Ametek 675 User guide

MODEL 675
Shark Cage
Intrinsically Safe
Submersible Level Transmitter
INSTRUCTIONS FOR INSTALLATION AND OPERATION
C US
K796478 Rev. C
1/2023

Model 675 Series Submersible Level Transmitter
2
Contents
Section 1: Introduction ..................................................................................................................... 1
1.1 System Description ......................................................................................................... 1
1.2 Model Number ................................................................................................................. 2
Section 2: Installation ....................................................................................................................... 3
2.1 Safety Information ........................................................................................................... 3
2.2 Unpacking & Inspection .................................................................................................. 3
2.3 Operational Checkout...................................................................................................... 3
2.4 Mounting ......................................................................................................................... 4
2.5 Wiring ............................................................................................................................... 6
2.6 Cable Termination............................................................................................................ 8
Section 3:Accessories................................................................................................................... 10
3.1 Parts & Accessories....................................................................................................... 10
3.2 Ordering Parts & Accessories ....................................................................................... 10
Section 4: Troubleshooting ............................................................................................................ 11
4.1 Problem/Cause/Checks ................................................................................................ 11
4.2 Factory Assistance ........................................................................................................ 11
4.3 Equipment Return.......................................................................................................... 12
Section 5: Specications................................................................................................................ 14
5.1 Model 675 Series Transmitter ....................................................................................... 14
Section 6: Drawings........................................................................................................................ 15
6.1 Intrinsic Safety ............................................................................................................... 15
6.2 Outline Drawings ........................................................................................................... 16
AMETEK STC makes no warranty of any kind with regard to the material contained in this manual,
including, but not limited to, implied warranties or tness for a particular purpose. STC shall not be
liable for errors contained herein or for incidental or consequential damages in connection with the
performance or use of material.
© Copyright AMETEK PMT Products

Introduction
1
Section 1: Introduction
1.1 System Description
The Model 675 is specifically designed for slurry and highly viscous
applications where clogging of the sensor area is common. The Model
675 uses a 3.5” flush diaphragm to prevent unwanted clogging of the
sensing area. This submersible level device is made of 316 SS which offers
outstanding environmental protection and is available in depths up to
138 feet of water.
The non-fouling flush diaphragm is designed to eliminate unwanted
buildup of debris, fats, oils, greases, and other bio-solids by removing
any potential gaps on the measurement area. The high integrity seal’s
heavy construction eliminates the effects of turbulence on the sensor.
The 675 Series Transmitters indicate the level of liquid by continuously
measuring hydrostatic pressure via its sensing element, an ion implanted
siliconsemiconductor chipwithintegralWheatstoneBridgecircuit.Once
the sensor measures the pressure, the data is transmitted by a 4 to 20
mA output signal. This design provides for excellent reliability in remote
and inaccessible locations.
The Model 675 is approved for intrinsically safe operation in hazardous
locations as designated by Class I, Div 1, Groups A, B, C & D and Class
II, Groups E, F & G. when connected per Ametek drawing BK750535.
All Model 675 transmitters are equipped with a sealed cable termination
areaand moistureabsorbingdesiccantcanister. Thepurpose isto restrict
moisture from entering the transmitter through the cable vent.
Features
• Oversized 4.75” flush diaphragm to prevent clogging
• 0.25% Full Scale Accuracy
• Intrinsically Safe for Class 1 Division 1 Applications
• Custom Pressure Ranges and Cable Lengths
• Extremely rugged 316L SS construction
• Two-wire, 4-20 mA standard output
• Reverse polarity and surge protection
Applications
• Lift Stations
• Sewage Levels
• Slurries
• Storm Runoffs
• Pump Control

Model 675 Series Submersible Level Transmitter
2
1.2 Model Number
675 Level Transmitter
675 MODEL 675 submersible level transmitter
Sensing Port
P Shark cage 3.5” diameter diaphragm
Input / Output (approved power supply required)
B 12 to 28 VDC / 4 to 20mA (standard)
Pressure Ranges*
PSI BAR EQUIVALENTS
00006 0.4B 0-13.8 ft water 0-4.2 meters water
00015 001B 0-34.6 ft water 0-10.5 meters water
00030 002B 0-69.2 ft water 0-21.1 meters water
00060 004B 0-138 ft water 0-42.2 meters water
Electrical Connection**
M 22 AWG polyurethane vented cable with support bracket (K515072 cable)
P 22 AWG polyurethane vented cable with conduit adaptor (K515072 cable)
W 22 AWG polyurethane vented cable with cable support bracket and EMI
protection
Diaphragm Material
L 316L stainless steel (standard)
Fill uid
S Silicone oil (standard)
M Mineral oil
Cable Length
675 P B 0006 M L S 100 feet
Model Numbering
*Decimal points for non-standard ranges may be used
Decimal point requires one model code position, i.e. 1.08 = 4 positions

Installation
3
Section 2: Installation
2.1 Safety Information
Theoverallsystem isdesignedtopreventaccidentalshocktotheoperatorwhen
properly used. No design, however, can insure the safety of an instrument
improperly installed or used negligently. Read this manual carefully and
completely before operating the instrument. Failure to read this manual in
itsentiretycouldresultindamageto theinstrumentorinjurytothe operator.
To avoid possible shock hazard install in a grounded enclosure, prevent live
parts being touched and ground the sensor sheath and housing. Follow
wiring diagrams and local regulations. Installations where failure of this
equipment may cause personal injury, property loss, equipment damage or
financial loss, backup failsafe protection must be used.
2.2 Unpacking & Inspection
Carefully remove the contents of the shipping carton and check each item
against the packing list before destroying any packing material. If there is
any shortage or damage, report it to the factory immediately.
When this transmitter is used with the AMETEK PMT Products DDMC
Controller, the transmitter Model Number is identified on the nameplate of
the DDMC in the section labeled “USED WITH.” This is because the DDMC
is calibrated with, and should be used only with a specific Submersible
Transmitter. Look for a correlation between the two instruments.
2.3 Operational Checkout
Beforeinstallingthe675SeriesTransmitter,makesurethesystemisoperating
by doing a bench check.
WARNING:
Do not connect any wires while Power is applied.
For temporary connections, refer to diagrams in Wiring Section 2.5 of this
manual. Connect AC power to the controller and/or with which it is to be
used. Apply power and allow a five-minute warm-up.
With no pressure applied to the transmitter, the meter should display zero
(or for “drawdown” the reading corresponding to the depth below ground
level that the transmitter will be when installed.)

Model 675 Series Submersible Level Transmitter
4
2.4.2 Placement
The Model 675 Transmitter should be supported by customer-installed
strain relief cable that is attached to the tabs on the transmitter or optional
factory stainless steel support cable #K515183. Reference Figure 2-2 for
installation recommendations. Ametek does not recommend suspending the
transmitter supported only by its attached electrical cable.
Caution: Do not allow transmitter to remain in liquid when it freezes solid.
Thiswillapplymechanicalforcetothesending diaphragmofthetransmitter.
Excessive force will result in transmitter damage or destruction.
2.3 Operational Checkout (continued)
CAUTION: Do not simulate an increase in pressure by applying mechanical
force to the sensing diaphragm of the transmitter. Excessive force will result
in damage to or destruction of the transmitter.
When pressure is applied to the transmitter, the display should increase,
and then return to the original reading when pressure is removed. The
Transmitter can be pressurized by lowering it into water or by applying air
pressure from a calibration device.
2.4 Mounting
2.4.1 Dimensions
REV
H : \ EC N s\
REV
3:4
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
2 O F 2
K780728
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
U.S.G A UGE D IVISIO N
PM T P RO D UC TS
ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
H
N O N REN EW A BLE D ESIC C A N T
INSTALL IN A DRY ENVIRONMENT
1.0 HEX
20 AWG LEADS
PO TTED C A BLE EN D
(DO NOTREMOVE)
1.25
SPEC IFIED IN
.312
.25 THRU
X2
.74
1.00
10.29
C A BLE
THEMODELCODE
1.00
8.00
1.25
BO TTO M V IEW W ITH
PRO TEC TI V E PLA TE REM O V ED
4.75
3.495
DIAPHRAGM
SURFA C E
OPTIONAL
CONDUITADAPTOR
1 " H EX 1.57
1.05
REV
H : \ EC N s\
REV
3:4
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
2 O F 2
K780728
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
U.S.G A UGE D IVISIO N
PM T P RO D UC TS
ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
H
N O N REN EW A BLE D ESIC C A N T
INSTALL IN A DRY ENVIRONMENT
1.0 HEX
20 AWG LEADS
PO TTED C A BLE EN D
(DO NOTREMOVE)
1.25
SPEC IFIED IN
.312
.25 THRUX2
.74
1.00
10.29
C A BLE
THEMODELCODE
1.00
8.00
1.25
BO TTO M V IEW W ITH
PRO TEC TI V E PLA TE REM O V ED
4.75
3.495
DIAPHRAGM
SURFA C E
OPTIONAL
CONDUITADAPTOR
1 " H EX 1.57
1.05
REV
H : \ EC N s\
REV
3:4
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
2 O F 2
K780728
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
U.S.G A UGE D IVISIO N
PM T P RO D UC TS
ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
H
N O N REN EW A BLE D ESIC C A N T
INSTALL IN A DRY ENVIRONMENT
1.0 HEX
20 AWG LEADS
PO TTED C A BLE EN D
(DO NOTREMOVE)
1.25
SPEC IFIED IN
.312
.25 THRU
X2
.74
1.00
10.29
C A BLE
THEMODELCODE
1.00
8.00
1.25
B O TTO M V I EW W I TH
PRO TEC TI V E PLA TE REM O V ED
4.75
3.495
DIAPHRAGM
SURFA C E
OPTIONAL
CONDUITADAPTOR
1 " H EX 1.57
1.05
REV
H : \ EC N s\
REV
3:4
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
2 O F 2
K780728
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
8 2 0 PEN N SY LV A NI A BO U L EV A RD , F EA STERV I LL E, P A 1 9 0 5 3
U.S.G A UGE D IVISIO N
PM T P RO D UC TS
ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
H
N O N REN EW A BLE D ESIC C A N T
INSTALL IN A DRY ENVIRONMENT
1.0 HEX
20 AWG LEADS
PO TTED C A BLE EN D
(DO NOTREMOVE)
1.25
SPEC IFIED IN
.312
.25 THRU
X2
.74
1.00
10.29
C A BLE
THEMODELCODE
1.00
8.00
1.25
B O TTO M V I EW W I TH
PRO TEC TI V E PLA TE REM O V ED
4.75
3.495
DIAPHRAGM
SURFA C E
OPTIONAL
CONDUITADAPTOR
1 " H EX 1.57
1.05

Installation
5
2.4.3 Model 675 Series Transmitter
CAUTION: The cable grommet is specially installed by factory-trained
personnel to assurethatitremains watertight.Anyadjustmentorremovalof
thegrommetmaydestroythewatertightfeaturethusexposingthetransmitter
to water seepage, causing an electrical short and transmitter failure. Any
adjustment or removal of the cable grommet voids the warranty.
CAUTION: The diaphragm seal assembly is installed by factory trained
personnel and should not be modified in the field. Any adjustment or removal
of the diaphragm seal assembly voids the warranty.
CAUTION: The waterproof cable should not be kinked or nicked, which will
allow water to seep into the cable and short out the transmitter.
Figure 2-2
Transmitter Installation Considerations
2.4.4 Provide Signal Noise Isolation
Thetransmitter shouldnotbemountedcloseto highcurrentswitchingrelays
or in an enclosure containing such relays. Low voltage wiring (transmitter
signal wires and analog output wires) should be separated from high voltage
wiring (115, 230 & 440 Vac) and should be shielded.
FACTORY OR

Model 675 Series Submersible Level Transmitter
6
2.5 Wiring
WARNING:
Do not connect any wires while AC Power input is applied.
2.5.1 Surge Protection
Surge protectors are available as an option item (see Parts & Accessories
in Section 3 of this manual). It is strongly recommended to protect from
secondarysurges andlightningonoutdoor installations.Installinaccordance
with the applicable drawing that is supplied with the surge protector and
the following instructions:
1. Lightning protection devices should be placed as close to the meter or
transmitter as possible and wired in accordance with Local Electrical
Codes in an approved watertight enclosure.
2. If the distance between the meter and transmitter, or meter and recorder
is less than 100 ft., only one protector per line is needed.
3. Use No. 8 AWG ground wire or better from protector.
4. Keep ground wire less than one foot long and tie to a suitable ground rod
or metal frame ground. Surge capability is only as good as the grounding
method. All ground connections must be installed.
5. Install protectors in weather-tight enclosures.
6. Run signal lines shielded and away from power lines.
7. Mount the fused switch panel as close to the meter as possible. Wire
according to the Local Electrical Code.
8. Lead lines for 110 Vac and 220 Vdc protectors should be cut as short as
practical.
Figure 2-3
Transmitter Wiring Identication

Installation
7
2.5.1 Surge Protection (Continued)
CAUTION: Thisor anyinstallationcannotprotectagainstadirectlightning
strike,orsecondary strikesofsufficientmagnitude.AMETEKPMTProducts
cannot accept liability for damage due to lightning or secondary surges.
2.5.2 Lightning Protection Wiring
Here is a typical wiring arrangement to a typical controller/ meter. Shown
here are connectors to the AMETEK PMT Products DDMC Controller in
the Levelmate III NEMA 4X enclosure option.
5A/250VAC
Slo blo fuse
BLA C K
W H I TE
W H I TE
G REEN
G REEN
BLA C K
C U S TO M E R
PO W ER
C U S TO M E R
PO W ER
C U S TO M E R
CONNECTIONS
C U S TO M E R
CONNECTIONS
BLA C K
G REEN
RED
D RA I N
BLA C K
BLA C K
W H I TE
G REEN
BLA C K
G REEN
W H I TE
BLA C K
RED
Fi g u r e 2 - 4
Wiring w ith Lig ht ning
Protection Options
Fi g u r e 2 - 5
Wiring w ith No Lig ht ning
Protection Options
.005.01
H:\ MA NUALS\ K796478\
1:1
8 2 0 P EN N SYLV A N IA BO UL EV A RD , FEA STERV I LLE, PA 1 9 0 5 3
DATE
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
12345678
87654321
REVISION HISTORY
APPROVED
DATE
DESCRIPTION
LTR
ZONE
LM I I I A SSY . SLD A SM
U.S.G A UG E D IVISION
1 O F 1
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
TOLERANCES ON
FINISH
2 DEC. PL.
MATERIAL
3 DEC. PL.
DIMENSIONS ARE IN INCHES.
ANGLES
1°
SIZE
D
CAGE CODE
65048
DWG NO.
WEIGHT SHEET
TITLE
D
SCALE
DRAWN
CHECKED
APPROVED
SUPERCEDES
USED ON
NEXT ASS`Y
E-FILE
UNLESS OTHERWISE SPECIFIED
PM T P RO D U C TS
PRO TEC TO R
BLA C K ( LIN E 2 )RED ( EQ UI P 1 )
BLA C K ( EQ U I P 2 ) RED ( LI N E 1 )
TR A N SM I TTE R
LIG HTNING
RED
RED ( LI N E 1 )
BLA C K ( LIN E 2 )
BLA C K ( EQ U I P 2 )
RED ( EQ UI P 1 )
ANALOG
O UTPUT
LIG HTNING
PRO TEC TO R
G REEN
RED
BLA C K
D RA I N
5A/250VAC
Slo blo fuse
C U STO M ER G RO UN D
W IRE FO R
LI G H TN IN G P RO TEC TO RS
# 8 A WG
C USTO M ER G RO UN D
W IRE FO R
L I G H TN I N G P RO TE C TO R S
# 8 A WG

Model 675 Series Submersible Level Transmitter
8
2.5.3 Lightning Protection Installation Concept
1. Lightning protection devices should be placed as close to the instrument
as possible.
2. If the distance between the meter and transmitter, or the meter and recorder
is less than 100 ft., only 1 protector per line may be used.
3. This or any installation cannot protect against a direct lightning strike, or
secondary strikes of sufficient magnitude. AMETEK PMT Products cannot
accept responsibility for damage due to lightning or secondary surges.
4. Proper installation including grounding require detailed installation
drawing. Consult factory.
2.6 Cable Termination
Instructions to installing the Ametek Submersible Transmitter using the
supplied desiccant canister:
Remove Power Source During Installation.
This Ametek submersible transmitter is equipped with a sealed termination
area and moisture absorbing desiccant canister. The purpose is to restrict
moisture from entering the transmitter from the cable termination. It
is important that the cable termination not be altered. Both potting and
Figure 2-6
Lightning Protection Concept

Installation
9
solder blockers are used to restrict the moisture path. If a shorter length of
cable is required, it is highly recommended that the cable be coiled instead
of being cut.
The assembly is shipped complete to prevent moisture from entering during
shipmentandstorageandtoshowtheuserhowitwill ultimatelybeconnected.
To install the cable termination, it is recommended that a NEMA box be
employed. The submersible cable enters the box through an included strain
relief (cable is a 0.24” diameter). The red wire is the V+ lead and the black is
the V- lead in a 4/20 mA loop. The green wire is a safety ground and should be
tied to earth ground. The shield wire connection to earth ground is optional
depending on EMI conditions in the area. The shield wire is terminated to
the case internally.
The tubing should be connected to the desiccant canister though the use of
the included fittings. There is one fitting at the cable end and another at the
canisterinlet.Thetubingis removable fromthe fittingsforeaseofconnection
and replacement of the canister. Remove the yellow plug from the canister
outlet prior to use.
The canister has a blue color when installed. Entering moisture becomes
trapped within the desiccant canister. If moisture is absorbed inside in
sufficient amounts, the color changed to pink. At that point the canister
should be replaced. Use Ametek part #K234436 for full original assembly
with tubing. The fitting and tubing at the canister inlet can be removed using
a small wrench and reused with the replacement cartridge only part
#K234446.
2.6 Cable Termination (Continued)
Figure 2-7
Desiccant Canister
Complete assembly
with tubing
part #K234436.
Replacement
cartridge only
part #K234446

Model 675 Series Submersible Level Transmitter
10
Section 3: Accessories
3.1 Parts & Accessories
LMA912
30Vdc Lightning and surge protector for excitation and signal lines
to the milliampere transmitter or meter analog output lines to other
instruments
LMA918
Lightning & surge protector for 115Vac input line to a controller /meter
LMA919
Lightning & surge protector for 230Vac input line to a controller/meter
K234436
Moisture Absorbing Desiccant Canister original kit with tubing
K234446
Replacement cartridge only (some assembly required)
3.2 Ordering Parts & Accessories
When ordering replacement parts, supply the following information:
1. Part description and part number.
2. Quantity of each item required.
3. Shipping instructions and address.
Contact:
AMETEK STC
PMT Products
205 Keith Valley Road
Horsham, PA 19044
U.S.A.
Tel: 215-674-1234
Email: mctpmt.sales@ametek.com
www.ametekusg.com

Accessories
11
Section 4: Troubleshooting
WARNING:
If the Level Measurement System is located in a hazardous environment,
do not open the enclosure cover or make/break any electrical connections
without first disconnecting electrical power at the source. Ensure that the
wiring, electrical fittings and conduit connections conform to the electrical
codes for the specific location and hazard level.
4.1 Problem/Cause/Checks
Controller/meter Display Drifting:
May be water in cable causing short circuit; look for kink or damaged cable;
checkforbrokenwires,looseorcorrodedconnections,orobviousshortcircuits;
With transmitter wires disconnected, resistance between red or black lead
and shield should not exceed 15 megohms.
Controller/meter Display Incorrect:
May be wrong transmitter connections; check wiring.
May be defective transmitter; check as above, replace transmitter.
May also be controller/meter problems, such as calibration.
4.2 Factory Assistance
AMETEK STC
PMT Products
205 Keith Valley Road
Horsham, PA 19044
U.S.A.
Tel: 215-674-1234
Email: mctpmt.sales@ametek.com

Model 675 Series Submersible Level Transmitter
12
4.2 Factory Assistance (Continued)
Please provide the following information:
• Instrument Model Number and serial number
• Description of problem being experienced
• Description and location of the installation
4.4 Equipment Return
In order to provide the best service, any equipment being returned for repair
or credit must be pre-approved by the factory.
In many applications, sensing elements are exposed to hazardous materials.
• OSHA mandates that our employees be informed and protected from
hazardous chemicals.
• Material Safety Data Sheets (MSDS) listing the hazardous materials to
which the sensing element has been exposed MUST accompany any repair.
It is your responsibility to fully disclose all chemicals and decontaminate
the sensing element.
To obtain a return authorization (RA#)
Contact: Tel: 215-674-1234
email: mctpmt.sales@ametek.com
• Please provide the following information:
• Model Number of Return Equipment
• Serial Number
• Original Purchase Order Number
• Process Materials to which the equipment has been exposed.
• MSDS sheets for any hazardous materials
• Billing Address
• Shipping Address
• Purchase Order Number for Repairs

Troubleshooting
13
Please include a purchase order even if the repair is under warranty. If repair
is covered under warranty, you will not be charged.
Ship equipment freight prepaid to:
AMETEK STC
PMT Products
205 Keith Valley Road
Horsham, PA 19044
Tel: 215-674-1234
*mark the RA# clearly on the outside of the carton and all paperwork.

Specifications
14
Section 5: Specications
5.1 Model 675 Series Transmitter
Ranges:
• User customizable ranges between 0-6
psi (13.8 ft of water) and 0-60 psi (138 ft
of water)
Output:
• 4 to 20 mA, 2 wire, current limited to 30
mA DC
Power Supply:
• 12 to 40 VDC with reverse polarity surge
protection; Limited to 28 VDC for Intrinsic
Safety with Approved Power Supply.
Loop Resistance:
1400 ohms maximum at 40 volts
Temperature Range: **
• Ambient Operating: -25° to 180°F (-32°
to 82°C)
• Storage: -40° to 180°F (-40° to 82°C)
** If submerged in a liquid that has
frozen, damage will result.
Overrange Eect:
• ±0.15% full scale at 200% of maximum
range
Overrange Limit:
• 200% of maximum range
Burst Pressure:
• 3X Upper Range Limit
Accuracy:
• ±0.25% full scale, BFSL (including
linearity, hysteresis and repeatability)
Zero Oset:
• ±1.00% full scale set at 77°F (25°C)
Span:
• ±0.50% full scale set at 77°F (25°C)
Temperature Eects:
• Compensated: 32° to 122°F (0°C to
50°C);
• Maximum: 2.5% URL output change
for ±25°C temperature change within
compensated range when calibrated
at 25°C. Consult factory for lower or
alternate pressure ranges.
Power Supply Eect:
• ±0.005% full scale per volt
Diaphragm Seal:
• 316L SS construction with 4.75” OD and
3.5” sensing area
Construction:
• Diaphragm: 316L stainless steel
• Housing Type: 316 stainless steel
• Nut/Washer Type: 316 stainless steel
• Cable Grommet: Viton standard. Please
contact factory for other options.
• Housing O Ring: Viton standard. Please
contact factory for other options.
• Cable Jacket: Polyurethane (Standard).
See Model Code.
Media Compatibility:
• Reference materials of construction
Electrical Connection:
• Attached 20 gauge vented polyurethane
shielded cable. Unspliced lengths
available up to 5000 ft. (1662 m)
Weight:
• 7 lb. 3 oz (Without cable)
Approvals:
• Meets CSA requirements for
intrinsically safe operation in
hazardous locations as designated by
Class I, Div 1, Groups A, B, C & D and
Class II, Groups E, F & G. Temperature
Code T3C (when connected per
Ametek drawing K750535).
Options and Accessories:
• DDMC Meter Controller and Housing
• Stainless steel support cable part
#K515183 (factory installed with tie
wraps).
***see drawing K750535 for cable length
limits for intrinsically safe installation.
C US

Drawings
15
Section 6: Drawings
6.1 Intrinsic Safety
TH I S D RA W I N G I S T H E PRO PERTY O F A M ETEK I N C . A LL RI G H TS A RE RESERVED A N D N EI TH ER T H I S D RA W I N G N O R A N Y I N F O RM A TI O N I T
C O N TA I N S I S TO BE C O PIED , REPRO D UC ED , D I SCLO SED TO O TH ERS, O R U SED W ITH O U T W RI TTEN PERM I SSI O N FRO M A M ETEK I N C.
LI M I T S O F A C C EPTA BL E W O RK M A N SH I P A RE D EFI N ED I N M S- 6 4 5 - A .
1
1
2
2
3
3
4
4
A
B
A
B
UNLESS OTHERWI SE SPECI FI ED
DI MENSI ONS ARE I N I NCHES.
TOL ERANCES ON
FINISH
MATERI AL
2 D EC. P L . 3 D EC. P L . A N GL ES
± .01 ± .005 ± 1°
REVISIONHISTORY
APPROVEDDATEDESCRIPTIONLTRZONE
B65048
WEI GH T SHEET
B
DATE
DRAWN
CHECKED
APPROVED
SUPERCEDES
USED ON
NEXT ASS` Y
E- FI LE SCALE
SI ZE CAGE COD E DWG N O.
TI TLE
i
i
i i
i i
WARNING
WARNING
REVI SI ON S TO TH I S DOCU MEN T REQU I RE AGEN CY N OTI FI CATI ON .
REFER TO DOCUM ENT EN 201-17.

Model 675 Series Submersible Level Transmitter
16
6.2 Outline Drawings
REV
H : \ EC N s\
REV
3:4
8 2 0 P EN N SYL V A N I A B O U L EV A RD , F EA STERV I L LE, P A 1 9 0 5 3
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
2 O F 2
K780728
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
8 2 0 P EN N SYL V A N I A B O U L EV A RD , F EA STERV I L LE, P A 1 9 0 5 3
U.S.G A UGE DIVISIO N
PM T P RO D U C TS
ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT
LIMITS OF ACCEPTABLE WORKMANSHIP ARE DEFINED IN MS-645-A.
A
B
C
D
A
B
C
D
1234
4321
CONTAINS IS TO BE COPIED, REPRODUCED, DISCLOSED TO OTHERS, OR USED WITHOUT WRITTEN PERMISSION FROM AMETEK INC. REFER TO SHEET 1 FOR REVISION HISTORY.
C65048
WEIGHT SHEET
C
SCALE
SIZE CAGE CODE DWG NO.
THIS DRAWING IS THE PROPERTY OF AMETEK INC. ALL RIGHTS ARE RESERVED AND NEITHER THIS DRAWING NOR ANY INFORMATION IT ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL.
H
N O N REN EW A BLE D ESIC C A N T
INSTALL IN A DRY ENVIRONMENT
1.0 HEX
20 AWG LEADS
PO TTED C A BLE EN D
(DO NOTREMOVE)
1.25
SPEC IFIED IN
.312
.25 THRU
X2
.74
1.00
10.29
C A BLE
THEMODELCODE
1.00
8.00
1.25
BO TTO M V IEW W I TH
PRO TEC TIV E PLA TE REM O V ED
4.75
3.495
DIAPHRAGM
SURFA C E
OPTIONAL
CONDUITADAPTOR
1 " H EX 1.57
1.05

AMETEK STC
PMT Products
205 Keith Valley Road
Horsham, PA 19044
Tel: 215-674-1234
Email: mctpmt.sales@ametek.com
www.ametekusg.com
K796478 Rev C 1/2023
EDO 1-23-110
Table of contents
Other Ametek Transmitter manuals
Popular Transmitter manuals by other brands

Long Range Systems
Long Range Systems T74C232 user manual

Bauer
Bauer 707 Instruction book

Linear
Linear MULTI-CODE 3083 installation instructions

ADTEK
ADTEK ST-VA Operation manual

Dwyer Instruments
Dwyer Instruments 616W Series Installation and operating instructions

Emerson
Emerson Rosemount Oxymitter 4000 instruction manual