The ALD-300 is a hand-held leak detector that uses the
infrared detection principle. Compared with the traditional
leak detector, its sensor has longer life, higher detection
accuracy, easy to operate and can detect a wider range of
refrigerant. ALD-300 is equipped with large LCD screen, so
that the test results are more intuitive. The exclusive desi-
gn of appearance is in accordance with human body me-
chanics to make it the best experience for users.
Specifications
- Sensor principle: infrared spectrum absorption
- Sensor life: 10 years
- Sensitivity: max 4g /yr
- Alarm mode: sound and light alarm, LCD display
- Battery: built-in rechargeable lithium battery 3.7V 3000mAh
- Working time: continuous 6H
- Charging: 4 hours
- Operating environment:-10°C to 52°C/ Relative humidity (20%
to 85% RH)
- Storage temperature: -20°C to 60°C (-4°F to 140°F)
- Weight: 415g (14.6oz)
- Size: 201mm * 86mm * 38mm (7.9 "* 3.3" * 1.5 ")
- Certication: SAE_J1627, SAE_J2791, SAE_J2913; EN14624: 2012; CE
certication
Structure
1. Flexible probe
2. Case
3. Probe tip
4. USB Port
5. Buzzer
6. Battery
7. Peak
8. Leak
9. Sensitivity
10. Button
④
①
②
⑤
⑥
⑦
⑨
⑩
⑧
③
GAS/RSET
H2CO2HC R1234YF
PEAK
SEN: L
WARM UP
PEAK
MUTESENS
ON/OFF
GAS/RSET
H2CO2HC R1234YF
PEAK
SEN: L
WARM UP
PEAK
MUTESENS
ON/OFF
GAS/RSET
H2CO2HC R1234YF
PEAK
SEN: L
WARM UP
PEAK
MUTESENS
ON/OFF
- Check the device has sufficient battery
level.Turn on ( on/off button ) and wait
for 30 seconds before testing.
- Adjust the sensitivity ( sens ).
Setup
Key Operation
- ON/OFF key: press the button for 2 seconds
to power on/off.
- RSET key: long press the button for 3 seconds
to reset sensitivity benchmark.
- PEAK key : press the button to record the
maximum value of leakage.
- SENS key: press the button to adjust sensitivity
levels. By default sensitivity is set to medium.
- MUTE key: press the button to turn on/off the buzzer.
GAS/RSET PEAK
MUTESENS
ON/OFF
GAS/RSET
H
2
CO
2
HC R1234YF
PEAK
SEN: L
WARMUP
PEAK
MUTESENS
ON/OFF
GAS/RSET
H2CO2HC R1234YF
PEAK
SEN: L
WARM UP
PEAK
MUTESENS
ON/OFF
- Slowly move probe ( approx 3 inch/sec )
at a distance of 0.25 inch near suspected
leak area.
- Detection: when a leak is detected, the
screen will show the intensity of the
leak and audible tone will change to a
siren sound.