Astronergy CHSM72M-HC User manual

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
Crystalline Silicon PV Module Installation Manual
1. Introduction
1.1 Purpose
1.2 Limitation of Liability
1.3 Precautions for Installation
2. Safety
2.1 General Safety
2.2 Installation Safety
3. Mechanical Installation
3.1 Installation Condition
3.2 Installation Methods
4. Electrical Installation
4.1 Installation Condition
4.2 Grounding
5. Maintenance

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
1. Introduction
1.1 Purpose
This document provides detailed instructions and valuable safety information regarding the
installation, electrical connection, and maintenance of following Chint Solar Crystalline Photovoltaic
modules:
CHSM60M(BL)-HC(166) CHSM60M-HC(166) CHSM72M-HC(166)
All the instructions should be read and understood before installation. The installers should
be trained and conform to all safety precautions in this guide when installing the module. Keep
this guide in a safe place for further reference.
1.2 Limitation of Liability
Because the use of this manual and the conditions or methods of installation, operation, use
and maintenance of photovoltaic (PV) products are beyond Chint Solar’s control, Chint Solar
does not afford the responsibility and expressly disclaims liability for loss, damage, or expense
arising out of or in any way connected with such installation, operation, use or maintenance.
Chint Solar reserves the right to change the manual without prior notice.
1.3 Precautions of Installation
1.3.1 Module’s unpack and transfer
a) When the whole pallet of modules are delivered to the site and unloaded, make sure the
safety of the modules especially if they need to be lifted for roof projects. Put them into a
protective device and then lift it to the roof in case of bumping against the wall during the
lifting process.
b) Firstly, tear the stretch film, then move away the top cover after cutting off each module
packing strip while unpacking. Two operators work as a group, grasp the module frame
tightly in the same direction and take out the module one by one. It is a must that the
operators remove the adhesive tape of the fixed module one by one, rive one piece and
then take out one piece of module. We don’t allow to tear off all the adhesive tape at one
time in to prevent the whole package from toppling over or falling down. The whole process
must be taken very gently. Don’t collide with any hard objects or let any parts of the frame
touch and drag on the ground.
c) After unpacking the modules should be installed that day as far as possible. It’s
recommended to take the right amount of modules according to the progress of the project

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
every day. Heavy rain and other inclement weather may have the potential to soak the
packaging which can affect product reliability, such as storms, typhoons, hurricanes or other
events in which they may be blown away. If the users need to store modules before
installation, do not open the package, the goods should be stored in a room temperature,
dark, dry and ventilated place.
1.3.2 Module’s Stack
a) When a module is taken out of the box, cardboard bedding below should be applied in order
to avoid contact with cement surface / ground, hard metal or tile. Modules should be placed
neatly and should not be dropped, slammed or scratched.
b) When stacking modules, it needs to be stacked neatly in the horizontal plane, under the
condition of the glass facing down and the back way piled up, while the cardboard bedding
need to be underside the modules. If the modules will be installed on the rooftop, the
number of each stack is suggested no more than 20. In case of the poor load-bearing
capacity, it’s recommended that the designer and/or installer check with the structural
engineer or architect to determine the amount of load allowable for specific location. During
the whole process, the installation tools and other objects must be prevented from
contacting the module surface.
c) If the modules are requested to be classified by current, the handling personnel are required
to carry out of the level of the current and make a mark separately according to the power
on the list. (e.g. 275W-L, identifies the modules of the packaging according to the power on
the list, indicating a low current position; 275W-H, compared to high current position).
Usually, the same series of modules in the same current position are required in
accordance with the system design requirements.
d) If the modules are color-coded and marked the corresponding logo on the carton due to the
customer requirements, when modules are taken out and stacked, they should be labeled to
avoid confusion. Usually the same row or the same square have the same color according
to the system design requirements.
e) Due to the complexity and difference of the construction site, these precautions may not
cover all items, please refer to the specific construction standards.
2. Safety

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
2.1 General Safety
2.1.1 Consult and follow local codes and other applicable laws concerning required permitting
as well as installation & inspection requirements, rules, and regulations.
2.1.2 PV modules should be installed and maintained by qualified personnel.
2.1.3 Use the same performance modules within a given series.
2.1.4 Follow all safety precautions of all components used in the system.
2.1.5 Do not shade portions of the PV module surface from the sun for a long period of time.
The shaded cell may become hot (hot spot phenomenon), which can result in solder joints
peeling off.
2.1.6 Do not clean the glass surface with chemicals.
2.1.7 Do not drop the PV module or drop objects onto the PV module.
2.1.8 Do not concentrate sunlight on the modules or panels.
2.1.9 Do not attempt to disassemble the modules, and do not remove any attached components
from the modules.
2.1.10 Do not scratch or hit at the back sheet, the glass, the terminal box. Do not pull the cables
or touch them with bare hands.
2.1.11 Do not drill holes in the frame or scratch the insulating coating of the frame.
2.1.12 Keep the PV module packed in the carton until installation.
2.1.13 Do not use modules near equipment or in places where flammable gases may be
generated.
2.1.14 Do not use modules in an environment with aliphatic, aromatic, phenols, ketones,
halogenated substance or mineral oil, which may corrode the junction box by chemical
attack.
2.2 Installation Safety
2.2.1 Wear protective clothing such as head gear, insulating gloves, safety shoes as prescribed
by local safey codes. Use insulated tools when installing the modules.
2.2.2 Do not install the modules in heavy rain, snow, or otherwise wet or windy conditions.
2.2.3 Completely cover the PV module surface with an opaque material during PV module
installation and wiring to prevent accidental charge buildup.
2.2.4 Plug in connectors tightly when working on wiring.
2.2.5 Due to the risk of electrical shock, do not perform any work if the terminals of PV module
are wet.
2.2.6 Do not touch the terminal box and the end of output cables (connectors) with bare hands.
2.2.7 Do not unplug the connector under load.

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
2.2.8 Do not work alone.
2.2.9 Wear a safety harness if working far above the ground.
2.2.10 Do not wear metallic jewelry, which can cause electric shock, while installing or
troubleshooting the PV system.
2.2.11 Follow the safety regulations for any and all other system components, including wires,
connectors, charging regulators, batteries, inverters, etc.
2.2.12 Do not expose wires to direct sunlight. Use UV-resistant cable.
2.2.13 Do not damage the surrounding PV modules or mounting structure when replacing a PV
module.
2.2.14 Do not change any PV module components (diode, junction box, connectors, etc.).
2.2.15 The maximum reverse current is 20.25A for module with Isc≤9.61A and 27A for module
with Isc>9.61A. Application of the blocking diode and fuse in the combiner box are
recommended for reverse current protection when more than two strings are connected in
parallel.
2.2.16 A certain gap is maintained between the PV module and the mounting surface to prevent
the mounting surface touching the junction box.
2.2.17 Standing on the solar PV module is forbidden and also prohibit installation tools or other
objects hitting surface of the solar PV module.
2.2.18 The solar modules are recommended to be installed over a fireproof and insulating roof
covering when installed on a roof.
2.2.19 PV cable connection cannot be too tight, it is recommended that the connector and the
backsheet have a certain gap.
2.2.20 In sandy regions, in order to avoid getting sand into the connector, we suggest to short
circuit module connectors before installation. If grains of sand get into the connectors it,
may cause internal live parts wear and tear and affect electrical safety.
3 Mechanical Installation
3.1 Installation Conditions
3.1.1 Extreme environment temperature:-40℃to +85℃
3.1.2 Operating temperature:-40℃to +85℃
3.1.3 Please refer to the detailed mounting instructions as Chapter 3.2.
3.1.4 Tilt Angle selection: The installation should be facing north in the southern hemisphere
and facing south in the northern hemisphere.
3.1.5 To maintain the modules’ Class C fire rating, the fire class of the roof and building
materials should be higher than Class C.
3.1.6 To maintain the modules’ fire performance type 1(for US market), it could be possible to
achieve the Class A system fire rating, with a Class A class racking system.

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
3.2 Installation Methods
3.2.1 Bolting through the mounting holes
All modules (excluding the double glass module) must be securely fastened with at least 4
bolts ( Figure a and Figure b). For maximum security against strong winds or heavy snow falls, all
of the mounting holes are recommended to be used(Figure c).
Fig a Fig b
Fig c
Remark: As for above diagram, the solid red arrows indicate primary bolt positions; dashed
blue arrows indicate positions where bolts can be added for additional support.
Bolts are inserted as described in the process below (Sketch figure d).
a) Place the module on the supporting bars underneath.
b) Insert the four stainless-steel bolts (M6) through the holes (7x11.5mm) or stainless-steel
bolts (M8) through the holes (9x14mm) in the frame according to the Figure a & Figure b.
For maximum security against strong winds and heavy snow, all available mounting holes
should be used.
c) Secure each bolt to the frame with stainless-steel washers, one for each side of the
mounting structure; and screw on either a stainless-steel spring washer or a toothed lock
washer. Finally, secure with a stainless steel nut.
d) The reference value of tightening torques should be within 9~12Nm & 17~23 Nm
respectively for M6 & M8 bolts, depending on bolt class. For the bolt grade, the technical

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
guideline from the fastener suppliers should be followed.
For the torque value, recommendations from specific clamping hardware suppliers should
prevail.
Fig d
3.2.2 Clamping on the frame surface
3.2.2.1 Single glass module
Modules can be laid either across the supporting bars (Figure e ).
Fig e

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
Fig f Fig g
Remark:
1) The length of supporting bars must be longer than the length of module frame, otherwise
please confirm with our product team to get approval.
Module type
Dimensions
L*W*H (mm)
Figure a
Figure b
Figure c
Figure e
D=1/4L
±50
(mm)
Figure f
M=200±
50(mm)
Figure g
M=200±
50(mm)
CHSM60M(BL)-HC
1765*1048*35
+5400
-2400
------
+5400
-2400
+1800
-1800
+1800
-1800
CHSM60M-HC
CHSM72M-HC
2108*1048*35
+5400
-2400
+2400
-2400
+5400
-2400
+5400
-2400
+1800
-1800
+1800
-1800
To fasten the module:
a) Place the module on the two supporting bars (not provided). The bars should be made with
stainless material and treated with an anti-corrosion process (e.g., anodic oxidation
treatment) or aluminum profile. Each solar PV module needs at least four clamps to fix. Do
not make the clamp contact the glass directly or make the aluminum frame deformation in
the installation process, and avoid the shadow of solar PV components.
b) The bar’s top surface contacted with module frame should come with grooves compatible
with an M8 bolt.
c) If the bars do not come with grooves, holes of a suitable diameter may need to be drilled to
allow bolts to be attached to the bars at the same locations as mentioned above.
d) Secure each clamp by attaching plain washer, spring washer, and nut, in that order.
e) Both of close-ups of Figure h, indicating the middle clamps and Figure i, indicating the side
clamps for reference. Suggest the dimensions for middle clamps are: a ≥40 mm, b ≥26 mm,
c= 8 mm, d ≥28 mm, and Ø = 9 mm. The torque for tightening the nut and bolts are
recommended 17~23Nm when the property class of bolts and screws is Class 8.8.

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
Figure h
Figure i
f) Especially for Figure e ,f and g mounting method, the modules may be mounted using
clamps designed for solar modules refer to Figure j, the modules must be supported along
the length of the edge, and should overlap the array rail by 10mm –14mm
Figure j
4 Electrical Installation
4.1 Installation Condition
4.1.1 The electrical characteristics are within ±10% of the indicated values of Isc. Voc and
Pmpp under the standard test conditions (irradiance of 1000 W/m2, AM1.5 spectrum, cell
temperature of 25℃.
4.1.2 The IEC & UL standard maximum system voltage for the regular module series is 1000V,
the 1500V standard products are also available according to the requirements. The IEC &
UL standard maximum system voltage for half-cell module series is 1500V (except for
black modules).
4.1.3 Connect quantity of modules that match the voltage specifications of the inverters used in
system. Modules must not be connected together to create a voltage higher than the
permitted maximum system voltage under the lowest local temperature conditions.
4.1.4 Under normal conditions, a photovoltaic module is likely to experience conditions that
produce more current and/or voltage than reported at standard test conditions.
Accordingly, the value of Isc marked on this module should be multiplied by a factor of 1.25
when determining component conductor ampacities, fuse sizes, and size of controls

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
connected to the PV output.
4.1.5 Refer to Section 690-8 of the National Electrical Code for an additional multiplying factor
of 125%(80% derating)which may be applicable.
4.1.6 Each module (or series-connected string of modules) shall be provided with the maximum
series fuse, specified 15A for modules with Isc≤9.61A & 20A for modules with Isc>9.61A.
4.1.7 Use a special solar cable and plugs for installing the PV system and make sure that all
connections are safe and tight. The cable should be 4 mm2(12AWG), and able to
withstand the maximum possible system open-circuit voltage.
4.1.8 Bypass diodes are included in module junction boxes to avoid decreased module
performance in the event of shade. Please check the relevant product datasheet for the
specific diodes of J-box.
4.1.9 Prohibit interconnection between different types of connectors.
4.2 Grounding
(n) Grounding the aluminum frame with copper wire
4.2.1 The grounding requirements must be checked in accordance with the applicable
regulations and standards before work is started.
4.2.2 Use the marked 5.5 mm grounding holes to ground the anodized frame. Use one M5 nut,
two M5 cut washers, one M5 plain washer, one M5 spring washer, and one M5 bolt and
the copper wire. All nuts, bolts, and washers are type M5 and should be made of
stainless steel (Fig. (n) ).
4.2.3 Put the bolt through the cup washer and wrap the copper wire around the bolt. (Note that
the copper wire cannot be attached directly to the aluminum.)
4.2.4 Put the bolt through the cut washer and then through the hole in the aluminum frame.
4.2.5 Add the spring washer and nut on the other side of the bolt and tighten to secure all parts.

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
The tightening torque should be 210±20 N•cm.
4.2.6 Approve the use of UL-467 certified bonding and grounding devices, including Burndy
(formerly Wiley Electronics) Washer Electrical Equipment Bonding (WEEB) and similar
devices, such as barbed washers, that meet the requirements of UL-467 as suitable for
electrical bonding and grounding PV modules to PV mounting systems.
4.2.7 Other grounding methods may be allowable when tested with the racking system per
UL 2703 requirements.
5 Maintenance
5.1 Regularly carry out a visual inspection for dirt, dust, bird dropping, leaves, and other detritus
covering the modules.
5.2 If snow is present, a soft-bristled brush with soft bristles may be used to clean the surface of
the modules.
5.3 Regular electrical and mechanical inspection by a licensed professional will keep the
system safe and operating at maximum efficiency.
5.4 Recommended PV module Clean-up period
To get high output performance, PV module needs to be cleaned-up periodically as below:
①Normal: Minimum one time per every month; Dust weather: Right away after the dust
wind;
②The period of the PV module cleaning shall be determined by the condition of the
weather & pollution. O&M operator shall keep a record of weather condition everyday with
data.
5.5 Condition of Cleaning
5.5.1 Use clean water or filtered water with soft type material (a sponge) to wipe the PV
module. Never use chemicals on the surface of the module.
5.5.2 Cleaning after sunset or before sunrise is recommended for safety of O&M operator
shock from heat stroke.
5.5.3 Do not use abrasive powder, abrasive cleaners, scrubber cleaners, polishers, sodium
hydroxide, benzene, nitro-thinners, acid or alkali and other chemical substances.
5.5.4 Do not clean broken glass or modules with broken lines or exposed wires, as it may
cause the electric shock.

Chint Solar (Zhejiang) Co.,Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/
CHINT SOLAR (ZHEJIANG) Co., Ltd.
Add: 1335 Bin’an Rd, Binjiang District, Hangzhou, China 310053
Tel: 86-571-5603 1888
Fax: 86-571-5603 2333
http://energy.chint.com/
This manual suits for next models
2
Table of contents
Other Astronergy Solar Panel manuals

Astronergy
Astronergy CHSM60M/F-B User manual

Astronergy
Astronergy CHSM60M(DG)/F-B User manual

Astronergy
Astronergy CHSM5001T User manual

Astronergy
Astronergy CHSM54M-HC User manual

Astronergy
Astronergy CHSM6610M User manual

Astronergy
Astronergy CHSM6610M User manual

Astronergy
Astronergy CHSM6610M User manual

Astronergy
Astronergy ASM6610 Series User manual
Popular Solar Panel manuals by other brands

GEM
GEM 2881506 quick start guide

Aspect
Aspect SUNSOCKET EP-55A user guide

Baxi
Baxi Solarflo Commissioning, maintenance & servicing guide

Apricus
Apricus AP series Installation & operation manual

Solon
Solon Black 160/05 Assembly and installation instructions

ENN Solar Energy
ENN Solar Energy EST-110 installation manual