Amtech Axpert-VT240S User guide

$07(&+$07675HY$35127,&(5HDGWKLVJXLGHWKRURXJKO\EHIRUHXVLQJWKH$[SHUW976DQGVWRUHLQDVDIHSODFHIRUUHIHUHQFH0DNHVXUHWKDWWKLVJXLGHLVGHOLYHUHGWRWKHILQDOXVHU96\VWHP+SN:a+SN:96\VWHP+SN:a+SN:6WDUWXS*XLGH$[SHUW976

Contents
Introduction ............................................................................................................................. 1
Chapter-1: Installation Procedure ......................................................................................... 2
Chapter-2: Operation Panel (Digital Keypad) ....................................................................... 4
Chapter-3: Initial Start-Up and Keypad Operation ............................................................... 6
3-1 Selection of Control Mode .......................................................................................... 6
3-2 Initialization of Motor Constants.................................................................................. 6
3-3 Automatic tuning & Test operation.............................................................................. 7
3-4 Test Operation (v/f control mode) ............................................................................... 10
Chapter-4: Remote Terminal Operation................................................................................ 12
4-1 Start/ Stop Operation from terminal ............................................................................ 12
4-2 Speed Reference setting selection ............................................................................. 13
Chapter-5: Control Input / Output ........................................................................................ 17
Chapter-6: Control Functions & Parameter Settings........................................................... 19
6-1 Monitor parameters..................................................................................................... 19
6-2 Block-A parameters .................................................................................................... 24
6-3 Block-B parameters .................................................................................................... 25
6-4 List of key parameters ................................................................................................ 26


Start up Guide for Axpert-VT240S Series AC Drive
1
Introduction
This Start-Up Guide is not meant to replace the compete Instruction Manual. This is a
supplementary document intended to provide concise instructions covering the most common
installation and configuration options. For detailed instructions, safety precautions, proper
mounting, installation, configuration and operation, please refer to the appropriate revision of
the Axpert-VT240S complete Instruction Manual.
WARNING: Only qualified personnel should plan or implement the installation, start-up,
operation and maintenance of this equipment. Personnel must read the entire INSTRUCTION
MANUAL before attempting to install, operate or troubleshoot the Axpert-VT240S.
There are ten key elements to the basic installation and start up of a Variable Frequency Drive. In this
Start-Up Guide we will cover the following steps. For more information, please refer to the complete
Instruction Manual.
1. Physically install the VFD with consideration for ambient temperature and proper cooling, adequate
room around the VFD for airflow and mounting properly to protect the VFD for the specific environment.
If mounted inside or outside of another enclosure, make sure the environment that the VFD is mounted
in is properly evaluated and the correct NEMA rated drive or enclosure is used to suit the application.
For example, if outside, a NEMA3R, clean room, NEMA1 or IP20, a dirty, dusty environment, a
NEMA12.
2. Check that the VFD is of the correct voltage and current rating to suit the application.
3. Use the required peripheral devices, such as Circuit Breaker or Input Fuses, Line or Load reactors,
DC Bus choke, DB resistors, push buttons and selector switches to suit the application.
4. Connect the AC input voltage, AC motor and control wiring using proper sized cables and wires with
appropriate grounding and shielding to assure proper operation. Make sure that the requirements of
the local electrical codes are adhered to for a proper installation.
5. Power up the VFD and familiarize yourself with the operation of the keypad, such as navigating
through the parameters and how to change parameters.
IMPORTANT NOTE! Whenever undertaking the start-up of a VFD, especially if anyone has been
operating the VFD prior to the start-up, it is advisable to set all of the parameter values to their
factory default values. By knowing that all of the parameters are at the default values, this can
save a lot of troubleshooting later on through mis-operation by having a parameter set to a
value not needed by the application. An incorrectly programmed parameter can look like a
defective VFD. Setting parameter C09-7 to “9” will reset all user parameters to default. If drive is
supplied with some logic, ensure that you have related parameter list to input after default.
6. Review the parameters and determine which ones need to be changed to meet the requirements of
your application. The motor parameters (B00-0 to B00-7 for v/f control and B01-0 to B01-7 for vector
control mode) must be entered for precise protection of the AC motor used. The method for start/stop,
speed reference, and values for the Accel/decel rate and minimum and maximum speeds are all
important parameters to be considered.
7. Start the motor and assure proper rotation and the expected load currents are displayed, (See
Parameter D02-0 - Output Current in Amps). Find the read-only parameters that display information
like a digital meter to show operational parameters such as input and output voltages, DC Bus voltage,
load currents, motor speed and frequency, power used and run time.
8. Review the Fault Codes and what they mean. Look at the Fault History parameters and how the
VFD will display the last ten faults and operational values that existed at the time of the fault.
9. Test all of the system operators, such as pushbuttons, remote keypad, selector switches, to assure
proper operation and control. Verify starting and stopping and correct speed control.
10. Once the installation is complete and the system operates as desired, It is advised to fully
document all parameter value changes, jumper changes and control wiring to simplify troubleshooting
or system duplication in the future. This will help to get better technical support if need arises.

Amtech
2
Chapter-1: Installation Procedure
Always confirm the following points before turning ON the power after completing wire.
1. First, visually inspect the VFD
and ensure that the VFD has not been damaged in transport. If any
damage has occurred, do not energize the VFD, and contact the supplier.
2. Mount the VFD according to the detail Instruction Manual, Chapter 2 “Installation and Wiring”.
3. Be aware of the ambient temperature. Use the VFD within the specified ambient temperature
(50ºC).
4. Connect the main circuit terminals L1, L2, L3 to the line side and terminals U, V, W to the motor side
as shown in Fig.1. Refer Chapter-2 of detail Instruction Manual for the terminal layout of other models.
Tighten the terminals with the specified torque as specified in Table-2-3, Chapter-2 of detail Instruction
manual for the Axpert-VT240S Series AC Drive. Make sure that none of the terminal section screws
are loose and there is no short circuit state in the terminals caused by wire scraps, etc.
1 4
2 5
3 6
E E
L+1
B
MCCB*
U
V
W
L1
L2
L3
L+2
(DCL)*
L
-
VT2
40
S
M
MC*
76D DB resistor*
Noise filter*
(ACL)*
Power supply
Line Reactor
DC Choke
Fig. 1 Example of main circuit wiring (018L, 022H and smaller)
(* Indicates optional equipment, refer detail IM for other models)
5. Connect the system ground to the ground terminal of the VFD.
6. Remove the coupling to the motor and machine, so that the machine can be run as a single unit.
7. With the 400V Series (075H or higher), there are some sections in the inverter, which operate with
an AC power supply, such as fan and magnetic contactor. In this case, set the power changeover
connector on the transformer auxiliary PCB according to the power voltage. If this connector is not
set correctly, the fan and magnetic contactor could burn.
380V: JP-380 440V: JP-440
400V: JP-400 460V: JP-460
415V: JP-415 480V: JP-480 (factory setting)
8. Make sure that the power supply is within the tolerable range.
9. Always correctly install the front cover and outer cover before turning the power ON.

Start up Guide for Axpert-VT240S Series AC Drive
3
1-1 Turning Power ON and Starting VT240S
Turn the power ON.
(1) LCD operation panel (V24-OP1)
The LCD operation panel startup screen is shown below.
(2) LED operation panel (V24-OP2)
All LEDs on the numeric display will turn ON for a
short time, and then "
", "
"
and "
" will appear.
The "LCL" and "Hz" LEDs will also turn ON.
!"
#"
$"
%& %"'( )" *+," '%-"
!"#$%
!"#$%!"#$%
!"#$%&
&&
&
'#(%
'#(%'#(%
'#(%&
&&
&
&
&&
&
#)*+)*&,-./).012
#)*+)*&,-./).012#)*+)*&,-./).012
#)*+)*&,-./).012&
&&
&
344
344344
3445
55
54
44
46&&ṭ:
6&&ṭ:6&&ṭ:
6&&ṭ:&
&&
&
Normal display
Checking the operation after
power ON
!"##$%&## '(##')'# !"##$%&## '(##')'# !"##$%&## '(##')'#
* The value after ROM is the
software version

Amtech
Chapter-2: Operation Panel (Digital Keypad)
2-1 Outline of operation panel types and functions
LCD operation panel (V24-OP1)
LED operation panel (V24-OP2)
Status indications LEDs
FWD (Forward) The drive is running in
the forward direction.
When both LEDs flicker simultaneously, it indicates that DC
Brake or pre-excitation is in action.
If only the "FWD" or "REV" LED is flickering, this indicates
that a command in the reverse direction has been received,
and the drive is decelerating.
REV (Reverse) The drive is running in
the reverse direction.
FLT (Fault)
The drive has detected a fault and has stopped.
Turns OFF when the +
STOP
RS
MO keys are pressed or the sequence input RESET signal
is input.
LCL (Local)
The drive is in the Local Mode and can be operated from the Operation Panel (FWD,
REV and STOP only). When LED is off, the drive is in the Remote Mode and can be
controlled from the terminal block. To change Modes between Local and Remote, pres
s
+
STOP
LC
SE
. Change this setting in stop condition.
Parameter increase/decrease knob
Status indications LED
Data display section (LCD)
Parameter operation keys
Operation keys
Parameter operation keys
Data display section (LCD)
Parameter operation keys
Operation keys
Parameter operation keys
Unit indications LED
Sign display LED
Parameter/value increase/decrease
keys
Status indications LED

Start up Guide for
Axpert
-
VT240S
Unit indication LEDs
(LED panel dedicated)
HzƒA ƒ%
Indicates the unit of the parameter value shown on
Minus polarity indication LED (
LED panel dedicated)
—— Lights
when the number on the display is a minus number.
Operation keys
Starts the drive in the forward direction in Local
Starts the drive in the reverse direction in Local
Stops the drive. The motor will either coast to a
on C00-1.
Held down for 2
sec.
When this key is held down for two seconds or longe
coast to stop.
During LCL, the motor will first decelerate to a st
During RMT, the motor will coast to a stop from the
+
STOP
LC
SE
Changes control Modes from Local to Remote, or vice
Mode, "LCL" LED is on.
In default condition, the Lo
Even while the drive is at a stop, this selection c
such as RUN, JOG, etc., are being received at the t
with Parameter C09
+
STOP
RS
MO
Resets a fault, putting out FLT LED.
Parameter operation keys
Parameter operation knob
!"#
$%&#
Changes the block No. mode displayed on the indicat
the key is pressed:
Monitor →
Parameter A
'('#
!)"#
Fixes Parameter number or set its values.
Parameter
Select
Valve change
Parameter increase/decrease key, parameter increase
or
Increases the parameter
or
Decreases the parameter No. or parameter setting va
or
+
When the parameter is being set with the sub
increases the parameter's main
+
or
When the parameter is being set with the sub
decreases the parameter's main No.
Operations dedicated for LED panel
Held down
Increases the parameter No. or
Held down
Decreases the parameter No. or setting value at a f
VT240S
Series AC Drive
(LED panel dedicated)
Indicates the unit of the parameter value shown on the display.
LED panel dedicated)
when the number on the display is a minus number.
Starts the drive in the forward direction in Local Mode only.
Starts the drive in the reverse direction in Local Mode only.
Stops the drive. The motor will either coast to a
stop or ramp down to a stop as selected
When this key is held down for two seconds or longer during operation, the motor will
During LCL, the motor will first decelerate to a stop, and then coast to a full
During RMT, the motor will coast to a stop from the current output frequency/speed.
Changes control Modes from Local to Remote, or vice
-
versa. When the drive is in Local
Mode, "LCL" LED is on.
In default condition, the Lo
cal/Remote selection is disabled while the drive is
Even while the drive is at a stop, this selection cannot be made if operating commands
such as RUN, JOG, etc., are being received at the terminal. This lock can be released
with Parameter C09
-2.
Resets a fault, putting out FLT LED.
Parameter operation knob
Changes the block No. mode displayed on the indicator in the following order each time
the key is pressed:
Parameter A
→Parameter B →Parameter C →
Utility Mode U.
Fixes Parameter number or set its values.
When main & sub-No. Selection method (C11-
7=2) is selected for
parameter setting method, moves from sub-No. S
election to main No.
selection.
Moves the digit to increment or decrement.
Parameter increase/decrease key, parameter increase/decrease knob
Increases the parameter
No. or parameter setting value.
Decreases the parameter No. or parameter setting value.
When the parameter is being set with the sub
-
No. selection method (C11
increases the parameter's main
No.
When the parameter is being set with the sub
-
No. selection method (C11
decreases the parameter's main No.
Operations dedicated for LED panel
Increases the parameter No. or
setting value at a fast speed.
Decreases the parameter No. or setting value at a fast speed.
stop or ramp down to a stop as selected
r during operation, the motor will
op, and then coast to a full
stop.
current output frequency/speed.
versa. When the drive is in Local
cal/Remote selection is disabled while the drive is running.
annot be made if operating commands
erminal. This lock can be released
or in the following order each time
Utility Mode U.
7=2) is selected for
election to main No.
No. selection method (C11
-7=1),
No. selection method (C11
-7=1),
setting value at a fast speed.
ast speed.

Amtech
Chapter-3: Initial Start-
up and Keypad Operation
The VT24
0S has various setting items. Some of these include
the power supply and motor before actually starting
The methods for the VT240S basic test operation and
3-1 Selection of Control M
ode
With the VT240S, four control modes a
parameter C30-
0 (control mode selection).
* C30-0 is set with a 2-digit value (
f1
(1) Control modes
Refer to the following table, and select the
Control mode
Normal-duty
1) V/f control
2) IM sensor-less
vector control
3) IM close loop
vector control
4) PM
motor close
loop control
Heavy-duty
1) V/f control
2) IM sensor-less
vector control
3) IM close loop
vector control
4) PM motor
close
loop control
Normal-duty setting:
Select this when the maximum load rate in respect t
The overload standard will be 120% of the device's
Heavy-duty setting:
Select this when the maximum load rate in res
The overload standard will be 150% of the device's
3-
2 Initialization of motor constants
Input the motor rating parameters.
up and Keypad Operation
0S has various setting items. Some of these include settings
that must be made according to
the power supply and motor before actually starting operation.
The methods for the VT240S basic test operation and adjustment are explained in this section.
ode
With the VT240S, four control modes a
nd two overload modes can be selected. These are se
0 (control mode selection).
f1
, f0).
Refer to the following table, and select the
mode, which suits the application.
Explanation
The IM
is controlled keeping the ratio of voltage and
frequency constant.
The IM is vector-
controlled without a speed sensor.
The speed can be controlled.
PLEASE REFER FULL INSTRUCTION MANUAL
motor close
PLEASE REFER FULL INSTRUCTION MANUAL
The IM
is controlled keeping the ratio of voltage and
frequency constant.
The IM is vector-
controlled without a speed sensor.
The speed can be controlled.
PLEASE REFER FULL INSTRUCTION MANUAL
close
PLEASE REFER FULL INSTRUCTION
MANUAL
Select this when the maximum load rate in respect to the rated load is low.
The overload standard will be 120% of the device's rated current for one minute.
Select this when the maximum load rate in res
pect to the rated load is high.
The overload standard will be 150% of the device's rated current for one minute.
2 Initialization of motor constants
Input the motor rating parameters.
Set the parameters shown in Table 4-2-1.
Automatic tuning will
automatically change the parameters, so it is
recommended to write down the values set
in Table 4-2-2 or Table 4-2-3.
The figure to the left shows the information
provided on a typical AC motor nameplate.
There are several important m
that will be used to program the drive to
provide accurate motor operation and
protection. The motor HP will be
programmed in KW. To change from HP to
KW, multiply by 0.75. The 10HP shown
would be 10 x 0.75 = 7.5KW. For this case
motor, assumin
g the input voltage >460,
B00-0=6, B00-1=2, B00-
2=7.5, B00
that must be made according to
adjustment are explained in this section.
nd two overload modes can be selected. These are set with the
C30
-
0
is controlled keeping the ratio of voltage and
11
controlled without a speed sensor.
12
PLEASE REFER FULL INSTRUCTION MANUAL
13
PLEASE REFER FULL INSTRUCTION MANUAL
14
is controlled keeping the ratio of voltage and
21
controlled without a speed sensor.
22
PLEASE REFER FULL INSTRUCTION MANUAL
23
MANUAL
24
o the rated load is low.
pect to the rated load is high.
Automatic tuning will
automatically change the parameters, so it is
recommended to write down the values set
The figure to the left shows the information
provided on a typical AC motor nameplate.
There are several important m
otor values
that will be used to program the drive to
provide accurate motor operation and
protection. The motor HP will be
programmed in KW. To change from HP to
KW, multiply by 0.75. The 10HP shown
would be 10 x 0.75 = 7.5KW. For this case
g the input voltage >460,
2=7.5, B00
-3=460,

Start up Guide for Axpert-VT240S Series AC Drive
7
B00-4=60.00, B00-5=60.00, B00-6=15.0
Table 4-2-1
Applicable mode
Parameter No.
Name
C30-0 = 11 or 21
B19-0 = 1, 2
B00
-
0
B00-1
B00-2
B00-3
B00-4
B00-5
B00-6
B00
-
7
Rated input voltage
setting
[No.]
Max/base frequency simple setting [Hz]
Motor rated output [kW]
Rated output voltage [V]
Maximum frequency (Note 1) [Hz]
Base frequency (Note 1) [Hz]
Motor rated current [A]
Carrier frequency
(Note 1)
The maximum frequency cannot be set below the base frequency, and the base frequency
cannot be set above the maximum frequency.
3-3 Automatic tuning & Test operation
Automatic tuning measures the constants of the connected motor, and automatically adjusts the
parameters so that the system is used to the fullest.
The VT240S automatic tuning function performs different measurements for each of the four control
modes. Carry out automatic tuning each time the motor being used or the applicable control mode is
changed. The automatic tuning mode is set with parameter B19-0 (automatic tuning selection). Refer
detail instruction manual for other control modes.
B19-0 Name
1 Simple adjustment mode for v/f control mode
2 High-function adjustment for v/f control mode
Automatic tuning will automatically change the parameters, so it is recommended to write down
the values set in Table 4-5-2 or Table 4-5-3.
Table 4-2-2
Applicable mode
Parameter No.
Name
Explanation
C30-0 = 11 or 21
B19-0 = 1
A02
-
2
A03-0
B02-0, 1
B02
-
4,
5
Manual torque boost setting
DC brake voltage
R1: Primary resistance
L
σ
: Leakage inductance
The basic parameters, such as
boost voltage and brake voltage,
are adjusted without rotating the
motor.
Table 4-2-3
Applicable mode
Parameter No.
Name
Explanation
C30-0 = 11 or 21
B19-0 = 2
A02-2
A03-0
B02-0, 1
B02-4, 5
A02-5
A02-6
Manual torque boost setting
DC brake voltage
R1: Primary resistance
L
σ
: Leakage inductance
Slip compensation gain
Max. torque boost gain
The parameters related to the
slip compensation and max.
Torque
boost are adjusted while
rotating the motor.
The magnetic saturation
characteristics are measured at
the voltage boost, and are
adjusted to match the max.
torque boost.

Amtech
3-3-1
Automatic tuning operation procedures
Separate the motor and load, machine, etc., and con
1)
Selecting and executing the automatic tuning mode
Select the automatic tuning mode and execute automa
•
The operation panel's operation mode must be set to
sure that the "LCL" LED is ON. If not, press the
LED turns ON.
• Set A05-
0 to 1. (Set the expanded setting display ON.)
• Using B19-
0 (automatic tuning selection), select the automati
working conditions.
•
The automatic tuning standby state will be entered
•
During the automatic tuning standby state and the a
will flicker.
•
To exit the automatic tuning standby state, press t
2) Starting automatic tuning
Automatic tuning will start when the
rotation direction.
To stop, press the
key or input the emergency stop signal (EMS) from t
*
Once automatic tuning starts, all panel operations
are disabled until the operation ends.
3)
During automatic tuning execution
The progression state can be confirmed with D22
4) Normal
completion of automatic tuning
When the automatic tuning ends normally, the "LCL"
The "RUN"
LED will change from a stable light to the OFF stat
5
) Abnormal completion of automatic tuning
If automatic tuni
ng ends abnormally, the "FLT" LED will turn ON and
Investigate and check according to the error codes.
Automatic tuning operation procedures
(V/f control mode)
Separate the motor and load, machine, etc., and confirm the safety on the load side.
Selecting and executing the automatic tuning mode
Select the automatic tuning mode and execute automatic tuning
.
The operation panel's operation mode must be set to "Local" to execute automatic tuning. Make
sure that the "LCL" LED is ON. If not, press the
!
"#$
+
"$%&'
keys, and confirm that the "LCL"
0 to 1. (Set the expanded setting display ON.)
0 (automatic tuning selection), select the automatic tuning mode according to the
The automatic tuning standby state will be entered when the
!
"#$
key is pressed.
During the automatic tuning standby state and the automatic tuning execution state, the
To exit the automatic tuning standby state, press the
key.
Automatic tuning will start when the
key or
key is pressed according to the required
key or input the emergency stop signal (EMS) from the terminal block.
Once automatic tuning starts, all panel operations other than the
"$%&'
,
!"
#$%
and
are disabled until the operation ends.
During automatic tuning execution
The progression state can be confirmed with D22
-0.
completion of automatic tuning
When the automatic tuning ends normally, the "LCL" LED will change from a flicker to a stable light.
LED will change from a stable light to the OFF state.
) Abnormal completion of automatic tuning
ng ends abnormally, the "FLT" LED will turn ON and a message will appear.
Investigate and check according to the error codes.
Upper level:
The steps required for tuning are
indicated (lit).
Lower level:
The finished steps are indicated (lit).
The step currently being executed is
indicated with a flicker.
"Local" to execute automatic tuning. Make
keys, and confirm that the "LCL"
c tuning mode according to the
utomatic tuning execution state, the
"LCL" LED
key is pressed according to the required
he terminal block.
keys
LED will change from a flicker to a stable light.
a message will appear.
The steps required for tuning are
The finished steps are indicated (lit).
The step currently being executed is
indicated with a flicker.

Start up Guide for Axpert-VT240S Series AC Drive
9
3-3-2 Automatic tuning error messages
If automatic tuning ends abnormally, the following message will appear. Investigate and confirm the
state following the error code.
– n
Automatic tuning step
No. Cause and remedy
n=1 The motor may not be connected correctly.
Check the connection.
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=2 The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=3 The load and machine may not be separated.
Separate the load and machine.
Lengthen the acceleration time (A01-0).
Lengthen the deceleration time (A01-1).
If the motor vibrates, adjust the torque stabilizing gain (B18-2).
Normally, the d
efault value (1.00) is set, but increase the setting value in increments of approx.
0.05 according to the state of hunting. Please return to regulated value (1.00) of a set value
once, and reduce it by carving about 0.05 when the hunting phenomenon is not controlled
even in case of maximum value (4.00).
n=4 The load and machine may not be separated.
Separate the load and machine.
If the motor vibrates, increase the torque stabilizing gain (B18-2).
Normally, the d
efault value (1.00) is set, but increase the setting value in increments of approx.
0.05 according to the state of hunting. Please return to regulated value (1.00) of a set value
once, and reduce it by carving about 0.05 when the hunting phenomenon is not controlled
even in case of maximum value (4.00).
n=5 When the motor does not stop
Increase the acceleration/deceleration time (A01-0, A01-1).
When the motor does stop
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=6 The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=8 Indicates that the output voltage did not stabilize for 1 second or more during magnetic pole
position estimation for the PM motor.
n=9 Indicates that the PM motor magnetic pole estimation did not end normally even after retrying
three times.

Amtech
3-4 Test
operation (V/f control mode)
When finished with automatic tuning, test run the i
errors. Use the following procedures to test the op
Refer to Chapter 3 for details on using the operati
1) To
enable operation with the operation panel, confirm
!
"#$
+
"$%&'
keys, and confirm that the "LCL" LED turns ON.
2) Set speed
setting input point selection: C02
The motor will rotate with the next step.
Confirm the safety around the motor before starting
3) Press the
!"
#$%
and display D00
The "FWD"
lamp will turn ON, and the display will change from
value will gradually increase, and after several se
be
cause as the factory settings, the direct setting
acceleration ramp time 1 (A01-
0) is set to 10
1. Did the motor run?
2.
Is the run direction correct? Check the wiring and
3. Is the rotation smooth?
4) Press the
key and confirm that the motor runs in reverse.
(Note)
Do not carry out this step if a
5) Press the
key and stop the motor.
6) Press the key.
The motor will
Change the frequency to 50
Hz with the following operation.
7) Press the
!"
#$%
key several times.
".
8) Press the
!
"#$
key once.
The display will stop at "
This completes the preparation for changing the out
moved with the
ke
y. The output frequency can be Incremented/D
keys.
9) Move the digit with the
key, and using the
press the
!
"#$
key. The output frequency will rise to 50 Hz.
(Note) T
he operation panel frequency change operation is se
time at the factory shipment settings, and therefor
using the
keys, without having to press the
When the
!
"#$
key is pressed, the current setting value will be s
operation (V/f control mode)
When finished with automatic tuning, test run the isolated motor, and make
sure that there are no
errors. Use the following procedures to test the operation with the operation panel.
Refer to Chapter 3 for details on using the operation panel.
enable operation with the operation panel, confirm that the "LCL" LED is ON. If not, press the
keys, and confirm that the "LCL" LED turns ON.
setting input point selection: C02
-0= 3 (panel fixed).
CAUTION
The motor will rotate with the next step.
Confirm the safety around the motor before starting the next step.
and display D00
-0 on the monitor. Then press the
key. Operation will start.
lamp will turn ON, and the display will change from "
" to a value display. The
value will gradually increase, and after several seconds, will change to "
cause as the factory settings, the direct setting
frequency (A00-
0) is set to 10
0) is set to 10
sec.
CHECK
Is the run direction correct? Check the wiring and operation if abnormal.
key and confirm that the motor runs in reverse.
Do not carry out this step if a
load, which cannot be run in reverse,
is connected.
key and stop the motor.
The motor will
forward run at the output frequency 10 Hz.
Hz with the following operation.
key several times.
The Display will alternate between "
", and the last digit will flicker.
This completes the preparation for changing the output frequency. The digit to change can be
y. The output frequency can be Incremented/D
ecremented with the
key, and using the
key
, raise the frequency to 50
key. The output frequency will rise to 50 Hz.
he operation panel frequency change operation is set to be changed (C11
time at the factory shipment settings, and therefore the output frequency is changed in real time
keys, without having to press the
!
"#$
key.
key is pressed, the current setting value will be saved.
sure that there are no
that the "LCL" LED is ON. If not, press the
key. Operation will start.
" to a value display. The
". This is
0) is set to 10
Hz and the
is connected.
" and "
put frequency. The digit to change can be
ecremented with the
, raise the frequency to 50
.00 Hz. Then,
t to be changed (C11
-2=1) in real
e the output frequency is changed in real time

Start up Guide for
Axpert
-
VT240S
Series AC Drive
CAUTION
A 10-second acceleration and 20-second deceleration ramp time are set as defaults. The motor
will slowly increase its speed to the set value.
When making a setting (using the
keys), check that the motor operates correctly at
each increment of approx. 10Hz.
10) Press the
!"
#$%
key several times, and display D00-0. When the output frequency ("D00-0"
display) reaches 50Hz, press the
!"#$
key.
The display will decrease to "0.00" in several seconds. The "FWD" or "REV" LED will flicker for two
seconds while the DC-brake is applied and the motor will stop.
11) Press the key, and test the reverse run at 50Hz.
(Note) Do not carry out this step if a load which cannot be run in reverse is connected.
This completes the test operation with the operation panel.
After this, refer to Chapter 5 and carry out the settings and adjust the load operation to match the
user's application.
12) Acceleration / Deceleration Time
Program the required acceleration time and deceleration time in parameters A01-0 and A01-1
respectively. The value programmed is the time from zero to maximum frequency in seconds
(Acceleration Time) or maximum frequency to zero in seconds (Deceleration Time).

Amtech
Chapter-4: Remote Terminal Operation
4-1 Start / Stop Operation from terminal
In default condition, basic operation (start/stop) control is from digital operation panel (LCL). The basic
operations (start/stop) can be controlled from terminal shown in the below fig.
When LCL LED is off, the drive is in the Remote Mode and can be controlled from the terminal block
(sequence input signals). To change Modes between Local and Remote, press
!"#$
and
%&%
'!
keys
simultaneously
+
STOP
LC
SE
.
Change this setting while operation is stopped
.
Select start/stop command method using C00-0.
4-1-1 Two wire start/stop (C00-0=1): This mode is also called maintined type start/stop. In this
method, the F:RUN or R:RUN is through 2-wire. Assign sequence command, F.RUN and R.RUN with
C03-0=1 and C03-2=2. In this example, PSI1 is used. Connect two wires to PSI1 and RY0 through
switch (NO) for forward run. When the switch is closed, the drive will start. It will stop when the switch is
opened.
PSI1
F: RUN
RY0
START
4-1-2 Two wire start/stop with separate input for direction change (C00-0=2): Set the sequence
command, F.RUN and R.RUN with C03-0=1 and C03-2=2. In this example, PSI1 and PSI2 are used.
As in default condition, PSI2 is assigned to RESET in C03-7, set C03-7=0. In this mode, the start/stop
is controlled by the switch connected between PSI1 & RY0 and the direction is decided by the status of
the switch connected between PSI2 & RY0. If the switch at PSI2 is open, the direction is forward. If the
switch at PSI2 is closed, the direction is reverse.
Reverse
PSI2
PSI1
F: RUN
RY0
R: RUN (REV)
Start
4-1-3 Three wire start/stop (self hold): This mode is also called as momentary start/stop as the
start/stop operations are through push buttons. Set the sequence command, F.RUN and HOLD with
C03-0=1 and C03-5=2. In this example, PSI1 and PSI2 are used. As in default condition, PSI2 is

Start up Guide for Axpert-VT240S Series AC Drive
13
assigned to RESET in C03-7, set C03-7=0. In this mode, the start operation is controlled by normally
open type push button connected between PSI1 & RY0 and stop by normaly close type push button
connected between PSI2 & RY0. Press start push button to start the drive. Press stop push button to
stop the drive.
F: RUN
HOLD
RY0
Stop
PSI2
PSI1
Start
4-2 Speed reference setting selection
The ten types of speed setting inputs shown below can be used.
One of the ten types of inputs can be selected by setting a parameter or with the sequence input.
In default condition, the speed reference is from the digital operation panel (keypad) A00-0. The speed
reference can be assigned to any of the following.
4-2-1 Keypad (A00-0)
The frequency reference from keypad when the start/stop operation is through terminal can be assigned
by setting following parameters.
Step-1: Set C03-D=0.
Step-2: Set the desired frequency in A00-0.
4-2-2 Potentiometer (or 0-10V)
To assign the potentiometer (or 0-10V) as speed reference, one needs to connect the potentiometer (or
0-10V) to any one analog input from AI1, AI2 or AI3. Follow below steps to use potentiometer (or 0-10V)
as speed reference.
Step-1: Select the analog input. In this example, the potentiometer (or 0-10V) is connected to AI1. Set
C12-0=1 and DIP switch DS1-2 to OFF position.
2k/2W
AI1
P10
Potentiometer
COM
DS1-2=OFF
Step-2: Assign the selected analog input (AI1, AI2 or AI3) to speed setting input1, speed setting input2 or
speed setting input3 using C07-0, C07-1 and C07-2. By default, AI1 is assigned to speed setting input1
(C07-0=2)
Step-3: Set speed setting input using C03-D, C03-E or C03-F. In our example, as we have used speed
setting1, we need to set C03-D=16: ON Fixed.
If one requires switching the speed reference between digital operation panel (A00-0) and potentiometer
(or 0-10V), assign any sequence input (PSI) to C03-D. For example, PSI5 is assigned to switch reference.
Set C03-D=5 and C03-3=0. When PSI5 is open, the speed reference will be through keypad (A00-0) and
when PSI5 is closed the speed reference will be potentiometer (or 0-10V).

Amtech
14
4-2-3 Speed reference through 4-20mA
To assign the 4-20mA as speed reference, one needs to connect the 4-20mA analog signal to any one
analog input from AI1, AI2 or AI3. Follow below steps to use 4-20mA as speed reference.
Step-1: Select the analog input. In this example, the 4-20mA analog signal is connected to AI2. Set
C12-4=2 and DIP switch DS1-3 to ON position.
Step-2: Assign the selected analog input (AI1, AI2 or AI3) to speed setting input1, speed setting input2 or
speed setting input3 using C07-0, C07-1 and C07-2. By default, AI2 is assigned to speed setting input2
(C07-1=3)
4-20mA signal
AI2
COM
DS1-3=ON
Step-3: Set speed setting input using C03-D, C03-E or C03-F. In our example, as we have used speed
setting2, we need to set C03-E=16: ON Fixed.
If one requires switching the speed reference between digital operation panel (A00-0) and 4-20mA),
assign any sequence input (PSI) to C03-E. For example, PSI5 is assigned to switch reference. Set
C03-E=5 and C03-3=0. When PSI5 is open, the speed reference will be through keypad (A00-0) and
when PSI5 is closed the speed reference will be 4-20mA.
4-2-4 Speed reference through ±10V signal
To assign the ±10V signal as speed reference, one needs to connect the ±10V analog signal to any one
analog input from AI1, AI2 or AI3. Follow below steps to use ±10V signal as speed reference.
+/-10V signal
AI
3
COM
Step-1: Select the analog input. In this example, the ±10V analog signal is connected to AI3.
Step-2: Assign the selected analog input (AI1, AI2 or AI3) to speed setting input1, speed setting input2 or
speed setting input3 using C07-0, C07-1 and C07-2. Assign AI3 to speed setting input3 (C07-2=4)
Step-3: Set speed setting input using C03-D, C03-E or C03-F. In our example, as we have used speed
setting3, we need to set C03-F=16: ON Fixed.
If one requires switching the speed reference between digital operation panel (A00-0) and ±10V signal),
assign any sequence input (PSI) to C03-F. For example, PSI5 is assigned to switch reference. Set
C03-F=5 and C03-3=0. When PSI5 is open, the speed reference will be through keypad (A00-0) and
when PSI5 is closed the speed reference will be ±10V signal.
4-2-5 Speed reference through Increment / Decrement push buttons (static pot or electronic pot)
To assign the Increment / Decrement push buttons as speed reference, one needs to connect two push
buttons to PSI for increment and decrement the speed reference. Follow below steps to use static pot as
speed reference.
Step-1: Assign FUP and FDW to any PSI using C04-7 and C04-8 respectively. In this example, PSI5 is
assigned to Increment push button and PSI6 is assigned to Decrement push button. Set C04-7=5,
C04-8=6, C03-3=0 and C03-4=0.

Start up Guide for Axpert-VT240S Series AC Drive
15
RY0
FDW
FUP
PSI6
PSI5
Step-2: Set C03-D=0.
Note that the speed reference will be incremented or decremented from the A00-0 set value. So, set the
initial desired speed reference to A00-0. When the ON state continues, the frequency is incremented/
decremented with the currently valid acceleration time.
4-2-6 Use of Multiple Preset Speed reference
To assign multiple preset speed reference, one needs to connect selector switches to digital inputs (PSI)
to select the desired preset speed. Follow below steps to use preset speed reference. This drive has
facility to select the speed as per the binary logic as well as direct method. Both the methods are
described here. In this example, only two digital inputs PSI2 and PSI3 are used for preset speed setting.
PSI1 is used for start.
Binary method for speed selection:
Step-1: Connect selector switch for start between PSI1 & RY0.
Step-2: Assign PSI2 to S0 by setting C04-2=2 and PSI3 to S1 by setting C04-3=3. As PSI1 and PSI2
are assigned to other functions in default conditions, clear them first by setting C03-1=0 and C03-7=0.
Connect selector switches S0 and S1 between PSI2 & RY0 and PSI3 & RY0 respectively.
S0
PSI2
PSI1
PSI2
RY0
S1
S0
S1
Start
F: RUN
Step-3: Set C04-0=16
Step-4: Set B11-8=1 for binary method for speed selection
Step-5: Set the desired frequency in parameter B11-0, B11-1 and B11-2
Step-6: When both the switches are OFF, the previous set frequency will be selected.
Step-7: Keep only S0 switch to ON position, the frequency set in B11-0 will be selected.
Step-8: Keep only S1 switch to ON position, the frequency set in B11-1 will be selected.
Step-9: When both the switches are kept to ON position, the frequency set in B11-2 will be selected.
Below table shows how the multiple preset speed (frequency) can be selected using more digital inputs
(PSI1 ~ PSI7).
Refer detail instruction manual for more detail and timing diagrams on this
application.

Amtech
16
(1) For binary mode (B11-8 = 1)
Sequence command Selected
frequency
SE S3 S2 S1 S0
**
OFF OFF OFF B11-0
OFF OFF ON B11-1
OFF ON OFF B11-2
OFF ON ON B11-3
ON OFF OFF B11-4
ON OFF ON B11-5
ON ON OFF B11-6
ON ON ON B11-7
*: SE and S3 are not used.
Direct method:
Step-1: Connect selector switch for start between PSI1 & RY0.
Step-2: Assign PSI2 to S0 by setting C04-2=2 and PSI3 to S1 by setting C04-3=3. As PSI1 and PSI2
are assigned to other functions in default conditions, clear them first by setting C03-1=0 and C03-7=0.
Connect selector switches S0 and S1 between PSI2 & RY0 and PSI3 & RY0 respectively.
S0
PSI2
PSI1
PSI2
RY0
S1
S0
S1
Start
F: RUN
Step-3: Set C04-0=16
Step-4: Set B11-8=2 for direct method
Step-5: Set the desired frequency in parameter B11-0 and B11-1
Step-6: When both the switches are OFF, the previous set frequency will be selected.
Step-7: Keep only S0 switch to ON position, the frequency set in B11-0 will be selected.
Step-8: Keep only S1 switch to ON position, the frequency set in B11-1 will be selected.
The table shows how the multiple preset speed
(frequency) can be selected using more digital inputs
(PSI1 ~ PSI7).
Refer detail instruction manual for
more detail and timing diagrams on this
application.
(2) For direct select mode (B11-8 = 2)
Sequence command Selected
frequency
SE S3 S2 S1 S0
OFF OFF OFF OFF OFF Previous values
OFF OFF OFF OFF ON B11-0
OFF OFF OFF ON OFF B11-1
OFF OFF ON OFF OFF B11-2
OFF ON OFF OFF OFF B11-3
ON OFF OFF OFF OFF Previous values
ON OFF OFF OFF ON B11-4
ON OFF OFF ON OFF B11-5
ON OFF ON OFF OFF B11-6
ON ON OFF OFF OFF B11-7
When S0 to S3 are all OFF, or when two or more are set
between S0 and S3, the previous values will be held.
If there are no previous values because the power has been
turned ON, etc., "0" will be set.

Start up Guide for Axpert-VT240S Series AC Drive
17
Chapter-5: Control Input/Output
Fig. 5-1-a
F
A
VT2
40S
+15V
0V
0V
0VOP
RY
RY
11k
Ω
2kΩ
2W 10kΩ
750
Ω
Analog output
• Changeable to 0 to 10V
or 4 to 20mA
0 to 10V max. 1mA
4 to 20mA max. 500Ω
• All terminal functions can
be changed.
Serial communication
(RS-485)
CN2 and TB3 cannot be
used simultaneously.
2
4
1
5VOP
Terminator
PSO1
PSO2
PSO3
PSOE
DATA+
0VOP
5VOP
DATA+
DATA-
0VOP
3
CN2 : Modular Connector
PSI1
PSI2
PSI3
PSI4
PSI5
PSI6
PSI7
RY0
4.7kΩ
RY24V
4.7k
Ω
RY0V
Sink
Source
Sink/source logic changeover
RY24
510Ω
11k
Ω
10kΩ
510Ω
20kΩ
P10
AI1
AI2
AI3
COM
0V
0V
COM
AO1
AO2
COM
COM
RY24V
RY
0
V
RA
RC
FA
FB
FC
Sequence output
(Relay output)
• RA-RC
Max. 250VAC 1A
Max 30VDC 1A
• FA-FB-FC
Max. 125VAC 0.4A
Max. 30VDC 1A
• All terminal functions can
be changed.
Sequence output
(Open collector output)
• Max. 30VDC 50mA
• PS03 can be changed to
pulse output
• All terminal functions can
be changed.
Sequence input
• 5mADC
• PSI7 can be changed to
pulse input
•
All terminal functions can be
changed.
Analog input
• AI1, AI2
Changeable to voltage
signal or current signal
Voltage signal max. 10VDC
Current signal max.
20mADC
• A13 max. ±10VDC
•
All terminal functions can be
changed.
Frequency setting
20k
Ω
DATA-
Forward run
Emergency stop
Reset signal
Reverse run
Forward jog
Reverse jog
Run
Fault
READY 1
Current
detection
Speed attained
(Note2)
1 1
W2
W1
2 2
(N
ote1)
(Note1)
(Note1)
(Note4)
(Note4)
(Note3)
(Note5)
TB3 : Terminal
(Notes)
1. Four COM terminals are internally connected.
2. No connection shall be made between RY0, COM and 0VOP since this section is insulated.
3. This diagram is an example of the sink logic connection.
4. RY24 and RY0 must not be shorted.
5. P10 and COM must not be shorted.
Fig. 5-1-b
DS1
TB2
PSI5
PSI7
PSO2
PS
O
E
FB
FC
FA
PSI4
PSI6
PSO1
PSO3
RY0
RC
RA
CN2
TB1
AI1
AO1
AO2
RY24
PSI2
COM
COM
PSI1
PSI3
AI3
COM
AI
2
COM
P10
2
2
1
W1
1
W
2
W
4
2
1
2
1
W
3
SG D
-
D+
1 2 3 4
ON
TB3
Table of contents
Other Amtech Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Lippert
Lippert JT's Strong Arm Travel Trailer Installation and owner's manual

Spectrex
Spectrex SharpEye 777915 Series installation guide

GMTCNT
GMTCNT GSTD2556 user guide

Weller
Weller Zero Smog TL Translation of the original instructions

fiorini
fiorini SET PLUS 2.0 - 25 Use and maintenance manual

SMC Networks
SMC Networks INR-244-757 Operation manual