Amcor D-1000 User manual

D-1000
GENERAL INFORMATION
EXPLODED VIEWS - PARTS LISTS
ENGLISH
Webedition 08/2001
Attention! 3 minutes delay on all units with ‘Alfa-14’
controller. When starting or restarting the unit, it will take
3 minutes before the compressor and the fan will start
running.
Achtung! Wenn Sie das Gerät (wieder) in Betrieb setzen,
wird bei allen Geräten, die mit einem Zeitschaltuhr ‘Alfa-14’
ausgestattet sind, der Anlauf des Kompressors und der des
Ventilators um 3 Minuten verzögert.
Attention! Quand vous mettez ou remettez votre appareil
en fonctionnement, le compresseur et le ventilateur de tous les
appareils equipés d’une horloge électronique ‘Alfa-14’
commencent à fonctionner après 3 minutes.
Attentie! Wanneer u het apparaat wilt (her)starten en het
apparaat is uitgevoerd met een ‘Alfa-14’ tijdschakelaar, dan
duurt het 3 minuten voordat compressor en ventilator starten.

You can’t control humidity and haze outdoors.
But in an indoor swimming pool and other
humid interior spaces where hot stuffy air,
steamy windows and walls are frequent
phenomena, you can.
That’s why you need Amcor.
Amcor’s dehumidifiers clear the air in damp interior
spaces.
Condensation is removed from windows, walls and
ceilings.
Vaporous stuffy air is drawn off, clean air is pumped
back in.
You simply set the dial and the air humidity remains at
the required level.
And, the Amcor dehumidifier is an energy saver.
Water evaporating from a swimming pool, bathroom,
archive, store or from wet objects and surfaces increases
the humidity of the air and creates the hazy and stuffy air
often found in the hall.
At the same time water condenses on the cooler parts in
the hall: windows, walls, ceilings, etc.
Water condensation is not only an aesthetic defect, it can,
in the long run, cause structural damage.
There are two methods for drying the air in humid
spaces:
- by ventilation,
- by heat pumps.
The Amcor dehumidifier is designed as a heat pump and
has, through energy saving, a considerable advantage
over a ventilation system.
AMCOR DEHUMIDIFIERS
For safety reasons, read this information
carefully before operating.
Persons who are not familiar with this type of
product must not use it.
We strongly recommend keeping this
information in a safe place for future reference.
This appliance must be earthed.
The unit is designated for indoor
operation.
>10°
SAFETY
Refer to the rating plate for voltage and
power input. The installation must be in
accordance with regulations of the country
where the installation is performed.
The minimum distance between air inlet(s)
and/or air outlet(s) and any object must be
40 cm.
* The unit is safe. It has been approved by many safety
institutions around the world. However, as with other
electrical appliance, use it with care.
* Keep out of reach of children.
* Do not clean the unit by spraying it or immersing
it in water.
* Do not insert any object into an opening of the unit.
* Disconnect from the mains before cleaning the unit or
any of its components.
* Never connect to an electrical outlet using an extension
cord. If an outlet is not available, one should be
installed by a licenced electrician.
* Any service other than regular cleaning or filter
replacement should be performed by an authorized
service representative. Failure to do so could result in a
loss of warranty.
* When the unit is placed in a (swimming) pool, connect
to the mains via a transformer or a breaking switch,
conform the regulations regarding electrical
installations.
2

The fan (1) sucks the humid air through the evaporator
(2). There the air is cooled and the moisture in the air
condenses into water. This water is collected in the tray
(3) and drained away through the sump and piping.
The compessor (5) pumps the heat, which has been
extracted from the air, into the condensor (6).
There, this heat is once again released, and absorbed by
the dry air. The ready wired control box monitors and
controls the operation.
HOW THE “AMCOR” DEHUMIDIFIER WORKS
ELECTRICAL WIRING
The unit can be supplied with a cord and an earthed plug. If it ever becomes necessary to replace this plug, be sure to
use an earthed plug suitable for the power supply in your area and conform your national safety standard.
The wires of the cable are coloured in accordance with the standard electrical code.
Blue Neutral
Brown Live
Green/Yellow Earth
The blue (neutral) wire should be connected to the terminal in the plug marked N or coloured black.
The brown (live) wire should be connected to the terminal in the plug marked L or coloured red.
The green/yellow (earth) wire should be connected to the terminal in the plug marked E or coloured green or marked
with this symbol:
The unit must be connected to the power supply with the appropriate leads.
The cord should pass through holes with rubber grommets.
Properly fused disconnect switches must be installed between the unit and the power source.
The unit must be wired with an isolation (mains) switch accessible from outside the wet area in which the unit is
installed, to comply with IEE regulations.
MAINTENANCE
The appliance is actually maintenance free, exept in cases
of soiling. In this case the filter has to be cleaned.
124
35
6
3

1. Correct positioning
It is possible to place the unit against the wall. The
base of the unit at the air inlet must be clear of any
obstruction by at least 400 mm. The top of the unit must
be clear of any obstruction by at least 400 mm.
2. Electrical connections
The Amcor D-1000 must be connected to the power
supply with appropriate leads.
The cord should pass through the hole with the rubber
grommet on the top left side of the unit. Properly fused
disconnect switches must be installed between the unit
and the power source.
3. Condensate drainline
The end of the condensate drain pipe protrudes from
the base of the dehumidifier on the back extending the
pipe long enough to reach the nearest drain outlet and
insert its end.
Check that the condensate water tube does not at any
point slope upwards, which would cause a blockage.
A “U”trap, located in a place where the water will not
freeze, will prevent unpleasant odours from being drawn
into the conditioned space. Where it is necessary for
condensate pipework or an electrical cable to pass
through a wall, a lined or sleeved hole should be made.
Ensure that pipework and cables do not touch each other.
The hole should be sealed when installation is completed.
INSTALL AND OPERATE YOUR AMCOR D-1000
4. Humidity control
The unit is controlled by a manually adjustable,
automatic humidistat, that switches the dehumidifier On
and Off, to maintain the desired humidity level.
The humidistat should be 24V wall mounted type.
It should be well ventilated and positioned at a height of
about 1.50 m above the floor. The two leads of the
humidistat should be connected to the appropriately
marked terminals on the terminal strip in the electrical
control panel. Those two leads should then be fed to the
vertical, white plastic conduit attached to the internal
dividing panel. Set the humidistat to the level of relative
humidity required in the controlled space. For example,
for normal comfort conditions the setting should be about
50% R.H.
5. Filter
The filter should be regularly checked and if necessary,
removed for cleaning or replacement. Slide the framed
filter forwards and lift it out. Hold it under streaming
water and flush it clean. Let the trapped water drip off the
filter fabric and replace the dried filter in reverse order.
6. De-icer control
Your Amcor D-1000 is equipped with an automatic
de-icer control that guards against ice forming on
refrigeration coils, in low temperature operation, by
shutting off the compressor.
Note: The fan will keep running until all the ice has
defrosted and then, the unit will start up again.
4
AMCOR MODEL D-1000
The Amcor D-1000 is a large capacity unit designed to
run highly efficiently in a domestic, commercial or
industrial environment.
The D-1000 keeps air dry and comfortable, prevents
condensation, and creates a better climate to prevent
damages caused by exessive humidity, such as: rusting of
equipment, dry rot of walls, mould growth in store
romms, etc.
It is ideal for places such as: restaurants, bars, printing
presses, indoor swimming pools, jacuzzis, garages,
animal enclosures, cellars, stores, boat sheds, weekend
cottages, archives, etc.
It can be positioned against the wall on legs. Model D-1000

PROCEDURE ON START UP
When the installation has been completed, carry out the
following procedure:
1. Make sure that the air filter has been fitted and that
unfiltered air cannot be drawn in.
2. Check the condensate drain system for leaks.
3. Check whether the unit has been correctly wired
according to the wiring diagram supplied.
PROCEDURE ON START UP D-1000
1. Switch off the power source at the mains, before
servicing the unit.
2. Do not operate the unit with the filter removed.
3. The discharge air outlet grille and the return air filter
must not be covered at any time.
The minimum distance between inlet(s) and/or outlet(s)
and any object must be 40 cm.
4. If the unit has been switched off, wait at least 3
minutes before switching it on again. Safety cutouts
and overload protective devices are fitted to protect the
fan motor and the compressor.
5. Do not rapidly adjust the humidistat setting from one
extreme to the other and back again.
6. For best results, close all windows to keep out
additional moisture laden air.
PRECAUTIONS D-1000
If the unit does not operate:
1. Make sure unit is connected properly.
2. Check fuse.
3. Ensure that the humidistat is in the required mode.
If the unit “short-cycles”:
1. Make sure that the filter is not blocked and that
evaporator is not iced up.
Leaking:
1. Make sure that condensate water tray outlet is not
blocked.
2. Make sure the plastic condensate water tube is
securely attached and that it does not slope upwards
at any point, causing a blockage.
TROUBLESHOOTING D-1000
5
TECHNICAL DATA / D-1000
MODEL D-1000
ELECTRICAL SUPPLY 230 V
FREQUENCY 50 Hz
MOISTURE REMOVAL AT 30°C 3.0 l/h
40-100% R.H.
POWER INPUT 1260 W
CURRENT 5.7 A
REFRIGERANT R407C (or R22)
REFRIGERANT CHARGE 1260 g
NET WEIGHT 58 kg
LENGTH 1130 mm
WIDTH 260 mm
HEIGHT 680 mm
"AMCOR" D - 1000
0
20
40
60
80
100
120
15 20 25 30 35
TEMP. deg. C
kg. / 24hr.
85
80
75
70
65
60
55
50
MOISTURE REMOVAL

EXPLODED VIEW / D-1000
6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
151617
18
19
20
21
22
23
24
25
26
6
27
28
55
32/56
29
33
31
54
30
34
35
36

7
EXPLODED VIEW / D-1000
MOISTURE REMOVAL / D-1000
“AMCOR” D1000 - MOISTURE REMOVAL AT DIFFERENT ROOM TEMP. EN R.H.% (kg water/24h)
RELATIVE HUMIDITY %
85 80 75 70 65 60 55 50
ROOM
TEMP. °C
15 40 36 33 30 27 24 23 17
20 56 51 46 42 37 33 30 26
25 75 68 62 56 50 44 39 35
30 93 85 77 70 62 55 49 44
35 101 92 83 76 68 60 53 48
43
44
45
46
47
53
52
51
50
49
48
42
41
40
39
38
37

PARTSLIST / D-1000
DRAWING NO. PART NO. QTY. PART NAME NO.
A2-1827-011 A414274 1 TOP COVER-RIGHT 1
A3-1827-015 O77001 1 PANEL-RIGHT 2
A1-1827-014 A382904 1 FRONT PANEL 3
A1-1827-046 A338666 1 LOUVERS 4
A3-1827-032 A442545 1 HOLDER-LOUVERS R 5
A2-1827-064 A433345 1 WALL-RIGHT 6+8
A3-1827-006 A431004 1 DRIAN PAN 7+21
429152/3 2+2 DIFFUSER 9
271264 2 SCROLL-BLOWER 10
A3-1827-043 A438684 1 DROPS DEFLECTOR 11
A1-1827-040 A342565 1 WALL FRONT 12
A2-1827-023 A342554 1 COVER 13+14
A2-1827-028 A501084 1 FOOT-RIGHT 15
A3-1827-031 A339094 1 HOLDER-FILTER 16
A3-1827-017 A436526 1 AIR FILTER 17
A2-1827-029 A501094 1 FOOT-LEFT 18
410715 1 DRIAN PIPE 19
A1-1827-004 A326472 1 BASE 20
A2-1827-035 A433355 1 WALL-LEFT 22+6
386117 1 DEFROST CONTROL 23
A1-1827022 A330675 1 PANEL-BACK 24+55
425002 1 CAPACITOR-FAN MOTOR 25
DEPENDS OF COM 1 CAPACITOR-COMPRESSOR 26
497103 2 GROMMET 27
A3-1827-033 A442554 1 HOLDER-LOUVERS L 28
508027 2 CLIP 29
346526 1 TERMINAL BLOCK 30
482301 1 TRANSFORMER 31
275016 1 TERMINAL & FUSE HOUSING 32
429182 1 CONTACTOR 33
A3-1827-016 O77002 1 PANEL-LEFT 34
A2-1827-013 A414274 1 TOP COVER-LEFT 35
A3-1827-012 A372454 1 CROSS BAR 36
A3-1827-042 A433374 1 CONNECTING PANEL-R 37
A3-1827-030 A434624 1 DIRECTIVE WALL 38
271264 2 BLOWER WHEEL 39/42
291016 1 FAN MOTOR 40+41
DEPENDS OF COM 3 SCREW 43
ORDER WITH COM. 3 SPRING WASHER 44
ORDER WITH COM. 3 WASHER 45
ORDER WITH COM. 3 SLEEVE 46
ORDER WITH COM. 3 RUBBER GROMMET 47
274312 1 COMPRESSOR 48
292026 1 STRAINER-DISTRIBUTOR 49
442002 1 CAPILLARY TUBE 50
A1-1827-019 X1002080678 1 EVAPORATOR 51
A2-1827-042 A433384 1 CONNECTING PANEL-L 52
A1-1827-018 X1204100722 1 CONDENSER 53
A2-1827-034 A422494 1 CONTROL BOARD 54
326101 1 FUSE 56

DEHUMIDIFIER D-1000
274838
SNS1 SNS2 HYG
DEFROST TIMER
ALFA - 14/1
GNDP F M
S
0
CAPACITOR
FAN
MOTOR
CAPACITOR
COMP.
RS
C
3
1
TO CONDENSATOR
TO EVAPORATOR
TO HYGROSTAT
LINE 230V/50HZ
N
L
GREEN/YELLOW GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
BLUE BLUE
BLUE
BLACK
BLACK
BLACK
BROWN
BROWN
BROWNWHITE
WHITE
RED
BLUE
WIRING DIAGRAM / D-1000
9

Amcorex B.V.
Anton Phillipsweg 9-11
1422 AL UITHOORN - Holland
Tel. +31 (0)297 56 00 79
Fax +31 (0)297 52 30 62
Internet: www.amcorex.com
e-mail: [email protected]
Amcor (Appliances) Ltd.
9 Ryan Drive, West Cross Centre
Great West Road, Brentford
Middlesex TW8 9ER
United Kingdom
Tel. +44 (0)20 8560 4141
Fax +44 (0)20 8232 8814
e-mail: [email protected]
Table of contents
Other Amcor Dehumidifier manuals
Popular Dehumidifier manuals by other brands

Sharp
Sharp DW-209EX Operation manual

Carlton
Carlton DH2400 quick start guide

Royal Sovereign
Royal Sovereign RDH-300 Series owner's manual

Morris
Morris Premier plus MDD-10251W instruction manual

Ingersoll-Rand
Ingersoll-Rand HRD Series Operator's instruction manual

Kinghome
Kinghome GDN20AZ-A3EBA2A owner's manual