 2" (50 mm)
away from the spark plug
leads.
NOTE: The use of resistance
spark plug cable or individual
5,000 ohm resistors (mount-
ed either at the spark plug or
coil) is recommended.
NOTE: Do NOT run the input
power line through a series
of normally closed switches.
NOTE: The CD200 should not
be used to power ignition-
powered panel instruments.

www.altronicinc.com 5
ALTRONIC CD200 IGNITION SYSTEM
8.0 OPERATION
8.1
IGNITION DELAY:
On cranking, there will be a delay of two disc revolutions—after the
power is ON and the engine begins rotating—before the CD200 unit
commences outputs to the ignition coils. This delay is to allow iden-
ticationofthepick-upindexholetoinsurepropersynchronization
with the engine. A greater delay of more revolutions to allow for
engine purging can be added to the programming. See section 9.9.
8.2
MANUAL TIMING SWITCH:
TheCD200unithasaTIMINGswitchlocatedunderawhiteplastic
cap at the end of the case. Using a timing light, set the timing to
thedesiredpositionwiththeenginerunningatNORMALOPER-
ATINGSPEED.Replacethewhitecapoverthetimingswitchonce
the proper timing is set. Switch position 7 gives the most advanced
timing. The timing retards approximately one (1) engine degree for
each switch position as the switch is moved to position 6, 5, 4, 3,
2, 1, 0. Switch position 0 is full retard. Larger timing changes per
switch position can be programmed. See section 9.14.
8.3
ANALOG TIMING ADJUSTMENT:
The CD200 unit provides for analog timing adjustment in two ways:
•0-1,000ohmpotentiometerconnectedbetweenterminalsE
and F of the input harness.
• 4-20mAsignalappliedtoleadsFandGoftheinputharness.
8.4
RPM BASED TIMING CURVE:
The CD200 unit is shipped with an RPM-based timing curve (de-
fault programming) providing a 6-degree advance as the engine
speed increases from 0 to 600 RPM (FIG. 12). This timing change is
in addition to changes made with the manual switch (section 8.2) or
the analog timing input (section 8.3).
NOTE: On the rst start-up
after system installation,
verify correct ignition timing
by cranking the engine with
the fuel supply shut off.
NOTE: DO NOT switch from
position 7 to 0, or 0 to 7
while the engine is running.
The large timing change may
cause the engine to shut-
down or be damaged.
NOTE: The analog timing
retard is added to the retard
established by the manual
timing switch (see section
8.2 above and FIG.12).
NOTE: When checked at
different speeds, timing will
vary in accordance with the
programmed RPM curve
indicated.

FORM CD200 II 5-07
6
INSTALLATION INSTRUCTIONS
9.0 CUSTOMIZING THE CD200 UNIT
9.1
TERMINAL PROGRAM SETUP:
The CD200 is designed to be programmed by a Personal Computer
via the RS-485 Modbus communications link. See FIG. 13 for the
proper hookup. The CD200 unit case must be securely grounded
prior to programming.
The Terminal Program is included on the CD-ROM supplied with
eachCD200unit.Thersttimethattheterminalsoftwareisused
onaPC,theCommunicationsPortsettingsmustbeconguredin
order to establish communications. After loading the Terminal Pro-
gram from the CD-ROM, click on the Connection icon on the upper
tool bar. The Connection Setup window will appear. The port being
selected for use with the CD200 should also be set for 9600 baud,
no parity, 200 ms time out (8 data bits and 1 stop bit). The PC will
now be set to communicate with the CD200. Set the ID# for the
CD200 to 01.
9.2
PROGRAMMING CUSTOM VALUES:
A variety of numeric parameters can be entered by the user for cus-
tomized applications or the unit can be left at the factory default
settings. Changes to numeric values are made by placing the cursor
intheappropriateboxandtypinginthenewvalue.Whenthenew
numericvalueisrsttyped,itappearsinredtextonthePCscreen.
The values appearing in red have not yet been sent to the CD200
unit, but are being stored on the PC until being sent. Hitting the
EnterkeysendstheselectiontotheCD200.Theenteredvalueturns
green on the PC display, indicating that the new value has been suc-
cessfully communicated to the CD200 and stored.
9.3
SELECTING OPTIONAL FEATURES:
Other OFF/ON programming selections are made by activating or de-
activatingabluestatusagonthePCscreen.Whenthemousepoint-
erislocatedoverthestatusag,adouble-leftclickactivatesthestatus
agandmakesitappeartobe“ON”orglowingonthePCscreen,a
double-rightclickdeactivatesthefeatureandthestatusag.
9.4
DISC TYPE SETTING:
Thisnumericentry congures the DiscType (number ofholes or
protrusions) on the timing disc, excluding the index. This number is
normally equal to the number of cylinders on the engine for a cam-
shaft mounted disc and ½ the number of cylinders of the engine for
a crankshaft mounted disc. This value is used to test for the correct
disc and scales the rpm measurement and ignition timing angles to
thespecicdiscchosen.Defaultsetting=(0+1).
Entering a value of Zero (0+1), places the ignition in auto detect
mode. In auto detect mode, the ignition will automatically scale
rpm measurement and ignition timing angles to the disc pattern
observed.
NOTE: In order to program the
values, the CD200 must be
powered. Care should be tak-
en in changing entries when
the engine is operational to
avoid unstable or dangerous
operating conditions.
NOTE: Refer to sections 9.19
and 9.20 for additional pro-
gramming of unit 791070-12.
TERMINAL PROGRAM
SCREENS:
FIG. 14 — 7910X0-6, -8
FIG. 15 — 791070-12

www.altronicinc.com 7
ALTRONIC CD200 IGNITION SYSTEM
9.5
TEST DISC FLAG:
WhenthisstatusagisON,theCD200willtestforamatchofthein-
coming signal pattern observed by the CD200 to the Disc Type speci-
ed.Whenenabled,thistestisperformedaftersynchronizationto
thediscpatternandbeforeinitiatingrings.Whenthepatterndoes
not match the setting, the ignition will not re and the diagnostic
LED on the unit will signal the error by turning off until rotation
stops.Oncetheignitionisring,thediscpatternwillbemonitored
continuouslyand,ifanerrorisdetected,theunitwillstopringand
the alarm output switch will open. Firings will be inhibited and the
output switch will remain off for 5 seconds after input signals cease.
Iftheshutdownleadisgroundedaftertheunitisring,therings
will stop, the output switch will open and remain open for 5 seconds
after rotation stops.
ThediagnosticLEDontheunitwillturnoffuntilrotationstops.Af-
ter rotation stops it will blink the appropriate signal, see section 11.2.
Defaultsetting=OFF.
9.6
ON CRANK FLAG:
WhenthisstatusagisON,theignitionscalesrpmmeasurement
and timing angles for a signal pattern coming from a crankshaft-
mounteddisc.WhenthisstatusagisOFF,theignitionscalesrpm
measurement and timing angles for a signal pattern from a cam-
shaftmounteddisc.Defaultsetting=OFF.
9.7
LINE UP ANGLE:
This numeric entry has no impact on actual engine timing and is
only used as a reference to calculate the spark timing number for
displayintheTerminalSoftware.Whenthepickupisalignedwith
therstholeorprotrusiononthetimingdisc,theLineUpAngleis
the angular position of the crankshaft with respect to TDC of the
rstcylinderintheringorder.Entryrangeis0to100enginede-
greesBTDC.Thisvaluewillneedtobene-tunedtoprovideanac-
curatedisplayoftiming.Defaultsetting=40.0degreesBTDC.
9.8
INSERTION RETARD SETTING:
Thisnumericentrycongurestheminimuminternalelectronicin-
putsignaldelay.Entryrangeis2.0to25.5degreesofengineretard.
Defaultsetting=2.0degrees.
9.9
PURGE DELAY SETTING:
Thisnumericentryconguresthenumberofdiscrotations(engine
cycles) following successful synchronization to delay before ignition
outputsbegin.Entryrangeis0to255cycles.Defaultsetting=0.
9.10
OVERSPEED SETTING:
Thisnumericentrycongurestheenginerpmatwhichtheignition
willstopringoutputsduetoanoverspeedcondition.Theoverspeed
conditionalsoturnsoffthealarmoutputswitch.Whenrotationhas
fullystopped,theLEDontheCD200unitwillblinktheappropriate
code and the alarm output switch is restored to normal (closed). De-
faultsetting=2200RPM.
NOTE: The disc test for a
specic number of pulses is
not performed in auto detec-
tion mode (0 entry for Disc
Type Setting – section 9.4).

FORM CD200 II 5-07
8
INSTALLATION INSTRUCTIONS
9.11
RUN SPEED SETTING:
Thisnumericentryconguresthetransitionspeedfromcranktorun.
ThissettingalsodeterminesthetransitionofthediagnosticLEDon
theCD200fromcranktorunmodes.Defaultsetting=500RPM.
9.12
LOW VOLTAGE SETTING:
Thisnumericentryconguresthethresholdforthelowvoltagedi-
agnostic of the DC input voltage to the CD200. If the DC voltage de-
creasestothissetting,thediagnosticLEDontheCD200willblink
theappropriatecode.TheCD200willcontinuetotrytoreoutputs
regardlessofthevoltage.Defaultsetting=6volts.
9.13
ENABLE LED DIAGNOSTICS FLAG:
WhenthisLEDstatusagisactivated,theblinkcodediagnosticsfor
primary and secondary outputs are enabled. Default setting is ON.
9.14
SWITCH CAL:
Thesenumericentriescongurethetimingretardforeachposition
ofthemanualtimingswitchontheCD200case.Entryrangeis0to
25.5 degrees of engine retard. The active entry is indicated in blue.
Default setting is 7-6-5-4-3-2-1. If two degrees change per switch
position is desired, enter 14-12-10-8-6-4-2.
9.15
LOOP CAL:
Thesenumericentriesconguretheinterpolatedlookuptablefor
the ignition retard versus the analog current loop input signal. This
allows the operator to create custom spark timing maps versus the
currentloopinputsignal.Entryrangeis0to25.5degreesofengine
retard. The active entries are indicated in blue. Default sequence is
0 degrees retard at 4 mA, 16 degrees retard at 20 mA.
9.16
RPM CAL:
Thesenumericentriesconguretheinterpolatedlookuptablefor
retard versus the engine speed. This allows the operator to create
customsparktimingmapsversusenginerpm.Entryrangeis0to
25.5 degrees of engine retard. The active entries are indicated in
blue. Default sequence is 6 degrees retard at 0 RPM, decreasing to
0 degrees retard at 600 RPM.
9.17
CYLINDER CAL:
These numeric entries congure the amount of individual offset
timing retard added to the global timing for each individual output.
This feature can be used to map an evenly spaced timing disc to an
oddringangleenginepattern.Entryrangeis0to50degreesof
engine retard. Default settings are 0. Contact the factory for further
details of this feature.

www.altronicinc.com 9
ALTRONIC CD200 IGNITION SYSTEM
9.18
ENERGY FLAGS:
Select one of four output energy settings for the CD200:
Bit 1 OFF Bit 0 OFF Vcap = 150 volts
Bit 1 OFF Bit 0 ON Vcap = 160 volts
Bit 1 ON Bit 0 OFF Vcap = 170 volts
Bit 1 ON Bit 0 ON Vcap = 180 volts
Default setting is 160 volts at the capacitor. This voltage can only be
measured using a device with an input impedance of 1 megaohm or
higher with no other device connected.
9.19
UNIT 791070-12 – ENABLE SLAVE FIRING FLAG:
WhenthisLEDstatusagisactivated,theignitionwillgeneratea
secondslaveringforeach(x+1) referencepulse.Fora(6+1)disc
pattern,theignitionwillre12outputswhenthisagisactivated,
and6outputswhenthisagisnotactivated.Modicationofthis
ag through the Terminal Program requires that the engine be
stoppedandtheG-leadbegrounded.
9.20
UNIT 791070-12 – SLAVE FIRING ANGLE SETTING:
Thisnumericentrycongurestheangleoftheslaveringrelative
tothestandardringsthataregeneratedforeach(x+1)reference
pulse.Entryrangeis25.0°to60.0°whichisusedtosettheslaver-
ing angle on a 12-cylinder, 4-cycle engine. The slave angle must be
thesmallerofthetwoanglesthatdenetheengineringpattern.
For example, ring patterns of either 30°–90° or 90°–30° would
requiretheslaveanglebeenteredas“30”.Modicationofthisvalue
through the Terminal Program requires that the engine be stopped
andtheG1leadbegrounded.
The following patterns are applications suitable for unit 791070-12:
ENGINE SECT. 9.4 SECT. 9.20
NO. FIRING DISC SLAVE WIRING
CYLS. ANGLE SETTING ANGLE DIAGRAM
8 60°–120° 4+1 60° FIG. 10
8 120°–60° 4+1 60° FIG. 11
10 54°–90° 5+1 54° FIG. 10
10 90°–54° 5+1 54° FIG. 11
12 30°–90° 6+1 30° FIG. 10
12 40°–80° 6+1 40° FIG. 10
12 50°–70° 6+1 50° FIG. 10
12 55°–65° 6+1 55° FIG. 10
12 60°–EVEN 6+1 60° FIG. 10
12 75°–45° 6+1 45° FIG. 11
12 90°–30° 6+1 30° FIG. 11

FORM CD200 II 5-07
10
INSTALLATION INSTRUCTIONS
10.0
PC TERMINAL DISPLAY FUNCTIONS
10.1
ENGINE SPEED:
Indicates current speed of the engine in RPM based on disc signal.
10.2
SPARK TIMING:
Indicates the global spark timing of the engine in degrees before
TDC.ThisnumberistheLINEUPANGLEsettinglesstheTOTAL
RETARD.Slightdifferencesbetweenthisnumberandthetiming
readingobtainedwithatiminglightmayoccursincetheLINEUP
ANGLEenteredmaydifferslightlyfromtheactualangularposition
of the engine when the input pulse event is received by the CD200.
In this event, the Spark Timing number should be made to agree
withthetiminglightbychangingtheLINEUPANGLEentry.
10.3
SWITCH POSITION:
Indicates the current position of the manual timing switch on the
CD200 case.
10.4
LOOP INPUT:
Indicates the value of the external input current loop.
10.5
OBSERVED DISC:
Indicates the number of input events (timing holes or protrusions)
being recognized by the CD200 unit on the timing disc input signal
at this time.
10.6
INSERTION RETARD:
Indicates the amount of electronic insertion retard at this time.
10.7
SWITCH RETARD:
Indicates the amount of timing retard being added by the current
timing switch position at this time.
10.8
LOOP RETARD:
Indicates the actual amount of timing retard added from the cur-
rent loop versus retard lookup table curve at this time.
10.9
RPM RETARD:
Indicates the actual amount of timing retard being added by the
RPM versus retard lookup table curve at this time.
10.10
TOTAL RETARD:
Indicates the total global timing retard at this time. This number is
the sum of the Insertion Retard, Switch Retard, Loop Retard and
RPM Retard.
10.11
COUNTER:
Indicates the number of disc rotations (engine cycles) registered
since the engine was last started.

www.altronicinc.com 11
ALTRONIC CD200 IGNITION SYSTEM
10.12
PURGE COUNTER:
During a startup, indicates the number of purge cycles remaining
before the outputs are activated.
10.13
SUPPLY VOLTAGE:
Indicates the measured DC voltage supply level to the CD200.
10.14
SPARK REF. (A, B, C, ETC.):
Indicates the current spark reference number for each cylinder.
10.15
SYNCING:
Whenred,indicatesthatenginerotationhasbeensensedandthe
synchronization process is taking place.
10.16
INSYNC1:
Whenred,indicatesthattheindexinputhasbeenrecognizedonce.
10.17
INSYNC2:
Whenred, indicatesthattheindexhasbeenrecognizeda second
time and the ignition is ready to proceed.
10.18
PURGING:
Whenred,indicatesthatsynchronizationhasbeencompletedand
the purge cycle countdown is taking place.
10.19
TRYING:
Whenred,indicatesthattheCD200istryingtoreoutputs,buta
proper primary discharge event has not yet occurred.
10.20
FIRING:
Whenred,indicatesthatCD200issuccessfullyringprimaryoutputs.
10.21
LOCKOUT:
Whenred,indicatesthatringsarelockedoutuntilenginerotation
has ceased for a minimum of 5 seconds.
10.22
CRANKING:
Whenred,indicatesenginerotationbelowtheRunSpeedsetting.
10.23
RUNNING:
Whenred,indicatesenginerotationabovetheRunSpeedsetting.
10.24
DISC ERROR:
Whenred,indicatesthattheTestDiscstatusagisactivatedand
thetimingdiscpatternbeingsenseddidnotmatchtheDISCTYPE
selected.
10.25
G-LEAD:
Whenred,indicatesthattheG-leadisgrounded.
10.26
REMOTE:
Whenred,indicatesaremoteserialshutdowncommandisactive.

FORM CD200 II 5-07
12
INSTALLATION INSTRUCTIONS
10.27
SD-LEAD:
Whenred,indicatesthatashutdownhasoccurredwhichwasthe
resultofagroundedG-leadcondition.
10.28
SD-REMOTE:
Whenred,indicatesthatashutdownhasoccurredasaresultofa
remote serial shutdown command.
10.29
SD-OVERSPEED:
Whenred,indicatesthatashutdownhasoccurredasaresultofthe
engine reaching the Overspeed setting.
10.30
WDOG1:
When red, indicates that the microprocessor has re-booted since
the ignition has been powered-up.
10.31
WDOG2:
Whenred,indicatesthatthemicroprocessoriscurrentlyre-boot-
ing.Disregardtherstblinkwhenrstconnecting.
10.32
CHKSUM:
Whenred,indicatesamicroprocessorchecksumerror.
10.33
LOW VOLT:
Whenred,indicatesthattheinputDCvoltageisatorbelowtheLow
Voltage setting input.
10.34
NO CHARGE:
Whenred,indicatesthattheprimarystoragecapacitorhasfailedto
charge properly within the last ~2 seconds.
10.35
PRIMARY OPEN:
Whenred,indicatesthatanopenprimaryconditionhasbeende-
tected within the last ~2 seconds.
10.36
PRIMARY SHORT:
Whenred,indicatesthatashortedprimaryconditionhasbeende-
tected within the last ~2 seconds.
10.37
SECONDARY OPEN:
Whenred,indicatesthatanopensecondaryconditionhasbeende-
tected within the last ~2 seconds.
10.38
CRANKS LOG:
Indicates the total number of crank attempts seen by the CD200.
10.39
STARTS LOG:
Indicates the total number of successful starts seen by the CD200
asdenedbytheRunSpeedsettinginput.
10.40
CYCLE LOG:
Total number of engine cycles seen by the CD200.

www.altronicinc.com 13
ALTRONIC CD200 IGNITION SYSTEM
10.41
COLD BOOT LOG:
Indicates the number of times the input DC voltage has been
cycled to zero.
10.42
WARM BOOT LOG:
Indicates the number of times the microprocessor has restarted
without a complete loss of power.
10.43
GRAPHIC DISPLAY:
The CD200 Terminal Software provides a real time graphic display
of the secondary diagnostic numbers, global engine timing
(y-axis/10) and engine speed (y-axis x 10).
11.0 CD200 UNIT LED DIAGNOSTIC BLINK CODES
11.1
CD200 IGNITION BLINK CODES:
WhenevertheLEDDiagsstatusagisenabled(blue)byusingthe
CD200TerminalSoftware,theblinkingpatternoftheLEDonthe
side of the CD200 case can be used to interpret the general status
of the CD200 diagnostics without the use of the Terminal Software.
Withineachgroupofconditionsdescribedbelow,thepossibledi-
agnostic states are listed according to their number of blinks. The
LEDisONforabout2secondsbetweeneachblinksequenceand
the blinks occur evenly spaced at a faster rate.
11.2
LED SIGNALS WITH THE ENGINE STOPPED:
ON – STEADY = READY (NEW POWER UP OR LAST START ATTEMPT ABORTED)
ON – 1 BLINK – ON = FIRED LAST TIME ROTATING (STOPPED DUE TO STALL)
ON – 2 BLINK – ON = SHUTDOWN (BY GROUNDING G-LEAD WHEN RUNNING)
ON – 3 BLINK – ON = SHUTDOWN (BY REMOTE SERIAL REqUEST WHEN RUNNING)
ON – 4 BLINK – ON = SHUTDOWN (BY OVERSPEED WHEN RUNNING)
ON – 5 BLINK – ON = WRONG DISK PATTERN
ON – 6 BLINK – ON = LOW SUPPLY VOLTAGE (BELOW THRESHOLD WHEN RUNNING)
11.3
LED SIGNALS WITH ENGINE CRANKING:
Rotating, and still below running RPM.
ON/OFF/ON/OFF = PURGING (offfirstinputpulse,toggleseachrevolutionofpurge)
ON– STEADY = FIRING NORMALLY (RPM below running set point value)
OFF = WRONG DISC PATTERN DETECTED
11.4
LED SIGNALS WITH ENGINE RUNNING:
Whenring,andaboverunspeed.
ON – STEADY = FIRING NORMALLY (NO DIAGNOSTICS TO REPORT)
ON – 1 BLINK – ON = OPEN SECONDARY ALARM
ON – 2 BLINK – ON = PRIMARY SHORT ALARM
ON – 3 BLINK – ON = PRIMARY OPEN ALARM
ON – 4 BLINK – ON = NO CHARGE ALARM
ON – 6 BLINK – ON = LOW SUPPLY VOLTAGE

FORM CD200 II 5-07
14
INSTALLATION INSTRUCTIONS
13.0 RS-485 COMMUNICATIONS, MODBUS RTU
13.1
The CD200 is compliant to the Modicon Modbus RTU standard.
Maximum number of registers that can be read at one time is limit-
ed to 32. Maximum number of booleans that can be read at one time
is limited to 256. All communications are 8 data bits, no parity, 1
stop bit. The baud rate is 9600. The MODBUS address list follows:
13.2
24 READ-ONLY STATUS BITS
READABLE IN MULTIPLES OF 8 BITS
STARTING AT 8-BIT BOUNDARIES
ADDRESS FUNCTION
10001 Syncing
10002 InSync1
10003 InSync2
10004 Purging
10005 Trying
10006 Firing
10007 LockOut
10008 FIRED
10009 Cranking
10010 Running
10011 Wrong Disk
10012 GLead Shutdown Grounded
10013 Remote Shutdown Present
10014 GLead Shutdown Logged
10015 Remote Shutdown Logged
10016 Overspeed Shutdown Logged
10017 WDOG1 Reset Latched
10018 WDOG2 Reset Event
10019 CheckSum Error
10020 LOW Supply Voltage
10021 No Charge
10022 Open Primary
10023 Shorted Primary
10024 Open Secondary

www.altronicinc.com 15
ALTRONIC CD200 IGNITION SYSTEM
13.3
READ ONLY STATUS REGISTERS
ADDRESS FUNCTION
30001 Input Bit Mirror 10016–10001
30002 Input Bit Mirror 10032–10017
30003 Input Bit Mirror 10048–10033
30004 Input Bit Mirror 10064–10049
30005 RPM
30006 Timing xxx.xDEG signed
30007 Switch Position 1–8
30008 Current Loop Input xx.xmA
30009 Disk Observed X+1
30010 Insertion Retard xxx.xDeg
30011 Switch Retard xxx.xDeg
30012 Loop Retard xxx.xDeg
30013 RPM Retard xxx.xDeg
30014 Total Retard xxx.xDeg
30015 Cycle Counter HI
30016 Cycle Counter LO
30017 Supply Voltage xx.xVolts
30018 Spark Ref. Num. Output 1
30019 Spark Ref. Num. Output 2
30020 Spark Ref. Num. Output 3
30021 Spark Ref. Num. Output 4
30022 Spark Ref. Num. Output 5
30023 Spark Ref. Num. Output 6
30024 Spark Ref. Num. Output 7
30025 Spark Ref. Num. Output 8
30026 Spark Ref. Num. Output 9
30027 Spark Ref. Num. Output A
30028 Spark Ref. Num. Output B
30029 Spark Ref. Num. Output C
30034 Purge Delay Index Down Counter
30035 Distributor MUX code 0–15
30036 KEYCOMMAND
30037 Period Predivider
30038 Period MS16BITS
30039 Period LS16BITS
30040 FireStat:DelayStat

FORM CD200 II 5-07
16
INSTALLATION INSTRUCTIONS
13.4
8 READ/WRITE CONFIGURATION BITS
SUPPORTS WRITE SINGLE ONLY
READABLE IN MULTIPLES OF 8 BITS
STARTING AT 8BIT BOUNDARIES
ADDRESS FUNCTION
00001 DISK ON CAM=0 CRANK=1
00002 TEST FOR PROPER DISK YES=1
00003 ENABLE SECONDARY DIAGS YES=1
00004 ENERGY BIT0 00=~160 01=~170
00005 ENERGY BIT1 10=~180 11=~190
00006 SLAVE
00007 reserved
00008 reserved
13.5
4 READ/WRITE REGISTERS MIRROR COIL BITS
ADDRESS FUNCTION
40001 REG40001=CoilBits 00016-00001
40002 REG40002=CoilBits 00032-00017
40003 REG40003=CoilBits 00048-00033
40004 REG40004=CoilBits 00064-00049
13.6
8 READ/WRITE REGISTERS REGARDING APPLICATION
ADDRESS FUNCTION
40005 Disk+1 2,3,4,5,6,7,8,9,10,12
40006 Disk Lineup to TDC xx.x DEG
40007 Insertion Ret MIN=2.0 DEG xx.x
40008 Purge Delay Cycles 0-255
40009 RPM Over Speed Setpoint
40010 RPM Crank to Run Threshold
40011 Low Supply Voltage Limit xx.xV
40012 SLAVE ANGLE xx.x DEG

www.altronicinc.com 17
ALTRONIC CD200 IGNITION SYSTEM
13.7
12 READ/WRITE REGISTERS FOR CYLINDER RET. TABLE
ADDRESS FUNCTION
40017 OUTPUT 1 EXTRA RETARD DEG
40018 OUTPUT 2 EXTRA RETARD DEG
40019 OUTPUT 3 EXTRA RETARD DEG
40020 OUTPUT 4 EXTRA RETARD DEG
40021 OUTPUT 5 EXTRA RETARD DEG
40022 OUTPUT 6 EXTRA RETARD DEG
40023 OUTPUT 7 EXTRA RETARD DEG
40024 OUTPUT 8 EXTRA RETARD DEG
40025 OUTPUT 9 EXTRA RETARD DEG
40026 OUTPUT 10 EXTRA RETARD DEG
40027 OUTPUT 11 EXTRA RETARD DEG
40028 OUTPUT 12 EXTRA RETARD DEG
13.8
8 READ/WRITE REGISTERS FOR TIMING SWITCH RET. TABLE
ADDRESS FUNCTION
40033 TIMING SWITCH POS 0 DEG
40034 TIMING SWITCH POS 1 DEG
40035 TIMING SWITCH POS 2 DEG
40036 TIMING SWITCH POS 3 DEG
40037 TIMING SWITCH POS 4 DEG
40038 TIMING SWITCH POS 5 DEG
40039 TIMING SWITCH POS 6 DEG
40040 TIMING SWITCH POS 7 DEG

FORM CD200 II 5-07
18
INSTALLATION INSTRUCTIONS
13.9
21 READ/WRITE REGISTERS FOR LOOP RET. TABLE
ADDRESS FUNCTION
40049 LOOP RET MAP 0mA 0.00V DEG
40050 LOOP RET MAP 1mA 0.25V DEG
40051 LOOP RET MAP 2mA 0.50V DEG
40052 LOOP RET MAP 3mA 0.75V DEG
40053 LOOP RET MAP 4mA 1.00V DEG
40054 LOOP RET MAP 5mA 1.25V DEG
40055 LOOP RET MAP 6mA 1.50V DEG
40056 LOOP RET MAP 7mA 1.75V DEG
40057 LOOP RET MAP 8mA 2.00V DEG
40058 LOOP RET MAP 9mA 2.25V DEG
40059 LOOP RET MAP 10mA 2.50V DEG
40060 LOOP RET MAP 11mA 2.75V DEG
40061 LOOP RET MAP 12mA 3.00V DEG
40062 LOOP RET MAP 13mA 3.25V DEG
40063 LOOP RET MAP 14mA 3.50V DEG
40064 LOOP RET MAP 15mA 3.75V DEG
40065 LOOP RET MAP 16mA 4.00V DEG
40066 LOOP RET MAP 17mA 4.25V DEG
40067 LOOP RET MAP 18mA 4.50V DEG
40068 LOOP RET MAP 19mA 4.75V DEG
40069 LOOP RET MAP 20mA 5.00V DEG

www.altronicinc.com 19
ALTRONIC CD200 IGNITION SYSTEM
13.10
31 READ/WRITE REGISTERS FOR RPM RET. TABLE
ADDRESS FUNCTION
40070 RPM RET MAP 0000 RPM DEG
40071 RPM RET MAP 0100 RPM DEG
40072 RPM RET MAP 0200 RPM DEG
40073 RPM RET MAP 0300 RPM DEG
40074 RPM RET MAP 0400 RPM DEG
40075 RPM RET MAP 0500 RPM DEG
40076 RPM RET MAP 0600 RPM DEG
40077 RPM RET MAP 0700 RPM DEG
40078 RPM RET MAP 0800 RPM DEG
40079 RPM RET MAP 0900 RPM DEG
40080 RPM RET MAP 1000 RPM DEG
40081 RPM RET MAP 1100 RPM DEG
40082 RPM RET MAP 1200 RPM DEG
40083 RPM RET MAP 1300 RPM DEG
40084 RPM RET MAP 1400 RPM DEG
40085 RPM RET MAP 1500 RPM DEG
40086 RPM RET MAP 1600 RPM DEG
40087 RPM RET MAP 1700 RPM DEG
40088 RPM RET MAP 1800 RPM DEG
40089 RPM RET MAP 1900 RPM DEG
40090 RPM RET MAP 2000 RPM DEG
40091 RPM RET MAP 2100 RPM DEG
40092 RPM RET MAP 2200 RPM DEG
40093 RPM RET MAP 2300 RPM DEG
40094 RPM RET MAP 2400 RPM DEG
40095 RPM RET MAP 2500 RPM DEG
40096 RPM RET MAP 2600 RPM DEG
40097 RPM RET MAP 2700 RPM DEG
40098 RPM RET MAP 2800 RPM DEG
40099 RPM RET MAP 2900 RPM DEG
40100 RPM RET MAP 3000 RPM DEG

FORM CD200 II 5-07
20
INSTALLATION INSTRUCTIONS
13.11
7 READ/WRITE MISC. REGISTERS
ADDRESS FUNCTION
40122 Crank Counter
40123 Start Counter
40124 Cycle Counter HIGH
40125 Cycle Counter LOW
40126 REG40005 MSB=BAUD LSB=NODEID xed 9600n81:node1
40127 Cold Boot (powerup) Count
40128 Warm Boot ( reset ) Count
Table of contents
Popular Control Unit manuals by other brands

Federal Signal Corporation
Federal Signal Corporation SmartSiren Platinum Series Software manual

ABB
ABB CDPI-01 user manual

SVS
SVS LER-9 operating instructions

AWID
AWID SENTINEL-SENSE ADB-510 Installation & operation manual

HYDRO-RAIN
HYDRO-RAIN HRP-100 Instructions for operation

Sanela
Sanela SLS 02PT Instructions for use

Hewalex
Hewalex CKF 3325 installation manual

Kemper
Kemper ETA-THERM 130 Installation and operating manual

Microchip Technology
Microchip Technology dsPICDEM MC1H user guide

Beko
Beko BEKOMAT 13 CO Instructions for installation and operation

Versum Materials
Versum Materials GASGUARD AP11 BSGS eV Asia Installation, operation & maintenance manual

Viessmann
Viessmann 5205 Operation manual