
50 Hanover Road, Florham Park, Ne Jersey 07932 .ascovalve.com
Form No.V8714 - Sec. 1
Page 2 of 6 (Section 1 of 2)
SPECIFICATIONS
Force Output: 250 lbs
Stroke: 1 1/8 maximum
Electrical Characteristics:
perating Amperes (nominal)
Voltage * Inrush Running Holding
24V/50-60Hz
120V/50-60Hz
240V/50-60Hz
28.00
5.60
2.80
8.00
1.85
0.92
0.73
0.11
0.05
*50 Hz construction increases opening time 20%.
Opening Time: Fast Opening: 6 to 14 seconds
Slow Opening: 14 to 26 seconds
Note: Opening time doubles between -30F to -40F
(-34C to -40C). Timing not field adjustable.
Maximum Closing Time: One second
Temperature Limitations: Ambient -40F to 150F
(-40C to 66C)
Damper Arm Rating: Dri es damper in one direction only.
20 lb maximum at 2.85 in. radius at 20F to 150F
(-7C to 65C ) and 10 lb maximum at -40F to 20F
(-40C to -7C).
Damper Arm Travel: 2 maximum
INSTALLATION
Before installation, check nameplates to erify actuator and
al e selected are appropriate for the application.
IMPORTANT: After actuator installation, test all functions
and check out complete system before putting actuator/valve
into service.
Positioning/Mounting
Follow the V710 Series Gas al e and/or damper
manufacturer's instructions when installing the Hydramotor.
1. AH2D actuators can be installed to operate in any
position.
2. Install mounting gasket and position the actuator to
operate the al e (and damper if appropriate). Secure
actuator with the four mounting set screws. Torque set
screws to 80 ± 5 in-lbs [9,0 ± 0,5 Nm] using a 5/32 hex key
wrench.
3. For damper applications requiring the damper arm to
return upon power failure, the optional return spring and
spring plug (kit 440018) must be installed on the damper
arm. Connect linkage so that damper returns to the
desired position.
Wiring (Refer to Figure 3)
WARNING: Electrical hazard. To prevent the
possibility of death, serious injury or property
damage, open all circuits before inspection, service
or disassembly. Reassemble before operating.
Wiring must comply with local codes and the National
Electrical Code. Limit controls must conform to actuator
rating ( oltage, amperage, hertz). Wiring to meet NEC Class
I, suitable for 75 C. Wire limit controls to the hot side of power
supply.
1. Route wiring through one of the conduit knockout
openings. Install appropriate electrical fittings.
2. Connect the power wiring to terminals N (neutral) and L1
(hot). A green grounding screw with a cup washer is
pro ided beside the terminal strip for grounding.
3. Torque terminal screws to 8 to 12 in-lbs [0,9 to 1,3 Nm].
4. Connect auxiliary or al e o ertra el proof-of-closure
switch wiring to the common and normally open or
normally closed switch terminals.
5. Install nameplate/electrical co er with gasket and screws
(6) on actuator housing. Hand thread screws as far as
possible, thenĂĂ torque Ăscrews Ăe enlyĂ Ăin a ĂĂcrisscrossĂĂ
mannerĂto 30 to 35 in-lbs [3,4 to 4,0 Nm].
6. Operate actuator (complete system) through fi e cycles to
erify proper operation.
Figure 3. Typical AH2D Actuator Wiring.
Travel limit s itch
Auxiliary s itch
Grounding scre ith cup asher
Auxiliary and Overtravel Proof of Closure
Switch Ratings
15 Amps 120 Vac
7.5 Amps 240 Vac
Total connected load of auxiliary and o ertra el proof-of
-closure switches not to exceed 1800 VA.
CAUTI N: vertravel Proof-of-closure switch
must only be used with V710 Series Gas Valves
having an overtravel seal (V22 or V25 Suffix in catalog
number).