
Manual, Collision Sensor, Protector™,SR-61
Document #9610-60-1006-13
Pinnacle
Park
•
1031
Goodworth
Drive
•
Apex,
NC
27539
USA
•
T
el:
919.772.01
15
•
Fax:
919.772.8259
•
www.ati-ia.com
•
Email:
[email protected] 11
3.2.1 Test Switch Functionality
Once the Protector has been installed and connected as described in the preceding paragraphs,
proper electrical operation of the unit may be conrmed.
Supply the Protector with approximately 15 psi (1 bar) and ensure that the unit is electrically
connected to the user’s control circuit or to a test box per Figure 3.2. The switch should appear
closed.
Manually push the Protector to simulate a collision while observing the switch output. When the
collision occurs the switch will open and the test light will turn off.
Release the Protector and it will return to its working position. The test light will illuminate.
3.3 Pneumatic Connection
Compressed air is to be supplied to the port marked “P” in the range of 20 psi to 90 psi. This port accepts
#10-32 or M5 pneumatic ttings. The pressure setting required for a particular application can be estimated
using the procedure outlined in Section 3.3.2—Calculating Estimated Pressure Setting The exact pressure
required must be determined through testing using the procedure outlined in Section 3.3.3—Determining
Exact Pressure Required.
3.3.1 Operating Requirements
The Protector requires clean, dry, non-lubricated air delivered from a user-supplied, self-relieving
regulator. The Protector is certied for accurate and repeatable operation when supplied with air
at 20–90 psi (1.4–6.2 bar ) of pressure operated in an environment with an ambient temperature
range of 40–120°F (5–50°C). For connection to the user’s controls, the Protector is equipped with
a collision sensing switch. When the Protector is in the collision mode or the electrical cable to the
switch is disconnected an open circuit is generated.
Proper sizing of the Protector is imperative for the safe and reliable operation of the unit. Contact
ATI for assistance in selecting the proper unit.
Equivalent spring assist options of 5 psi (P05), 10 psi (P10), and 15 psi (P15) are available.
CAUTION: The level of the desired or required air pressure will vary according
to the weight, loading, and motion of the user’s tooling. Exercise caution while
increasing the air pressure supplied to the Protector. When the pneumatically-
suppliedforceissufcienttore-seattheProtectorthetoolingwillmovetoits
working position.
3.3.2 Calculating Estimated Pressure Setting
In order to determine the proper pressure setting for the collision sensor one must consider all
static and dynamic loads to which it is subjected. These include the loads produced due to the
static weight of the tooling, the inertial loads imposed by robot motion and the loads produced by
the end-effector when performing its intended tasks. Once these loads are calculated, the nominal
pressure setting for the break-away point can be determined. The calculation proceeds as follows:
3.3.2.1 Calculate Applied Loads
Figure 3.3 can be used to convert the forces acting on the end-effector tooling into the
resulting moment, torque, and axial loads applied to the Protector. Use the diagram
shown in Figure 3.3 and the formulas below to calculate the worst-case applied loads
for your application. All three load cases—Axial, Torque, and Moment—should be
assessed for their Static, Dynamic, and Working force components.
NOTICE: Not all of the component forces (Static, Dynamic, and Working) are
present during all phases of the robot program. As a result, the worst case conditions
for Axial, Torque, and Moment loads may occur at different times in the program.