Description PF1 SSR Power Controller
4 Ametek HDR Power Systems Rev 3
Table 1.2 General Specifications of PF1 SSR Models
Input line voltage: * 120, 240, 400, 480, or 575 Vac,
+10%, -15% , Single-phase
Line frequency: 50 or 60 Hz
Current rating:
As indicated by model number (refer to Table 1.1)
Thermostat contact rating: 120 Vac, 5 A; resistive (optional)
Voltage
Current
0 to 1.5 V (min); 0 to 10 V (max)
0 to 6 mA (min); 0 to 20 mA (max)
Control methods: 1. Potentiometer, 5 kΩ, 1/2 watt (Customer-supplied).
2. Temperature or process controller
Control signal input impedance:
Voltage input
Current input
1500 Ω
500 Ω
From power to ground 1,500 Vac
Current surge Subcycle I² T semiconductor fuse - OPTIONAL
Transient voltage spikes (dv/dt)
SCCR Rating
Metal Oxide Varistor (MOV) across each SCR pair
100kA
Phase-firing timebase 0º to 180º conduction per SCR
Controls: ZERO and SPAN potentiometers; 10-turn, screwdriver-adjustable.
Approvals UL/cUL (E151547), CE
Ambient Temperature range:
Environment 32 ºF to 122 ºF ( 0 ºC to 5 0ºC) surrounding air
Pollution degree 2
Overvoltage Category III
Storage 14 ºF to 158 ºF ( -10 ºC to 70 ºC)
Weight per unit: Current Rating
15 through 40 A
70 A
lbs
1.2
3
kg
0.55
1.36
Outline and mounting: See appropriate drawing in Appendix
* Specify with order
NOTE: The PF1 should be tested or operated with an adequate load since an open output will have line
voltage at the load connections.
1.7 Option OC (Overcurrent Trip)
The Overcurrent Trip Option (OC) provides circuit protection from output current overloads by serving
as a fast-gate shutdown (functions similar to an electronic fuse). Current transformers on the SCR
Power Control’s input lines allow Option OC to monitor instantaneous peak current. When the peak
current level exceeds the preset trip level, SCRs are gated off, and the load current is shut down within
1/2 cycle. Trip point is adjustable from 30% to 200% of the current transformer rating. The RESET
pushbutton on the OC Trip PCB must be manually reset to resume operation.
The Overcurrent Trip Option includes a Form C relay output and provisions for a remote overcurrent
reset push button. Reference Appendix G.
1.8 Option CL (Current Limit)
The Current Limit Option (CL) prevents the output current of an SCR Power Control from exceeding a
preset maximum current level, as determined by the current limit control setting (30% to 125%). The
current limit adjustment is located on the current limit PCB, reference Appendix F.