Galaxy 4" 910101-000513 Page 3 of 20
The user should arrange suitable platforms and safety barriers to enable easy and safe access to the filter
without climbing on pipes and other equipment. The user should verify that any platform, barrier, ladder or
other such equipment is built, installed and used in accordance with the relevant local authorized standards.
Check and re-tighten all bolts during commissioning and after the first week of operation.
Use only appropriate standard tools and equipment operated by qualified operators when installing,
operating and maintaining the filter.
When installation is required in hazardous environment sites, underground or high above ground, make sure
that the site design and the auxiliary equipment are appropriate and that installation procedures are carried
out in accordance with the relevant standards and regulations.
Ensure walking areas about the installation are slip free when wet.
Shipment and transporting
Shipping and transporting the filter must be done in a safe and stable manner and in accordance with the
relevant standards and regulations.
For shipping, lifting and positioning the filter, use only approved lifting equipment and authorized employees
and contractors.
Electricity
Electric wiring should be performed by an authorized electrician only, using standardized and approved
components.
The system must be installed with suitable electrical earthing that would prevent any electrostatic discharge
from the system.
Install a lockable main power cut-off switch close to the control panel.
If due to site constraints, the control panel is installed without a clear line-of sight of the filter, an additional
lockable power disconnect cut-off switch should be installed near each filter unit.
Installation of the filter should be performed so as to avoid direct water splashing on the electrical
components or on the control panel.
Pneumatics
Install a lockable main cut-off switch, featured with a pressure release mechanism, on the compressed air
supply line close to the control panel.
If the control panel is installed far away and there is no eye contact with the filter, a lockable compressed air
cut-off switch, featured with a pressure release mechanism, should be installed near each filter unit.
The user should make sure that the compressed air supplied to the filter never exceeds the maximum
designated pressure for this filter. An air-pressure reduction valve should be installed on the compressed air
supply line upstream of the filter’s pneumatic inlet port.
Hydraulics
Extra safety devices should be installed on hot water applications to avoid skin burn danger.
The user should install a manual Water Cut-off Valve next to the filter’s inlet port.
In cases where the downstream piping network downstream of the filter is pressurized an additional manual
Water Cut-off Valve should be installed next to the filter outlet port.
The user should make sure that the system includes a Pressure Release / Drainage Valve to enable release of
residual pressure prior to any maintenance procedure performed on the filter.
The user should make sure that the filter is never exposed to water pressure exceeding the maximum
designated pressure for this filter, if needed a Pressure Reduction Valve should be installed upstream of the
filter’s water inlet port.
Please note that the maximum working pressure indicated at the filter’s specifications table includes the
pressure caused by fluid hammer and pressure surge effects.