ACM8/CB Sub-Assembly - 3 -
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only and should be installed by qualified personnel.
1. Refer to Sub-Assembly Installation Instruction for mounting Rev. MS050913.
Carefully review:
Typical Application Diagram (pg. 4) Terminal Identification Table (pg. 5)
LED Diagnostics (pg. 5) Hook-up Diagrams (pg. 6)
2. Power supply input:
The units can be powered with one (1) power supply which will provide power for both board operation and the locking devices
or two (2) separate power supplies, one (1) to provide power for the board operation and the other to provide power for the
locking devices and/or access control hardware.
Note: The input power can be 12 to 24 volts DC (0.5A @ 12 volt, 0.3A @ 24 volt current consumption with all relays energized).
(a) Single power supply input:
If the unit and the locking devices are to be powered using a single power supply, connect the output
(12 to 24 volts DC) to the terminals marked [- Power +].
(b) Dual power supply inputs (Fig. 1c, pg. 4):
When the use of two power supplies is desired, jumpers J1 and J2 (located to the left of the power/control terminals) must
be cut. Connect power for the unit to the terminals marked [- Power +] and connect power for the locking devices to the
terminals marked [- Control +].
Note: When using DC power supplies polarity must be observed. When using AC power supplies polarity needs not to be
observed (Fig. 1d, pg. 4).
Note: For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories.
3. Output options (Fig. 1, pg. 4):
The ACM8 will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any combination of both
switched power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.
The ACM8CB will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM].
For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC].
For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Form “C” outputs:
When form “C” outputs are desired the corresponding output fuse (1-8) must be removed (ACM8 only). Connect negative (-)
of the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal marked [C].
For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked [NC].
For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].
(c) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device
being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
4. Input trigger options (Fig. 1, pg. 4):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the
terminal marked [GND].
5. Fire Alarm Interface options (Figs. 3 through 7, pg. 6):
A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will
trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch [SW1-SW8] OFF.
To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] ON.
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 4, pg. 6). For latching hook-up (Fig. 5, pg. 6).
(b) Normally Closed [NC] input:
For non-latching hook-up (Fig. 6, pg. 6). For latching hook-up (Fig. 7, pg. 6).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -].
Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition).
Jumper located next to TRG LED must be cut (Fig. 1a, pg. 4).
6. FACP Dry form “C” output (Fig. 1b, pg. 4):
Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] FACP for normally
open output or the terminals marked [NC] and [C] FACP for normally closed output.
Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies as indicated in the
installation manuals for the power supply.