Salus WT100 Specification sheet

WEATHER CONTROLLER
WT100
FOR CONTROL TEMPERATURE HEATING CIRCUIT
OPERATIONS AND INSTALLATION MANUAL
VERSION: 1.4
SOFTWARE VERSION:
v01.XX.XX
03-2018

2

3
TABLE OF CONTENTS
SAFETY INFORMATION……………………………………..4
GENERAL INFORMATION…………………………………. 5
INFORMATION ABOUT DOCUMENTATION………. 5
DOCUMENTATION STORAGE…………………………….5
USED SYMBOLS…………………………………………………5
WEEE DIRECTIVE 2012/19/UE…………………………..5
OPERATING THE REGULATOR………………………….. 8
DESCRIPTION OF DISPLAY MAIN WINDOW………………..8
CONTROLLER OPERATION…………………………………….8
USER’S MAIN MENU………………………………………… 9
WORK MODE…………………………………………………… 9
SCHEDULE………………………………………………………. 9
SUMMER/WINTER FUNCTION…………………………….10
GENERAL SETTINGS…………………………………………. 10
INFORMATION……………………………………………….. 10
ADDITIONAL FUNCTIONS……………………………………10
HYDRAULIC SCHEMES……………………………………..12
SCHEME 1…………………………………………………….. 12
SCHEME 2…………………………………………………….. 13
SCHEME 3…………………………………………………….. 14
INSTALLATION OF THE CONTROLLER……………… 15
ENVIRONMENTAL CONDITIONS………………………..15
INSTALLATION REQUIREMENTS………………………..15
EXTERNAL CIRCUITS CONNECTION………………….16
CONNECTING ELECTRICAL SYSTEM………………… 17
FIXING THE EXTERNAL WIRES…………………………..17
CONNECTION OF TEMPERATURE SENSORS………….18
CONNECTING WEATHER SENSOR (EXTERNAL)………18
TEMPERATURE SENSOR CHECKING……………………19
CONNECTING A ROOM THERMOSTAT………………..19
CONNECTING A HEAT SOURCE………………………… 19
SERVICE MENU………………………………………………. 20
SERVICES SETTINGS……………………………………….. 21
HEATING CIRCUIT……………………………………….. 21
HEAT SOURCE……………………………………………..21
PROTECTION……………………………………………….22
OTHER PARAMETERS…………………………………….22
FUNCTION……………………………………………………… 23
PROMPTS…………………………………………………..23
HEATING CIRCUIT…………………………………………23
FROST PROTECTION………………………………………24
POWER STOPPAGE………………………………………. 24
PREVENTION COOLING…………………………………. 24
PUMP ANTI STANDSTILL FUNCTION…………………..25
FUSE REPLACEMENT……………………………………..25
STORAGE AND TRANSPORT CONDITIONS………. 25
TECHNICAL DATA…………………………………………… 25

4
SAFETY INFORMATION
Requirements concerning safety are
listed in particular sections of this instruction.
Apart from them it in necessary to fulfill the
following requirements.
Prior to starting the assembly, repairs or
maintenance and during the execution of
any connection works, it is necessary to
switch off the mains supply and make sure
that no terminals no electrical wires are
energized.
After deactivating the controller, terminals
of the controller can be under a dangerous
level of voltage.
The controller can be utilized only in
accordance with its intended use.
Values of programmed parameters must
be set in accordance with a particular
building and hydraulic system.
Controller can be assembled only by
qualified installer and in accordance with
currently valid standards and regulations.
The controller is not an intrinsically safe
device. It means that in case of failure it
can be a source of sparks or high
temperature which surrounded by ashes
or flammable gases can cause fire or
explosion.
Modification of the programmed
parameters should be made only by a
person who read this manual.
Use only in heat circulation system made
in accordance with currently valid
regulations.
Electrical system including the controller
should be protected with fuse selected in
accordance with used loads.
The controller cannot be used with
damaged housing.
Never make any modifications in controller
structure.
The controller has electronic disconnection
for connected devices (operation 2.B
according to PN-EN 60730-1).
Before you open casing, first disconnect
power supply from the unit.
The controller must be installed in
accordance with the requirements of EN
60335-1 standard, by qualified and
authorized technician.
Short circuit at the outputs leads to
damage to the device (not output COM-
NO).
Do not operate the unit when it is
malfunctioning or was repaired by
unauthorized persons.
Do not mount the unit on flammable
materials.

5
General information
Weather controller WT100 is designed to
control the temperature in the heating circuit
with the valve 3 or 4-way equipped with a
drive-controlled 3-point with the possibility of
connecting additional circulation pump and
control the heat source through a dry contact.
Main functions performed:
weather control - the preset temperature
heating circuit is determined on the basis
of the programmed heating curve and the
measured outside temperature,
automatic detection season heating,
work with a room thermostat
controling the heat source
implementation of the return temperature
protection (against low temperature of the
return water) - protection from boiling
water in the boiler (coal boiler) in the
short-circuit of the boiler.
The controller is equipped with a timer (clock
operation is maintained for 48 hours with the
power off the controller).
Regulator is easy to operate in an intuitive
manner. It may be used in households and
other similar premises and in light industry
facilities.
Information about documentation
The regulator manual is divided into two
parts: for user and fitter. Yet, both parts
contain important information, significant for
safety issues, hence the user should read both
parts of the manual.
We are not responsible for any damages
caused by failure to observe these
instructions.
Documentation storage
Please keep this operation and assembly
manual and other valid documentation in a
safe place for future reference. In case of
moving or selling the device, hand this
documentation over to a new user or owner.
Used symbols
The following graphical symbols are used in
the manual:
- useful information and tips,
- useful information concerning
property damage, health or life threat for
people or pets.
Caution: important information were labeled
with the aforementioned symbols in order
make the manual easier to understand.
However it does not release the user nor
installer from responsibility of complying with
requirements which are not labeled with any
symbols!
WEEE Directive 2012/19/UE
Purchased product is designed and made of
materials of highest quality.
The product meets the requirements of the
Directive 2012/19/EU of 4 July 2012 on
waste electrical and electronic
equipment (WEEE), according to which it is
marked by the symbol of crossed-out wheeled
bin (like below), meaning that product is
subjected to separate collection.
Responsibilities after finishing a period of
using product:
dispose of the packaging and product at
the end of their period of use in an
appropriate recycling facility,
do not dispose of the product with other
unsorted waste,
do not burn the product.
By adhering obligations of waste electrical and
electronic equipment controlled disposal
mentioned above, you avoid harmful effects
on the environment and human health.


REGULATOR INSTRUCTION MANUAL
WT100

8
Operating the regulator
The controller has
TOUCH&PLAY system that
facilitates its operation.
Encoder is operated by its
rotating and pressing.
To start the controller, keep
pressed encoder knob for 3
seconds. When the message
"Active regulator?" must set YES. The screen
will display the main screen. Another press
will call the main menu.
Rotate the encoder TOUCH&PLAY increases or
decreases the value
parameter being edited. It
is the element of quick
operating of the regulator.
Short press the encoder to
input the selected
parameter or approval of
the selected value.
Pressing for 3 seconds to exit the selected
parameter or do not accept the selected
value.
All controller settings are made through a
rotary system MENU. After calling up the main
menu on the screen will display a screen with
icons representing the functions of the
controller.
Description of display main window
1. Regulator working modes:
- OFF mode
- AUTO mode (work with clock)
- COMFORT mode
- ECONOMY mode
- AUTO-ECO mode
2. temperature value: preset, current and
external (weather)
3. work pump CH: ON, OFF
4. valve mixer actuator position: ON –open,
OFF –closed, STOP - off.
5. working heat source (boiler switched on)
6. information from the room thermostat:
No icon –the thermostat is off,
–Heating –room temperature below
the preset,
–No heating –room temperature
above the preset.
7. active SUMMER mode
8. active frost protection function
9. clock time and weekday.
Controller operation
Heat source:
The controller controls the operation of heat
source, e.g. an automatic gas, oil or pellet
boiler, by activating or deactivating it
according to a heat demand of the central
heating system. Switching on and switching
off the heat source may be programmed in
intervals times, in the Schedule menu.
Heating circuit:
The controller controls the operation of one
direct heating circuit (radiators or floor) with
mixing valve and circulating pump. The
control heating circuit (decrease preset
temperature) can be programmed in intervals
times, in the Schedule menu.
The method of temperature control:
Weather control - on the basis of the signal
from the external (weather) temperature
sensor is calculated water temperature in
the heating circuit. As a result, despite the
changing external temperature room
temperature in heated rooms is
maintained at a preset level.
3sek.
1
2
3
4
5
6
7
9
STOP
8
preset
current
external
THU

9
Continous control –the preset
temperature of water in the heating circuit
is constant at the set value, without the
impact of changes in external
temperature.
Preset temperature setting in
Service menu (described in the
manual).
User’s main menu
Work mode
This option is used to switch on the respective
modes of work of the controller according to
user preferences.
To change the work mode to select:
Main menu Work mode
OFF - the controller turns off the
heating circuit. The frost protection
function remains active as long as it is
enabled in the service menu.
Activating this work mode also turns
off the heat source. The heat source
is not turns off during active function
heating buffer.
Auto - preset temperature in the
room changes according to the time
program. In periods of "day" is setting
Preset temperature. In periods of "night"
is setting (Preset temperature - Decrease
of work mode).
Comfort - preset temperature in the
room is constant and corresponds to the
entered value Preset temp.
Economy - preset temperature in the
room is constant and corresponds to the
entered value temperature (Preset
temperature - Decrease of work mode).
Auto-Eco - preset temperature in the
room changes according to the time
program. In periods of "day" is set Preset
temperature. In periods of "night" heating
circuit is completely turns off. The frost
protection function remains active as long
as it is enabled in the Service menu.
Schedule
The time intervals allow the introduction of
decrease preset temperature within a
specified time period for the heating circuit
and the turns on or turns off heat source, eg.
at night or when user leave the heated rooms.
As a result, the preset temperature can be
lowered automatically without loss of heat
comfort in the room.
Activation of time intervals in:
Main menu Schedule
and select a time schedule for the heating
circuit or heat source.
Decrease night time for the heating circuit and
the work of heat sources can be defined
separately for every day of the week: Monday
- Sunday.
Select the decrease of the preset temperature
and the beginning and end of a given time
interval.
Working of decrease temperature in the time
intervals are designated as "day" - this
corresponds to the Preset temperature and
"night" - corresponds to the Decrease of
work mode.
Action at intervals for the heat source are
marked as - heat source is turned on and
- a heat source is turned off.
Main menu
Information
Work mode
OFF
Auto
Comfort
Economy
Auto-Eco
Schedule
Circuit
Heat source
Summer\Winter
SUMMER mode:
OFF, ON, Auto
Summer mode ON temp.
[range 5..35ºC, fact.20]
Summer mode OFF temp.
[range 1..22ºC, fact.18]
General settings
Clock
Screen brightness
Screen contrast
Sound
Language
Service settings

10
Example time interval.
In the example below, a “night” period will last
from 00:00 till 06:00. “day” period will last
between 06:00 –09:00. From 15:00 to 22:00
the “day” period was entered. “night” period
will last from 22:00 to 00:00.
An interval is ignored if the
decrease value is set to “0”, even if
its range of hours was specified.
Summer/Winter function
The SUMMER / WINTER function is responsible
for the automatic or manual turns on of
heating. It also allows the loading of the HUW
container in the summer, without the need to
heat the central heating system. Must set the
parameter SUMMER mode = ON, in:
Main menu Summer/Winter Summer
mode
In SUMMER mode, all heat
recipients may be OFF, therefore,
make sure the boiler will not be
overheated.
If the external temperature sensor is
connected SUMMER function can be turned on
automatically using the Auto parameter,
including temperature settings for the
Summer mode ON temp. and Summer mode
OFF temp.
General settings
In general settings, can change the settings
date, time, brightness and contrast of the
screen. Can turn on and turn off the sound,
and change the language menu for the
controller.
Information
The information menu allows to view
information temperatures and allows to see
which devices are currently enabled. By
turning the encoder TOUCH&PLAY changes
between successive windows of information.
Additional functions
Easier support for the user, eg. if turn off
support for the heat source to all the features
associated with this parameter disappear -
you can then control the heating circuit. It's
the same when you turn off the heating circuit
- be able to control the heat source with using
a heat source contact and the heat source
sensor.
There is also possible to control the heating
circuit with mixing, with optional thermostat
influence the heating circuit.

INSTALLATION MANUAL AND SERVICE SETTINGS
WT100

12
Hydraulic schemes
Scheme 1
Hydraulic scheme with of the four-way valve controlling the central heating circuit or floor circuit
1
Legend:
TP –room thermostat (NO-NC)
T1 –heating circuit temperature sensor type CT10
T2 –external temperature sensor (weather) type CT6-P
T3 –return temperature sensor type CT10
T4 –heat source temperature sensor type CT10
P –pump heating circuit
SM –four-way valve + actuator
1 –heat source with (S) ON-OFF contact (gas- or oil- boiler)
2 –relief valve different pressure.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Kind of the system
Radiators system
(Underfloor heating)
Service settings Kind of the system
Max. temperature
80ºC (45ºC)
Service settings Heating circuit
Room thermostat
ON
Service settings Room thermostat
Start pump temp.
55ºC (20ºC)
Service settings Heating circuit
Return sensor
ON
Service settings Protection
In order to improve water flow in gravitational circuit of the boiler use large nominal DN cross-
sections of pipes and the four-way valve, avoid numerous elbows and cross-section reductions, apply
other rules regarding construction of gravitational systems, e.g. keeping of gradients, etc. In case
the return temperature sensor is mounted on the pipe - provide proper heat insulation to isolate it
from the environment and improve its thermal contact with the pipe by applying of the thermal
paste. The heat source preset temperature has to be high enough to ensure enough heating power
for the heating circuits while heating the return water.
1
The presented hydraulic diagram does not replace central heating engineering design and may be used for
information purposes only!

13
Scheme 2
Hydraulic scheme of the three-way valve controlling the central heating circuit (with a hydraulic
coupling)
2
Legend:
TP –room thermostat (NO-NC)
T1 –heating circuit temperature sensor type CT10
T2 –external temperature sensor (weather) type CT6-P
T4 –hydraulic coupling temperature sensor type CT10
P –pump heating circuit
SM –three-way valve + actuator
1 –heat source with (S) ON-OFF contact (gas- or oil- boiler)
2 –relief valve different pressure
3 –hydraulic coupling.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Kind of the system
Radiators system
Service settings Kind of the system
Max. temperature
80ºC
Service settings Heating circuit
Room thermostat
ON
Service settings Room thermostat
Start pump temp.
55ºC
Service settings Heating circuit
Cooling temp.
92ºC
Service settings Heat source
2
The presented hydraulic diagram does not replace central heating engineering design and may be used for
information purposes only!

14
Scheme 3
Hydraulic diagram of the three-way valve controlling circuit underfloor heating (with a hydraulic
coupling)
3
Legend:
TP –room thermostat (NO-NC)
T1 –heating circuit temperature sensor type CT10
T2 –external temperature sensor (weather) type CT6-P
T4 –hydraulic coupling temperature sensor type CT10
P –pump heating circuit
SM –three-way valve + actuator
1 –heat source with (S) ON-OFF contact (gas- or oil- boiler)
2 –relief valve different pressure
3 –hydraulic coupling.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Kind of the system
Underfloor heating
Service settings Kind of the system
Max. temperature
45ºC
Service settings Heating circuit
Room thermostat
ON
Service settings Room thermostat
Start pump temp.
20ºC
Service settings Heating circuit
3
The presented hydraulic diagram does not replace central heating engineering design and may be used for
information purposes only!

15
Installation of the controller
Environmental conditions
Due to the risk of fire is prohibited to use the
controller in explosive gas and dust
environment (eg. coal). Regulator should be
separated using appropriate enclosure.
The controller is designed for operation in the
environment where only dry conductive
contaminations may be present (2 degree of
contamination according to PN-EN 60730-1).
In addition, the controller may not be used in
water condensation conditions and it may not
be exposed to water.
Installation requirements
The controller is designed for vertical wall-
mounted installation. External circuit wires
are supposed be lead on surface. Mounting
hole locations are presented as in the casing.
Before opening the unit casing,
disconnect power supply. The unit
installation must be done at
disconnected voltage.
Controller must be installed by
qualified and authorized technician in
accordance with EN 60335-1 standard.
For how to open the unit casing see the
picture below.
Closing the unit casing see the picture below.
Installations regulator on the wall is shown in
the picture below.
The controller must be installed in a way that:
it is securely mounted on flat base, using
all mounting points,
degree of protection is ensured suitably to
environmental conditions,
dust and water access is prevented,
permissible operating temperature is not
exceeded for the controller,
air exchange inside casing is allowed,
access to dangerous parts is disabled,
electrical installation, to which the
controller is connected, must be equipped
with the device that allows disconnection
of both supply poles, in accordance
regulations that applies to such systems.

16
External circuits connection
TP –room thermostat (NO-NC),
T1 –temperature sensor mixer heating circuit
type CT10,
T2 –external temperature sensor type CT6-
P,
T3 –return temperature sensor type CT10,
T4 –heat source temperature sensor type
CT10,
L N PE –power supply 230V~, 50Hz,
P–CH pump,
SM –mixer actuator,
S–contact to operate the heating source type
ON-OFF,
FU –time-delay subminiature fuse.
The terminals for hazardous voltage: COM, NO, ZLo, ZN, ZLc, PN, PL, L, N.
The terminals safe voltage: TP, T1, T2, T3, T4
After turned on outputs: SM_OFF; SM_ON; P, on the terminals ZLo-ZN; ZLc-ZN, PL-PN giving is
230V~ voltage. After turned on output S is closed terminal COM with NO –without giving voltage.
Detailed description of the output S included in point 12.6.

17
Connecting electrical system
Regulator is designed to be fed with 230V~,
50Hz voltage. Supply is connected to
terminals L, N, PE.
The electrical system should be:
three core (with protective wire PE),
z in accordance with applicable
regulations.
Supply wires must be lead so as their contact
with sensor and other low-voltage cabling is
prevented, additionally, all cables may not
contact surfaces with temperatures that
exceed the cables operating temperature
limits.
The controller has no PE protective connector,
because the controller itself does not require
grounding. PE terminals of the pump, mixer
actuator shall be connected with PE of supply
network, according to periphery instructions
and regulation concerning electric systems.
Connecting mains supply 230V~
to terminals for sensors will
damage the regulator and creates
risk of an electric shock!.
Tips of the connected wires, especially power
leads, must be secured against splitting by
means of insulated clamps, in accordance with
the drawing below:
Securing wire tips: a) - right, b) - wrong.
Fixing the external wires
Electric cables external circuits are predicted
for the installation of surface-mounted. A
concealed external cable outlet should be
provided, as well as protection against the
wire being pulled out, loosened or strained,
using electric cable tray. It is not allowed to
leave any cable leads loose, to roll the excess
wire or to bend the wires into acute angles.
It is not allowed to roll the excess wire or to
leave disconnected cables inside the regulator
housing, as it may lead to damage to the
controller.
Example how to install the cables using
electric cable trays is shown in the figure
below.
Insulated clamp sleeve of 6 mm length

18
Connection of temperature sensors
Use only following sensor types: CT10, CT6-P.
The use of other sensors is prohibited.
Sensors cables could be extended by a cable
with cross-sectional area min. 0,5mm2, a total
cable length max. 15m.
Boiler temperature sensor should be installed
in thermostatic pipe installed in boiler. Mixer
temperature sensor should be installed in
sleeve located in stream of running water in
pipe, but also it can be installed on the pipe,
on condition that it is thermo isolated from the
environment.
Mounting temperature sensor: 1 - pipe, 2 –clamps,
3 - thermal insulation, 4 - temperature sensor.
Sensor must be protected from
getting loose from the surfaces to
which they are connected.
Good thermo contact should be maintained
between sensors and measured surface. To
this purpose thermoleading paste should be
used. It is not acceptable to lubricate sensors
with water or oil. Wires of sensors should be
separated from network electrical wires. In
such a case wrong readings of temperature
may be shown. Minimum length between
those wires should be 100mm. It is not
acceptable to allow for contact betweens wires
of the sensors and hot parts of the boiler and
heating installation. Wires of the sensors are
resistant to temperature not exceeding
100ºC.
From the regulator can also be formed to
correct an error reading from temperature
sensors: circuit heating, external, return and
boiler to the nearest 0,1°C.
The value correction set in:
Service settings →Temperature
correction
Connecting weather sensor
(external)
The regulator cooperates only with a weather
sensor of the CT6-P type. The sensor should
be installed on the coldest wall of the building,
usually this is the northern wall, under a roof.
The sensor should not be exposed to direct
sunlight and rain. The sensor should be fitted
at least 2m above the ground, far from
windows, chimneys and other heat sources
which could disturb the temperature
measurement (at least 1,5m).
Connect the sensor using cable of 0,5mm2
cross-section, up to 25m long. Polarity of the
leads is insignificant. Connect the other end of
the cable to the regulator.
Attach the sensor to the wall using tackbolts.
To access the tackbolts holes, unscrew the
sensor lid.

19
Temperature sensor checking
Temperature sensors CT10, CT6-P can be
checked by measuring their resistance in
given temperature. In case of big differences
between measured resistance value and
values in table below, the sensor should be
replaced with a new one.
CT10
Weather temp.
[°C]
Value
[Ω]
0
32 554
10
19 872
20
12 488
25
10000
30
8059
40
5330
50
3605
60
2490
70
1753
80
1256
90
915
100
677
CT6-P (weather)
Weather temp.
[°C]
Value
[Ω]
-25
901,9
-20
921,6
-10
960,9
0
1000,0
25
1097,3
50
1194,0
100
1385,0
125
1479,4
150
1573,1
Connecting a room thermostat
Room thermostat (NO-NC) connected to the
control affects the heating circuit.
The thermostat after contact opening reduces
the preset temperature heating circuit about
the service value Decrease of thermostat or
can turn off the pump in the parameter Off by
thermostat. The values of the parameters
must be chosen so that when of working the
room thermostat (contact opening) the
temperature in the room dropped.
Connecting a heat source
COM-NO terminals are used to connect the
contact heat source (no voltage) that turns on
and off the heat source. The heat source can
be automatic boiler gas or oil, which has a
contact ON-OFF. Terminals COM-NO does not
have galvanic isolation of 230V ~ and can
therefore only serve to disconnect circuit
voltage of 230V ~. Use separate relay in the
event of having to disconnect circuits at low
voltage.
Risk of electric shock caused by
current from a heat source.
Disconnect the controller and
heat source electrical supply and
make sure there is no dangerous
voltage on terminals.
Protect yourself against incidental
generation of supply voltage!
Connection to heat source (gas or oil boiler)
should be done by a qualified installer,
according to technical data of this boiler.

20
SERVICE MENU
Entrance to the service menu:
Password →[0000] →OK
Services settings
range
fact.
Heating circuit
Heat source
Protection
Room thermostat
Yes/No
No
Temperature correction:
T1 Circuit sensor
T2 External sensor
T3 Return sensor
T4 Boiler sensor
-4..+4ºC
-4..+4ºC
-4..+4ºC
-4..+4ºC
0
0
0
0
External sensor
Off/On
On
Manual control
Screed drying:
Active
Program selection: P1-P7
Yes/No
P1..P7
No
P1
Restore defaults settings
Yes/No
No
Heating circuit
range
fact.
Support
Off/On
On
Kind of the system:
Radiators system
Underfloor heating
Und.
Control method:
Weather control
Continous control
Weat.
Weather control *:
Heating curve
Curve parallel move
-15..15K
0
Preset temperature
20..40ºC
35
Decrease of work mode
0..15K
10
Decrease of thermostat *
0..30K
10
OFF by thermostat*
Yes/No
Yes
Start pump temp.
10..70ºC
35
Min. temperature
5..40ºC
20
Max. temperature
20..50ºC
40
Valve full opening time
60..200s
140
Valve input dead zone
0.0..2.0K
1.0
Valve dynamic
1..6
2
Valv delay
30..255
200
Heat source
range
fact.
Support
Off/On
On
Histeresis
1..30K
8
Min. temperature
10..70ºC
30
Max. temperature
50..90ºC
75
Buffer
Yes/No
No
Buffer preset temp.*
30..75ºC
60
HW priority
Yes/No
No
Cooling temp.
80..100ºC
88
OFF by thermostat*
Yes/No
No
Increrase temp.
1..20ºC
5
Protection
range
fact.
Return sensor
Off/On
Off
Min. temperature*
30..65ºC
40
Histeresis*
2..15K
8
Closing the valve*
0..50%
10
Frost protection
Off/On
On
Frost protection delay*
1..10h
4
Frost protection temp.*
5..10ºC
7
* not available when not connected the
corresponding sensor, the parameter is hidden or
is not appropriate settings in the menu.
Table of contents
Other Salus Controllers manuals
Popular Controllers manuals by other brands

baxiroca
baxiroca RWF40 Installation, use and maintenance instructions

Mitsubishi Electric
Mitsubishi Electric FX2N-1PG-E installation manual

Malossi
Malossi FORCE MASTER 2.1 Assembly instructions

Vescent
Vescent SLICE-QT quick start guide

Contemporary Research
Contemporary Research ICA-FT6 product manual

GRAUPNER
GRAUPNER PS 5,9V operating manual