ascon XE Series User manual

INSTRUCTION MANUAL
MIU.XE-6/96.12/E
COD. J30-154-1AXE- ING
Conf gurable Mult - nput
w th t me-proport on ng
output
XE Ser es
ASCON spa

Manuale XE nglese
1 IDENTIFICATION OF MODEL .......................................page 1
2 FUNCTION OF KEYS AND DISPLAYS .........................page 3
3 DIMENSIONS, INSTALLATION .....................................page 6
4 ELECTRICAL WIRING ...................................................page 8
5 Y2 - Y3 AUXILIARY OUTPUTS......................................page14
6 PASSWORDS ................................................................page17
7 PROGRAMMING PROCEDURE (see enclosed leaflet)
CONFIGURATION
PARAMETERS
8 OPERATING DIRECTIONS (see enclosed leaflet)
SET POINT
AUTO-TUNE
10 TECHNICAL DATA.........................................................page18
SERIAL COMMUNICATION
(see the nstruct on manual “SERIAL COMMUNICATION
SUPPLEMENT” MIU.-CS/E suppl ed separately)
GENERAL INDEX

1
Manuale XE inglese
Thank you for choosing an ASCON controller
The instruments of the XE series belong to the last generation of
microprocessor based controller, are universal, very powerful but
simple to use.
They are fitted with A TO-T NE, as aid for system start-up, and serial
communication for introduction into a distributed control network.
They are complete because all possible variables are always present.
Configuration of the instrument permits determination of the operating
mode according to the application required.
1 • IDENTIFICATION OF MODEL
Power supply
100…240 V 50/60 Hz
16 …28 V 50/60 Hz and 20…30 Vdc
Serial communication
20mA C.L. Std Ascon protocol
20mA C.L. Modbus/Jbus protocol
Au iliary output Y3
None
Fitted
3
5
1
2
0
1
Model code
OPTIONS
A
B
C
XE -
A B C
1.1 Identification of model
None 0
Beginning and end of scaleConfiguration code
239.5
239.5

2
Manuale XE inglese
239.5
239.5
Model code
Input X
OPZIONI
1.2 Configuration code
Configuration code
Beginning and end of scale
Auxiliary output Y3
Beginning and end of scale
(for mA and Volt input only)
1
st
part2
nd
part
Main output Y1
The controller is normally configured in the factory.
!
If this appears at the power-up
the controller IS NOT CONFIGURED
In order to configure the controller, follow the
configuration procedure reported in the enclosed leaflet
D
E
F
G
H
I
L
FD E G H I L
Auxiliary output Y2
9.999
9999
1 • IDENTIFICATION OF MODEL

3
Manuale XE inglese
6
7
5
4
11
Withdrawal
screw
Face
seal
IP54
Front
cover
12
9
10
8
2
1
Confirm data
Select digit
Increment digit
Edit Set point
Set point W
Process
variable "X"
Auto-tune in
course
Active serial
communication
Auxiliary
output
Y3 “ON”
Auxiliary
output
Y2 “ON”
Functions
(menu)
3Main output
Y1"ON"
3b Auxiliary output
Y1F (Cool)“ON”
3a Main output Y1
(heat) "ON"
239.5
239.5
2 • FUNCTION OF KEYS AND DISPLAYS

4
Manuale XE inglese
8888
____
8888
The value of measure X is expressed in engineering
units.
If above end of scale
If below beginning of scale
• In programmation: displays parameter values
• In configuration: displays the values of the 1
st part
of the configuration code (see enclosed leaflet)
(green) Displays the operating Set point value
• In programmation: displays the parameter codes
• In configuration: displays the index values of the 2
nd
part of the configuration code (see enclosed leaflet)
10
7.5
----
2 - Set point W
1 -Process
Variable (X) (green)
NUMERIC INDICATORS X, W
Lit with output Y1 “ON”
De-activated with continuous or dual action
discontinuous output
Lit with output
Y1 (heat) “ON” Only for HEAT/COOL
time proportional
output control
Lit with output Y1F
(cool) “ON”
Lit with output Y2 “ON”
Lit with output Y3 “ON” (only with Y3 option)
De-activated with continuous or dual action
discontinuous output
3
2
1
3 - Output Y1 (red)
3a - Output Y1 (heat)
3b - Output Y1F (cool)
4 - Output Y2 (red)
5 - Output Y3 (red)
LEDS FOR OUTPUT STATE
239.5
239.5
2 • FUNCTION OF KEYS AND DISPLAYS

5
Manuale XE inglese
Lit when Auto-Tune or Expert-Tune is in
course
Permanently lit when the serial
communication is enabled to write.
Flashes with signal in transit
Loop -
Break -
Alarm
With output Y2 active and configured as
Loop Break Alarm, all the front displays are
flashing (see p. 14)
6 - Auto-Tune (green)
7 - Serial comm. (green)
LEDS FOR OPERATING STATE
To modify Set point
Selects the digit to be modified
(see enclosed leaflet) Keys for
modifying
numeric
values of
any data
Increments the value of the flashing
digit, from 0 to 9
Permits access to menu of
functions to be programmed Keys for
data
programming
and
pressing
Enter or Scroll of values and modes of
operation
8 - Edit Set Point
9 - Digit selection
10 - Increment digit
11 - Functions
12 - Enter
KEYS
AT
SCI
239.5
239.5
2 • FUNCTION OF KEYS AND DISPLAYS

6
Manuale XE inglese
3.1 - Overall dimensions (in compliance with DIN 43700)
14 120
Advised
thickness
1 ÷ 16
48
96
Ring with hook and
locking screw
Wiring
protection
plate
Front cover
projection
W
-+
F
44
Panel apertures
45
+0.6
92
+0.8
110 min.
150 min.
with
protetection
IP65
60 min.
65 min.
with
protetection
IP65
3 • DIMENSIONS - INSTALLATION

7
Manuale XE inglese
3 • DIMENSIONS - INSTALLATION
275.8
275.8
3.2 - Panel installation
Knurl for hook
hold
Holding
hooks
Locking
screws
Seal ring fitting
!
AMBIENT
Temperature: 0 ÷ 50°C
Humidity : 30 ... 85uR%
Install away from:
• heat sources
• corrosive gases
• dusty environments
Do NOT force
!
cross-screwdriver
%
HR%
mV
V
A
kW
psi
Bar
°F
MPa
l/m
m
3
/h
Nm
3
/h
CO%
O
2
%
m
rh
Pa
kPa
mA
labels supplied
if different from
°C, remove and
apply plate with
requested unit.
B • Fixing with ringA • Panel fitting
C • Screw locking D • Plate for engineering units

8
Manuale XE inglese
28 screw terminals M3.5 Plate pin
Plate screw
3 gilded
terminals for
input signals
Cold joint
compensation
thermometer
Wiring
protection plate
1
Rotate
upwards
With eyelet
terminals
max.6.9
With tinned wire
6 ÷ 7
With fork
terminals
max.6.9
Cable
section wires
N°
0.25 ÷ 2.5
AWG
22 ÷ 14
2
1
2
Preferential
7
A • Terminal board B • Freeing the terminals
D • Protecting the terminal boardC • Effecting the connections
1
Lift the plate to free
the pin
2
Rotate
downwards
2
Depress the plate to
engage the pin
4 • ELECTRICAL WIRING

9
Manuale XE inglese
4 • ELECTRICAL WIRING
!
Single out supply line from power line
Keep away from teleruptors, electromagnetic contactors and
powerful motors
Keep away from power groups, in particular if with phase
control
Channel for low level signal conductors
Power supply and output channels
A
B
C D
A B
C D
Serial communication
Analogic inputs
Power supply
Outputs
B
C
D
A D D
Although this controller is designed to resist the heaviest disturbances
present in industrial environments (level IV of standard (IEC 801-4), it is
advised to keep to the following precautions:
Precautions
Advised conductor course

10
Manuale XE inglese
4 • ELECTRICAL WIRING
Wiring diagram
Schema di collegamento
“Switching” type
• Standard: 100 a 240Vac -15% +10%
• for low tension: 24Vac -15% +10%
24Vdc ±15%
Absorbed power 4VA
Single power supply
12
11
1 • Single power supply
Serial
communication
(optional)
2-wire
transmitter
Input
process
variable (X)
X
mA
Volt J, L,
K, S…
A
B
B
Pt100
6
2
TX
RX
i4…20 mA + 24 Vdc (2)
Y2
Y1
Y13
Relay Auxiliary
output
Single power supply
100…240 Vac - 50/60 Hz
Relay Main output
Relay Auxiliary output
(2
nd
channel cool)
Main output
Logic 0/15 Vdc
Y1
1
4
3
2
3
4
5
6
7
9
10
12
13
14
15
16
17
18
19
20
111
5
(-)
(-)
(+)

11
Manuale XE inglese
• Respect polarities
• For eventual extensions, use a
compensated cable suitable for the type
of thermocouple used
• The eventual shield must be well earthed
at only one end
A - For thermocouples J-L-K-S-R
Line: max. 150 Ω
7
9
for 3-wire connection only
Line: max. 20 Ω per wire
A
B
B
7
9
10
B - For RTD Pt100
C • Continuous, mA, Volt
Input mA, Volt
Auxiliary
supply for
transmitter
6
7
9
Rin
Xi
4…20 mA
6
7
9
Rin
Transmitter
+24 Vdc
For 2-wire transmitter For 3 or 4-wire transmitter
Xi
6
7
9
Rin
Transmitter
+24 Vdc
Rin = 30 Ω per mA
Rin= 10 KΩ per Volt
+24
Vdc
• For 3-wire connection, use cables of
same section (min. 1 sq.mm)
• For 2-wire connection, use cables of
adequate section (min. 1.5 sq.mm.)
Note:
with a 15 m. probe to controller distance
and a 1.5 sq.mm. section cable, the error
is about 1°C.
com.
2 • Process Variable (X)
4 • ELECTRICAL WIRING

12
Manuale XE inglese
A • Relay Single Action
Y1 16
17 V ~
Load NO contact, capacity 3A/250Vac Load
for resistive loads (transition 2 x 105
min. at 3A/250Vac)
3 • Main output Y1
B • Logic Single Action
Y1 19
20
Load
V ~
Relay or static contactor
Output 0/15Vdc
(20mA max.)
galvanically isolated
Y2 14
15 V ~
Load
NO contact, capacity 3A/250Vac Load
for resistive loads (transition 2 x 105
min. at 3A/250Vac)
4 • Auxiliary output Y2 (see pag.14)
Y3 17
18 V ~
Load
NO contact, capacity 3A/250Vac Load
for resistive loads (transition 2 x 105
min. at 3A/250Vac)
5 • Auxiliary output Y3 (option)
4 • ELECTRICAL WIRING

13
Manuale XE inglese
TX
RX
2
3
4
1
Transmission
Reception
Interface 20mA C.L. passive and
galvanically isolated
Consult Directions for use “SERIAL
COMMUNICATION SUPPLEMENT
MIU.-CS/E”
supplied separately.
Zener
2,7 V
6 • Serial communication (option)
Note
Zener 2,7 V Only for 20mA C.L.
4 • ELECTRICAL WIRING

14
Manuale XE inglese
5 • Y2 - Y3 AUXILIARY OUTPUTS
H
W
W 1 On
Off
On
Off
Beginning
of scale End of scale
Active high
(above)
Active low
(under)
Set point ∆W (1)
-0...300 units
compared to W1
Active Out
(above)
Active In
(under)
Set point I∆WI (1)
-0...300 units
compared to W1
Active high
(above)
Active low
(under)
Set point (1):
from beginning
to end of scale
(1)- The Set point of Y2 and Y3 is not limited by the limits of the main
Set point W1, but only by the scale span.
H
W 1 On
Off
-300 units +300 units
I∆WI
HI∆WI
H
W 1 On
Off
-300 units +300 units
∆W
Deviation
Band
Independent

15
Manuale XE inglese
239.5
239.5
Active high
(above)
Active low
(below)
Set point ∆W (1)
-300...+300 units
compared to W1
inhibition
W1
∆W
On
Off Startup
Deviation with startup inhibition
mA°C
Any interruption in the connections or
any anomaly in the operation of one
of the control loop components, will
cause the output Y2 to be energized
after a few minutes and the whole
front display will be flashing.
The alarm state will stop when the
anomaly causing it stops or
depressing any key for silencing it.
Y1
“Loop-Break-Alarm” LBA (control loop defect/interruption)
inhibition
W1
∆W
On
Off Startup
With ON-OFF
action "LBA"
feature is not available
!
5 • Y2 - Y3 AUXILIARY OUTPUTS

16
Manuale XE inglese
Only for models with option Y3 is
possible to have a double action
regulation (for instance Heat - Cool).
Output Y3 with index H=9, is
available as cool output.
Proportional band, cycle time, and
maximum output are settable
separately for Heat and Cool.
Double time programmable intervention (Heat - Cool) (Y3)
Where is Y1F Y3 = Cool outputs
Where is Y1C Y1 = Heat outputs
100%-100% 0 0
Dead
zone
Y1F Y1C
Cool
100% Heat
100%
Y1F limit
(0…-100%) Y1F limit
(0…-100%)
5 • Y2 - Y3 AUXILIARY OUTPUTS

17
Manuale XE inglese
6.1 Password of access to configuration
3333
In order to prevent tampering or inadvertent alterations of the configuration
or of some important parameters at the programming stage, 2 passwords
have to be entered.
6.2 Password of access to the 4th parameter group
1111
WpAss
3333
WpAss
1111
Enter password of access to configuration
(see enclosed leaflet)
OK
Return to normal
function
YES
NO
Introduction into configuration
Enter password of access to the 4
th
group
(see enclosed leaflet)
OK
Return to normal
function
YES
NO
Introduction into the 4
th
group
6 • PASSWORDS

18
Manuale XE inglese
Set point
Main
output Y1
Discontinuous with direct or reverse action
Relay with dual action 2 contacts NO, 3A/250Vac, 2x10
5
transitions
Logic 0.15 Vdc, 20mA max. (for static relays) galvanically isolated
Maximum output 10..100% (1st channel ) -10.. -100% (2nd channel )
Accuracy
(a25°C amb.)
0.2% ± 1 digit (for input with RTD Pt100 and thermocouples)
0.1% ± 1 digit (for input in current and voltage)
Process
Variable "X"
(configurable)
RTD Pt100 Pt100 (IEC 751)
With
configurable
scale field
Thermocouples J-K-S-R (IEC 584), L (DIN 43710)
Direct current 4..20mA, 0..20mA, Ri 30Ω
Direct voltage 0..1Vdc, 0..10Vdc, Ri 10KΩ
1 Local
Distinct ascent and descent
gradient slope 0.1...120.0% scale/min. or step gradient
Higher and lower limit from beginning to end of scale
Control
mode Algorithm PID, PI, PD, P or On - Off
Proportional band (P) 0,5..1000%
Integral action time (I) 0.1..100min., excludable
Derivative action time (D) 0.01..10min., excludable
Cycling time 1..200 sec.
Hysteresis 0.1..10% (for on-off control)
Dead zone 0..10% for dual action (heat-cool) control
Auto - Tune For automatic parameter adjustment (One shot)
10 • TECHNICAL DATA
Table of contents
Other ascon Controllers manuals

ascon
ascon K31D User manual

ascon
ascon e33 User manual

ascon
ascon QP Series User manual

ascon
ascon KX6 Installation and operation manual

ascon
ascon TLK72 B User manual

ascon
ascon X34S User manual

ascon
ascon Z31 User manual

ascon
ascon S2 Series User manual

ascon
ascon G2 Series User manual

ascon
ascon M4 series User manual
Popular Controllers manuals by other brands

DROPSA
DROPSA ADVANCED LUBRICATION CONTROLLER INSTRUCTION AND PRODUCT DATA SHEET

Johnson Controls
Johnson Controls TEC-2647-4 Installation & operation manual

Ducasa
Ducasa Smart Command Installation and operating manual

WEG
WEG SSW7000 user manual

Agromehanika
Agromehanika AG-TRONIK S1 Instructions for use

Selmo
Selmo Thesis Plus manual