
50-60 Hanover Road, Florham Park, New Jersey 07 32 www.ascovalve.com
Form No.V8700R1
Page 2 of 4
SPECIFICATIONS
Force Output: 250 lbs
Stroke: 1 1/8I
Electrical Characteristics:
Operating Amperes (nominal)
Voltage * Inrush Running Holding
24V/50-60Hz
120V/50-60Hz
240V/50-60Hz
28.00
5.60
2.80
8.00
1.85
0. 2
0.73
0.11
0.05
*50 Hz construction increases opening time 20%.
Opening Time: Fast Opening: 6 to 14 seconds
Slow Opening: 14 to 26 seconds
Note: Opening time doubles between -30_F to -40_F
(-34_C to -40_C). Timing not field adjustable.
Maximum Closing Time: One second
Temperature Limitations: Ambient -40_F to 150_F
(-40_C to 66_C)
Damper Arm Rating: Dri es damper in one direction only.
20 lb maximum at 2.85 in. radius at 20_F to 150_F
(-7_C to 65_C ) and 10 lb maximum at -40_F to 20_F
(-40_C to -7_C).
Damper Arm Travel: 2I maximum
INSTALLATION
Before installation, check nameplates to erify actuator and
al e selected are appropriate for the application.
IMPORTANT: After actuator installation, test all functions
and check out complete system before putting actuator/valve
into service.
Positioning/Mounting
Follow the V710 Series Gas al e and/or damper
manufacturer's instructions when installing the Hydramotorr.
1. AH2D actuators can be installed to operate in any
position.
2. Position the actuator to operate the al e (and damper if
appropriate), and secure with the two mounting set screws
(Figure 2). Torque set screws to 80 ± 5 in-lbs
[9,0 ± 0,5 Nm] using a 5/32I hex key wrench.
3. For damper applications requiring the damper arm to
return upon power failure, the optional return spring and
spring plug (kit 440006) must be installed on the damper
arm. Connect linkage so that damper returns to the
desired position.
Wiring
WARNING: Electrical hazard. To prevent the
possibility of death, serious injury or property
damage, open circuit before inspection, service or
disassembly. Reassemble before operating.
Wiring must comply with local codes and the National
Electrical Code. Limit controls must conform to actuator
rating ( oltage, amperage, hertz). Wire limit controls to the hot
side of power supply.
1. Remo e six screws and electrical co er.
2. Route wiring through one of the conduit knockout
openings. Install appropriate electrical fittings.
3. Connect the power wiring to terminals N (neutral) and L1
(hot). A green grounding screw with a cup washer is
pro ided beside the terminal strip for grounding.
(Figure 3).
4. Torque terminal screws to 8-12 in-lbs [0,9-1,3 Nm].
5. Connect auxiliary or al e o ertra el proof-of-closure
switch wiring to the common and normally open or
normally closed switch terminals (Figure 3).
6. Reinstall electrical co er on actuator housing.
7. Operate system through fi e cycles to erify proper
operation.
Figure 3. Typical AH2D Actuator Wiring.
NC
NO
COMM
Travel limit switch
Auxiliary or overtravel proof-of-closure switch
Grounding screw with cup washer
N
L1
1
2
3
4
LINE VOLTAGE
C
NO
Auxiliary and Overtravel Proof-of-Closure
Switch Ratings
15 Amps 120 Vac
7.5 Amps 240 Vac
Total connected load of auxiliary and o ertra el
proof-of-closure switches not to exceed 1800 VA.
CAUTION: Overtravel roof-of-closure switch
must only be used with V710 Series Gas Valves
having an overtravel seal (V22 or V25 Suffix in catalog
number).
Overtravel Proof-of-Closure Switch
The optional al e o ertra el proof-of-closure switch is set at
the factory to pro ide both a mechanical and electrical means
of pro ing al e closed position interlock to the primary
control. This switch is not to be field adjusted.