Escape route technology

2
EN
Hi-O Technology™ is a registered trademark of the
ASSA ABLOY Group.
ePED®is a registered trademark of
ASSA ABLOY Sicherheitstechnik GmbH.
Open Source Licenses ASSA ABLOY Sicherheitstechnik GmbH has the source code of
the software used in the scope of Open Source licenses
(such as FreeRTOS™, newlib, lwIP) available on request:
http://www.assaabloy.com/com/global/opensourcelicense/
1386D Firmware AP Version 3.3.0
Firmware SW Version 0.1.64
1386S Firmware AP Version 3.3.0
Firmware SW Version 0.1.64
Authorisation Code for Control (must be changed) 1 2 3 4
Authorisation Code for Settings (must be changed) 7 7 7 7
Authorisation Code for Installation (must be changed) 7 8 9 0
Publisher
ASSA ABLOY Sicherheitstechnik GmbH
Bildstockstrasse 20
72458 Albstadt
Germany
Phone: +49 (0)7431 1230
Telefax: +49 (0)7431 123 240
Internet: www.assaabloy.de
Email: albstadt@assaabloy.com
Document number, date
D0117001 03.2030
Copyright
©2020, ASSA ABLOY Sicherheitstechnik GmbH
This document and all its parts are copyrighted. Any use or changes outside the
strict limits of the copyright are prohibited and liable to prosecution, unless prior
consent has been obtained from ASSA ABLOY Sicherheitstechnik GmbH.
This particularly applies to any copying, translations, microforms, or storing and
processing in electronic systems.
Authorisation
codes
EN Read this manual thoroughly before use and keep it in a safe place for later
reference. The manual contains important information about the product,
particularly for the intended use, safety, installation, use, maintenance and
disposal.
Hand the manual over to the user after installation and pass the manual on to
the purchaser together with the product if the product is sold.

3EN
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fitting and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Hi-O Technology™ devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Authorisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Login with authorisation code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Initial commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Installation wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Emergency switch function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Alarms and messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Resetting to factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Warranty, disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Updated information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table of contents

4 Notes
EN
About this manual
Target group
The product must be installed and configured by an electrical engineering
specialist. Assembly work must be carried out by a specialist in the relevant trade
or suitably qualified personnel depending on the type of work.
Meaning of the symbols
Danger!
Safety notice: Failure to observe these warnings will lead to death or serious
injury.
Warning!
Safety notice: Failure to observe these warnings can lead to death or serious
injury.
Caution!
Safety notice: Failure to observe these warnings can lead to injury.
Attention!
Note: Failure to observe these warnings can lead to property damage and impair
the function of the product.
Note!
Note: Additional information on operating the product.
D
!
!
A
I
Notes

5Notes EN
Safety instructions
Warning!
Danger arising from modification of the product: The safety features of this
product are an essential requirement for its conformity with EltVTR. No changes
which are not described in this manual may be undertaken.
Danger due to missing Emergency Open button on the escape door: If the
release of the escape door is centrally controlled, it is no longer possible to
independently choose to exit the danger area in the case of danger. This always
requires an approval from the responsible inspection authority. Normally, a
constantly manned station equipped with a central release mechanism is
prerequisite for the approval.
Danger due to faulty commissioning: In order to ensure the safety of the
product, commissioning must be performed by a qualified person. ASSA ABLOY
Sicherheitstechnik GmbH offers training for qualification in the requisite skills.
Danger due to faulty maintenance: The owner is responsible for correct instal-
lation and functional inspection of the product and connected components. The
safe function must be tested by a trained qualified expert at least once per year.
Requirements established by inspection authorities must be complied with. ASSA
ABLOY Sicherheitstechnik GmbH offers training for qualification in the requisite
skills.
Danger arising from tampering or improperly performed repairs: If the ePED®
1386D10 door terminals or parts of the device cannot resume normal operation
after a fault or alarm message, or damage is present, the device may only be
repaired by a qualified person. Please contact the customer service of the installa-
tion company or the support department of ASSA ABLOY Sicherheitstechnik GmbH.
Danger due to unauthorised tampering: The authorisation codes (Page 2)
set at the factory are publically accessible and can be misused. Change the au-
thorisation codes before the ePED®1386D10 door terminal is freely accessible. Al-
ways use different codes for the authorisation levels („Authorisation“, page 13)
(between four and eight digits). Keep codes that are written down in a safe place.
!

6 Notes
EN
Intended use
Electrical locking devices of doors along escape routes are intended for use in
commercial applications.
The product has been designed for the safeguarding of escape routes and has
been tested according to the requirements of EltVTR. Deviating uses or device
combinations not described in the approval are not permitted.
ASSA ABLOY Sicherheitstechnik GmbH can provide the necessary planning informa-
tion for approved solutions and the device combinations required for your
application. The usage must be coordinated with the requirements of the
inspection authorities. Contact the responsible inspection authority for this
purpose.
Compliance with all relevant inspection authority requirements is mandatory for
the use, particularly with respect to the
· coordination of the safety concept with the responsible inspection authority
and
· modifications of door elements.
The device is suitable for installation, configuration and use, according to these
instructions. Any use beyond this is deemed as non-intended use; device
combinations which are not described are not permitted.

7Fitting and installation EN
Fitting
Prerequisites
Plan and install the wiring before the ePED®1386D10 door terminal has been
mounted (manual D01021xx ePED®Hi-O Technology™ bus).
Note!
Protection rating IP30 must be achieved: Switch boxes („Mounting/removing
the display“, Seite 10) which achieve a minimum protection rating of IP30
must be used for the installation.
Attention!
Limitation of function with incorrect operating voltage at the components: A
mains adapter in accordance with DIN EN 60950-1 SELV must be used. Separate mains
adapters must be connected for the supply of devices with power consumption higher
than 100 VA. The appropriate mains adapter, cable lengths, and cable cross sections
must be chosen according to the local circumstances. Check and ensure that the oper-
ating voltage at the connection points is suitable for the components.
Identification of the cable
Note!
Choose uniform identification for avoidance of errors: In order to avoid errors
and for a clearer overview during installation and maintenance, ASSA ABLOY Sicher-
heitstechnik recommends uniform identification and colour coding of the cable
cores Tab. 1 and Fig. 1.
Function Termi-
nal
Colours Typical
CAN bus
Hi-O J-Y(ST)Y 4x2
Hi-O
CAN_H 1 wt wt/br
CAN_L 2 br br
VB+ 3 gn gn
GND 4 ye wt/gn
I
I
Tab. 1:
Colour coding for
wiring
Fitting and installation

8 Fitting and installation
EN
Fig. 1:
Connections
1234
8765
J1 J2
SYSCON 4
Terminal strips
1 CAN_H wt
2 CAN_L br
3V
B+gn
4 GND ye
5 ln VB+
6 ln VB–
7 Fire alarm system VB+
8 Fire alarm system VB–
Syscon 4 plug connection
1 GND
2 CAN_H
3 CAN_L
4V
B+
No
fire alarm
1234
8765
J1 J2
Temporary
release
1234
8765
Fire alarm:
local
connection
1234
8765
J1 J2
Fire alarm:
central
connection
8765
J1 J2
VB– +

9Fitting and installation EN
Fig. 2:
Example
connection Escape door strike 331 – 24V1
A
B
C
D
E
F1
2
3
4
SYSCON 4
1234
8765
J1 J2
ASSA ABLOY
Interface for
locking systems 1386S00
Door terminal
1386D10
Hi-O Technology™
power supply
1Other locking
elements can
be connected
instead of the
escape door
strike 331
(manual
D00470). Only
one locking
element may be
connected.

10 Fitting and installation
EN
Mounting/removing the display
>62,5
60
1
2
1
2

11Fitting and installation EN
ASSA ABLOY
ASSA ABLOY
ASSA ABLOY
ASSAABLOY

12 Fitting and installation
EN
Hi-O Technology™ devices
Note!
Untested devices may have differing functionality: Hi-O Technology™ devices
not listed in the compatibility list have not been tested in the device combination
and may cause different functional processes. This applies especially for activa-
tors.
The maximum number of components may not be exceeded: A maximum of
four terminals (Emergency Open module 1386D00) and eight interfaces for locking
systems 1386S00 can be connected.
The maximum power consumption may not be exceeded: The voltage supply
must be sufficient for the power consumption of all connected components.
Limitation of function with incorrect operating voltage at the components: A
mains adapter in accordance with requirements SELV must be used. Separate mains
adapters must be connected for the supply of devices with power consumption higher
than 100 VA. The appropriate mains adapter, cable lengths, and cable cross sections
must be chosen according to the local circumstances. Check and ensure that the oper-
ating voltage at the connection points is suitable for the components.
I

13Configuration EN
Note!
Commissioning: All Hi-O technology™ devices must be connected to the bus for
the configuration. Then the operating voltage is switched on. Subsequently
connected devices are only recognised after renewed connection of the operat-
ing voltage.
At least one Emergency Open module is always necessary for operation of the
RWT locking module.
1 Configure the system via the ePED®Service Software (D01104xx ePED®Service
Software) manual).
Display
The display shows the current system
status. Operation takes place interac-
tively via the touchscreen (Fig. 3).
If no input takes place, the display
switches back to status display after 15
seconds.
The display shows operating symbols in
the header area and information for
interactive communication with the
user.
The toolbar is not always completely visible. One or two symbols are shown for
operation or navigation, a menu heading can be shown in the centre.
Authorisation
There are three authorisation levels:
Control Authorisation for calling up information
Settings Authorisation for calling up information and
restricted configuration
Installation Authorisation without restrictions
Each authorisation level is assigned a clear authorisation code in the factory.
These authorisation codes must be changed for commissioning. Each authorisa-
tion level must be assigned a clear authorisation code once again.
I
Fig. 3:
The display shows
operating symbols
and information
on the door status
or communication
Tab. 2:
Authorisation
levels
Configuration

14 Configuration
EN
Login with authorisation code
Enter authorisation code – lock, unlock, reset
1 Press the symbol
2 Enter an authorisation code.
Delete any numbers entered by mistake
with the [ ] key.
3 Confirm the entry with the [ ] key.
After entering a valid authorisation code,
you can unlock the door.
Enter an authorisation code – configuration
Some menus (such as the Systemmenu) can
only be opened with expanded authorisation.
An authorisation code for configuration is
required for this.
1 Press the symbol.
2 Press the symbol.
The symbol is no longer shown.
3 Press one of the symbols according to an
authorisation code (Tab. 2, page 13)
4 Enter an authorisation code.
Delete any numbers entered by mistake
with the [ ] key
5 Confirm the entry with the [ ] key.
The menu is displayed after entry of a
valid authorisation code.
Fig. 4:
Numeric keypad
for entering an
authorisation code
Fig. 5:
Numeric keypad
for entering an
authorisation code

15Configuration EN
Change authorisation codes for authorisation levels
1 Press the symbols in the following order:
2 Enter your authorisation code.
3 Press the System (Fig. 6) menu item.
4 Press the User Administration menu item.
The keyboard is displayed.
5 Press one of the symbols according to an authorisation code (Tab. 2, page 13).
6 Assign a new authorisation code.
Delete any numbers entered by mistake with the [ ] key
7 Confirm the entry with the [ ] key.
You have changed an authoisation code
8 If necessary, repeat from step 5 until all authorization codes have been
changed.
Fig. 6:
The
"System–
User Administration”
menu
Authorisation
level
Control
Settings
Installation

16 Configuration
EN
Warning!
Danger due to faulty commissioning: In order to ensure the safety of the
product, commissioning must be performed by a qualified person. ASSA ABLOY
Sicherheitstechnik GmbH offers training for qualification in the requisite skills.
Safety requirements during commissioning include:
· The owner has received a confirmation of approval for use from the inspection
authorities;
· Conformity of the products with the approval according to EltVTR.
· Mounting according to the installation manual;
· Testing of the unimpeded opening and closing function of the doors with the
escape route securing system deactivated;
· Bolting of the doors after activation of the escape route securing system.
· Allows the doors to be opened after actuation of the Emergency Open
push-button(s).
· The function must be tested when connected to fire alarm system.
· The commissioning must be documented. ASSA ABLOY Sicherheitstechnik GmbH
offers a test log book for this purpose.
Initial commissioning
All devices are connected to the Hi-O-Technology™ bus for the initial commission-
ing, but are not configured yet. If the voltage supply is switched on, the system is
in plug and play mode and the devices work with the factory settings.
Interfaces for locking systems cannot work with factory settings, because they must
be logically linked to the corresponding Emergency Open push-buttons. The
configuration must be completely finished before the interfaces for locking systems
can be commissioned.
Any changes which are made necessitate re-configuration.
!
Interface for
locking systems
Commissioning

17Configuration EN
Installation wizard
The installation wizard is provided for simple configuration and the system test,
particularly for the initial commissioning. A sequence of routines is processed
automatically.
Once it has been started, the installation wizard dialogue shows a series of
confirmation messages and user prompts.
Note!
Process the entire dialogue sequence: If a dialogue is closed via the Cancel key
or if the displayed action is not carried out, the installation must be started again
from the beginning. The RWT system configuration has not taken place and the
system cannot be locked.
Using the installation wizard
1 Press the
·Continue or OK button if the entire dia-
logue message is correct or if you have
taken the necessary action,
· the Cancel button if any part of the
dialogue message is incorrect or if you
have not taken the necessary action.
The installation is finished if you have been able to exit all messages with the
Continue or OK button.
Once the installation is complete, the ePED®1386D10 door terminal is in
normal operation status.
I
Fig. 7:
Example of a
prompt for action

18 Operation
EN
Emergency switch function
Pressing the red area in the centre initiates a release and a pre-alarm is triggered.
The emergency switch function is triggered if the display is pressed.
Fig. 8:
Press the
Emergency Open
switch
ASSA ABLOY
ASSA ABLOY
ca. 4 mm
Operation

19Operation EN
Display
ASSAABLOY
ASSA ABLOY
ASSA ABLOY
Illuminated ring with status display
The integrated illuminated ring enables easy
identification of the current status of the es-
cape door even with a large angle of vision.
ASSAABLOY
Release delay display (option)
If the release delay is activated, the remain-
ing wait time is displayed in seconds.
ASSAABLOY
ASSA ABLOY
Escape route pictogram and status display
The ePED®display door terminal 1386D10
shows the relevant pictogram when the
escape door is secured and indicates the
correct conduct if the door needs to be
operated in the event of an emergency.
ASSAABLOY
Operation and configuration
Authorised users are identified via an au-
thorisation code and are granted access to
the configuration and extended operating
functions („Configuration“, page 13).

20 Alarms and messages
EN
Alarms
Acoustic alarm
There are alarm statuses where an audible signal is activated, such as a pre-alarm.
The acoustic alarm takes place for a configured time span and is automatically
switched off again, or can be switched off with a control command. If another
alarm should occur, the acoustic alarm is restarted.
Pre-alarm and alarm
The pre-alarm is triggered if the open door is not closed and locked within a
configured time span after the temporary release. The pre-alarm is signalled in
multiple ways: via the display of the ePED®1386D10 door terminal, acoustically
and via the yellow flashing ring.
The pre-alarm is switched off automatically if the door is closed and locked within
the pre-alarm time.
If the door is not closed and locked within the pre-alarm time, a tamper alarm is
triggered.
Fire alarm
In the case of a fire alarm, the Hi-O-Technology™ components are actuated by a
fire alarm system. The escape route locking systems are automatically unlocked
and retain this status until actuation by the fire alarm system is lifted again.
If the actuation by the fire alarm system is lifted again, the components lock again
if no further release commands are issued.
Other Hi-O-Technology™ locking systems respond according to their respective
configuration.
Emergency unlocking
If the Emergency Open push-button is pressed, an Emergency unlocking or
release request is issued to the central control. If an Emergency unlock has been
triggered with an Emergency Open push-button, the Emergency Open push-but-
ton must be unlocked manually, wherein the system is also reset to normal
operation.
Pre-alarm
Fire alarm
and/or Emergency
unlocking
Alarms and messages